Medium Voltage Current and Voltage Transformers
11kV to 33kV ® OUTDOORDRY TYPE - POLYCRETE
Medium Voltage Current and Voltage Transformers Transformers 11kV to 33kV OUTDOOR DRY TYPE - POLYCRETE
®
……… In Service Since 1995
Manufactured & Supplied from Vacuum Interrupters & Instrument Transformers Division Located at Aurangabad , India Page 1
Medium Voltage Current and Voltage Transformers
11kV to 33kV ® OUTDOORDRY TYPE - POLYCRETE
Background-
Moulds , after the gelling is completed. This is followedbypostcuringprocess.
CG commenced manufacturing of Polycrete CTs & VTs in the year 1994-95. The Polycrete application for electrical products has been patented by CG in the year 1995. Since 1994-95 , more than 50000 products have been manufactured & supplied to Indian & International Customers. The CTs & VTs manufactured using Polycrete are in the kV Range of 11kVto33kV.
After the post curing is completed , the CT & VT castings are finished to remove flashes & excessive material. In order to improve the aesthetics , the castingsarepaintedwithPUBasedPaint.
Polycrete-
our R&DLaboratory for well defined parameters. The
Polycrete means Polymer Concrete & is a Solid Insulating Material. The main composition of Polycrete is Polyester Resin , Silica Flour & various chemicals used as binders. The mixing of the components is carried out under Vacuum to achieve void free castings. The Polycrete is Hydrophobic & thus ideal for Outdoor applications. The electrical application of Polycrete was established after thorough research and validation on samples & products at our Global R&D located in Kanjur Marg , Mumbai.
In process evaluation of the Polycrete Mix is carried
Finishing-
Incoming,InProcess&FinalQualityEvaluation
The Raw Materials are evaluated on periodic basis at
out on sampling basis , by Compressive Load Testing on Standard Blocks. The Electrical Routine Tests are carried out in our High Voltage & High Current Laboratories. These tests are carried out in accordance with the relevant IS / IEC standards specified by thecontract.
Design-
The construction of the product is evaluated & validated by state of art Electro Static Field Analysis Softwares at our R&D. This ensures distribution of electricalstresses. Moulding
The CT / VT active parts (i.e. Secondary & Primary Windings with Core) are assembled inside FRP Moulds & then the Polycrete is poured under vacuum and simultaneous application of Vibration to achieve void free castings. The Casting process takes place at Room Temperature & thus temperature related stresses are eliminated . Subsequently the Polycrete Moulded CTs & VTs are demoulded from the FRP
Page 2
Medium Voltage Current and Voltage Transformers
11kV to 33kV ® OUTDOORDRY TYPE - POLYCRETE
Manufacturing & Testing Facilities :
Typical Technical Details Description 1 kV Class 2 Standard 3 Basic Insulation Level – kV(rms) / kVp 4 Rated Primary Current
Current Transformers 12kV 36kV
Voltage Transformers 12kV 36kV
IS 2705 ; IEC 60044-1
IS 3156 ; IEC 60044-2
28 kV / 75 kVp
70 kV / 170 kVp
28 kV / 75 kVp
70 kV / 170 kVp
5 A to 2000 A
—
—
5 Short Time Current Rating 6 Rated Voltage Factor
Up to 40kA / 1.0S
—
—
7 Output & Accuracy Class 8 Mounting Dimensions
As per Customer Specifications
9 Mounting Holes 10 Overall Dimensions ( L x B x H in mm) 11 Product Weight (kg) without packing
—
350mm x 350mm
—
1.2 Cont/ 1.5 or 1.9 - 30 Seconds As per Customer Specifications
450mm x 450mm 350mm x 350mm
450mm x 450mm
4 x Dia 18 mm
4 x Dia 30 mm
4 x Dia 18 mm
4 x Dia 30 mm
400 x 400 x 600
500 x 500 x 800
400 x 400 x 600
500 x 550 x 830
50kg
Page 3
160kg
60kg
145kg
Medium Voltage Current and Voltage Transformers
11kV to 33kV ® OUTDOORDRY TYPE - POLYCRETE
Other Product Ranges from the Division
- Vacuum Interrupters up to 52kV - High Voltage CTs & IVTs up to 170kV - Air to Oil Type Condenser Bushings up to 72.5kV - Power Quality Products - Capacitor Switch ; Load Break Switch ; LT & HT APFC ; Harmonic Filters & Statcom - LV & MV Vacuum Contactors
Crompton Greaves Ltd. Vacuum Interrupters and Instrument Transfomers Division : Power Systems
D2 MIDC, Waluj, Aurangabad 431 136, Maharashtra, India Ph. : + 91-240-2558000, 2558031, Fax :+ 91-240-2554697 E-mail : Divisional Marketing North Region (India) East Region (India) West Region (India) South Region (India) International
: : : : : :