ElectroDharma Ingeniería S.A.
www.electrodharma.com
ELE Tabla de Contenido 1.-
INTRODUCCIÓN.................... INTRODUCCI ÓN................................................. ............................. .............................. ............................. ................... .................. . 3
Cualidades Costo Seguridad Ambiente 2.-
3 3 3 3
CONDUCTORES PREENSAMBLADOS PREENSAMBLADOS ............... ...................... ............... ................ ............... ............... ............... ............... ................ ............... ............... .............. ...... 3
Normas Aplicables ............... ....................... ................ ................ ................ ............... ............... ................ ................ ................ ................ ............... ............... ............... ............... .............. ...... 3 Calibres Utilizados ................ ........................ ................ ................ ................ ................ ................ ................ ............... ............... ................ ................ .............. .............. ................ ............. ..... 3 Características de los Conductores................ Conductores........................ ................ ................ ................ ................ ............... ............... ................ ................ ............... .............. .............. ....... 3 3.-
CRITERIOS PARA LA EXTENSIÓN Y REFUERZO DE LAS REDES DE BT ............... ....................... ................ ................ ............... ......... 3
3.1.CRITERIOS GENERALES ................................................ ....................... ......................... ........................ ......................... ......... 3 3.2.PUESTA A TIERRA ............................................... ...................... ......................... .......................... ......................... ................ 3 3.3.TIERRAS DE PROTECCIÓN ................ ........................ ................ ................ ................ ................ ................ ................ ................ ................ ................ .............. ...... 3 3.4.TIERRAS DE SERVICIOS ................ ........................ ................ ................ ................ ................ ................ ............... ............... ................ ................ .............. .......... .... 3 3.5.PUESTA A TIERRA AUXILIARES PARA TRABAJOS EN LA RED BT ................ ........................ ................ ................ ................ ........... ... 3 3.6.ASPECTOS RELATIVOS PARA EL TRASLADO DE REDES, CUANDO EXISTEN POSTACIONES CON REDES DE TELECOMUNICACIONES TELECOMUNICACIO NES .............................................. ..................... ......................... ........................ ........................ ............. 3 3.7.OTROS ASPECTOS A CONSIDERAR EN EL PROYECTO DE LA RED ELÉCTRICA............ ELÉCTRICA.................... ................ ............. ..... 3 3.8.CONSIDERACIONES CONSIDERACIONES GENERALES RELATIVAS A ARRANQUES PARA EMPALMES.............. EMPALMES....................... ................. ........ 3 3.9.NÚMERO DE SALIDAS DE LAS SED........................................... SED.................. ......................... ......................... ....................... 3 3.10.SECCIONES SECCIONES DE LOS CONDUCTORES CONDUCTORES DE LAS SALIDAS DE BT ............... ....................... ................ ................ ................ ............... ....... 3 3.11.PROTECCIÓN EN MT Y BT PARA TRANSFORMADORES TRANSFORMADORES AÉREOS ................ ........................ ................ ................ ................ ............ .... 3 3.12.COORDINACIÓN COORDINACIÓN DE PROTECCIONES PROTECCIONES EN TRANSFORMADORES TRANSFORMADORES ............... ....................... ................ ................. ................. ............. ..... 3 3.13.CONSIDERACIONES CONSIDERACIONES GENERALES RESPECTO DE LA RED BT........ BT ................ ................ ............... ............... ................ ................ .......... .. 3 3.14.ÁNGULOS MÁXIMOS....................... MÁXIMOS ................................................ ......................... ......................... ......................... ............. 3 3.15.RELACIÓN ENTRE CONDUCTORES CONDUCTORES DE COBRE Y DE ALUMINIO PREENSAMBLADO PREENSAMBLADO ............... ........................ ............ ... 3 3.16.CONEXIONES ELÉCTRICAS......................... ELÉCTRICAS ......................... ......................... ......................... ........................... 3 3.17.FUSIBLES DE PROTECCIÓN DE LAS SUBESTACIONES...... SUBESTACIONES.............. ................ ................ ................ ................ ................ ................ ........... ... 3 3.18.AISLACIÓN Y SELLADO DEL CONDUCTOR CONDUCTOR PREENSAMBLADO PREENSAMBLADO ................ ........................ ................ ................ ................ ............... ....... 3 3.19.OTROS ELEMENTOS ELEMENTOS DE LA RED ................ ........................ ................ ................ ................ ................ ................ ................ ................ ............... .............. ......... 3 3.20.PROCEDIMIENTO PROCEDIMIENTO DE MONTAJE DE LA RED ............... ....................... ................ ................ ................ ................ ................ ................ ................ .......... 3 4.-
ESTRUCTURAS INCLUIDAS EN LA NORMA ............... ....................... ................ ............... ............... ................ ............... ............... ................ ............... .......... ... 3
as (estructura portante) ............... ....................... ................ ................ ................ ............... ............... ................ ................ ................ ................ ............... .............. ............... .............. ...... 3 bs (estructura (estruct ura de remate)............................. remate).... ......................... ......................... ......................... .............................. ........... 3 hs (cambio de sección)....................... sección) ................................................. .......................... ......................... .......................... ........................ 3 es (límite (límit e de zona).............................. zona)..... ......................... ......................... ......................... ......................... ......................... 3 fs (disposición de cruce trifásico)....... trifásico) ............... ................ ................ ................ ................ ................ ................ ................ ................ ................ .............. .............. ................ .......... 3 qs (disposición (dispos ición de anclaje) ........................ ......................... ......................... ........................ ..................... 3 cs (disposición de paso con derivación lateral) ............... ....................... ................ ................ ................ ................ ................ ................ ................ ............... ............ ..... 3 xs (derivación con TMR desde vano) ............... ....................... ................ ................ ................ ................ ................ ................ ................ ................ .............. .............. ............ .... 3 ds (disposición de remate y derivación con TMR) ................ ....................... ............... ................ ................ ................ ................ ................ ................ .............. ......... ... 3 as' (disposición de anclaje)........ anclaje) ................ ................ ................ ................ ............... ............... ................ ................ ................ ................ ................ .............. .............. ................ .......... 3 bbs (transición red desnuda a red preensamblada) preensamblada) ................ ........................ ................ ................ ................ ................ ................ ............... ............... .............. ...... 3 zs (disposición de remate trifásico a monofásico en recta) ................ ....................... ............... ................ ................ ................ ................ ............... ............ ..... 3 se11 (SED en un poste con una salida y fusible NH)............................................. NH).................... ......................... ......................... .............. 3 se12 (SED trifásica trif ásica en un poste con dos salidas y fusibles NH) ................ ........................ ................ ................ ................ ................ ................ ............. ..... 3 se11t (SED trifásica en un poste con una salida e interruptor termomagnético)....................... termomagnético)............................... ................ ............... ....... 3 se1 (SED trifásica en dos postes con una salida y fusibles NH) ................ ........................ ................ ................ ................ ................ ................ ............. ..... 3 se2 (SED trifásica en dos postes con dos salidas y fusible NH) ................ ........................ ................ ................ ................ ................ ............... ............. ...... 3 se3 (SED trifásica en dos postes con tres salidas y fusible NH) ................ ........................ ................ ................ ................ ................ ............... ............. ...... 3 se4 (SED trifásica en dos postes con cuatro salidas y fusible NH) ................ ........................ ................ ................ ................ ................ .............. ......... ... 3 ce, distribución distri bución de empalmes ................................................ ....................... ......................... ........................ ........................ ................... 3 pc1, unión a un empalme con conductor concéntrico................ concéntrico........................ ................ ............... ............... ................ ................ ................ ............... ............ ..... 3 pc2, unión a dos empalmes con conductor concéntrico ................ ....................... ............... ................ ................ ................ ................ ............... .............. .......... ... 3 pts y pts1 (Puesta a tierra de servicio) ................ ....................... ............... ................ ................ ................ ................ ................ ................ ................ ............... ............... ........ 3 Resumen de estructuras estructur as....................... ................................................ ......................... ......................... ......................... ........................ 3 INDICE ............................. .............................. ............................. ............................. ............................... ................. .............. 3
ElectroDharma Ingeniería S.A. Guardia Vieja 255 Of. 503 Providencia – Manuel Antonio Matta 1335 Osorno Fonos (2)3319635-(2)33 (2)3319635-(2)3319708 19708 - (64)254640-(64)254 (64)254640-(64)254641 641
Página 2
de 34
2
ElectroDharma Ingeniería S.A.
www.electrodharma.com
ELE Tabla de Contenido 1.-
INTRODUCCIÓN.................... INTRODUCCI ÓN................................................. ............................. .............................. ............................. ................... .................. . 3
Cualidades Costo Seguridad Ambiente 2.-
3 3 3 3
CONDUCTORES PREENSAMBLADOS PREENSAMBLADOS ............... ...................... ............... ................ ............... ............... ............... ............... ................ ............... ............... .............. ...... 3
Normas Aplicables ............... ....................... ................ ................ ................ ............... ............... ................ ................ ................ ................ ............... ............... ............... ............... .............. ...... 3 Calibres Utilizados ................ ........................ ................ ................ ................ ................ ................ ................ ............... ............... ................ ................ .............. .............. ................ ............. ..... 3 Características de los Conductores................ Conductores........................ ................ ................ ................ ................ ............... ............... ................ ................ ............... .............. .............. ....... 3 3.-
CRITERIOS PARA LA EXTENSIÓN Y REFUERZO DE LAS REDES DE BT ............... ....................... ................ ................ ............... ......... 3
3.1.CRITERIOS GENERALES ................................................ ....................... ......................... ........................ ......................... ......... 3 3.2.PUESTA A TIERRA ............................................... ...................... ......................... .......................... ......................... ................ 3 3.3.TIERRAS DE PROTECCIÓN ................ ........................ ................ ................ ................ ................ ................ ................ ................ ................ ................ .............. ...... 3 3.4.TIERRAS DE SERVICIOS ................ ........................ ................ ................ ................ ................ ................ ............... ............... ................ ................ .............. .......... .... 3 3.5.PUESTA A TIERRA AUXILIARES PARA TRABAJOS EN LA RED BT ................ ........................ ................ ................ ................ ........... ... 3 3.6.ASPECTOS RELATIVOS PARA EL TRASLADO DE REDES, CUANDO EXISTEN POSTACIONES CON REDES DE TELECOMUNICACIONES TELECOMUNICACIO NES .............................................. ..................... ......................... ........................ ........................ ............. 3 3.7.OTROS ASPECTOS A CONSIDERAR EN EL PROYECTO DE LA RED ELÉCTRICA............ ELÉCTRICA.................... ................ ............. ..... 3 3.8.CONSIDERACIONES CONSIDERACIONES GENERALES RELATIVAS A ARRANQUES PARA EMPALMES.............. EMPALMES....................... ................. ........ 3 3.9.NÚMERO DE SALIDAS DE LAS SED........................................... SED.................. ......................... ......................... ....................... 3 3.10.SECCIONES SECCIONES DE LOS CONDUCTORES CONDUCTORES DE LAS SALIDAS DE BT ............... ....................... ................ ................ ................ ............... ....... 3 3.11.PROTECCIÓN EN MT Y BT PARA TRANSFORMADORES TRANSFORMADORES AÉREOS ................ ........................ ................ ................ ................ ............ .... 3 3.12.COORDINACIÓN COORDINACIÓN DE PROTECCIONES PROTECCIONES EN TRANSFORMADORES TRANSFORMADORES ............... ....................... ................ ................. ................. ............. ..... 3 3.13.CONSIDERACIONES CONSIDERACIONES GENERALES RESPECTO DE LA RED BT........ BT ................ ................ ............... ............... ................ ................ .......... .. 3 3.14.ÁNGULOS MÁXIMOS....................... MÁXIMOS ................................................ ......................... ......................... ......................... ............. 3 3.15.RELACIÓN ENTRE CONDUCTORES CONDUCTORES DE COBRE Y DE ALUMINIO PREENSAMBLADO PREENSAMBLADO ............... ........................ ............ ... 3 3.16.CONEXIONES ELÉCTRICAS......................... ELÉCTRICAS ......................... ......................... ......................... ........................... 3 3.17.FUSIBLES DE PROTECCIÓN DE LAS SUBESTACIONES...... SUBESTACIONES.............. ................ ................ ................ ................ ................ ................ ........... ... 3 3.18.AISLACIÓN Y SELLADO DEL CONDUCTOR CONDUCTOR PREENSAMBLADO PREENSAMBLADO ................ ........................ ................ ................ ................ ............... ....... 3 3.19.OTROS ELEMENTOS ELEMENTOS DE LA RED ................ ........................ ................ ................ ................ ................ ................ ................ ................ ............... .............. ......... 3 3.20.PROCEDIMIENTO PROCEDIMIENTO DE MONTAJE DE LA RED ............... ....................... ................ ................ ................ ................ ................ ................ ................ .......... 3 4.-
ESTRUCTURAS INCLUIDAS EN LA NORMA ............... ....................... ................ ............... ............... ................ ............... ............... ................ ............... .......... ... 3
as (estructura portante) ............... ....................... ................ ................ ................ ............... ............... ................ ................ ................ ................ ............... .............. ............... .............. ...... 3 bs (estructura (estruct ura de remate)............................. remate).... ......................... ......................... ......................... .............................. ........... 3 hs (cambio de sección)....................... sección) ................................................. .......................... ......................... .......................... ........................ 3 es (límite (límit e de zona).............................. zona)..... ......................... ......................... ......................... ......................... ......................... 3 fs (disposición de cruce trifásico)....... trifásico) ............... ................ ................ ................ ................ ................ ................ ................ ................ ................ .............. .............. ................ .......... 3 qs (disposición (dispos ición de anclaje) ........................ ......................... ......................... ........................ ..................... 3 cs (disposición de paso con derivación lateral) ............... ....................... ................ ................ ................ ................ ................ ................ ................ ............... ............ ..... 3 xs (derivación con TMR desde vano) ............... ....................... ................ ................ ................ ................ ................ ................ ................ ................ .............. .............. ............ .... 3 ds (disposición de remate y derivación con TMR) ................ ....................... ............... ................ ................ ................ ................ ................ ................ .............. ......... ... 3 as' (disposición de anclaje)........ anclaje) ................ ................ ................ ................ ............... ............... ................ ................ ................ ................ ................ .............. .............. ................ .......... 3 bbs (transición red desnuda a red preensamblada) preensamblada) ................ ........................ ................ ................ ................ ................ ................ ............... ............... .............. ...... 3 zs (disposición de remate trifásico a monofásico en recta) ................ ....................... ............... ................ ................ ................ ................ ............... ............ ..... 3 se11 (SED en un poste con una salida y fusible NH)............................................. NH).................... ......................... ......................... .............. 3 se12 (SED trifásica trif ásica en un poste con dos salidas y fusibles NH) ................ ........................ ................ ................ ................ ................ ................ ............. ..... 3 se11t (SED trifásica en un poste con una salida e interruptor termomagnético)....................... termomagnético)............................... ................ ............... ....... 3 se1 (SED trifásica en dos postes con una salida y fusibles NH) ................ ........................ ................ ................ ................ ................ ................ ............. ..... 3 se2 (SED trifásica en dos postes con dos salidas y fusible NH) ................ ........................ ................ ................ ................ ................ ............... ............. ...... 3 se3 (SED trifásica en dos postes con tres salidas y fusible NH) ................ ........................ ................ ................ ................ ................ ............... ............. ...... 3 se4 (SED trifásica en dos postes con cuatro salidas y fusible NH) ................ ........................ ................ ................ ................ ................ .............. ......... ... 3 ce, distribución distri bución de empalmes ................................................ ....................... ......................... ........................ ........................ ................... 3 pc1, unión a un empalme con conductor concéntrico................ concéntrico........................ ................ ............... ............... ................ ................ ................ ............... ............ ..... 3 pc2, unión a dos empalmes con conductor concéntrico ................ ....................... ............... ................ ................ ................ ................ ............... .............. .......... ... 3 pts y pts1 (Puesta a tierra de servicio) ................ ....................... ............... ................ ................ ................ ................ ................ ................ ................ ............... ............... ........ 3 Resumen de estructuras estructur as....................... ................................................ ......................... ......................... ......................... ........................ 3 INDICE ............................. .............................. ............................. ............................. ............................... ................. .............. 3
ElectroDharma Ingeniería S.A. Guardia Vieja 255 Of. 503 Providencia – Manuel Antonio Matta 1335 Osorno Fonos (2)3319635-(2)33 (2)3319635-(2)3319708 19708 - (64)254640-(64)254 (64)254640-(64)254641 641
Página 2
de 34
2
ElectroDharma Ingeniería S.A.
www.electrodharma.com
ELE 1.-
INTRODUCCIÓN El primer tendido aéreo protegido se instaló en Francia en 1955. Esta nueva técnica parecía atractiva y EDF (Distribuidora Francesa), Francesa), en asociación con algunos fabricantes de cables y proveedores de conectores (entre ellos SIMEL de Tyco Electronics), lo mejoraron hasta convertirse entre 1962 y 1977 en una sola envoltura aislada hecha en PVC. A partir de 1977, el polietileno reticulado, con sus características termomecánicas superiores, ayudó a solucionar los problemas de implementación de esta nueva tecnología (anclaje y suspensión del neutro portante y conexiones de perforación de la aislación). Las características técnicas de estos cables se describen en el estándar francés NFC 33 209, el nuevo estándar europeo HD626 describe ahora todos los tipos de cables aislados aéreos de BT (ABC de baja tensión). Por sus ventajas, es el sistema de distribución que actualmente se impone a nivel mundial.
Cualidades El sistema es completamente aislado y hermético. No sufre los efectos de la corrosión. Reduce el porcentaje de fallas en 5 veces.
Costo Solamente se instala un mazo de cables, reduce sustancialmente el nivel de hurto, no necesita aisladores, se pueden utilizar postes más pequeños
Seguridad El sistema ABC de BT permite trabajar con línea viva y sin riesgos, el sistema protege contra contactos accidentales, reduce el riesgo de incendio y electrocución, permite reducir las distancias de seguridad
ElectroDharma Ingeniería S.A. Guardia Vieja 255 Of. 503 Providencia – Manuel Antonio Matta 1335 Osorno Fonos (2)3319635-(2)33 (2)3319635-(2)3319708 19708 - (64)254640-(64)254 (64)254640-(64)254641 641
Página 3
de 34
3
ElectroDharma Ingeniería S.A.
ELE
www.electrodharma.com
Ambiente Reduce considerablemente la contaminación visual, posibilita instalar líneas de telecomunicaciones u otras líneas en los mismos postes Estética Sistema compacto, puede ser tendido en postes o adosado a muros.
2.-
CONDUCTORES PREENSAMBLADOS La red se construye con cables preensamblados que están formados por un haz de conductores de aluminio, cuya función es únicamente eléctrica y por un conductor de neutro que realiza la función portante, el cuál además aporta resistencia mecánica al conjunto y que esta constituido por una cuerda de alambres de aleación de aluminio. Todos los conductores, incluido el neutro, están aislados con polietileno reticulado (XLPE) de color negro con una alta resistencia a la intemperie y a los rayos ultravioleta. Los cables preensamblados se utilizan a la intemperie en redes aéreas, fijados en postes, con tensión de hasta 0,6/1 kV y en zonas con contaminación ligera, media, pesada o muy pesada. Se instalarán en lugares con temperaturas ambientes entre -5 ºC y 45 ºC, bajo condiciones extremas, expuestos a la radiación solar y en alturas de hasta 2500 m.s.n.m. Los conductores de aluminio, se emplearán en los niveles I y II (nivel de contaminación ligera y media respectivamente).
Normas Aplicables Los cables que se emplearán en la construcción de las redes de distribución protegida cumplirán con los requisitos, valores y procedimientos establecidos por la última revisión de las normas que se detallan a continuación: ElectroDharma Ingeniería S.A. Guardia Vieja 255 Of. 503 Providencia – Manuel Antonio Matta 1335 Osorno Fonos (2)3319635-(2)3319708 - (64)254640-(64)254641
Página 4
de 34
4
ElectroDharma Ingeniería S.A.
ELE
www.electrodharma.com
• ANSI/ICEA S-76-474
Neutral supported power cable assemblies with weather resistant extruded insulation rated 600 V. • ASTM B230/B230M Specification for aluminum 1350-H19 wire for electrical purposes. • ASTM B231/231M
Specification for concentric lay stranded aluminum 1350 conductors. • ASTM B398/B398M
Specification for aluminum 6201-T81 wire for electrical purposes. • ASTM B399/B399M
Specification for concentric lay stranded aluminum alloy 6201 T81 conductors
Calibres Utilizados Los calibres utilizados por el Grupo Saesa son los siguientes: • 1 x 25mm2 + 25mm2 • 2 x 25mm2 + 25mm2 • 3 x 50mm2 + 50mm2 • 3 x 95mm2 + 50mm2
Para uso en acometidas de empalmes trifásicos hasta 45 kVA se utilizara también preensamblado de 3 x 25 + 50 mm2
ElectroDharma Ingeniería S.A. Guardia Vieja 255 Of. 503 Providencia – Manuel Antonio Matta 1335 Osorno Fonos (2)3319635-(2)3319708 - (64)254640-(64)254641
Página 5
de 34
5
ElectroDharma Ingeniería S.A.
www.electrodharma.com
ELE Características de los Conductores Conductores por fase Sección nominal de los conductores de fase (mm2) Sección nominal del conductor neutro (mm2) Tensión nominal (V) Norma de fabricación y ensayos (Standard)
Tipo de Cable 1 2 25 25
3 50
3 95
25
25
50
50
600 ANSI/ICEA S-76-474
600 ANSI/ICEA S-76-474
600 ANSI/ICEA S-76-474
600 ANSI/ICEA S-76-474
Conductor de Fase Material del Conductor Área (mm2) Número mínimo de hilos Forma y tipo Diámetro conductor (mm) Alargamiento a ruptura (%) Resistencia óhmica a 20ºC Resistencia de aislación a 15,6ºC (MΩ x m) Material de aislación Espesor promedio nominal de la aislación (mm) Espesor mínimo en un punto de la aislación (mm) Corriente admisible en aire a 40 ºC (A) Diámetro final (mm)
H19 25 7 Compacto 6,13 1,5 1,153
H19 25 7 Compacto 6,13 1,5 1,153
H19 50 7 Compacto 8,70 1,5 0,577
H19 95 19 Compacto 11,72 1,5 0,303
843
843
798
614
XLPE 90ºC 1,15
XLPE 90ºC 1,15
XLPE 90ºC 1,53
XLPE 90ºC 1,53
1,04
1,04
1,38
1,38
83
83
121
188
8,43
8,43
11,76
14,78
Conductor de Neutro Portante Material de conductor Área (mm2) Número mínimo de hilos Forma y tipo Diámetro del conductor (mm) Alargamiento a la ruptura (%) Resistencia óhmica a 20ºC ( Ω /m) Resistencia de aislación a 15,6ºC (MΩ x m) Material de aislación Espesor nominal de la capa exterior (mm) Espesor mínimo en un punto (mm) Diámetro final (mm) Resistencia a la tracción (N/mm2) Alargamiento máximo antes de la ruptura (%) (1) Variación máxima del ensayo 168h a 135ºC (%) (2) Alargamiento a 200ºC en 15 días mínimo variación (%) (3) % de negro de humo mínimo (4)
Aleación de aluminio T-81 25 7 No compacto 6,40 3 1,340 813
Aleación de aluminio T-81 25 7 No compacto 6,40 3 1,340 813
Aleación de aluminio T-81 50 7 No compacto 9,05 3 0,670 771
Aleación de aluminio T-81 50 7 No compacto 9,05 3 0,670 771
XLPE 90ºC 1,15
XLPE 90ºC 1,15
XLPE 90ºC 1,53
XLPE 90ºC 1,53
1,04
1,04
1,38
1,38
8,70
8,70
12,11
12,11
Características de XLPE
12,5 250
12,5 250
12,5 250
12,5 250
25
25
25
25
25
25
25
25
2
2
2
2
Notas: ElectroDharma Ingeniería S.A. Guardia Vieja 255 Of. 503 Providencia – Manuel Antonio Matta 1335 Osorno Fonos (2)3319635-(2)3319708 - (64)254640-(64)254641
Página 6
de 34
6
ElectroDharma Ingeniería S.A.
www.electrodharma.com
ELE
(1) Corresponde al ensayo realizado antes del envejecimiento, de acuerdo con la norma ICEA S-76-474-2004 :”Initial Elongation at Ruptura, Minimun” (2) Después de las pruebas de envejecimiento, se admite la reducción indicada. (3) Variación de la elongación en la ruptura para los ensayos de envejecimiento en las condiciones indicadas. (4) El factor de potencia de la aislación puede ser afectado desfavorablemente por la oxidación cuando esta es expuesta al calor y a la luz. Para proteger la aislación de la radiación ultravioleta se emplea negro de humo. El contenido del negro de humo afectará las propiedades mecánicas de la aislación. Otros antecedentes eléctricos del cable son (conductores de fase): 1x25+25mm2 115 1,458
3x50+50mm2 124 0,745
3x95+50mm2 200 0,373
Corriente admisible (1) (A) Resistencia eléctrica a 60ºC, 50Hz (2) (Ω /m) Resistencia eléctrica a 1,602 0,822 0,411 90ºC, 50Hz (2) (Ω /m) Reactancia inductiva media 0,068 0,086 0,084 por fase a 50Hz (Ω /m) Caída de tensión a 60ºC y 2,762 1,253 0,654 cos φ=0,93 (2) (V/km) Caída de tensión a 90ºC y 3,030 1,377 0,715 cos φ=0,93 (2) (V/km) Notas: (1) Condiciones de referencia: un solo cable expuesto al sol, Irradancia (radiación) solar de 1000 W/m2, temperatura ambiente de 40ºC y de 90ºC en los conductores, sin viento y considerando un sistema de cargas equilibradas. (2) Los valores de la resistencia eléctrica (efectiva) y caída de tensión unitaria se encuentran referidos a la temperatura más probable de 60ºC en los conductores. Además se indica la caída de tensión en la máxima temperatura de funcionamiento. De todas maneras para determinar con mayor precisión la caída de tensión deberá calcularse previamente la temperatura de los conductores correspondientes a la carga transmitida teniendo en cuenta la sobretemperatura ΔT2 del conductor con respecto al ambiente para una corriente I2, cumple aproximadamente la relación ΔT2= ΔT1 x (I2/I1), siendo ΔT1 e I1, la sobretemperatura y corriente en condiciones conocidas como las que se indican en la tabla. Una vez hallada la temperatura real debe de corregirse el valor de la resistencia efectiva de la citada tabla y luego calcular la caída de tensión con la ElectroDharma Ingeniería S.A. Guardia Vieja 255 Of. 503 Providencia – Manuel Antonio Matta 1335 Osorno Fonos (2)3319635-(2)3319708 - (64)254640-(64)254641
Página 7
de 34
7
ElectroDharma Ingeniería S.A.
ELE
www.electrodharma.com
fórmula ΔV=K x (Rcos φ + X sen φ)[V/km], siendo K=1,73 para sistemas trifásicos y k=2 para sistemas monofásicos. La tabla siguiente muestra el templado de los conductores para las condiciones que establece la reglamentación vigente para la zona geográfica 3. Para tal efecto, las condiciones contempladas en el cálculo son las siguientes: • • •
La temperatura del neutro portante de aleación AL 6201-T81, se supone inferior a 50ºC cuando la temperatura de las fases llegue a 90ºC. La presión de viento utilizada es de 40 kGf/m2. La tabla se encuentra referida a la aleación de Al 6201-T81, cuyo módulo de elasticidad es de 7000 kG/mm2 y cuyo coeficiente de dilatación térmica de 2,3x10-5.
ElectroDharma Ingeniería S.A. Guardia Vieja 255 Of. 503 Providencia – Manuel Antonio Matta 1335 Osorno Fonos (2)3319635-(2)3319708 - (64)254640-(64)254641
Página 8
de 34
8
ElectroDharma Ingeniería S.A.
www.electrodharma.com
ELE NUMERO DE FASES SECCIÓN DE FASES SECCIÓN DEL NEUTRO PORTANTE PESO DEL CONJUNTO DIAMETRO DEL CONJUNTO TEMPERATURA ºC
1
2
3
3
1
2
3
3
mm²
25.00
25.00
50.00
95.00
25.00
25.00
50.00
95.00
mm²
25.00
25.00
50.00
50.00
25.00
25.00
50.00
50.00
kgf/m
0.19
0.29
0.83
1.27
0.19
0.29
0.83
1.27
cm
1.72
1.99
3.43
4.33
1.72
1.99
3.43
4.33
VANO m
Tensión en kgf
Flecha en m
3 00 .0 0
3 00 .0 0 5 00 .0 0
5 00 .0 0
0 .0 5
0 . 08
0 .1 3
0 .2 0
0
2 15 .4 0
2 05 .3 7 4 04 .4 7
3 88 .9 7
0 .0 7
0 .1 1
0 .1 6
0 .2 6
5
1 78 .5 2
1 72 .7 4 3 71 .3 6
3 63 .1 0
0 .0 8
0 .1 3
0 .1 7
0 .2 7
10
1 44 .0 4
1 43 .9 5 3 39 .9 3
3 39 .1 8
0 .1 1
0 .1 6
0 .1 9
0 .2 9
15
1 13 .7 6
1 20 .0 9 3 10 .4 7
3 17 .2 6
0 .1 3
0 .1 9
0 .2 1
0 .3 1
20
8 9. 67
1 01 .4 5 2 83 .3 1
2 97 .3 2
0 .1 7
0 .2 2
0 .2 3
0 .3 3
-5ºC y presion del viento 40kgf/m²
25
7 2. 33
8 7. 41
2 58 .6 7
2 79 .3 0
0 .2 1
0 .2 6
0 .2 5
0 .3 6
30
6 0. 43
7 6. 89
2 36 .6 8
2 63 .0 8
0 .2 5
0 .3 0
0 .2 7
0 .3 8
35
5 2. 19
6 8. 90
2 17 .3 1
2 48 .5 2
0 .2 9
0 .3 3
0 .3 0
0 .4 0
40
4 6. 27
6 2. 69
2 00 .4 1
2 35 .4 7
0 .3 3
0 .3 6
0 .3 2
0 .4 2
45
4 1. 83
5 7. 75
1 85 .7 7
2 23 .7 7
0 .3 6
0 .4 0
0 .3 5
0 .4 4
50
3 8. 38
5 3. 72
1 73 .1 1
2 13 .2 6
0 .3 9
0 .4 2
0 .3 7
0 .4 7
-5ºC y presion del viento 40kgf/m²
3 00 .0 0
3 00 .0 0 5 00 .0 0
5 00 .0 0
0. 07
0 .1 1
0 .1 9
0 .2 9
0
1 97 .8 5
1 86 .9 4 3 85 .6 6
3 71 .4 1
0 .1 1
0 .1 8
0 .2 4
0 .3 9
5
1 63 .4 7
1 58 .9 5 3 55 .9 8
3 50 .2 8
0 .1 3
0 .2 1
0 .2 6
0 .4 1
10
1 32 .7 6
1 35 .4 3 3 28 .2 8
3 30 .9 0
0 .1 6
0 .2 4
0 .2 8
0 .4 3
15
1 07 .3 5
1 16 .5 5 3 02 .7 6
3 13 .2 0
0 .2 0
0 .2 8
0 .3 1
0 .4 6
20
8 8. 01
1 01 .8 3 2 79 .5 6
2 97 .0 8
0 .2 5
0 .3 2
0 .3 3
0 .4 8
25
30
7 4. 05
9 0. 45
2 58 .7 1
2 82 .4 3
0 .2 9
0 .3 6
0 .3 6
0 .5 1
30
6 4. 07
8 1. 58
2 40 .1 5
2 69 .1 4
0 .3 4
0 .4 0
0 .3 9
0 .5 3
35
5 6. 77
7 4. 55
2 23 .7 4
2 57 .0 7
0 .3 8
0 .4 4
0 .4 2
0 .5 6
40
5 1. 26
6 8. 87
2 09 .2 9
2 46 .1 0
0 .4 3
0 .4 8
0 .4 5
0 .5 8
45
4 6. 96
6 4. 20
1 96 .5 9
2 36 .1 2
0 .4 6
0 .5 1
0 .4 7
0 .6 1
50
4 3. 52
6 0. 29
1 85 .4 1
2 27 .0 2
0 .5 0
0 .5 4
0 .5 0
0 .6 3
-5ºC y presion del viento 40kgf/m²
3 00 .0 0
3 00 .0 0 5 00 .0 0
5 00 .0 0
0. 10
0 .1 5
0 .2 5
0 .3 9
0
1 79 .2 5
1 69 .8 5 3 67 .3 6
3 56 .8 9
0 .1 7
0 .2 6
0 .3 5
0 .5 5
5
1 48 .5 4
1 47 .1 5 3 41 .4 7
3 39 .9 0
0 .2 0
0 .3 0
0 .3 7
0 .5 7
10
1 22 .5 7
1 28 .6 2 3 17 .6 4
3 24 .3 0
0 .2 4
0 .3 5
0 .4 0
0 .6 0
15
1 02 .0 9
1 13 .8 4 2 95 .9 4
3 10 .0 0
0 .2 9
0 .3 9
0 .4 3
0 .6 3
20
8 6. 72
1 02 .1 2 2 76 .3 3
2 96 .8 9
0 .3 4
0 .4 4
0 .4 6
0 .6 6
25
35
7 5. 38
9 2. 77
2 58 .7 4
2 84 .8 8
0 .3 9
0 .4 8
0 .4 9
0 .6 8
30
6 6. 93
8 5. 23
2 43 .0 3
2 73 .8 6
0 .4 4
0 .5 2
0 .5 2
0 .7 1
35
6 0. 47
7 9. 05
2 29 .0 3
2 63 .7 4
0 .4 9
0 .5 7
0 .5 5
0 .7 4
40
5 5. 40
7 3. 91
2 16 .5 7
2 54 .4 4
0 .5 4
0 .6 0
0 .5 9
0 .7 7
45
5 1. 32
6 9. 56
2 05 .4 6
2 45 .8 7
0 .5 8
0 .6 4
0 .6 2
0 .7 9
50
4 7. 97
6 5. 85
1 95 .5 4
2 37 .9 5
0 .6 2
0 .6 8
0 .6 5
0 .8 2
25
3 00 .0 0
3 00 .0 0 5 00 .0 0
5 00 .0 0
0 .1 3
0 . 19
0 .3 3
0 .5 1
0
1 61 .1 1
1 55 .5 7 3 50 .6 8
3 45 .4 2
0 .2 4
0 .3 8
0 .4 7
0 .7 4
5
1 35 .1 2
1 37 .8 4 3 28 .5 9
3 31 .7 6
0 .2 9
0 .4 2
0 .5 1
0 .7 7
10
1 14 .1 6
1 23 .4 4 3 08 .4 4
3 19 .1 5
0 .3 4
0 .4 7
0 .5 4
0 .8 0
15
9 7. 99
1 11 .8 0 2 90 .1 5
3 07 .5 1
0 .4 0
0 .5 2
0 .5 7
0 .8 3
20
8 5. 74
1 02 .3 4 2 73 .6 4
2 96 .7 4
0 .4 5
0 .5 7
0 .6 1
0 .8 6
-5ºC y presion del viento 40kgf/m²
40
7 6. 42
9 4. 57
2 58 .7 7
2 86 .7 9
0 .5 1
0 .6 2
0 .6 4
0 .8 9
30
6 9. 19
8 8. 11
2 45 .4 0
2 77 .5 6
0 .5 6
0 .6 6
0 .6 8
0 .9 2
35
6 3. 48
8 2. 68
2 33 .3 7
2 69 .0 0
0 .6 1
0 .7 1
0 .7 1
0 .9 5
40
5 8. 85
7 8. 04
2 22 .5 4
2 61 .0 4
0 .6 6
0 .7 5
0 .7 5
0 .9 7
45
5 5. 03
7 4. 04
2 12 .7 7
2 53 .6 3
0 .7 1
0 .7 9
0 .7 8
1 .0 0
50
5 1. 82
7 0. 55
2 03 .9 4
2 46 .7 2
0 .7 5
0 .8 3
0 .8 1
1 .0 3
-5ºC y presion del viento 40kgf/m²
3 00 .0 0
3 00 .0 0 5 00 .0 0
5 00 .0 0
0. 20
0 .3 0
0 .5 2
0 .8 0
0
1 31 .7 8
1 36 .1 7 3 24 .1 4
3 29 .6 3
0 .4 6
0 .6 7
0 .8 0
1 .2 1
5
1 15 .4 5
1 25 .5 4 3 08 .5 9
3 20 .5 5
0 .5 3
0 .7 3
0 .8 4
1 .2 4
10
1 02 .6 0
1 16 .6 2 2 94 .3 9
3 12 .0 4
0 .5 9
0 .7 8
0 .8 8
1 .2 7
15
9 2. 47
1 09 .0 7 2 81 .4 4
3 04 .0 5
0 .6 6
0 .8 4
0 .9 2
1 .3 1
20
8 4. 40
1 02 .6 4 2 69 .6 1
2 96 .5 4
0 .7 2
0 .8 9
0 .9 6
1 .3 4
25
50
7 7. 86
9 7. 09
2 58 .8 1
2 89 .4 7
0 .7 8
0 .9 4
1 .0 0
1 .3 7
30
7 2. 48
9 2. 26
2 48 .9 3
2 82 .8 0
0 .8 4
0 .9 9
1 .0 4
1 .4 1
35
6 7. 97
8 8. 02
2 39 .8 7
2 76 .5 1
0 .8 9
1 .0 4
1 .0 8
1 .4 4
40
6 4. 15
8 4. 27
2 31 .5 5
2 70 .5 6
0 .9 5
1 .0 8
1 .1 2
1 .4 7
45
6 0. 87
8 0. 93
2 23 .8 9
2 64 .9 3
1 .0 0
1 .1 3
1 .1 6
1 .5 0
50
5 8. 01
7 7. 93
2 16 .8 3
2 59 .5 9
1 .0 5
1 .1 7
1 .2 0
1 .5 3
25
ElectroDharma Ingeniería S.A. Guardia Vieja 255 Of. 503 Providencia – Manuel Antonio Matta 1335 Osorno Fonos (2)3319635-(2)3319708 - (64)254640-(64)254641
Página 9
de 34
9
ElectroDharma Ingeniería S.A.
www.electrodharma.com
3.BT
ELE CRITERIOS PARA LA EXTENSIÓN Y REFUERZO DE LAS REDES DE 3.1.-
CRITERIOS GENERALES
La construcción de redes se proyectará aérea, excepto que por condiciones expresas establecidas por los clientes del Grupo SAESA u otras condiciones sea necesario construir redes subterráneas en BT. Todas las redes de BT, aéreas, tanto urbanas como rurales, ya sea monofásicas, bifásicas o trifásicas, se construirán con conductor preensamblado, en esto se incluyen todas las ampliaciones o extensiones de red. Cuando sea necesario reemplazar conductores desnudos en mal estado por mantenimiento, o aumentos de sección por aumento de capacidad de la red, en todos estos casos, se utilizarán conductores preensamblados. En el caso de transformación de red monofásica o bifásica a trifásica, se retirarán los conductores desnudos existentes y se reemplazarán por conductores preensamblados.
3.2.-
PUESTA A TIERRA
Todo tramo de red de BT, debe incluir una tierra de servicio nueva, en el límite de zona o cambio de sección, aunque existan otras tierras en las zonas o semizonas atendidas por el transformador de distribución. También deben incluirse las uniones puentes de todos los neutros de zonas y semizonas de los transformadores de distribución adyacentes.
3.3.-
TIERRAS DE PROTECCIÓN
En cada transformador de distribución se debe proyectar una tierra de protección, la que debe conectarse al estanque de él.
ElectroDharma Ingeniería S.A. Guardia Vieja 255 Of. 503 Providencia – Manuel Antonio Matta 1335 Osorno Fonos (2)3319635-(2)3319708 - (64)254640-(64)254641
Página 10
de 34
10
ElectroDharma Ingeniería S.A.
ELE 3.4.-
www.electrodharma.com
TIERRAS DE SERVICIOS
El neutro de cada transformador debe ser aterrizado conectándolo a la malla de tierra común con la tierra de protección. El conductor de neutro debe aterrizarse por lo menos cada 200 m a lo largo de la red.
3.5.-
PUESTA A TIERRA AUXILIARES PARA TRABAJOS EN LA RED BT
Los únicos puntos accesibles para instalación de tierras auxiliares provisorias para la ejecución de trabajos en la red, son los APR donde van instalados los fusibles NH en las Subestaciones de Distribución.
3.6.- ASPECTOS RELATIVOS PARA EL TRASLADO DE REDES, CUANDO EXISTEN POSTACIONES CON REDES DE TELECOMUNICACIONES En los proyectos se debe considerar que en conjunto con las redes de distribución y alumbrado público existen redes de telecomunicaciones apoyadas en los postes del GRUPO SAESA, de acuerdo con esto considerar lo siguiente: • Considerar en los vanos, la flecha de la red de distribución de modo que
mantenga una distancia razonable con las redes de telecomunicaciones • Con el objeto de evitar la degradación de las condiciones técnicas existentes
para la red eléctrica, considerar en el proyecto que en la nueva disposición, a lo menos se mantengan las condiciones de servicio y seguridad equivalentes a la situación existente, tanto para las redes eléctricas como para las de telecomunicaciones.
3.7.- OTROS ASPECTOS A CONSIDERAR EN EL PROYECTO DE LA RED ELÉCTRICA • Minimizar la cantidad de cruces aéreos de calzadas, sobretodo en avenidas
anchas, con el objeto de disminuir el riesgo de corte de cables por el paso de vehículos con carga alta. Cuando se proyecten cruces, el proyecto deberá diseñar el cruce de forma tal que se respete la altura mínima de los cables ElectroDharma Ingeniería S.A. Guardia Vieja 255 Of. 503 Providencia – Manuel Antonio Matta 1335 Osorno Fonos (2)3319635-(2)3319708 - (64)254640-(64)254641
Página 11
de 34
11
ElectroDharma Ingeniería S.A.
www.electrodharma.com
ELE
sobre la calzada, tanto para las redes eléctricas como también para las de telecomunicaciones existentes. La altura a considerar es la que establece el reglamento. • Cuando se proyecte la construcción de un alimentador sobre la ruta de una red de BT existente, el proyectista procurará instalar los postes de MT en forma coincidente o adyacente a cada poste de BT.
3.8.- CONSIDERACIONES GENERALES RELATIVAS A ARRANQUES PARA EMPALMES • Considerar que los empalmes trifásicos hasta 150 kVA se derivaran de la red
empleando como acometidas cable preensamblado de sección adecuada a la potencia del empalme • Sobre 150 kVA los empalmes se construirán derivando la acometida directamente de una Subestación de Distribución • Los empalmes monofásicos se derivaran desde cajas de conexión o serán individuales, en función de la densidad de clientes que presente la red. Se proyectarán hasta 2 empalmes en forma individual, sobre esto se empleará la caja concentradora de empalmes
3.9.-
NÚMERO DE SALIDAS DE LAS SED
En la tabla se indica para la red aérea, los tipos de transformadores y número de salidas de las subestaciones de distribución (SED), empleadas por el Grupo SAESA. Se asume que todos los transformadores son para redes de MT de 13,2 y 23 kV y BT 400/231V o 231V. Tipo de Transformador
Aéreo Bifásico
Aéreo Trifásicos
Potencia (kVA) 5 10 15 15 30 45 75 100 150 200 300 500
ElectroDharma Ingeniería S.A. Guardia Vieja 255 Of. 503 Providencia – Manuel Antonio Matta 1335 Osorno Fonos (2)3319635-(2)3319708 - (64)254640-(64)254641
Número de Salidas en BT 1 1 1 1 1 1 2ó1 2ó1 2ó1 3ó2 4, 3 ó 2 4
Página 12
de 34
12
ElectroDharma Ingeniería S.A.
ELE
www.electrodharma.com
3.10.- SECCIONES DE LOS CONDUCTORES DE LAS SALIDAS DE BT Los conductores de conexión entre los bornes de fases y/o neutro de los transformadores y los APR, y entre los APR y los conductores preensamblados de los alimentadores de BT de la SED, son de cobre, NYSA de color negro, para una temperatura de trabajo permanente de 70ºC. Las secciones de los conductores de conexión indicados, se detallan en la siguiente tabla: SECCIÓN DE LOS CONDUCTORES DE CONEXIÓN Potencia Nº de Sección de las Salidas Conexión de Neutro en (kVA) Salidas de las Fases en [mm2] [mm2] Fase y Tubo Aire Tubo Aire Neutro 15 1 35 35 35 35 30 1 35 35 35 35 45 1 35 35 35 35 75 1 70 35 70 35 75 2 35 35 35 35 100 1 70 70 70 70 100 2 70 70 70 70 150 1 120 70 120 70 150 2 70 70 70 70 200 2 70 70 70 70 200 3 70 70 70 70 300 2 120 70 120 70 300 3 70 70 70 70 300 4 70 70 70 70 500 4 120 70 120 70 Nota: - Utilizar el mismo conductor para la conexión desde los APR a la Red - Tubo o aire se refiere a si las salidas del transformador están expuestas al aire libre o existe una canalización
ElectroDharma Ingeniería S.A. Guardia Vieja 255 Of. 503 Providencia – Manuel Antonio Matta 1335 Osorno Fonos (2)3319635-(2)3319708 - (64)254640-(64)254641
Página 13
de 34
13
ElectroDharma Ingeniería S.A.
ELE
www.electrodharma.com
3.11.- PROTECCIÓN EN MT Y BT PARA TRANSFORMADORES AÉREOS Los transformadores llevan en MT como protección, un desconectador fusible, adecuado a las capacidades nominales de los mismos y coordinados con la protección de BT. En la tabla siguiente se resumen las protecciones a emplear.
3.12.- COORDINACIÓN DE PROTECCIONES EN TRANSFORMADORES La siguiente tabla muestra los tipos de transformadores utilizados generalmente por la empresa (aéreos), el número de salidas y la protección en BT.
TT/DD (kVA)
TABLA DE SELECCIÓN DE FUSIBLES NH PARA SED Protección en BT Nº de Fases Salidas Int. Fusible NH Termomag. GTR GL (A) (kVA) (A) 1 30 1 1 60 1 90 1 3x30 1 50 1 50 1 75 2 2x50 1 100 3 2 2x50 1 160 2 2x75 2 2x100 3 3x75 2 2x160 3 3x100 4 4x75 4 4x125
5 10 15 15 30 45 75 75 100 100 150 150 200 200 300 300 300 500 Notas 1) Los fusibles NH son talla 2
ElectroDharma Ingeniería S.A. Guardia Vieja 255 Of. 503 Providencia – Manuel Antonio Matta 1335 Osorno Fonos (2)3319635-(2)3319708 - (64)254640-(64)254641
Prot. en MT Fusible Curva T (A) 1 1 1 1 1 2 2 2 3 3 6 6 6 6 8 8 8 15
Página 14
de 34
14
ElectroDharma Ingeniería S.A.
ELE
www.electrodharma.com
2) En el lado de BT de la SED, se emplean desconectadores APR monopolares, de 630 A y 500 V 3) Los termomagnéticos tienen curva de operación tipo C
3.13.- CONSIDERACIONES GENERALES RESPECTO DE LA RED BT 1) En general proyectar subestaciones de 300 kVA con 4 zonas, es decir 4 alimentadores, cada una de estas 4 salidas independientes con preensamblado de 3x95 + 1x50 mm2. El transformador queda con 4 juegos de protecciones NH con fusibles gTR 75 kVA 2) Para 300 kVA el menor número de zonas a proyectar es 2 alimentadores, donde cada salida independiente es con preensamblado de 3x95+1x50 mm2. El transformador queda con 2 juegos de protecciones NH con fusibles gTR 160 kVA. 3) Al proyectar un empalme, con subida/bajada en poste, desde el T/D ya sea existente o proyectado, se aceptarán alternativas en el uso de las secciones de los conductores aéreos en la red con preensamblado, siempre que se ajusten a la capacidad de transporte de la red y a la demanda máxima de las cargas de la red proyectada. 4) El número máximo de arranques y/o empalmes desde una subestación esta limitado a 4. 5) La red de BT podrá ser trifásica, bifásica o monofásica, dependiendo del tipo de consumo. Las redes que salgan de transformadores trifásicos con sus respectivas protecciones serán de la misma naturaleza y en lo posible deberán quedar enmalladas entre ellas cuando pertenezcan a una misma zona de distribución, o sea, cuando estén alimentadas a través de una misma protección en BT, esto conduce a mejorar la regulación de voltaje en los puntos más alejados respecto del T/D y eleva el nivel de corriente de cortocircuito en caso de fallas asegurando la correcta operación de las protecciones asociadas.
ElectroDharma Ingeniería S.A. Guardia Vieja 255 Of. 503 Providencia – Manuel Antonio Matta 1335 Osorno Fonos (2)3319635-(2)3319708 - (64)254640-(64)254641
Página 15
de 34
15
ElectroDharma Ingeniería S.A.
www.electrodharma.com
ELE
6) Las prolongaciones de línea podrán ser monofásica o bifásicas dependiendo del tipo de consumo y de la caída de tensión. 7) Las redes de BT que se proyecten deberán quedar en lo posible interconectadas con otras líneas de áreas de distribución diferentes, pero de igual tensión, a través de límites de zona, quedando con la misma secuencia de fases. Esto permitirá transferir cargas de una subestación a otra con facilidad. 8) Proyectar las redes de BT con una caída de tensión máxima de un 6%, con el objeto de contemplar el crecimiento vegetativo de la demanda. 9) Proyectar la red de manera que para 30 ºC y sin viento, la altura mínima con respecto al nivel normal o con respecto a la rasante del camino sea de 5 m. La posición del neutro de la red preensamblada corresponde a la posición del neutro tradicional. 10) El vano máximo quedará establecido en las tablas de templado. No obstante en las zonas urbanas el vano esta determinado por la distancia entre las luminarias.
3.14.- ÁNGULOS MÁXIMOS
β
Solo red de BT en poste de 8,70 m 2 Cable de aluminio, fases de 95 mm Neutro portante de 50 mm2 b max grados sexagesimales 11°
Combinación de red de MT y BT Para la BT: 2 Cable de aluminio, fases de 95 mm Neutro portante de 50 mm2 Sección del conductor de AT en mm
b max grados sexagesimales
25 35 70 120
ElectroDharma Ingeniería S.A. Guardia Vieja 255 Of. 503 Providencia – Manuel Antonio Matta 1335 Osorno Fonos (2)3319635-(2)3319708 - (64)254640-(64)254641
6,85° 5,03° 2,8° 2,8°
Página 16
de 34
16
ElectroDharma Ingeniería S.A.
www.electrodharma.com
ELE Los valores se obtienen de la relación siguiente:
⎛
β = 2 × sen −1 ⎜⎜
R
⎝ 6 × T
A
− F + 2 × T H
N
⎞ ⎟⎟ ⎠
: ángulo de las líneas concurrentes en grados sexagesimales R : resistencia del poste a 20 cm (BT) o 15 cm (AT) desde la punta FH : corresponde a la fuerza ejercida por el viento sobre la superficie expuesta del poste y los conductores a 40 kG/m2 aplicada a 20 cm o 15 cm según corresponda TA : es la tensión de templado a -5 °C de los conductores de AT TN : es la tensión de templado del neutro portante del cable de aluminio a -5°C (600 kG) β
3.15.- RELACIÓN ENTRE CONDUCTORES DE COBRE Y DE ALUMINIO PREENSAMBLADO Tipo Conductor
de
Sección mm2
Capacidad en A
Cu AWG 6
13
114
Cu
16
121
Preensamblado
3x35+50
110
Cu AWG 4
21
150
Cu
25
168
Preensamblado
3x70+50
175
Cu AWG 2
33
204
Cu
35
205
Preensamblado
3x95+50
200
3.16.- CONEXIONES ELÉCTRICAS Para la conexión tanto de conductores entre sí, como para la conexión de empalmes a la red, se adoptaron los conectores estancos de perforación, que permiten unir conductores de diferentes secciones, sin necesidad de retirar la aislación. La conexión permanece estanca y la presión de ella es asegurada por medio de pernos fusibles que tienen sus torques de apriete calibrados. Para la unión de las puestas a tierra, continua empleándose el terminal tipo UDC ElectroDharma Ingeniería S.A. Guardia Vieja 255 Of. 503 Providencia – Manuel Antonio Matta 1335 Osorno Fonos (2)3319635-(2)3319708 - (64)254640-(64)254641
Página 17
de 34
17
ElectroDharma Ingeniería S.A.
ELE
www.electrodharma.com
3.17.- FUSIBLES DE PROTECCIÓN DE LAS SUBESTACIONES Se emplean fusibles NH tamaño 2 para todas las potencias de transformadores aéreos desde 45 hasta 500 kVA. De preferencia se emplean los fusibles tipo gTr, recomendados para proteger transformadores. Los fusibles gTr, permiten una sobrecarga del transformador de un 30 % durante 10 horas y 50 % durante 2 horas
3.18.- AISLACIÓN Y SELLADO DEL CONDUCTOR PREENSAMBLADO En todos los puntos de terminación, límites de zona, etc., se colocarán terminaciones termocontráctiles o de contracción en frío, ambas tecnologías están disponibles. El objetivo es sellar el conductor e impedir el ingreso de agua a su interior.
3.19.- OTROS ELEMENTOS DE LA RED Para toda la red monofásica, bifásica o trifásica, se empleará en las estructuras de paso una grampa de suspensión. Las retenciones se realizarán con grampas de retención cuyo tipo dependerá de la sección del conductor de neutro. Se emplearán diferentes grampas de retención para los conductores trifásicos y monofásicos/bifásicos. También en los conductores concéntricos para los empalmes, se empleará una grampa de retención apropiada a la dimensión de los conductores.
3.20.- PROCEDIMIENTO DE MONTAJE DE LA RED El procedimiento de construcción de la red es sencillo, sobre todo considerando que los conductores son de aluminio, lo que los hace bastante livianos. Esto facilita el montaje de los conductores. Para ello se emplearán dispositivos apropiados como poleas, separadores, y portacarretes. El montaje debe realizarse con cuidado, evitando daños en los conductores o en la aislación ElectroDharma Ingeniería S.A. Guardia Vieja 255 Of. 503 Providencia – Manuel Antonio Matta 1335 Osorno Fonos (2)3319635-(2)3319708 - (64)254640-(64)254641
Página 18
de 34
18
ElectroDharma Ingeniería S.A.
4.-
ELE ESTRUCTURAS INCLUIDAS EN LA NORMA
www.electrodharma.com
Las estructuras que se incluyen en la norma de distribución preensamblada trifásica son las siguientes:
Código as bs hs es fs qs cs xs ds as' bbs zs se11 se12 se11t se1 se2 se3 se4 ce pc1 pc2 pts
Descripción Disposición portante Disposición de remate Cambio de sección Límite de zona Disposición de cruce trifásico Disposición de anclaje Disposición de paso con derivación lateral Derivación con TMR desde vano Disposición de remate y derivación con TMR Disposición para ángulos mayores Transición red desnuda a preensamblada Disposición de remate trifásico a monofásico en recta SED trifásica en un poste con una salida y fusible NH SED trifásica en un poste con dos salidas y fusible NH SED trifásica en un poste con una salida e interruptor termomagnético SED trifásica en dos postes con una salida y fusible NH SED trifásica en dos postes con dos salidas y fusible NH SED trifásica en dos postes con tres salidas y fusible NH SED en dos postes con cuatro salidas y fusible NH Distribución de empalmes Unión a un empalme con conductor concéntrico Unión a dos empalmes con conductor concéntrico Puesta a tierra de servicio
Figura 1 Figura 2 Figura 3 Figura 4 Figura 5 Figura 6 Figura 7 Figura 8 Figura 9 Figura 10 Figura 11 Figura 12 Figura 13 Figura 14 Figura 15 Figura 16 Figura 17 Figura 18 Figura 19 Figura 20 Figura 21 Figura 22 Figura 23
as (estructura portante) Es una estructura similar a la “a” , “ap” y otras portantes, lo nuevo que presenta es la grampa de suspensión (2) y el soporte de ésta (7). La grampa se encuentra diseñada para trabajar a ángulos máximo de 5º. La grampa también se puede utilizar con conductor preensamblado monofásico y bifásico (as1 y as2 respectivamente la nomenclatura de las estructuras) con los mismos materiales indicados en la hoja de la norma. ElectroDharma Ingeniería S.A. Guardia Vieja 255 Of. 503 Providencia – Manuel Antonio Matta 1335 Osorno Fonos (2)3319635-(2)3319708 - (64)254640-(64)254641
Página 19
de 34
19
ElectroDharma Ingeniería S.A.
www.electrodharma.com
ELE
Figura 1. Estructura portante
bs (estructura de remate) Posee similares características a las estructuras de remate tradicionales y a la estructura de remate con preensamblado monofásico y bifásico existente actualmente. Se puede utilizar hasta una distancia de 25 metros con T.M.R. y sin tirante (para casos en que no se pueda instalar el tirante). Para el caso monofásico y bifásico la grampa de retención (6) se cambia ya que en este caso, el neutro portante es de 25mm2 y la grampa descrita es para neutros de 50mm2. Las puntas protectoras de cable son solicitadas de acuerdo a la sección del conductor (fases y neutro).
Figura 2. Estructura de remate ElectroDharma Ingeniería S.A. Guardia Vieja 255 Of. 503 Providencia – Manuel Antonio Matta 1335 Osorno Fonos (2)3319635-(2)3319708 - (64)254640-(64)254641
Página 20
de 34
20
ElectroDharma Ingeniería S.A.
www.electrodharma.com
ELE hs (cambio de sección)
Esta estructura, al igual que la versión Tm-G, permite realizar el cambio de sección del conductor. Es de uso exclusivo con conductores trifásicos, pues es el único que tiene dos secciones (95mm2 y 50mm2). La unión entre los conductores se realiza por medio de conectores de perforación estancos.
Figura 3. Estructura de cambio de sección
es (límite de zona) Básicamente es la misma estructura de otras normativas, se debe tener cuidado en las grampas de retención (6) para el caso de disposiciones monofásicas y bifásicas (es1 y es2) pues es diferente a la trifásica, además de los protectores de punta de cable que dependen de la sección del conductor.
Figura 4. Límite de zona ElectroDharma Ingeniería S.A. Guardia Vieja 255 Of. 503 Providencia – Manuel Antonio Matta 1335 Osorno Fonos (2)3319635-(2)3319708 - (64)254640-(64)254641
Página 21
de 34
21
ElectroDharma Ingeniería S.A.
www.electrodharma.com
ELE fs (disposición de cruce trifásico)
Esta disposición se realiza en caso de que se desee enmallar la distribución en BT, para proyectarla se supone existente una estructura as y se proyecta una fs para realizar el cruce entre ambas líneas.
Figura 5. Disposición de cruce trifásico
qs (disposición de anclaje) La disposición de anclaje cumple los mismos propósitos que las conocidas anteriormente, es decir, anclar la línea en ambos sentidos (hasta 90º).
Figura 6. Disposición de anclaje ElectroDharma Ingeniería S.A. Guardia Vieja 255 Of. 503 Providencia – Manuel Antonio Matta 1335 Osorno Fonos (2)3319635-(2)3319708 - (64)254640-(64)254641
Página 22
de 34
22
ElectroDharma Ingeniería S.A.
ELE
www.electrodharma.com
cs (disposición de paso con derivación lateral) Es utilizada parta derivar lateralmente, en TMR la red de distribución, por ejemplo al pasar por la calle principal para alimentar una calle lateral, o bien un empalme trifásico. Su utilización se encuentra restringida a un vano no superior a 30m. En el caso de derivaciones monofásicas y bifásicas, cambia el ítem 14 (grampa de retención) y la cantidad de conectores dentados estanco. En ese caso las estructuras se llaman cs1 y cs2 respectivamente.
Figura 7. Disposición de paso con derivación lateral
xs (derivación con TMR desde vano) Esta disposición es nueva y permite derivar en cualquier parte del vano, con la condición que la TMR no sea superior a 15metros. Este tipo de derivaciones (con TMR), se utilizará para no invadir propiedad de terceros (pasar sobre sitios) o sobre casas, no existiendo alternativa con otra disposición para evitar esta situación, lo que ocurre con frecuencia en las esquinas de calles. Al igual que en otras disposiciones se pueden realizar derivaciones monofásicas, bifásicas y trifásicas cambiando el ítem 3 (grampa de retención) y el ítem 4 (conector dentado estanco)
ElectroDharma Ingeniería S.A. Guardia Vieja 255 Of. 503 Providencia – Manuel Antonio Matta 1335 Osorno Fonos (2)3319635-(2)3319708 - (64)254640-(64)254641
Página 23
de 34
23
ElectroDharma Ingeniería S.A.
www.electrodharma.com
ELE
Figura 8. Derivación con TMR desde vano
ds (disposición de remate y derivación con TMR) Esta disposición es similar a las utilizadas actualmente (d, remate y derivación con TMR), con la limitación que la TMR no debe de ser superior a 25 metros.
Figura 9. Disposición de remate y derivación con TMR ElectroDharma Ingeniería S.A. Guardia Vieja 255 Of. 503 Providencia – Manuel Antonio Matta 1335 Osorno Fonos (2)3319635-(2)3319708 - (64)254640-(64)254641
Página 24
de 34
24
ElectroDharma Ingeniería S.A.
www.electrodharma.com
ELE as' (disposición de anclaje)
Esta disposición es utilizada con ángulos mayores a 5º y menores a 11º, se observa que es utilizada sin tirante.
Figura 10. Disposición de anclaje
bbs (transición red desnuda a red preensamblada) Esta disposición sirve para realizar la transición desde la red desnuda a red preensamblada, por ejemplo cuando se requiera extender la red BT o bien en casos de reemplazo del conductor desnudo por preensamblado.
Figura 11. Transición red desnuda a red preensamblada ElectroDharma Ingeniería S.A. Guardia Vieja 255 Of. 503 Providencia – Manuel Antonio Matta 1335 Osorno Fonos (2)3319635-(2)3319708 - (64)254640-(64)254641
Página 25
de 34
25
ElectroDharma Ingeniería S.A.
ELE
www.electrodharma.com
zs (disposición de remate trifásico a monofásico en recta) Esta disposición se utilizará al rematar una línea trifásica y continuar con una monofásica o bifásica en recta.
Figura 12. Disposición de remate trifásico a monofásico en recta
se11 (SED en un poste con una salida y fusible NH) Al igual que en otros casos facilita el proyecto y la valorización. Corresponde a subestaciones en un poste protegida con fusibles NH.
Figura 13. SED trifásica en un poste con una salida y fusible NH ElectroDharma Ingeniería S.A. Guardia Vieja 255 Of. 503 Providencia – Manuel Antonio Matta 1335 Osorno Fonos (2)3319635-(2)3319708 - (64)254640-(64)254641
Página 26
de 34
26
ElectroDharma Ingeniería S.A.
ELE
www.electrodharma.com
se12 (SED trifásica en un poste con dos salidas y fusibles NH) Corresponde a subestaciones en un poste con dos salidas o alimentadores.
Figura 14. SED trifásica en un poste con dos salidas y fusibles NH
se11t (SED trifásica en un poste con una salida e interruptor termomagnético) Esta disposición es utilizada para subestaciones trifásicas de 15kVA o en subestaciones monofásicas, al igual que las otras SED incluye todos los componentes de BT para su valorización.
Figura 15. SED trifásica en un poste, una salida e interruptor termomagnético ElectroDharma Ingeniería S.A. Guardia Vieja 255 Of. 503 Providencia – Manuel Antonio Matta 1335 Osorno Fonos (2)3319635-(2)3319708 - (64)254640-(64)254641
Página 27
de 34
27
ElectroDharma Ingeniería S.A.
ELE
www.electrodharma.com
se1 (SED trifásica en dos postes con una salida y fusibles NH) Esta disposición corresponde a una SED trifásica en dos postes con una salida protegida con fusibles NH, incluye todos los materiales necesarios para la distribución en BT a excepción del fusible NH que es seleccionado de acuerdo a la potencia del transformador.
Figura 16. SED trifásica en dos postes, una salida y protección con fusibles NH
se2 (SED trifásica en dos postes con dos salidas y fusible NH) Presenta las mismas características que las otras estructuras de SED, con la diferencia que es para dos circuitos de salida.
Figura 17. SED trifásica en dos postes con dos salidas y fusible NH ElectroDharma Ingeniería S.A. Guardia Vieja 255 Of. 503 Providencia – Manuel Antonio Matta 1335 Osorno Fonos (2)3319635-(2)3319708 - (64)254640-(64)254641
Página 28
de 34
28
ElectroDharma Ingeniería S.A.
ELE
www.electrodharma.com
se3 (SED trifásica en dos postes con tres salidas y fusible NH)
Presenta las mismas características de las otras estructuras de SED, con la diferencia que esta es para tres circuitos de salida. Una característica especial de esta configuración es que el circuito que se encuentre solo debe de ser rematado en uno de sus lados en el siguiente poste.
Figura 18. SED trifásica en dos postes con tres salidas y fusible NH
se4 (SED trifásica en dos postes con cuatro salidas y fusible NH) Esta estructura facilita el trabajo de proyecto y valorización. En este caso, para la SED que posee cuatro salidas, se incluyen todos los materiales de BT y como estructura es independiente de la potencia del transformador.
ElectroDharma Ingeniería S.A. Guardia Vieja 255 Of. 503 Providencia – Manuel Antonio Matta 1335 Osorno Fonos (2)3319635-(2)3319708 - (64)254640-(64)254641
Página 29
de 34
29
ElectroDharma Ingeniería S.A.
www.electrodharma.com
ELE
Figura 19. SED trifásica en dos postes con cuatro salidas y fusibles NH
ce, distribución de empalmes En general, los empalmes se conectan a la red por medio de una caja concentradora que es capaz de admitir hasta 9 acometidas distribuidas en grupos de a tres, en cada una de las fases. La conexión de la caja a la red, se realiza por medio de fusibles Neozed. Una excepción al empleo de la caja concentradora de empalmes es cuando la densidad de clientes es baja, principalmente en zonas rurales, y concurren sólo hasta dos empalmes a un poste. En este caso las acometidas se conectan directamente a la red a través de los fusibles Neozed.
Figura 20. Distribución de empalmes ElectroDharma Ingeniería S.A. Guardia Vieja 255 Of. 503 Providencia – Manuel Antonio Matta 1335 Osorno Fonos (2)3319635-(2)3319708 - (64)254640-(64)254641
Página 30
de 34
30
ElectroDharma Ingeniería S.A.
ELE
www.electrodharma.com
pc1, unión a un empalme con conductor concéntrico Esta disposición muestra la unión de la red preensamblada a un conductor concéntrico (en caso de que la estructura sea de remate y exista un empalme más allá)
Figura 21. Unión a un empalme conductor concéntrico
pc2, unión a dos empalmes con conductor concéntrico Estructura utilizada para la unión de dos conductores concéntricos a la red preensamblada existente.
Figura 22. Unión a dos empalmes con conductor concéntrico ElectroDharma Ingeniería S.A. Guardia Vieja 255 Of. 503 Providencia – Manuel Antonio Matta 1335 Osorno Fonos (2)3319635-(2)3319708 - (64)254640-(64)254641
Página 31
de 34
31
ElectroDharma Ingeniería S.A.
ELE
www.electrodharma.com
pts y pts1 (Puesta a tierra de servicio) Estructura utilizada para la puesta a tierra de servicio para redes preensambladas. pts se utiliza para un neutro de sección 50mm² y pts1 para un neutro de sección de 25mm2 de redes preensambladas.
Figura 23. Puesta a tierra de servicio en estructura de remate.
ElectroDharma Ingeniería S.A. Guardia Vieja 255 Of. 503 Providencia – Manuel Antonio Matta 1335 Osorno Fonos (2)3319635-(2)3319708 - (64)254640-(64)254641
Página 32
de 34
32
ElectroDharma Ingeniería S.A.
www.electrodharma.com
ELE Resumen de estructuras
Las estructuras tanto trifásicas como monofásicas y bifásicas contempladas en la norma son las que se resumen a continuación: Código as as2 as1 bs bs2 bs1 hs es es2 es1 fs fs2 fs1 qs qs2 qs1 cs cs2 cs1 xs xs2 xs1 ds ds2 ds1 as' as'2 as'1 bbs bbs2 bbs1 zs zs2 se11 se12 se11t se1 se2 se3 se4 ce pc1 pc2 pts
Descripción Disposición portante Disposición portante bifásica Disposición bifásica monofásica Disposición de remate Disposición de remate bifásica Disposición de remate monofásica Cambio de sección Límite de zona Límite de zona bifásico Límite de zona monofásico Disposición de cruce trifásico Disposición de cruce bifásico Disposición de cruce monofásico Disposición de anclaje Disposición de anclaje bifásico Disposición de anclaje monofásico Disposición de paso con derivación lateral Disposición de paso con derivación lateral bifásica Disposición de paso con derivación lateral monofásica Derivación con TMR desde vano Derivación con TMR desde vano bifásica Derivación con TMR desde vano monofásica Disposición de remate y derivación con TMR Disposición de remate y derivación con TMR bifásica Disposición de remate y derivación con TMR monofásica Disposición para ángulos mayores Disposición para ángulos mayores bifásica Disposición para ángulos mayores monofásica Transición red desnuda a preensamblada Transición red desnuda a preensamblada bifásica Transición red desnuda a preensamblada monofásica Disposición de remate trifásico a monofásico en recta Disposición de remate trifásico a bifásico en recta SED trifásica en un poste con una salida y fusible NH SED trifásica en un poste con dos salidas y fusible NH SED trifásica en un poste con una salida e interruptor termomagnético SED trifásica en dos postes con una salida y fusible NH SED trifásica en dos postes con dos salidas y fusible NH SED trifásica en dos postes con tres salidas y fusible NH SED en dos postes con cuatro salidas y fusible NH Distribución de empalmes Unión a un empalme con conductor concéntrico Unión a dos empalmes con conductor concéntrico Puesta a tierra de servicio
ElectroDharma Ingeniería S.A. Guardia Vieja 255 Of. 503 Providencia – Manuel Antonio Matta 1335 Osorno Fonos (2)3319635-(2)3319708 - (64)254640-(64)254641
Página 33
de 34
33