Stan Standard ard PLN, PLN, Uku Ukuran Kabel abel Minim inimal al vs Amp Ampere ere
11th January 2011
http ttp://r ://read eadm medon edong. g.b blogs logsp pot.co ot.co.i .id d/201 /2011/01/s 1/01/stan tand dard ard-pln -pln-u -uku kurran-ka an-kab b... ...
Standard PLN, Ukuran Kabel Minimal vs Ampere
BESARA BESARAN N DAY DAYA YG TERSED TERSEDIA IA VA
Watt
GOL
MCB / MCCB Fasa
Besar Kabel by AKLI
kVA
@ PF = 0.8 0.8
450
0,45
360
TR
2
1ɸ
220 V
NYY NYY / NYM NYM
3 x
2.5 mm²
900
0,9
720
TR
4
1ɸ
220 V
NYY NYY / NYM NYM
3 x
2.5 mm mm²
1.300
1,3
1.040
TR TR
6
1ɸ
220 V
NYY NYY / NYM NYM
3 x
4
mm² mm²
2.200
2,2
1.760
TR
10
1ɸ
220 V
NYY NYY / NYM NYM
3 x
4
mm²
3.500
3,5
2.800
TR TR
16 16
1ɸ
220 V
NYY NYY / NYM NYM
3 x
4
mm² mm²
4.400
4,4
3.520
TR
20
1ɸ
220 V
NYY NYY / NYM NYM
3 x
4
mm²
5.500
5,5
4.400
TR TR
25 25
1ɸ
220 V
NYY NYY / NYM NYM
3 x
4
mm² mm²
7.700
7,7
6.160
TR
35
1ɸ
220 V
NYY NYY / NYM NYM
3 x
6
mm²
11.000
11
8.800
TR TR
50 50
1ɸ
220 V
NYY NYY / NYM NYM
3 x
6
mm² mm²
13.900
13,9
11.120
TR
63
1ɸ
220 V
NYY NYY / NYM NYM
3 x
10
mm mm²
rounded (VA)
A
Type Kabel Toefoer
V
3.949
3. 900
3,9
3.159
TR
6
3ɸ
380 V NYY NYY / NYFGBY NYFGBY
4 x
4
mm² mm²
6.582
6.600
6,6
5.265
TR
10
3ɸ
380 V NYY NYY / NYFGBY NYFGBY
4 x
4
mm²
10.531
10.600
10,6
8.425
TR
16
3ɸ
380 V NYY NYY / NYFGBY NYFGBY
4 x
6
mm² mm²
13.164
13.200
13,2
10.531
TR
20
3ɸ
380 V NYY NYY / NYFGBY NYFGBY
4 x
10
mm²
16.454
16.500
16,5
13.164
TR
25
3ɸ
380 V NYY NYY / NYFGBY NYFGBY
4 x
10
mm² mm²
23.036
23.000
23
18.429
TR
35
3ɸ
380 V NYY NYY / NYFGBY NYFGBY
4 x
16
mm²
32.909
33.000
33
26.327
TR
50
3ɸ
380 V NYY NYY / NYFGBY NYFGBY
4 x
16
mm² mm²
41.465
41.500
41,5
33.172
TR
63
3ɸ
380 V NYY NYY / NYFGBY NYFGBY
4 x
25
mm²
52.654
53.000
53
42.123
TR
80
3ɸ
380 V NYY NYY / NYFGBY NYFGBY
4 x
35
mm² mm²
65.818
66.000
66
52.654
TR
100
3ɸ
380 V NYY NYY / NYFGBY NYFGBY
4 x
50
mm²
82.272
82.500
82,5
65.818
TR
125
3ɸ
380 V NYY NYY / NYFGBY NYFGBY
4 x
50
mm² mm²
105.309
105.000
105
84.247
TR
160
3ɸ
380 V NYY NYY / NYFGBY NYFGBY
4 x
70
mm²
131.636
131.000
131
105.309
TR
200
3ɸ
380 V NYY NYY / NYFGBY NYFGBY
4 x
95
mm² mm²
148.090
147.000
147
118.472
TR
225
3ɸ
380 V NYY NYY / NYFGBY NYFGBY
4 x
95
mm²
164.545
164.000
164
131.636
TR
250
3ɸ
380 V NYY NYY / NYFGBY NYFGBY
4 x
120 mm² mm²
197.454
197.000
197
157.963
TR
300
3ɸ
380 V NYY NYY / NYFGBY NYFGBY
4 x
150 mm mm²
233.654
233.000
233
186.923
TM
355
3ɸ
380 V NYY NYY / NYFGBY NYFGBY
4 x
150 mm² mm²
279.726
279.000
279
223.781
TM
425
3ɸ
380 V NYY NYY / NYFGBY NYFGBY
4 x
240 mm mm²
329.090
329.000
329
263.272
TM
500
3ɸ
380 V NYY NYY / NYFGBY NYFGBY
4 x
240 mm² mm²
414.653
414.000
414
331.722
TM
630
3ɸ
380 V NYY NYY / NYFGBY NYFGBY
4 x
300 mm mm²
TABEL TABEL DAYA DAYA & UKU RAN KABEL (STANDAR AKLI)
Diposting 11th January 2011 oleh Amar Label: akli, cable, kabel, standard pln, ukuran kabel 13
Lihat komentar komentar
ADI 13 DI 13 Juli 2012 00.55 cara ngitungnya gimana pak ???? Balas
oni zacheus 15 Juli 2012 23.53 daya = kuat arus x tegangan x waktu contoh: 440 kwh = 2A x 220V x 1jam
1d i3
19/07/17 15 02
Standard PLN, Ukuran Kabel Minimal vs Ampere
http://readmedong.blogspot.co.id/2011/01/standard-pln-ukuran-kab...
Kalo rumus penampang kabel saya lupa,,,, mata pelajaran kelas 2 smp Balas
bin jaber 4 April 2014 17.37 Assalamu'alaikum, mau tanya? Cara mengetahui ukuran kaber dengan daya 3500 VA kabel NYY/NYM 3 x 4 mm, itu bagaimana caranya .... ? Balas
komputer dan aksesoris 9 Mei 2014 22.11 ok sukron infonya... Balas
R-one 28 Agustus 2014 09.00 mau tanya type cable NYFGBY ukuran 1x4x150mm2 diameternya brp? dan klo mau menggunakan cable gland, cable gland type brp yg di pilih? terimaksih sebelumnya Balas
aceng kalem 15 November 2014 01.32 mas ni smua tganga 220 volt ya ?? klo yg 380 volt gmana Balas
Suci Fitriani 16 Oktober 2015 11.38 kunjungi juga https://aksesoriskabelterbaik.wordpress.com/mengenal-cable-gland-dengan-spesifikasinya/ http://www.syafa-electric.com/
dan
Balas
Prastio B 28 Maret 2016 16.56 wkwkwkwkwkwkwk Balas
Halla Abin 3 Maret 2017 08.17 Terima kasih banyak ..... Balas
catur nugroho 12 Maret 2017 22.40 Tabel ini saya bandingkan dengan tabel di PUIL kok beda ya. Contoh: saya ingin menggunakan kabel NYY untuk arus 35A 3phase kalau di tabel puil bisa menggunakan ukuran 4x6mm2, tetapi ditabel ini untuk arus 35A menggunakan 4x16mm2. Yang benar acuannya mana y? Balas
2d i3
19/07/17 15 02
Standard PLN, Ukuran Kabel Minimal vs Ampere
http://readmedong.blogspot.co.id/2011/01/standard-pln-ukuran-kab...
suharianto labani 16 Mei 2017 11.17 Selamat siang semua, problem saya yaitu : Meteran 1.300 watt oleh pemasang instalasi, kabel out dari meteran 3x1,5mm dipasang mereka. Apakah Tidak menyalahi aturan PLN dengan pemasangan demikian, trim's Balas
suharianto labani 16 Mei 2017 11.41 Selamat siang semua, problem saya yaitu : Meteran 1.300 watt oleh pemasang instalasi, kabel out dari meteran 3x1,5mm dipasang mereka. Apakah Tidak menyalahi aturan PLN dengan pemasangan demikian, trim's Balas Balasan Heru 11 Juni 2017 01.03 Sebaiknya 3 x 4 mm Balas
Beri komentar sebagai:
Publikasikan
3d i3
19/07/17 15 02