C-Linx Configuration Software
Fike Corporation
C-Linx Configuration Software Version 6.4.4.0 Copyright © 2014 Fike Corporation Report Printed on 23/12/2014 Project Filename 'C:\Users\cbonilla\Deskt 'C:\Users\cbonilla\Desktop\Programaciones\19-12-14 op\Programaciones\19-12-14 DC GART OSINERGMIN.lnx'
Cheetah Xi Panel 001 Configuration Sales Outlet Information WESTFIRE SUDAMERICA SRL Calle Las Palomas 277 Lima, Surquillo Lima 34
Customer Information Name Address City, State ZIP
Page 1 of 12
C-Linx Configuration Software
Fike Corporation
Cheetah Xi Panel 001 Miscellaneous Settings AC Trouble Delay
12 hours
Abort Type
5
Panel Walktest
Enabled
Fan Restart
Automatic Restart
Auxiliary Loop Module
No Module
Auxiliary Power Module
No Module
Aux Battery Supervision
Disabled
Transformer Type
240VAC
Main Battery Supervision
Enabled
SLC Wiring Style
Style 4 - Class B
Ground Fault Supervision
L1 Enb L2 Enb
Unsilence Time
24 hours
Silence Reminder
Disabled
Silence Inhibit
Disabled
Silence Mode
UL Silence Mode
Panel Sync Protocol
System Sensor
Panel Switch Operation
Drill/Silence/Acknowledge Switches Enabled
Positive Alarm Sequence
Disabled
New Device Record Missing Trb
Disabled
Auto Message Sent at 12:00AM
Disabled
Eclipse Device Error AHU Fire Dept Key
Device Error is Trouble Not Required to restart AHU
Defaults Panel Line 2 Message
WESTFIRE SUDAMERICA
Password 1
1000
Password 2
0000
Password 3
0000
Password 4
0000
Password 5
0000
Password 6
0000
Password 7
0000
Password 8
0000
Default Photo Sensor
Page 2 of 12
C-Linx Configuration Software
Fike Corporation
Common Settings Custom Message Line 1
'1-001 PHOTO DETECT'
Custom Message Line 2
'LOOP 1'
Custom Message Line 3
'ADDRESS 001'
Zone Assignments
001
Alarm Verification
Alarm Verification Disabled
Alarm Sensitivity Settings Sensor Broadcast State
Sensor Broadcasts ALARM
Pre-Alarm 1
Disabled
Pre-Alarm 2
Disabled
Acclimate High
2.0%
Acclimate Low
2.5%
Pre-Discharge Type
Type A: Alarm Only
Drift Compensation Warning
80%
Drift Compensation Trouble
100%
Walktest Level
Walktest using Smoke at Alarm Level
Device Summing Settings Broadcast Threshold 1
Disabled
Broadcast Threshold 2
Disabled
Broadcast Threshold 3
Disabled
Broadcast Threshold 4
Disabled
Broadcast Threshold 5
Disabled
Broadcast Threshold 6
Disabled
Broadcast Threshold 7
Disabled
Broadcast Threshold 8
Disabled
Summing Address 1
No Device
Summing Address 2
No Device
Summing Address 3
No Device
Summing Address 4
No Device
Summing Address 5
No Device
Summing Address 6
No Device
Summing Address 7
No Device
Summing Address 8
No Device
Summing Alarm Level
Disabled
Summing Activation State
Summing Disabled
Remote Annunciator Settings Remote Annunciator Type
No Annunciator
Remote Annunciator Silence
Non-Silenceable
Remote Annunciator PAS
Disabled Page 3 of 12
C-Linx Configuration Software
Fike Corporation
Default Photo/Heat Sensor Common Settings Custom Message Line 1
'1-001 PHO/HT DETECT'
Custom Message Line 2
'LOOP 1'
Custom Message Line 3
'ADDRESS 001'
Zone Assignments
001
Alarm Verification
Alarm Verification Disabled
Alarm Sensitivity Settings Sensor Broadcast State
Sensor Broadcasts ALARM
Pre-Alarm 1
Disabled
Pre-Alarm 2
Disabled
Acclimate High
2.0%
Acclimate Low
2.5%
Flame Enhancement
Enabled
Pre-Discharge Type
Type A: Alarm Only
Drift Compensation Warning
80%
Drift Compensation Trouble
100%
Walktest Level
Walktest using Smoke at Alarm Level
Device Summing Settings Broadcast Threshold 1
Disabled
Broadcast Threshold 2
Disabled
Broadcast Threshold 3
Disabled
Broadcast Threshold 4
Disabled
Broadcast Threshold 5
Disabled
Broadcast Threshold 6
Disabled
Broadcast Threshold 7
Disabled
Broadcast Threshold 8
Disabled
Summing Address 1
No Device
Summing Address 2
No Device
Summing Address 3
No Device
Summing Address 4
No Device
Summing Address 5
No Device
Summing Address 6
No Device
Summing Address 7
No Device
Summing Address 8
No Device
Summing Alarm Level
Disabled
Summing Activation State
Summing Disabled
Page 4 of 12
C-Linx Configuration Software
Fike Corporation
Remote Annunciator Settings Remote Annunciator Type
No Annunciator
Remote Annunciator Silence
Non-Silenceable
Remote Annunciator PAS
Disabled
Default Photo/Duct Sensor Common Settings Custom Message Line 1
'1-001 DUCT DETECT'
Custom Message Line 2
'LOOP 1'
Custom Message Line 3
'ADDRESS 001'
Zone Assignments
001
Alarm Verification
Alarm Verification Disabled
Alarm Sensitivity Settings Sensor Broadcast State
Sensor Broadcasts ALARM
Pre-Alarm 1
Disabled
Pre-Alarm 2
Disabled
Acclimate High
2.0%
Acclimate Low
2.5%
Pre-Discharge Type
Type A: Alarm Only
Drift Compensation Warning
80%
Drift Compensation Trouble
100%
Walktest Level
Walktest using Smoke at Alarm Level
Page 5 of 12
C-Linx Configuration Software
Fike Corporation
Device Summing Settings Broadcast Threshold 1
Disabled
Broadcast Threshold 2
Disabled
Broadcast Threshold 3
Disabled
Broadcast Threshold 4
Disabled
Broadcast Threshold 5
Disabled
Broadcast Threshold 6
Disabled
Broadcast Threshold 7
Disabled
Broadcast Threshold 8
Disabled
Summing Address 1
No Device
Summing Address 2
No Device
Summing Address 3
No Device
Summing Address 4
No Device
Summing Address 5
No Device
Summing Address 6
No Device
Summing Address 7
No Device
Summing Address 8
No Device
Summing Alarm Level
Disabled
Summing Activation State
Summing Disabled
Remote Annunciator Settings Remote Annunciator Type
No Annunciator
Default Ion Sensor Common Settings Custom Message Line 1
'1-001 ION
Custom Message Line 2
'LOOP 1'
Custom Message Line 3
'ADDRESS 001'
Zone Assignments
001
Alarm Verification
DETECT'
Alarm Verification Disabled
Page 6 of 12
C-Linx Configuration Software
Fike Corporation
Alarm Sensitivity Settings Sensor Broadcast State
Sensor Broadcasts ALARM
Pre-Alarm 1
Disabled
Pre-Alarm 2
Disabled
Acclimate High
065 MIC
Acclimate Low
065 MIC
Pre-Discharge Type
Type A: Alarm Only
Drift Compensation Warning
90%
Drift Compensation Trouble
100%
Walktest Level
Walktest using Smoke at Alarm Level
Smoldering Enhancement
Disabled
Device Summing Settings Broadcast Threshold 1
Disabled
Broadcast Threshold 2
Disabled
Broadcast Threshold 3
Disabled
Broadcast Threshold 4
Disabled
Broadcast Threshold 5
Disabled
Broadcast Threshold 6
Disabled
Broadcast Threshold 7
Disabled
Broadcast Threshold 8
Disabled
Summing Address 1
No Device
Summing Address 2
No Device
Summing Address 3
No Device
Summing Address 4
No Device
Summing Address 5
No Device
Summing Address 6
No Device
Summing Address 7
No Device
Summing Address 8
No Device
Summing Activation Level
Disabled
Summing Activation State
Summing Disabled
Remote Annunciator Settings Remote Annunciator Type
No Annunciator
Remote Annunciator Silence
Non-Silenceable
Remote Annunciator PAS
Disabled
Default Heat Sensor
Page 7 of 12
C-Linx Configuration Software
Fike Corporation
Common Settings Custom Message Line 1
'1-001 HEAT DETECT'
Custom Message Line 2
'LOOP 1'
Custom Message Line 3
'ADDRESS 001'
Zone Assignments
001
Alarm Verification
Alarm Verification Disabled
Alarm Sensitivity Settings Pre-Alarm 1
Disabled
Pre-Alarm 2
Disabled
Daytime Alarm
135°F
Nighttime Alarm
135°F
Pre-Discharge Type
Type A: Alarm Only
Walktest Level
Walktest using Heat at 135°F
Fixed Temp or Rate
Sensor Implements Fixed Temperature Detection
Remote Annunciator Settings Remote Annunciator Type
No Annunciator
Remote Annunciator Silence
Non-Silenceable
Remote Annunciator PAS
Disabled
Default Monitor Module Common Settings Custom Message Line 1
'1-001 INPUT MANALRM'
Custom Message Line 2
'LOOP 1'
Custom Message Line 3
'ADDRESS 001'
Input Function
Manual Alarm
Input Latching Type
Latching Input
Input Contact Type
Normally Open Contact
Input Wiring Style
Class B
Input Short Detection
Short Detection is Disabled
Zone Assignments
001
Default Mini Monitor Module
Page 8 of 12
C-Linx Configuration Software
Fike Corporation
Common Settings Custom Message Line 1
'1-001 MINI MANALRM'
Custom Message Line 2
'LOOP 1'
Custom Message Line 3
'ADDRESS 001'
Input Function
Manual Alarm
Input Latching Type
Latching Input
Input Contact Type
Normally Open Contact
Input Short Detection
Short Detection is Disabled
Zone Assignments
001
Default Pull Station Module Common Settings Custom Message Line 1
'1-001 PULL STATION'
Custom Message Line 2
'LOOP 1'
Custom Message Line 3
'ADDRESS 001'
Input Function
Manual Alarm
Zone Assignments
001
Default Control Module Common Settings Custom Message Line 1
'1-001 OUTPUT MODULE'
Custom Message Line 2
'LOOP 1'
Custom Message Line 3
'ADDRESS 001'
Zone Assignments
001
Drill Output Pattern
On Continuous
Silence
Output is Silenceable
Positive Alarm Sequence
PAS is Disabled
Power Supply Monitor
Monitor is Enabled
Output Control Settings Priority
State
Action
Pattern
01
Alarm
Zone 001
On Continuous
32
Test Alarm
Zone 001
Walktest
Default Relay Module
Page 9 of 12
C-Linx Configuration Software
Fike Corporation
Common Settings Custom Message Line 1
'1-001 RELAY MODULE'
Custom Message Line 2
'LOOP 1'
Custom Message Line 3
'ADDRESS 001'
Zone Assignments
001
Drill Operation
Drill Operation Disabled
Silence
Output is Non Silenceable
Positive Alarm Sequence
PAS is Disabled
Relay Monitoring
Relay Monitoring is Disabled
Dry Contact
Dry Contact Not Used
Output Control Settings Priority
State
Action
Relay State
01
Alarm
Zone 001
On
Default Release Module Common Settings Custom Message Line 1
'1-001 RELEASING MOD'
Custom Message Line 2
'LOOP 1'
Custom Message Line 3
'ADDRESS 001'
Zone Assignments
No Zone Assignments
Output Control Settings Output Type
No Output Device
Output State
No Output State
Default FAAST Sensor Common Settings Custom Message Line 1
'1-001 FAAST DETECT'
Custom Message Line 2
'LOOP 1'
Custom Message Line 3
'ADDRESS 001'
Zone Assignments
001
FAAST States Fire 2
Disabled
No Alarm Verification
Fire 1
Alarm, Latching
No Alarm Verification
Action 2
Disabled, Non-Latching
No Alarm Verification
Action 1
Disabled, Non-Latching
No Alarm Verification
Alert
Disabled, Non-Latching
No Alarm Verification
Acclimate
Disabled Page 10 of 12
C-Linx Configuration Software
Fike Corporation
FAAST Daytime Sensitivity Fire 2
Range 1 [0.00046% to 0.04980
Disabled
Fire 1
Range 4 [1.00000% to 3.98819
2.50000% ft
Action 2
Range 1 [0.00046% to 0.04980 Disabled
Action 1
Range 1 [0.00046% to 0.04980 Disabled
Alert
Range 1 [0.00046% to 0.04980 Disabled
FAAST Nighttime Sensitivity Fire 2
Range 1 [0.00046% - 0.04980%] Disabled
Fire 1
Range 4 [1.00000% to 3.98819
2.50000% ft
Action 2
Range 1 [0.00046% to 0.04980 Disabled
Action 1
Range 1 [0.00046% to 0.04980 Disabled
Alert
Range 1 [0.00046% to 0.04980 Disabled
FAAST Miscellaneous Pre-Discharge Type
Type A: Alarm Only
Walktest
Disabled
Particulate Level Display
Fire 1 Level
Air Flow Display
020% Off Normal, Indicate Trouble After 000 seconds
Security
Test Button Locked, Isolate Button Locked, Passcode = 1111
Device Disable
Device cannot be Disabled by Holding the Isolate Button
Analog Broadcast
Increasing Step Disabled, Decreasing Step Disabled
Reference Address
Disabled
Isolate Broadcasts
No Alarm is Broadcast during Isolate
Relay Configuration Relay 1
Non-latching, Fire 2
Relay 2
Non-latching, Fire 1
Relay 3
Non-latching, Action 2
Relay 4
Non-latching, Action 1
Relay 5
Non-latching, Alert
Relay 6 A
Non-latching, High Airflow, Low Airflow, Isolate
Relay 6 B
Filter Minor, Filter Urgent, Filter Door, Configuration
Relay 6 C
Aspirator, Low Voltage, Comm, Time, Sensor
Addressable Devices Adr
1-001
Type
Custom Message 1
Function
Custom Message 3
Mini Monitor Module Manual Release
Custom Message 2 Zone 1
'SW PRESION DESCARGA' '2000-FMM-1003'
Page 11 of 12
Zone 2
Zone 3
Zone 4
'DATA CENTER GART' 002
000
000
000
C-Linx Configuration Software
1-002
1-003
1-004
1-005
1-006
1-007
1-008
1-009
1-010
1-011
1-012
1-013
1-014
1-015
1-016
1-017
1-018
1-019
Mini Monitor Module Supervisory Mini Monitor Module Supervisory Release Module Output - Solenoid Control Module Output Photo/Heat Sensor Photo-Alarm, Heat-Alarm Photo/Heat Sensor Photo-Alarm, Heat-Alarm Photo/Heat Sensor Photo-Alarm, Heat-Alarm Photo/Heat Sensor Photo-Alarm, Heat-Alarm Control Module Output Mini Monitor Module Abort Pull Station Module Manual Release Photo/Heat Sensor Photo-Alarm, Heat-Alarm Photo/Heat Sensor
Fike Corporation
'SW PRESION BAJA' '2000-FMM-1002'
'2000-FMM-1001'
'2000-FMD-1001'
'2000-FDF-1001'
'2000-FDF-1003'
'2000-FMO-1002'
'2000-FED-1001'
002
002
'LUZ DESCARGA'
Output
'2000-FMO-1003'
002
002
002
Page 12 of 12
000
000
000
000
000
000
000
000
000
000
000
000
000
000
000
000
000
000
000
000
000
'DATA CENTER GART' 002
000
000
000
'DATA CENTER GART' 002
000
000
000
'DATA CENTER GART' 002
000
000
000
'DATA CENTER GART' 002
000
000
000
'DATA CENTER GART' 002
000
000
000
'DATA CENTER GART' 002
000
000
000
'DATA CENTER GART' 002
'ALARMA SHP PRO' '2000-FMM-1007'
000
'DATA CENTER GART'
'SUPERVISION SHP PRO' '2000-FMM-1006'
000
'DATA CENTER GART'
'PROBLEMA SHP PRO' '2000-FMM-1005'
000
'DATA CENTER GART'
'DETECTOR FALSO PISO'
Control Module
000
'DATA CENTER GART'
'DETECTOR FALSO PISO' '2000-FDF-1005'
000
'DATA CENTER GART'
'EST. MAN. DESCARGA'
'2000-FMR-1001'
Supervisory
002
'PULSADOR DE ABORTO' '2000-FMM-1004'
000
'DATA CENTER GART'
'LUZ NIVEL 1'
Output
Mini Monitor Module
002
'DETECTOR FALSO TECHO' '2000-FDF-1004'
000
'DATA CENTER GART'
'DETECTOR TECHO'
'APAGADO A/A'
Supervisory
002
'DETECTOR FALSO TECHO' '2000-FDF-1002'
000
'DATA CENTER GART'
'DETECTOR TECHO'
Relay Module
Mini Monitor Module
002
'LUZ NIVEL 2' '2000-FMO-1001'
000
'DATA CENTER GART'
'DESCARGA NOVEC 1230'
'2000-FDF-1006'
Supervisory
002
'SW DESCONEXION'
Photo-Alarm, Heat-Alarm
Mini Monitor Module
'DATA CENTER GART'
000
000
000
'DATA CENTER GART' 002
000
000
000