MODULE OF THREE PHASE CIRCUITS
Reference Books: 1. B.L. Thareja, Volume-I,Basic Electrical Engineering. 2. R.G. Karandikar, Basic Electricity and Electronics - II
66
Zagdu Singh Charitable Trust’s (Regd.)
Thakur College of Engineering & Technology (Approved by AICTE, Govt. of Maharashtra & Affiliated to University of Mumbai) ISO 9001 : 2000 Certified
3 THREE PHASE CIRCUITS MOTIVATION: Present chapter deals with three phase systems and the behavior of the three phase system for 3-ph circuit with the concept of phaser diagram. The Chapter also highlights the comparision of single phase and three phase supply system.
SYLLABUS: OBJECTIVE: 1. 2. 3. 4. 5.
Genera Generatio tionn of three phas phasee voltage voltagess and curre current. nt. Balanc Balanced ed star star and and delt deltaa connec connectio tion. n. Relationshi Relationshipp between between phase phase and line line currents currents and voltages. voltages. Measur Measureme ement nt of power power by by wattmet wattmeter er method method.. Nume Numeri rica cals ls rela related ted to to topi topic. c.
KEY NOTATIONS : (Refer fig. 3.2,3.3) eR = Instantaneous value of generated voltage in winding RR 1 eY = Instantaneous value of generated voltage in winding YY1 eB = Instantaneous value of generated voltage in winding BB1 Em = Maximum voltage of induced voltage in each Winding. IL = line current Iph = phase current VL = RMS value of line voltage Vph = RMS value of phase voltage Zph = impedance/phase P = Total power
67
Zagdu Singh Charitable Trust’s (Regd.)
Thakur College of Engineering & Technology (Approved by AICTE, Govt. of Maharashtra & Affiliated to University of Mumbai) ISO 9001 : 2000 Certified
Q = Total reactive reactive power S = Total apparent power
KEY DEFINITIONS: Single Phase System – It is a system which generates single alternating voltage and current. It uses only one winding. Phase sequence or phase order – The – The sequence in which the voltage in the three phases reaches maximum positive value. Phase sequence of three phase system is R-Y-B. The direction of rotation of the three phase machines depends on the phase sequence. Line voltage – It – It is the voltage at any instant between two lines. Between R and Y line we have VRY. Phase voltage – It – It is the voltage of individual phases with respect to neutral. We have VR, VY, VB. Line current – It – It is the Phase current in any phase. We have IR, IY, IB Phase current – It – It is the current in individual phases. We have iR, iY, iB Balanced system – a – a three phase system is said to be balanced if (a) The voltages and current in the three phase are equal in magnitude and differ in phase from one another by 1200. (b) The all loads connected across the three phase have same magnitude and power factor (identical). (c)
Star connection (wye connection) – It is obtained by connecting similar terminals (start or finish) of the three windings together. This common point is called as neutral point. The remaining three ends of the windings are brought out for the external connection.
Delta connection (mesh connection) – It is obtained by connecting one end of the winding to the starting end of the other winding such that it produces a closed loop.
LEARNING RESOURCES: 1. B.L. Thareja, Volume-I,Basic Electrical Engineering. 2. R.G. Karandikar, Basic Electricity and Electronics – II
68
Zagdu Singh Charitable Trust’s (Regd.)
Thakur College of Engineering & Technology (Approved by AICTE, Govt. of Maharashtra & Affiliated to University of Mumbai) ISO 9001 : 2000 Certified
IMPORTANT RELATIONS: 1. Voltage, Voltage, current current and and power power relations relations in balanc balanced ed star star connected connected load: load:
VL = √3V ph IL = I ph Reactive power Q = 3V ph I ph sin ǿ 2. Voltage, cyrrent cyrrent and power relation in balanced delta connected load:
VL = V ph IL = √3 I ph P = 3V ph I ph cos ǿ S = 3V ph I ph = √3 VL IL Q = √3 VL IL sin ǿ S = √3 VL IL No.of hours allotted: 8 Hours Week allotted: 1.5 Lecture schedule Sr. no.
Topic
Hours required
1.
A.C.fundamental
2hrs
2.
Waveforms, diagram, diagram
3.
A.C circuit
4hrs
4.
Resonance circuit
2hrs
5.
Compensative study
2hrs
6.
Application area
2hrs
vector 4hrs phasor
69
Zagdu Singh Charitable Trust’s (Regd.)
Thakur College of Engineering & Technology (Approved by AICTE, Govt. of Maharashtra & Affiliated to University of Mumbai) ISO 9001 : 2000 Certified
INTRODUCTION TO TOPIC: Generation of three phase voltages: voltages : A system which generates a single alternating voltage and current is termed as single phase system. It utilizes only one winding. A polyphase system utilizes more than one winding. It will produce as many induced voltages voltages as the number of winding. A three phase system consists of three separate but identical windings that are displaced by 120 electrical degrees from each other. When these three windings are rotated in an anticlockwise direction with constant angular velocity in a uniform magnetic field, the emfs are induced in each winding which have same magnitude and frequency but displaced 120 0 from one another
Fig:3.1 The instantaneous values values of generated voltage in winding RR 1, YY1 and BB1 are given by eR = Em sin ө eY = Em sin (ө - 1200) eB = EB sin (ө - 240 0) (All are in time domain) Where Em is the maximum value of induced voltage in each winding. The waveform of these three voltages is shown in Fig
Fig 3.2. Phasor diagram of these three induced voltage.
70
Zagdu Singh Charitable Trust’s (Regd.)
Thakur College of Engineering & Technology (Approved by AICTE, Govt. of Maharashtra & Affiliated to University of Mumbai) ISO 9001 : 2000 Certified
Fig3.3 STAR OR WYE CONNECTION: In the method, similar terminals (start or finish) of the three winding are joined together as shown in Fig. 3.5. The common point is called star or neutral point.
Fig.3.4 iR = Im sin ө iY = Im sin (ө - 120 0) iB = Im sin (ө - 240 0) iR + iy + iB = Im sin ө +I m sin (ө - 120 0) + Im sin (ө - 240 0) = 0 (All are in time domain)
71
Zagdu Singh Charitable Trust’s (Regd.)
Thakur College of Engineering & Technology (Approved by AICTE, Govt. of Maharashtra & Affiliated to University of Mumbai) ISO 9001 : 2000 Certified
Fig.3.5 DELTA OR MESH CONNECTION: CONNECTION: In this method, dissimilar terminals of the three winding are joined together i.e. ‘finish’ terminal of one winding is connected to ‘start’ terminal of other winding and so on as shown in Fig.3.8 This system is also called three phase, three wire system.
Fig.3.6 For a balanced system sum of the three phase voltages voltages round the closed mesh is zero. The three emfs are equal in magnitude but differ in phase from one another by 120 0. eR = Em sin ө eY = Em sin (ө - 120 0) eB = Em sin (ө - 240 0) eR + eY + eB = Em sin ө + E m sin (ө – 120 0) + E m sin (ө - 240 0) = 0 (All are in time domain) APPLICATIONS: Application of three phase systems are1. Three phase systems are generally used for Industrial purpose. 2. It is generally used where large power application required e.g. Sub-stations, in transmission systems where high efficiency required, etc. 3. In High voltage voltage transmis transmission sion system system it is is mostly mostly used. used. KEY DERIVATIONS: 1. VOLT VOLTAG AGE E, CU CURR RRE ENT AN AND D POW POWER RELA RELATI TION ONS S IN BALA BALANC NCE ED CONNECTED LOAD -
STAR STAR
Relation between line voltage and phase voltage: Since the system is balanced, the three phase voltages VRN, VYN and VBN are equal in magnitude and differ in phase from one another by 120 0.
72
Zagdu Singh Charitable Trust’s (Regd.)
Thakur College of Engineering & Technology (Approved by AICTE, Govt. of Maharashtra & Affiliated to University of Mumbai) ISO 9001 : 2000 Certified
Fig. 3.7 Let VRN = VYN = VBN = V ph Where V ph indicates rms value of phase voltage = Vph ∠ 00 0 = Vph = V ph ∠-2400 Let VRY = VYB = VBR = VL Where VL indicates rms value of line voltage. Applying Kircoff ‘s voltage law, = + = = V ph ∠ 00 - V ph ∠ -1200 = V ph + j0 + 0.5 V ph + j0.866 V ph = 1.5 V ph + j0.866 V ph = √3 V ph ∠ 300 Similarly, = + = √3 V ph ∠300 = + = √3 V ph ∠300 Thus in a star connected three phase system V L = √3 V ph and line voltages lead respective phase voltages by 30 0 . Phasor Diagram: (Lagging power factor )
73
Zagdu Singh Charitable Trust’s (Regd.)
Thakur College of Engineering & Technology (Approved by AICTE, Govt. of Maharashtra & Affiliated to University of Mumbai) ISO 9001 : 2000 Certified
Fig. 3.8 Relation between line current and phase current: From the fig 3.9, it is clear that line current is equal to the phase current. IL = I ph Power: The total power in three phase system is the sum of powers in the three phases. For a balanced load, the power consumed in each load phase is the same. Total Tot al power power P = 3 power power in eac eachh phas phasee = 3 V ph I ph cos ǿ In a star connected three phase system, V ph = VL / I ph = IL P = 3 VL/ 3 IL cos ǿ = VL IL cos ǿ Where ǿ is the phase difference between phase phase voltage and corresponding phase phase current. Similarly, total total reactive reactive power Q = 3V ph I ph sin ǿ = VL IL sin ǿ Total apparent power S = 3 V ph I ph = 3 VL IL 2. VOLT VOLTAG AGE, E, CURR CURRE ENT AND AND PO POWE WER R RELA RELAT TIONS IONS IN BALAN ALANCE CED D DEL DELATA ATA CONNECTED LOAD-
74
Zagdu Singh Charitable Trust’s (Regd.)
Thakur College of Engineering & Technology (Approved by AICTE, Govt. of Maharashtra & Affiliated to University of Mumbai) ISO 9001 : 2000 Certified
Fig. 3.9 Relation between line voltage and phase voltage : From Fig 3.11, It is clear that line voltage is equal to phase voltage. VL = V ph Relation between line current and phase current : Since the system is balanced, the three phase current I RY,IYB and I BR are equal in magnitude but differ in phase from one another by 120 0. Let IRY = IYB = I ph Where I ph indicates rms value of phase current. = I ph ∠0 0 = I ph ∠-120 0 = I ph ∠-2400 Let IR = IY = IB = IL Where IL indicates rms value of line current. Applying Kirchhoff’s current law, + = = = I ph ∠0 0 – I ph ∠-240 0 = I ph + j0 + 0.5 I ph – j0.866 I ph = I ph ∠-30 0 Similarly , = = I ph ∠-30 0 = = I ph ∠-30 0 Thus in a delta connected three phase system, I L = I ph and line current are 30 0 behind the respective phase current. Phasor Diagram: (Lagging ( Lagging power factor )
75
Zagdu Singh Charitable Trust’s (Regd.)
Thakur College of Engineering & Technology (Approved by AICTE, Govt. of Maharashtra & Affiliated to University of Mumbai) ISO 9001 : 2000 Certified
Fig.3.10 Power: Total power power P = 3 V ph I ph cos ǿ In a delta connected three phase system, V ph = VL I ph = IL/ P = 3 VL IL / 3 cos ǿ = VL IL cos ǿ Total reactive power Q = 3V ph I ph sin ǿ = VL IL sin ǿ Total apparent power S = 3 V ph I ph = VL IL BALANCED Y / AND /Y CONVERSION: Any balanced star connected system can be completely converted into equivalent delta connected system and vice versa. For a balanced star connected load, Line voltage = V L Line current = I L Impedance/ phase = Z y V ph = VL / I ph = IL ZY = V ph/I ph = VL/ IL For an equivalent equivalent delta connected connected system, system, the line voltage and and current must have have the same values as in the star connected connected system i.e. Line voltage = V L Line current = I L Impedance/phase = Z
76
Zagdu Singh Charitable Trust’s (Regd.)
Thakur College of Engineering & Technology (Approved by AICTE, Govt. of Maharashtra & Affiliated to University of Mumbai) ISO 9001 : 2000 Certified
V ph I ph Z ZY
= = = =
VL I L/ V ph / I ph = VL / IL / Z /3
VL / IL = 3ZY
3. RELATIO RELATION N BETWEEN BETWEEN POWER IN DELTA DELTA AND STAR STAR SYSTE SYSTEM M Let a balanced load be connected in star having impedance per phase as Z ph. For star connected load, V ph = VL / I ph = V ph / Z ph = VL / Z ph IL = I ph = VL / Z ph Now PY = VL IL cos ǿ = V L VL / Z ph cos ǿ = / Z ph cos ǿ For delta connected load, V ph = VL I ph = V ph / Z ph = VL / Z ph IL = I ph = VL/Z ph Now P = LVIL cos ǿ = VL VL / Z ph cos ǿ = 3 Z ph cos ǿ =3 PY Thus power consumed by a balanced star connected load is one third of that in the case of delta connected load. SOLVED NUMERICALS:
1. Three equal impedances each 8 + j10 ohms are connected in star. This is further connected to a 440 V, 50 Hz, three phase supply. Calculate the active and reactive power and line li ne and phase currents. (Dec-10, 10marks)
Data:
Z ph = 8 + j10 Ω VL = 440 V
f = 50 Hz For star connected load, V ph = VL/√3 = 440/√3 = 254.03V Z ph = 8+j10 = 12.81 <51.34 0 Ω
77
Zagdu Singh Charitable Trust’s (Regd.)
Thakur College of Engineering & Technology (Approved by AICTE, Govt. of Maharashtra & Affiliated to University of Mumbai) ISO 9001 : 2000 Certified
Z ph = 12.81 Ω ǿ = 51.34 0 I ph = V ph/Z ph = 250.03/12.81 = 19.83 A IL = I ph = 19.83 A P
= √3 VL IL cos ǿ = √ 3 440 19.83 cos (51.340) = 9.44 kW
Q = √3 VL IL sin ǿ = √3 440 19.83 sin (51.340) = 11.81kVAR.
(Ans)
415 V. 50 Hz, three phase voltage is applied to three star connected identical impedances. Each impedance consists of a resistance of 15 Ώ, capacitance of 177 µF and inductance of 0.1 Henry in series. Find (i) phase current (ii) line li ne current (iii) power factor (iv) active power (v) reactive power (vi) total VA.Draw a neat phasor diagram. If the same impedances are connected in delta, find (i) line current (ii) power consumed. 2.
Data:
VL = 415 Ω
F = 50 Hz
R = 15 Ω
C = 177 µF
L = 0.1 H For star connected load, V ph = VL/√3 = 415/√3 = 239.6 V XL = 2πfL =2π
50 0.1 = 31.42 Ω
Xc = 1/2 fC = 1/2π /2π
50
177
10.6 = 17.98 .98 Ω
Z ph = R + jXL – jXC = 15 + j31.42 – j17.98 = 15 + j13.44 = 20.14 <41.860 Ω Z ph ǿ Power factor
= 20.14 = 41.860 = cos ǿ = cos (41.860) = 0.744 (lagging)
I ph
= V ph/Z ph = 239.6/20.14 = 11.9 A
78
Zagdu Singh Charitable Trust’s (Regd.)
Thakur College of Engineering & Technology (Approved by AICTE, Govt. of Maharashtra & Affiliated to University of Mumbai) ISO 9001 : 2000 Certified
IL P
= I ph = 11.9 A = √3VL IL cos ǿ = √3
415
11.9
0.744
= 6.36 kW Q
= √3 VL IL sin ǿ = √3
415
11.9
sin (41.860)
= 5.71 kVAR S
= √3VL IL = √3
415
11.9
= 8.55 kVA
If same impedances are connected in delta, VL = V ph = 415 V Z ph = 20.14 Ω I ph = V ph/Z ph = 415/10.14 = 2061 A IL = √3 I ph = √3
20.61 = 35.69 A
P = √3 VL IL cos ǿ 79
Zagdu Singh Charitable Trust’s (Regd.)
Thakur College of Engineering & Technology (Approved by AICTE, Govt. of Maharashtra & Affiliated to University of Mumbai) ISO 9001 : 2000 Certified
= √3
415
35.69
0.744
= 19.09 kW
(Ans)
STAR AND DELTA CONNECTION: 1. A circuit has XL=20 Ω at 50Hz its resistance being 15 Ω.For an applied voltage of 200V at 50Hz,Calculate: 1. P.F. 2. Current Current 3. Value Value of shunting capacitance capacitance to bring the resultant resultant current current into phase with the applied voltage4.resultant curren tin case 3. 10Marks (Dec-10) 2. Three idnetical coils, each having resistance of 15 Ώ and inductance of 0.03 H, are connected in delta across a three phase ,50 Hz ,230 V supply. Calculate the phase current, line current, and total power absorbed. draw phasor diagram. 10Marks (June 2008 ) 3. Three non inductive resistances each of 100 ohm connected in star to 3 phase 440V supply. Three ideal equal choke are also connected in delta to the same supply, the reactance of one of the coil being equal to 100 ohm. Calculate i) line current ii) power factor of the system. 10Marks (Dec2007 ) 0 [ I L = 8.03∠ − 7.15 , p.f=0.317 ] 4. A balanced three phase load connected in delta draws a power of 10 kW at 440 V at a power power factor factor of 0.6 lead. Find the lead, find the values values of the circuit elements and (May 2004) the reactive voltamperes drawn.
8 Marks [2.873 Ω , 4.975 Ω , 18.079 KVAR] 5. Three Three equal impedances each 8 + j10 ohms are connected in star. This is further connected to a 440 V, 50 Hz, 3 φ supply. Calculate the active and reactive power and line and and phase currents. (Dec-10,Dec. 88)
10Marks[ 9.458 KW, 11.806 KVAR, 19.85 A, 19.85 A] 6.A balanced delta connected load of impedance (8 – j6) ohm per phase is connected to a three phase 230 V, 50 Hz supply. Calculate : (i) line current (ii) power factor (iii) reactive power. Draw phasor diagram. (May 94)
10Marks
[39.83 A, 0.8 leading, 9.52 KVAR]
7. Three Three coils, each having resistance of 8 Ω inductance of 0.02 H are connected in (i) star (ii) delta to a 3 φ, 230 V, 50 Hz ac supply. Calculate in both cases, the various line and phase quantities and the total power absorbed. (May 98)
[ 13.05 A, 132.79V, 10.17 Ω, 4.088 kW, 39.33 A, 68.12A, 10.17 Ω, 37.124kW] 8. Three Three similar coils A, B, and C are available. Each coil has 9 _ resistance and 12 _ reactance. They are connected in delta to a 3φ, 440 V, 50 Hz supply. Calculate phase 80
Zagdu Singh Charitable Trust’s (Regd.)
Thakur College of Engineering & Technology (Approved by AICTE, Govt. of Maharashtra & Affiliated to University of Mumbai) ISO 9001 : 2000 Certified
current, line current, power factor, total kVA, active power and reactive power. If these coils are connected in star across same supply, calculate all the above quantities. 10Ma 10Mark rks s [May [May 91] 91] [ 29.33 A, 50.8 A, 0.6 lagging, 38.72 KVA, 23.23 KW, 30.97 KVAR, 16.94 A, 16.94 A, 0.6 lagging,12.91 KVA, 7.74 KW, 10.33 KVAR ] 9.415 415 V, 50 Hz, three three phase phase volta voltage ge is applie applied d to three three star star conne connecte cted d identi identical cal impedances. Each impedance consists of a resistance of 15 _, capacitance of 177 µF and inductance of 0.1 henry in series. Find (i) phase current (ii) line current (iii) power factor (iv) active power (v) reactive power (vi) total VA. Draw a neat phasor diagram. If the same impedances are connected connected in delta, find (i) line current (ii) power consumed.
10 Marks (May 88) [11.9 A, 11.9 A, 0.744 lagging, 6.36 KW, 5.71 KVAR, 8.55 KVA, 35.69 A, 19.09 KW ] 10.Each phase of a delta connected load consists of a 50 mH inductor in series with a parallel combination of 50 Ω resistor and 50 µF capacitor. The load is connected to three phase, 550 V, 800 rad/sec AC supply. Find (i) phase current (ii) line current (iii) power drawn (iv) power factor (v) reactive reactive power (vi) kVA rating of of the load. 10Marks (May 95,Dec-10)
[24.59 A, 42.604 A, 18.151 KW, 0.447 lagging, 36.3 KVAR, 40.59 KVA] 11.Calculate the active and reactive components of the current in i n each phase of a star connected connected 5000 V, 3φ, alternator alternator supplying 3000 KW at a pf of 0.8. 8 Marks Marks (May 98)
[250 A, 150A] 12.A three phase, 208 volt generator supplies a total of 1800 W at a line current of 10 A when three identical impedances are arranged in Wye connection across the line terminals of the generator. Compute the resistive and reactive components of each phase impedance. 8 Marks (Dec. 89)
[6
Ω ,
10.39 Ω ]
13. Three Three similar choke coils are connected in star to a 3φ supply. If the line current is 15 A, the total power consumed is 11 kW and the volt-ampere input is 15 kVA, find the line and phase voltages, the VAR input and the reactance reactance and resistance of each coil. If these these coils coils are are now connect connected ed in delta delta to same same supply supply,, calcu calculat late e phase phase and and line currents, active and reactive power. 10Marks (Dec. 92) (Dec. 91, May 97, Jan 2004)
[577.36 V, 333.35 V, 10.19 KVAR, 15.11 Ω , 18.289 Ω , 25.98 A, 45 A, 32.98 KW, 30.59 KVAR] 14. Three Three identical coils connected in delta to a 440 V, three phase supply take a total power of 50 kW and a line current of 90 A. Find phase current, power factor, total apparent power taken by the coils. (Dec. 92)
81
Zagdu Singh Charitable Trust’s (Regd.)
Thakur College of Engineering & Technology (Approved by AICTE, Govt. of Maharashtra & Affiliated to University of Mumbai) ISO 9001 : 2000 Certified
[57.961 A, 0.7289 lagging, 68.589 KVA]
8 Marks
15.A 3 φ star connected source feeds 1500 kW at 0.85 power factor lag to a balanced mesh connected load. Calculate the current, its active and reactive components in each phase of the source and the load. The line voltage is 2.2 kV. 8 Marks (Dec. 95)
[463.11 A, 393.64 A, 243.95 A] 16.A balanced three phase load connected in delta draws a power of 10.44 kW at 200 V at a power factor of 0.5 lead. Find the values of the circuit elements and the reactive voltamperes drawn. (May 95)
10Marks [ 0.908 Ω , 27.878 , 13.555 Ω
KVAR]
MEASUREMENT OF POWER:
Example: Three coils each each with a resistance resistance of 10 Ω and reactance reactance of 10 Ω are connected in star across a three phase, 50 Hz, 400 V supply. Calculate (i) Line current and (ii) Readings on the two wattmeter’s connected to measure the power. Data:
R = 10 Ω
XL = 10 Ω
VL = 400 V For star connected load, V ph = VL/√3 = 400/√3 = 230.94 V Z ph = R + jXL = 10 + j10 = 14.14 <45 0 Ω Z ph = 14.14 Ω ǿ = 450 Power factor = cos ǿ = cos (450) = 0.707 (lagging) I ph
= V ph/Z ph = 230.94/14.14 = 16.33 A
IL
= I ph = 16.33 A
P
= √3VLIL cos ǿ = √3
400
16.33
0.707
82
Zagdu Singh Charitable Trust’s (Regd.)
Thakur College of Engineering & Technology (Approved by AICTE, Govt. of Maharashtra & Affiliated to University of Mumbai) ISO 9001 : 2000 Certified
Also
= 7998.83 W W1 – W2 = 7998.83 W Tan ǿ = √3
W1 –W –W2 / W1+W2
Tan 450 = √3
W1-W2 / 7998.83
W1-W2 = 4618.13 W Solving equations (1) and (2), W1
= 6308.48 W
W2
= 1690.35W
1. Three identical coils each having a resistance of 8 Ω and inductance of 0.02 H are connected in (i) star and (ii) Delta across 3φ, 400 V, 50 Hz supply. Draw neat phasor diagram and calculate the readings of two wattmeters connected to measure power. Also calculate pf of the circuit. 10 Marks (May 2000)
[W1=8.99kW, W2=3.38kW, 0.7866 lag W 1=26.979kW, W1=10.144kW, 0.7866 lag] 2. Thre identical coils each having a reactance of 20Ω and resistance of 10Ω are connected in (i) star (ii) delta across a 440 V, 3 phase line. Calculate for each method of connection the line current and readings on each of the two watt meters connected to measure the power. 10 Marks (Jan 2003)
[11.3609A, 4171.79 W. -299.073 W, 34.083 A, 12515.59W, -697.227W] 3. Two wattmeters connected to measure the total input to a balanced 3 φ circuit indicate 2000 W and 500 W respectively; the latter reading being obtained by reversing the terminals of current coil. Find the pf of the circuit. 8 Marks (May 96)
[0.3272 lagging] 4. Find the power and power factor of the balanced circuit in which the wattmeter readings are 5 k Ω and 0.5 kW, the latter being obtained after the reversal of current coil terminals of the wattmeter. (May 96)
8 Marks [4.5 kW, 0.427 lagging]
83
Zagdu Singh Charitable Trust’s (Regd.)
Thakur College of Engineering & Technology (Approved by AICTE, Govt. of Maharashtra & Affiliated to University of Mumbai) ISO 9001 : 2000 Certified
5. Three star connected impedances Z1 = ( 20+ j37.7 ) per phase are conncted in parallel with thre delta connected connected impedances impedances Z2 = ( 30- j59.3 ) per phase. The line volt voltag age e is 398 398 V. Find Find line line curr curren ent, t, p.f, p.f, powe powerr and and reac reacti tive ve VA take taken n by the the combination. combination . 10Marks ( Dec 2006 ) 6. 3 - phase ,220 V ,50 Hz ,11.2 KW induction motor has full load efficiency 88% and draws a line current of 38 A under full load when connected to 3 hase 220 V supply. Find thwe reading on the two wattmeter connected in the circuit to measure the input to the motor. motor. Dete Determi rmine ne also also the pf at whichh whichh the motor motor is opera operating ting.. 8Marks ( June 2007 ) 7. Two wattmeters connected to measure the power input to 3 phase circuit, indicate 2500W and 500W respectively, Find the power factor of the circuit
i) when both reading are positive ii) When When later later readin reading g is obtai obtained ned after after rever reversin sing g the conne connecti ction on to the current coil of one instrument. 10Marks
(Dec -07,Dec-10) -07,Dec-10)
[0.36 lag , 0.65lag] 8. A 3-ph RYB system has effective line voltage 173.2v.Wattmeter in lines R and Y read read 301w 301w and and 1327 1327w w resp respec ecti tive vely ly.. Find Find the the impe impede denc nce e of the the bala balanc nce e star star connected load. 10 Marks
(Dec-08)
[Z==12.45<47.5 Ω] 9. Calculate the total power and reading of two wattmeters connected to measure power in t hree phase balance load, if the reactive power is 15 KVAR, and load P.F. is 0.8 lagg. 10 Marks [20KW]
SHORT QUESTIONS:
84
(Dec-08)
Zagdu Singh Charitable Trust’s (Regd.)
Thakur College of Engineering & Technology (Approved by AICTE, Govt. of Maharashtra & Affiliated to University of Mumbai) ISO 9001 : 2000 Certified
1. Explain two wattmeter method for power measurement in 3-ph delta connected balance load. Also draw the phasor diagram. 10 marks (Dec-10)
2. Show only two t wo wattmeter are sufficient to measure 3-ph power. Also state advantages of two wattmeter. 10 marks
(May-10)
3. Show that the algebraic sum of all potential difference in delta nerwork is zero. (Show graphically).
8 marks (Dec 2007) 4. Prove that for 3 phase balanced b alanced delta connected lode line current is
current. 10 marks
Also
define
power triangle (June 2008)
in
3
3 times phase
phase
circuits.
5.Deduce the relationship between phase and line quantities (voltage, current, power) in the circuit of a three phase delta connected connected system. Also draw neat diagram diagram
10 marks.
(Dec. 98, Dec. 2000, Dec. 2001,
July 2002, May-10) 6.Deduce the relationship between phase and line quantities (voltage, current, power) in the circuit of a three phase star connected system. Also draw neat diagrams.
8 marks
(Dec. 96,
May 98, Dec. 98) 7. Explain merits of two wattmeter method for power measurement, giving circuit diagram and phasor.
5marks (Jan 2004, June 2008) 8. Explain with phasor diagram of how two wattmeter can be used to measure power in 3phase system. Also
expla explain in 5marks
the variat variation ions s in the the wattm wattmete eterr read readings ings with load power power facto factors. rs. (Jan 2003)
OBJECTIVES QUESTIONS : 1. A delta circuit has each element of value R/2. The equivalent elements of star circuit will be (a) 2R
(b) 6R 85
Zagdu Singh Charitable Trust’s (Regd.)
Thakur College of Engineering & Technology (Approved by AICTE, Govt. of Maharashtra & Affiliated to University of Mumbai) ISO 9001 : 2000 Certified
(c) 3/2 R Ans:(--)
(d) R/6
2. In case of delta connected circuit, when one resistor is open, power will be (a) zero (b) reduced reduced to 1/3 (c) reduced by 1/3
(d) unaltered
Ans:(--) 3. For three phase star connected circuit, (a) Line vo voltage = phase voltage (c) Line current = √3 phase current
(b) Line current= ph phase current (d) None of the above is true
Ans:(--)
4. Which of the following is true for a three phase delta connected circuit (a) Line vo voltage = phase voltage (b) Line current= ph phase current (c) Line current = 1/ √3 phase vo voltage
(d) Li Line ccuurrent = √3 phase current
Outcomes: In some applications single phase ac supply is not suitable; so some load needs a polyphase ac supply. The word polyphase means many, thus a polyphase ac supply is the one which produces many phases simultaneously. 2. A poly polyph phas asee syst system em has has an adva advant ntag agee of more more outp output ut,, smal smalle lerr size size,, more more powe powerr is transmitted, small cross sectional area of conductors, better power factor, high transmission efficiency etc over the single phase system. system. Hence they are preferred practically. 3. Secondly the power is dependent on power factor cosΦ alongwith Voltage & Current. So in order to measure the 3 ph active power, we need to use an instrument which will sanse voltage, current as well as the power factor and give the reading directly in watts. The instrument which can do this is a Wattmeter. 1.
Ans:(--) 5. In three phase star connections, line voltage is the same as (a) Phase voltage
(b) 1/√3 phase voltage
(c) √3 phase voltage
(d) 3 phase current
Ans:(--)