PowerCube 1000 (with DCB) V300R001
Quick Installation Guide
Issue: 03 Date: 2013-03-18 HUAWEI TECHNOLOGIES CO., LTD.
Precautions ■ Safety Precautions To ensure safety of humans and the equipment, pay attention to the safety symbols on the equipment and all the safety instructions in this document. The "NOTE", "CAUTION", and "WARNING" marks in other documents do not represent all the safety instructions. They are only supplements to the safety instructions. When operating Huawei equipment, in addition to following the general precautions in this document, follow the specific safety instructions given by Huawei. Huawei will not be liable for the consequences that are caused by the violation of the safety operation regulations and design, production, and usage standards. ■ Local Safety Regulations When operating Huawei equipment, you must follow the local laws and regulations. The safety instructions in this document are only supplements to the local laws and regulations. ■ Personnel Requirements Only trained and qualified personnel are allowed to install, operate, and maintain Huawei equipment. You can modify default parameters only after being granted approval from Huawei technical support. ■ Symbols Alerts you to a potentially hazardous situation that could, if not avoided, result in equipment damage, data loss, performance deterioration, or unanticipated results.
Provides additional information to emphasize or supplement important points of the main text.
■ Human Safety To prevent electric shock, get tools insulated and wear electrostatic discharge (ESD) gloves when connecting cables. To prevent dust inhalation or contact with the eyes, take adequate preventive measures when drilling holes.
Installation Tools
Flat-head screwdriver (M3 and M4)
Wire stripper
Hammer drill
Cable tie
ESD gloves
Phillips screwdriver (M3 and M4)
Hydraulic pliers
Heat gun Crane (with a capacity of greater than 2 t)
Protective gloves
Adjustable wrench
Claw hammer
Fuse extracting unit PVC insulation tape
Socket wrench
Marker
Diagonal pliers
COAX crimping tool
Clamp meter
Electrician's knife
Heat shrink tubing
Antitheft wrench
Hoist cable (7 m or 22.97 ft)
Torque wrench
Insulation gloves
1
Removable gantry (consisting of two triangle supports, one guide beam, and one lever block)
Power Cube Architecture and Network Diagram 1. ECC and ESC-1D is Mandatory Device. 2. EPS-10G only used in the scenario with new diesel generators provide main power supply. The reused D.G. used in the scenario with new diesel generators provide backup power, and it is also called backup D.G.. The reused D.G. used in the scenario without new D.G. provide main power supply. 3. Indoor DC air conditioner only used in indoor scenario. 4. The backup D.G., Mains supply, ESPS48200B, DC ammeter, is optional.
Outdoors Mandatory Device
Device only used in the Scenario with a New D.G.
Device only used in the Scenario with a Reused D.G.
Optional Device
ECC
EPS-10G
The reused D.G.
Mains suppiy
Device
Scenario
ESC-1D(DCB)
The backup D.G.
New D.G.
New D.G. + Mains New D.G. + External D.G. New D.G. + Solar New D.G. + Solar+ Mains New D.G. + Solar+ Back up D.G. Reused D.G.
Reused D.G. + Mains
2
ESPS48200B
DC ammeter
Power Cube Power Cube
EPS-10G ECC ESC-1D
Power Cube Architecture and Network Diagram AC power cable (a) DC power cable (d) Signal cable (s) Optional
a
Power Cube architecture
s1 s3
s2 Power system
Battery temperature sensor
d1
DCB
d2 ECC
DC air conditioner/natural ventilation
Door status sensor
HPMU
ESC-1D
(d1) DC power cable to the DC air conditioner or natural ventilation in the ESC (d2) DC power cable between the DCB and the power system (s1) Signal cable to the DC air conditioner or natural ventilation in the ESC for alarm generation (s2) Signal cable to the battery temperature sensor in the ESC (s3) Signal cable to the door status sensor in the ESC
3
b
Network diagram With a New D.G.(Outdoors)
GPRS/IP Network NetEco
Back up D.G.
Mains supply
s1
a1 d1
s2
D.G. ECC
a2 d3
Fuel tank
d2
ESC -1D
DC-powered load
Power Cube
PV modules Junction box (a1) AC input power cable to the external D.G (a2) AC input power cable for mains supply (d1) DC power cable to the DC-powered load (d2) DC power cable between PV modules and the junction box (d3) DC power cable between the ESPS48200B and the junction box (d4) DC power cable to indoor DC air conditioner 1 (d5) DC power cable to indoor DC air conditioner 2 (s1) Signal cable between the OMU and the transport network . (Optional, Global System for Mobile Communications (GSM) antenna is required when the OMU is connected to the transport network by GPRS.) (s2) Signal cable for controlling the external D.G. (s3) Signal cable to indoor DC air conditioner 1 for alarm generation (s4) Signal cable to indoor DC air conditioner 2 for alarm generation
4
Installation Procedure 1.New D.G.+DCB (Outdoors) 1) Installing Devices a. Securing the Power Cube
b. Switching Off All Power Circuit Breakers of the Power Cube c Adding Diesel Fuel, Engine Oil, and Water to the EPS d. Installing DCBs
2) Installing Cables a. Connecting a Ground Cable to the ECC
b. Connecting Cables Between the ECC and Both the DC Air Conditioner and Door Status Sensor
c. Connecting Cables Between the ESC and the ECC
d. Connecting a Ground Cable to the ESC e. Connecting a Power Cable to the D.G. Storage Battery
f. Connecting DC Power Cables to DC-powered Loads
g. Connecting Communications Cables to the HPMU
h. (Optional, only used without NetEco) Connecting Signal Cables to the HPMU
i. Checking Cable Connections
3) Powering On and Commissioning the Power Cube a. Powering On Batteries
b. Set parameters on the HPMU
c. Powering On the D.G.
d. Powering On Loads
This document takes New D.G. + DCB as the basic scenario, please installing other scenarios according to the basic scenario.
5
New D.G.+DCB (Outdoors) 1. Installing Devices
a
Securing the Power Cube Route hoist cables through the four lifting holes at the bottom of the Power Cube and secure them at the base of the energy plant system (EPS). Then hoist the EPS and the ECC to the installation place using a crane.
1.To avoid friction between the hoist cables and the cabinet when hoisting the Power Cube, place foamed plastics where the hoist cables contact the cabinet. 2.For disassemble the Power Cube into the ECC, D.G., and base fuel tank, and then install them, please see the Removing and Installing the Power Cube Quick Installation Guide.
If paint flakes off during transportation, repaint the areas devoid of paint. The cabinet bottom is the particular place to the focused on, because the bottom fuel tank may leak if it rusts.
Install expansion bolts in the mounting holes to secure the cabinet.
Φ: 16 mm (0.63 in.)
Marker
M12x60 (4 pcs)
55–60 mm (2.17–2.36 in.)
If the concrete base is to small , please install the expansion bolt inside the Power Cube. Unit: mm
6
Determine the place for installing the ESC using a marking-off template and install expansion bolts. Socket wrench
Bolt Spring washer Flat washer Expansion tube M12x60 (4 pcs)
Ф 16 55–60 mm (2.17–2.36 in.)
Notes: Please must do it and fasten battery cabin.
Fasten hoist cables to the lifting eyes on the ESC top and hoist the ESC to the installation place. Securing the ESC using expansion bolts.
Antitheft bolt
b
Switching Off All Power Circuit Breakers of the Power Cube Switch off the AC, BAT1–, BAT2–, BLVD, and LLVD circuit breakers in the power distribution unit (PDU) of the power system in the ECC and turn off the BC power switch.
Switch the DG INPUT, MAINS INPUT, and AC output circuit breakers as well as the auto mains failure (AMF) power switch of the Integrated Automatic Transfer Switch (IATS) to the OFF position. Press the EMERGENCY STOP button.
Power system
OFF OFF BC OFF OFF
7
OFF
c
Adding Diesel Fuel, Engine Oil, and Water to the EPS Yanmar and Kubota can be in EPS-10G, the operation must according to actual conditions. Add 800 to 1000 liters of diesel fuel at the diesel fuel filler port. Yanmar
Diesel fuel filler port
Notes: Please do not reuse a water pipe or oil pipe to instead diesel oil pipe.
Add 6 liters of engine oil at the oil pan filler port and 37 liters of engine oil at the auxiliary engine oil filler port.
Yanmar Please use manual pump to add engine oil at the oil pan filler port.
Oil pan filler port
Auxiliary engine oil filler port
8
Notes: Please do not reuse a water pipe or diesel oil pipe to instead oil pipe.
Add about 14 liters of water at the water filler port. Water filler port
Notes: Please do not reuse a oil pipe or diesel oil pipe to instead water pipe.
d
Installing DCBs
DC air conditioner and natural Ventilation can be used in the door of ESC-1D, the operation must according to actual conditions.
Switch the circuit breaker in the ESC to the OFF position. The battery baffle should be rotate 90 degree for the ESC-1D with DC air conditioner.
Battery baffle
ESC-1D (DC air Conditioner)
90 °
9
Install DCBs and connect cables between them. Connect DCBs and the ESC busbar.
1. DCBs must be placed in strict accordance with the following figure. Otherwise, you will not be able to connect cables to the DCBs or the DCBs will short circuit. 2. When connecting cables to DCBs, wear protective gloves and use insulated tools (such as a wrench with its handle wrapped with PVC insulation tape). 3. Partially tighten bolts first. After all cables are connected to DCBs, tighten the bolts on DCBs. The reference torque for tightening bolts is 20–25 N.m (177.02–221.27 lbf.in.). 4. Before connecting a cable to a DCB, remove the protective lid from the DCB and then reinstall it after connecting the cable.
-
+
-
+
-
+
-
+
-
+
-
+
+
-
+
-
+
-
+
-
+
-
+
-
-
+
-
+
-
+
-
+
-
+
-
+
-
+
-
+
-
-
+
-
+
-
+
+
-
+
-
+
-
-
+
-
+
-
+
+
-
+
-
+
-
+ -
+
+ -
+
+ -
(connect negative terminal of battery)
+
- 48V
-
(connect to the electrical control cabinet)
+
+ -
+ +
+ -
+ +
COAX crimping tool
Cord end terminal
Heat shrink tubing
Hydraulic pliers
OT terminal
10
+
-
+
+
-
+
-
+
-
-
+
-
+
-
+
+
-
+
-
+
-
-
+
-
+
-
+
+
-
+
-
+
-
-
+
-
+
-
+
+
-
+
-
+
-
+ -
Cabling of the PowerCube.
Heat gun
-
-
2. Connecting Cables Prepare terminals as required before connecting cables.
+
+ RTN+
+
- 48V
a
Connecting a Ground Cable to the ECC
The cross-sectional area of the ground cable is 25 mm2 (0.98 in.2).
Notes: Please make the connected cable and the label at the two ports of cable , that named ‘site ground’.
ECC ground bar
Site ground bar
b
Connecting Cables Between the ECC and Both the DC Air Conditioner and Door Status Sensor
No.
Cable
One End
Appearance
1
Positive power cable to the DC air conditioner
RTN port on the ESC transfer busbar
RTN+ busbar of the PDU in the power system of the ECC
2
–48 V DC power cable to the DC air conditioner
–48V port on the ESC transfer busbar
DC output LLVD F14 (20A) circuit breaker of power system in the ECC
3
Signal cable to the DC air conditioner for alarm generation
ALM port on the ESC transfer busbar
DI6 port on the analog digital input/output (ADIO) of the HPMU in the ECC
4
Signal cable to the door status sensor
GATE port on the ESC transfer busbar
DI5 port on the ADIO of the HPMU in the ECC
11
The Other End
DI5
+
DI6
- +
3
4
1 +
F14(20A)
GATE ALM RTN -48V
2 + -+ + -
-
1 4
c
3
2
Please install the cable of the ESC-1D (natural ventilation) according to ESC-1D (DC air conditioner), the installation method is the same.
Notes: Please make the connected cables and the label at the two ports of every cable , that named: 1. ‘RTN-air con’. 2. ‘-48V-air con’. 3. ‘ALM+’ ‘ALM-’…AS the figure DI5. 4. ‘GATE+’. ‘GATE-’ …AS the figure DI6.
Connecting Cables Between the ESC and the ECC
No.
Cable
One End
Appearance
1
Positive output DC power cable to storage batteries
Positive busbar of the ESC
BAT1+ port on the battery transfer busbar in the ECC
2
Negative output DC power cable to storage batteries
Negative busbar of the ESC
BAT1– port on the battery transfer busbar in the ECC
3
Signal cable to the battery temperature sensor
Battery temperature sensor
TEM_BAT port of the CPMU01 in the ECC
12
The Other End
Protective covers must be removed from the positive busbar of the ESC, negative busbar of the ESC, and battery transfer busbar in the ECC before cable connection and must be reinstalled after cable connection.
TEM_BAT 3 3 1
BAT1+ -48V
2
BAT1-
2
Notes: Please make the connected cables and the label at the two ports of every cable , that named: 1. ‘RTN-BAT1+’. 2. ‘-48V-BAT1-’.
RTN
1
d
Connecting a Ground Cable to the ESC
Notes: Please make the connected cables and the label at the two ports of every cable , that named: ‘ESC ground’.
ECC ground bar
ESC ground bar
13
e
Connecting a Power Cable to the D.G. Storage Battery
No.
Cable
One End
Appearance
1
Power cable to the D.G. storage battery
Negative terminal of the D.G. storage battery
The Other End Generator (connected)
Step1 Remove the protective lid from the negative terminal of the D.G. storage battery.
Step2 Push back the protective lid of the negative cable to expose the wiring terminal.
Step3 Connect the negative cable to the negative terminal of the D.G. storage battery. Reinstall the protective lid to the wiring terminal.
When Connect the negative cable to the negative terminal of the D.G. storage battery, the reference torque for tightening bolts is 5 N·m.
f
Connecting DC Power Cables to DC-powered Loads
No.
Cable
One End
Appearance
1
Positive DC power cable to the DC-powered load
RTN+ busbar of the Power system
DC input positive terminal of the DC-powered load
2
Negative DC power cable to the DC-powered load
DC output circuit breaker of the Power system
DC input negative terminal of the DC-powered load
1 2
+ -
The pictures are for reference only. The operation must be in accordance with the actual conditions.
BLVD LLVD
Notes: Please make the connected cable and the label at the two ports of cable , that named : 1.XX+ XX-; … about the loads.
DC-powered load
14
The Other End
g
Connecting Communications Cables to the HPMU (Optional: only installing when OMU is used) Out-of-Band Communication Scenario 1: Communication over the GPRS 1 Install the subscriber identity model (SIM) card.
Step 1 Remove the model card. model card
Step 2 Install the SIM card. SIM
2 Install the Global System for Mobile Communications (GSM) antenna. Cable
One End
Appearance
GSM antenna (Optional)
RF port of the OMU
RF
GSM antenna If the GSM antenna base has a plastic shell, remove the plastic shell to ensure a good magnetic attachment.
The GSM antenna is installed in the upper part of the side panel of the ESC cabinet.
Scenario 2: Communication over the Ethernet Cable
One End
Appearance
(Optional) Communications cable between the OMU and the Ethernet
ETH port of the OMU
The Other End IP network
ETH
IP Network Transmission equipment that supports TCP/IP
15
In-Band Communication (over the HPMU)
Please check that OMU-B is not installed over the In-Band Communication, if OMU-B is installing, please remove it.
Pin Number of the RJ45 Connector to the MON Port of the UMTS13.0 or GBSS12.0
Scenario 1: UMTS13.0 and GBSS12.0 (excluding the BTS3900E) 1 Prepare a cable as shown in the following figure. View A
1
8 T+ TR+ R-
2 Connect the communications cable.
Pin Identification of the Connector to the COM_OUT Port of the HPMU
1
T+
2
T-
4
R+
5
R-
Cable
One End
(Optional) Communications cable between the UTMS13.0 and the HPMU
MON1 port of the base band
COM_OUT port
unit (BBU)
of the HPMU
HPMU
Appearance
The Other End
COM_OUT COM_OUT T+ T- R+ R-
BBU MON1
Pin Number of the DB15 Connector to the MON Port of the BTS3900E in the GBSS12.0
Scenario 2: GBSS12.0 (pole-mounted BTS3900E) 1 Prepare a cable as shown in the following figure.
2 Connect the communications cable.
11
R-
12
R+
13
T-
14
T+
HPMU COM_OUT
T+ T- R+ R-
MON port of the BTS3900E in the GBSS12.0
16
Pin Identificat ion of the Connecto r to the COM_OU T Port of the HPMU
h
(Optional, only used without NetEco) Connecting SignalCables to the HPMU
The following table describes the signal cables connection to the HPMU.
Port
Default
Settings (only used after software Version 827 of the HPMU)
DO1
D.G. run.
-
When DO_1 is closed, an alarm is generated. (connect to communication equipment ) DO2
Reset D.G. 1. (connect to the EPS-10G or the reuse D.G. )
D.G. fault. When DO_2 is closed, an alarm is generated. DO_2 can be set to report alarm for D.G. fault. (connect to communication equipment )
DO3
DO4
Reset D.G. 2. (only used in two diesel generators
DO_3 can be set to report alarm to no mains.(connect
scenario, connect to the backup D.G.)
to communication equipment )
Starts or stops D.G. 2 (DG2_On/Off). (only used in two
-
diesel generators scenario, connect to the backup D.G.)
1. After software Version 827 of the HPMU, DO2 and DO3 can be used as dry contact, by setting the default parameters of ADIO Backup DO2 and ADIO Backup DO3 to Alarm close. 0# Enter MAIN MENU MAIN MENU Settings 2009-06-16 Enter Enter Enter password Status Scene Set end with #: Batt1 Volt: 52.3 V Status Maintenance System Set ># Batt2 Volt: 50.6 V Maintenance Settings Alarm Set Supplier: SDG Settings Enter Alarm Set Enter Critical Point Dry Node Setting Clr Hist Alarm
Back up DI 1 Normal open Back up DI 2 Normal open
ADIO Backup DO2 Enter DG Reset ADIO Backup DO3 DG Reset
ADIO Backup DO2 Enter ADIO Backup DO2 Alarm close Alarm close ADIO Backup DO3 ADIO Backup DO3 DG Reset DG Reset Enter
ADIO Backup DO2 Alarm close ADIO Backup DO3 Alarm close 2. The user password is 0#, the engineer password is 1#, both the user password and the engineer password can be reset on the menu. 3. Information on the liquid crystal display (LCD) described on page 17 is for reference only.
i
Checking Cable Connections
No.
Check Item
1
Ensure that the cabinets are securely installed and cables are securely installed.
2
Use a clamp meter to verify that the cables are connected properly.
3
No short circuit occurs between the –48 V power cable and any of the ground bar, positive bus bar, three-phase live wire, neutral wire, and ground cable. No short circuit occurs between the three-phase live wire, the neutral wire, and the ground cable.
17
3. Powering On and Commissioning the Power Cube
a
Powering On Batteries Switch the battery circuit breakers of the ESC and the BAT1– ,BAT2–, F2 circuit breaker of the Power system to the ON position.
Check the AMF power switch is set to the OFF position.
Power system ON ON BAT1- BAT2- F2
OFF
b
Set parameters on the HPMU 1. The user password is 0#, the engineer password is 1#, both the user password and the engineer password can be reset on the menu. 2. The following table describes the buttons on the HPMU panel. Button
Function
or
Allows you to view menu items and set the value of a menu item.
Cancel
Returns to the previous menu without saving the settings of the current menu item.
Enter
Enters the main menu from the standby screen, enters a submenu from the main menu, or saves the settings of a submenu item.
3. Information on the liquid crystal display (LCD) described on pages 18– 23 is for reference only. Check that the Product Set is PowerCube 1000 (only used after software Version 827 of the HPMU).Set basic parameters on the HPMU (System Type, Zone, Date, Time, Batt1 Cap, Batt2 Cap, Install Date).
Parameter Setting on the HPMU Parameter
Value
Scene Set (only used after software Version 827 of the HPMU)
Product Set
Set based on actual requirements
Date
Set based on actual requirements
Solar&DG&Batt DCB
Set based on actual requirements
Step 1: Set application parameters. a. Initial power-on Please Select System Type: Solar & DG
or
Parameter
Value
Battery Set
Zone
Time Battery Type
Value
System Set
PowerCube 1000
Application Set System Type
Parameter
Please Select System Type: Solar&DG&Batt
18
Batt 1 Cap
Set based on actual requirements
Install Date
Set based on actual requirements
Cable L
Set based on actual requirements
Cabel S
Set based on actual requirements
b. Non-initial power-on MAIN MENU
MAIN MENU
2009-06-16 Enter Status Batt1 Volt: 52.3 V Maintenance Batt2 Volt: 50.6 V Settings Supplier: SDG
Settings Battery Set DG Set Application Set
Settings Battery Set DG Set Application Set
Status Maintenance Settings
Enter
Enter Enter password end with #: >#
System Type Solar&DG&Batt Battery Type: DCB
0# Enter
Settings Scene Set System Set Alarm Set
System Type Solar&DG&Batt Battery Type: DCB
Step2: Check that the Product Set is PowerCube 1000 (only used after software Version 827 of the HPMU). MAIN MENU 2009-06-16 Enter Status Batt1 Volt: 52.3 V Maintenance Batt2 Volt: 50.6 V Settings Supplier: SDG
MAIN MENU Status Maintenance Settings
Enter Enter password end with #: >#
1# Enter
Settings Scene Set System Set Alarm Set
Product Set Enter Product Set Para Will Init Please Select: ENTER: Continue PowerCube 1000 CANCEL: Quit Step 3: Set system parameters. 2009-06-16 Enter Batt1 Volt: 52.3 V Batt2 Volt: 50.6 V Supplier: SDG
MAIN MENU
MAIN MENU
Status Maintenance Settings
Status Maintenance Settings
Date: 2009-07-06 Time: 13:27 Zone: GMT+8:00
Enter Local Address: 1 Lang: English Disp Contrast: 5 Modify User PWD
Enter
Date: 2009-07-06 Time: 13:27 Zone: GMT+8:00
Enter password end with #: >#
0# Enter
Settings Scene Set System Set Alarm Set
Date: 2009-07-06 Time: 13:27 Zone: GMT+8:00
Step 4: Set battery parameters. 2009-06-16 Enter Batt1 Volt: 52.3 V Batt2 Volt: 50.6 V Supplier: SDG
Settings Battery Set DG Set Application Set
MAIN MENU
MAIN MENU
Status Maintenance Settings
Status Maintenance Settings
Enter Timing BC: Enable BC Duration: 30 days
Limit-Curr Coef 0.3 C Cable L: 5m Cabel S: 35mm^2
Enter
Max Discharge: Disable Max Disch Time: 24 h
Enter password end with #: >#
Batt 1 Cap: 600Ah Batt 2 Cap:
0# Enter Settings Scene Set System Set Alarm Set
Install Date: 2009-01-01 BMU Number: 0 Piece
Limit-Curr Coef 0.3 C Cable L: 5m Cabel S: 35mm^2
Set communication parameters on the HPMU.
For GPRS networking, the SIM card needs to support voice services (over circuit switching) and data servcies (over packet switching).
19
A. (Optional: only setting when OMU is used) Set communication parameters on the HPMU. Scenario 1: GPRS+SMS or SMS networking
Parameter Setting on the HPMU (GPRS+SMS) Item
Value
Item
System Set Server IP Address
Obtained from the EMS
Server IP Backup
Obtained from the EMS
Value
NetEco Num
Number of the SIM card in the short message service (SMS) modem on the NetEco side
User1 to User5 Phone Num
Set based on actual requirements
SMS Test Num
Set based on actual requirements
APN Name Obtained from the survey table Net Para Set Comm Method
APN Number GPRS+SMS (if the SMS modem is configured)
User Name
Obtained from the survey table User name for accessing the GPRS (specified if the APN is used or left blank if the APN is not used)
SMC Num
Obtained from the survey table
User Password Password for accessing the GPRS (specified if the APN is used or left blank if the APN is not used)
Parameter Setting on the HPMU (SMS) Item
Value
Comm Method
SMS (if the SMS modem is configured)
SMC Num
Obtained from the survey table
Item
Value
NetEco Num
Number of the SIM card in the short message service (SMS) modem on the NetEco side
User1 to User5 Phone Num
Set based on actual requirements
SMS Test Num
Set based on actual requirements
Step 1: Set system parameters. 2009-06-16 Batt1 Volt: 52.3 V Batt2 Volt: 50.6 V Supplier: SDG
Enter
Enter Local Address: 1 Lang: English Disp Contrast: 5 Modify User PWD
MAIN MENU
MAIN MENU Enter Status Maintenance Settings
Status Maintenance Settings
Date: 2009-07-06 Time: 13:27 Zone: GMT+8:00
Server IP Addr: 0.0.0.0 Server IP Backup: 0.0.0.0
Enter password end with #: >#
Settings Battery Set DG Set Application Set
User1 Phone Num >
SMS Test Num >
MAIN MENU Status Maintenance Settings
MAIN MENU Status Maintenance Settings
Settings Enter Engineer Set Net Para Set Disconection Set
User2 Phone Num >
APN Name >
Enter
Comm Method GPRS+SMS Dial Up/Down Dial up
User3 Phone Num >
APN Number >
20
Settings Scene Set System Set Alarm Set
Server IP Addr: 0.0.0.0 Server IP Backup: 0.0.0.0
Step 2: Set network parameters. 2009-06-16 Enter Batt1 Volt: 52.3 V Batt2 Volt: 50.6 V Supplier: SDG
0# Enter
Enter password end with #: >#
0# Enter Settings Scene Set System Set Alarm Set
SMC Num
Neteco Num
>
>
User4 Phone Num >
User Name >
User5 Phone Num >
User Password >
Step3:The dialup service is successful if both the GPRS and SMS are used in networking, the value of GPRS IP Addr is not 0.0.0.0, If the RUN indicator on the OMU01 panel is blinking slowly (on for 1s and then off for 1s), the HPMU is successfully connected to the NetEco and the NetEco has obtained the correct site information. OMU IP Addr: 0.0.0.0 GPRS IP Addr: 0.0.0.0
2009-6-16 Batt1 Volt: 52.3 V Batt2 Volt: 50.6 V Supplier: SDG
If only the SMS is used in networking, check the validity of the SMS test number on the LCD and then test the SMS function. If the number receives 210231***************, the settings related to the SMS are correctly set on the HPMU. 0# MAIN MENU MAIN MENU 2009-06-16 Enter Enter Enter password Enter Maintenance Batt1 Volt: 52.3 V Reset HPMU Status Status end with #: Batt2 Volt: 50.6 V Sms Test Maintenance Maintenance ># Supplier: SDG DG Test Settings Settings Maintenance Reset HPMU Sms Test DG Test
Enter Caution: Start Sms Test? ENTER: Continue CANCEL: Quit
Before performing the SMS test, ensure that the SMS test number is valid.
Scenario 2: Communication over the Ethernet
Parameter Setting on the HPMU Item
Value
Item
Net Para Set Comm Method
Value
System Set ETH
Server IP Address
Obtained from the EMS
Server IP Backup
Obtained from the EMS
OMU IP
Set according to the network plan
OMU Mask IP
Set according to the network plan
Gateway IP
Set according to the network plan
Step 1: Set network parameters. 2009-06-16 Enter Batt1 Volt: 52.3 V Batt2 Volt: 50.6 V Supplier: SDG
MAIN MENU Status Maintenance Settings
Settings Battery Set DG Set Application Set
MAIN MENU Status Maintenance Settings
Settings Enter Engineer Set Net Para Set Disconection Set
Enter
Comm Method GPRS+SMS Dial Up/Down Dial up
Enter password end with #: >#
Enter
Comm Method GPRS+SMS Dial Up/Down Dial up
Step 2: Set system parameters. 2009-06-16 Ente Batt1 Volt: 52.3 V r Batt2 Volt: 50.6 V Supplier: SDG
Ente r
Local Address: 1 Lang: English Disp Contrast: 5 Modify User PWD
Ente r
OMU Mask IP 0.0.0.0 OMU Mask IP 0.0.0.0
MAIN MENU Status Maintenance Settings
Date: 2009-07-06 Time: 13:27 Zone: GMT+8:00
MAIN MENU Status Maintenance Settings
Enter
Server IP Addr: 0.0.0.0 Server IP Backup: 0.0.0.0
Gateway IP 0.0.0.0 Site ID: >
21
0# Enter Settings Scene Set System Set Alarm Set
Enter password end with #: >#
Comm Method ETH Dial Up/Down Dial up
0# Enter
Server IP Addr: 0.0.0.0 Server IP Backup: 0.0.0.0
Settings Scene Set System Set Alarm Set
OMU IP 0.0.0.0 OMU Mask IP 0.0.0.0
B. In-Band Communication (over the HPMU) 2009-06-16 Batt1 Volt: 52.3 V Batt2 Volt: 50.6 V Supplier: SDG
Parameter Setting on the HPMU Item
Value
Enter
System Set Local Address
MAIN MENU
Status Maintenance Settings
Status Maintenance Settings Enter
27
0# Enter
Enter password end with #: >#
c
MAIN MENU
Settings Scene Set System Set Alarm Set
Enter
Local Address: 27 Lang: English Disp Contrast: 5 Modify User PWD
Powering On the D.G. a. Switch the DG INPUT and AC output circuit breakers of the IATS to the ON position. b. Flip the AMF power switch to the ON position and check that the EMERGENCY STOP button is ejected. c. Switch the AC circuit breaker of the Power system and the BC power switch to the ON position.
Before starting the D.G., ensure that the fuel tank, engine oil tank, and water tank are filled. ON
Power system OFF
AC
ON
BC ON
ON
DG INPUT
ON
63A
The D.G. starts to charge DCBs. Check whether the information on the HPMU standby screen matches the actual configurations. If yes, proceed to step 6. If no, check cable connections and part configurations. HPMU 2009–06–16 Batt1 Volt: 52.3 V Batt2 Volt: 50.6 V Supplier: SDG
Phase A: 215.7 V Phase B: 216.2 V Phase C: 215.7 V Ambient: 25°C
Current Batt: Batt1 Batt Status: Discharge
Batt Remain Cap: 100% Batt Backup Time: 86.5h
Batt1: 10.0A Batt2: 0.0A Batt Tmp: 0°C Board Tmp: 27°C
OMU IPAddr: 0.0.0.0 GPRS IPAddr: 0.0.0.0
22
SDG Batt: 0.0V DG1 Batt: 0.0V Fuel1 Lev: 0cm Fuel2 Lev: 0cm
System Type: DG & DCB Alarm Status: Exist Alarm
SIMOnline Stat: Dis Online GSMReg Stat: Unregister
GPRS Dial Pro: No Dial GSM Sig Quality:
On the HPMU standby screen, choose Status > Maintenance > Reset HPMU > DG Test > Enter: Continue and press Enter. The Power Cube stops the running D.G. After that, the Power Cube starts the smart diesel generator (SDG) and then stops it. Finally, the HPMU displays SDG test: Pass. 0# 2009–06–16 MAIN MENU Enter MAIN MENU Enter Enter password Enter Maintenance Status Reset HPMU Batt1 Volt: 52.3 V Status end with #: Maintenance Sms Test Batt2 Volt: 50.6 V Maintenance ># Settings DG Test Supplier: SDG Settings
Maintenance Reset HPMU Sms Test DG Test
Enter Caution: Enter Close all DG Start DG Test? Please wait ENTER: Continue CANCEL: Quit
Test open SDG Please wait
Test close SDG Please wait
Test Result Mains: Off SDG test: Pass On the HPMU standby screen, choose Status > Maintenance > Reset HPMU > Oil-Clean Test > ENTER: Continue and press Enter. If the DG-M indicator (green) on the IATS is steady on, the test succeeds. 2009-06-16 Enter Batt1 Volt: 52.3 V Batt2 Volt: 50.6 V Supplier: SDG
Maintenance Oil-Clean Test Control Mode: Auto
d
Enter
MAIN MENU
MAIN MENU
Status Maintenance Settings
Status Maintenance Settings
Enter Enter password end with #: >#
0# Enter
Maintenance Reset HPMU Sms Test DG Test
Caution: Oil Clean Test? ENTER: Continue CANCEL: Quit
Powering On the Load Check whether the values on the HPMU standby screen are the same as the actual configurations. If there is an alarm from the HPMU, CPMU01 and the AMF25, rectify the fault by referring to the PowerCube 1000 Maintenance Guide (V300R001). Switch on the DC-powered load connecting to the power system and the AC-powered load connecting to the IATS. Check that the circuit breakers of F1,(for FAN),F14(for DC air condition),F3(for BC) is set to ON. If no alarm is generated after the Power Cube runs for five minutes, the commissioning is successful. Then take fireproof mud out of the packaging box in the cabinet base to block cable holes. After that, reinstall the plate, close all cabinet doors, and hand the keys over to the persons in charge.
23
HUAWEI TECHNOLOGIES CO., LTD. Huawei Industrial Base Bantian Longgang Shenzhen 518129 People’s Republic of China www.huawei.com