System Manual
TEM Evolution System System List of Limit Values, PLC release : 2.50.13 CPU-P
Last revised on: 2012-09-26 Docu-ID: GW_620_2020_2.50.13_MWM_en_CPU-P
We reserve the right on necessary technical modification of the product, deviating from this document in order to improve the engines. The reproduction, transmission or use of this document or its content is not permitted without express written authorization. This is the translation of the German original document. In case of dispute the German original version will be taken as a reference.
System Manual This document applies to the following gas engines: Series: 620, 2020
Imprint: MWM GmbH Service documentation Carl-Benz-Straße 1 68167 Mannheim Germany Phone: Phone: +49 +49 (0) 6 21 21 3 84-0 84-0 Fax: +49 +49 (0) 6 21 3 84-88 84-88 41 www.mwm.net Printed in Germany All rights reserved
© GW_620_2020_2.50.13_MWM_en_CPU-P
System Manual This document applies to the following gas engines: Series: 620, 2020
Imprint: MWM GmbH Service documentation Carl-Benz-Straße 1 68167 Mannheim Germany Phone: Phone: +49 +49 (0) 6 21 21 3 84-0 84-0 Fax: +49 +49 (0) 6 21 3 84-88 84-88 41 www.mwm.net Printed in Germany All rights reserved
© GW_620_2020_2.50.13_MWM_en_CPU-P
TEM Evolution System System
Notes 1
Notes
1.1
Validity
Column
Explanation
This list of limit values is only valid for gas engines with the TEM-Evo-System.It is only suitable for the engine type indicated on the front page.
Fault
Event of type »Fault« The genset is shut down immediately.
The list of limit values is valid for the following software release until a new list of limit values will be published.
Fault SC
Event of type »Fault SC« The genset is stopped by controlled shutdown. Refer to »Function »Function Fault Fault SC« on page 5.
Alarm
Event of type »Alarm«. »Alarm «. The alarm is recorded as a note in the operation log.
Alarm RP
Event of type »Alarm »A larm RP« The permitted power is reduced by 20%, based on the maximum power. The alarm is recorded in the operation log. Refer to »Function »Function Alarm Alarm RP« on page 5.
• 2.5 2.50.13 0.13 CPUCPU-P P
Please observe the following documents: • Manufactu Manufacturer rer's 's operat operating ing instruct instruction ionss • User Guide Guide and and System System Manual Manual for the TEM-Ev TEM-Evo o System, System, particularly the system manual “Operation log”«
Time of delay with Limit value for monitoring with delay time unit RA
1.2
Design ign of of th the Li List of of Lim Limiit Va Values
Column
Explanation
Identification Name of the limit value Sensor monitoring
RA: Remote acknowledgement 10 h: Remote Remote acknowle acknowledgem dgement ent is possible possible every every 10 10 h X: Faul Faultt that that can can be be remo remote tely ly ackn acknow owle ledg dged ed (all alarms can be remotely acknowledged).
Monitoring Monitoring of the measured value for observance of the limit value Undershooting of a limit value with a fault © GW_620_2020_2.50.13_MWM_en_CPU-P
Page 3
TEM Evolution System
Notes
Column
Explanation
Undershooting of a limit value with an alarm Undershooting of a limit value with a message Exceeding a limit value with a fault Exceeding a limit value with an alarm Exceeding a limit value with a message Limit value
Limit value for monitoring with a unit For parameter-depending limit values that value is indicated which results from the default value of the parameter. The way to find the default value of the parameter is described in column »Comment«.
Delay
Time of delay with unit
RA
see before
Level
Acknowledgement of the monitoring is only possible with an USB Authorisation Dongle with the indicated authorisation level.
Comment
Comment
© GW_620_2020_2.50.13_MWM_en_CPU-P
Page 4
TEM Evolution System
Notes 1.2.1
Function Fault SC
ower
Load run
During load run (mains parallel mode) a fault of the type »Fault SC« causes the controlled shutdown of the genset.
set permitted p a r a m e t e r i s e d r a m p
When a »Fault SC« appears the admissible power is immediately set to the current actual power. Thus a further increase of the power is prevented. After expiration of the delay time (e.g. 5 minutes) the admissible power is reduced to 0.0 %. The set power follows the admissible power to a parameterisable ramp. • Setting of the delay timet: Parameter »10033 Delay time fault SC« • Specification of the ramp for the set power: Parameter »23007 Power control set ramp controlled shutdown« In case that the value of the actual power is below 10 %, the genset is deselected. Note
If all faults of type »Fault SC« can be acknowledge in the operation log during the shut down process, the power is increased again to the externally demanded power and the load run is continued.
Shutdown
5 minutes Fault SC
Figure 1: 1.2.2
Time
Controlled shutdown of the genset with a »Fault SC« Function Alarm RP
»Alarm RP« events are logged as »Alarm« in the operation log. Additionally, the permitted power is reduced by 20%, based on the maximum power. The power reduction is marked in the operation log by the alarm »Power reduction to safe power«.
Idle mode
If the genset is not operated in load run, every fault of type »Fault SC« causes the immediate shutdown of the genset. With a pending »Fault SC« a start of the genset or the idling operation are impossible.
© GW_620_2020_2.50.13_MWM_en_CPU-P
Page 5
TEM Evolution System
Notes 1.3
Abbreviations
Abbreviations
Explanation
Explanation
MK
Jacket water control
AES
Demand of external starting preparations
NA
Handling of mains fault
AKR
Anti-knock governor
NATL
ALD
Intake air throttling
Monitoring of the exhaust gas temperature after exhaust turbocharger
AVW
Preheating air inlet
NAWT
Exhaust gas temperature after exhaust heat exchanger
AWG
Exhaust wastegate
NFI
Lube oil pressure after filter
BY
Exhaust bypass
NK
Emergency cooling circuit
CH4
Additional CH4 compensation
NKS
Emergency cooler - dry cooler
CH4K
Extension of option CH4.
NKV
Valve position NK valve
DK
Leakage check
NKAT
Monitoring of the exhaust gas temperature after catalyst
GK
Intercooler circuit
NMOT
Monitoring of the exhaust gas temperature after engine
GKS
Intercooler-dry cooler
QEÜ
Acknowledgement of external monitorings
GKV
Valve position of the GK valve
REC
Registration of receiver pressure
GL
Monitoring of the generator bearing temperatures
RL
Control of cabin air temperature
GLU
Generator air temperature
RL1
Cabin ventilation with admixture or frequency-controlled coolers
GW
Generator winding temperatures
SATL
HK
Heat utilization with heating circuit
Measuring and limitation of the exgaust turbocharger speed
HKV
Valve position HK valve
VAWT
Measuring of the heating water temperature before exhaust gas heat exchanger
Abbreviations
© GW_620_2020_2.50.13_MWM_en_CPU-P
Page 6
TEM Evolution System
Notes
Abbreviations
Explanation
VBP
Compressor bypass
VKWT
Jacket water temperature before jacket water heat exchanger
VNK
Heating water temperature before emergency cooler
VSWT
Measuring of jacket/heating water before lube oil exchanger
xM
Parameterisable messages
xMW
Parameterisable data
xPR
Parameterisable control circuits
ZG
Dual gas operation with change of the gas type only at a standstill
ZGM
Dual gas operation with composite mode
ZM
Dual gas operation with composite mode and change of the gas type under load
ZU
Dual gas operation with change of the gas type under load
© GW_620_2020_2.50.13_MWM_en_CPU-P
Page 7
TEM Evolution System
List of Limit Values 2
List of Limit Values
Identification
Sensor monitoring
RA Monitoring
T202 Jacket water GK inlet
Fault SC
500 ms
X
T206 Jacket water engine outlet
Fault SC
500 ms
X
Fault SC
500 ms
Alarm
98.0 °C (208.4 °F)
2s
Fault
99.0 °C (210.2 °F) 20.0 °C (68 °F)
2s
¹ Monitoring must be acknowledged individually
30 s
Level Comment
X
240 min
Message
80.0 °C (176 5 min °F)
Fault
98.0 °C (208.4 °F)
Fault Alarm
RA
X
Collective fault jacket water temperatures P497 Jacket water engine outlet
Delay
[GK]
Message T207 Jacket water engine inlet
Limit value
2s
Power reduction; Limit value: Par. 13400; island: delay 30s X
0 ms
T206 and T207 failed, automatically acknowledgeable
X
After 24 h this alarm changes to a fault SC. Alarm
1.50 bar
30 s
X
Enable from set power > 30,0 %
Fault SC
1.00 bar
24 h
10 h
Enable from set power > 30,0 %; not island
© GW_620_2020_2.50.13_MWM_en_CPU-P
Page 8
TEM Evolution System
List of Limit Values Identification
Sensor monitoring
RA Monitoring
P196 Lube oil before filter
Fault SC
X
T208 Lube oil
L234 Lube oil level
Fault SC
Fault SC
500 ms
Limit value
Delay
RA
Level Comment
Alarm
3.00 bar
0 ms
Operational oil pressure
Fault ¹
0.30 bar
1 min
Start prelubrication; delay at a standstill: 60s
Fault ¹
2.80 bar
0 ms
Operational oil pressure
Alarm
105.0 °C (221 °F)
2s
Fault SC
110.0 °C (230 °F)
2s
Message
85,0 %
0 ms
500 ms
500 ms
L234.1 Lube oil level
Filtered value Enable only during oil change
Alarm
110,0 %
20 s
10 h
enable + delay variable
Fault ¹
120.0 %
20 s
10 h
With the engine at a standstill, delay 1s
Message
50.0 %
0 ms
Alarm
40,0 %
20 s
10 h
enable + delay variable
Enable only during oil change
Fault ¹
30.0 %
20 s
10 h
With the engine at a standstill, delay 1s
Bearing lubrication is due Alarm
0 ms
Due now
Alarm
0 ms
Due in 48 hours
Alarm
0 ms
Due now
Alarm
0 ms
Due in 48 hours
Oil filter change is due
¹ Monitoring must be acknowledged individually
© GW_620_2020_2.50.13_MWM_en_CPU-P
Page 9
TEM Evolution System
List of Limit Values Identification
Sensor monitoring
RA Monitoring
Limit value
Delay
RA
Level Comment
Oil change is due Alarm
0 ms
Due now
Alarm
0 ms
Due in 48 hours 1. Pre-lubrication error
Xxxx Number of prelube faults
T201 Receiver
Fault SC
500 ms
Alarm
0
0 ms
Fault
5
0 ms
Message
52.0 °C 5 min (125.6) 55.0 °C (131 2 s °F)
X
Message
T203 Inlet air
Alarm
Fault SC
57.0 °C (134.6 °F)
2s
Message
30.0 °C (86 °F)
0 ms
Alarm
35.0 °C (95 2 min °F) 40.0 °C (104 2 min °F)
10 h
Limit value: Par. 13800 + 5.0K
500 ms
Fault SC Alarm
¹ Monitoring must be acknowledged individually
[GK] Power reduction; Limit value: Par. 13800; island: delay 30s Limit value: Par. 13800 + 3.0K
20.0 °C (68 °F)
30 s
© GW_620_2020_2.50.13_MWM_en_CPU-P
With [AVW] limit value: Par. 23230/23231 + 3.0K
X
[RL without T404] enable; Limit value Par. 13900 - 5.0K [RL without T404] enable; Limit value Par. 13900 Enable after 1 h engine running; Limit value Par. 23230 - 5.0K
Page 10
TEM Evolution System
List of Limit Values Identification
Sensor monitoring
RA Monitoring
T461 Combustion chamber A1
Fault SC
X
500 ms
500 ms
10 h
Fault SC
500 ms
X
T205 Cold junction B T46x.7 Combustion chamber average
Fault SC
500 ms
X
Level Comment
Fault SC
240 °C (464 2 min °F)
10 h
Fault
600 °C (1112 °F)
10 h
Alarm
240 °C (464 20 s °F)
Fault SC
240 °C (464 2 min °F)
Alarm
450 °C (842 0 ms °F)
Fault
450 °C (842 500 ms °F)
Limit value 50K-120K below average value
X
T204 Cold junction A
¹ Monitoring must be acknowledged individually
RA
600 °C 6s (1112 °F) 240 °C (464 20 s °F)
Alarm
Fault SC
Delay
For each cylinder individually Fault
T471 Combustion chamber B1
Limit value
6s
Limit value 50K-120K below average value; island operation: delay. 8 min; During this time the power reduction is under the limit value For each cylinder individually
Limit value 50K-120K below average value 10 h
Limit value 50K-120K below average value; island operation: delay. 8 min; During this time the power reduction is under the limit value
Average value side A
© GW_620_2020_2.50.13_MWM_en_CPU-P
10 h
Limit value 100K (mains) / 160K (island) above set value
Page 11
TEM Evolution System
List of Limit Values Identification
Sensor monitoring
RA Monitoring
Limit value
Delay
RA
T47x.7 Comb. chamber aver. B
Level Comment
Average value side B Alarm Fault
450 °C (842 0 ms °F) 450 °C (842 500 ms °F)
10 h
T4xx.2 Act. combustion chamber
Limit value 100K (mains) / 160K (island) above set value Filtered value
Fault
0 ms
More than 2 sensors failed automatically acknowledgeable
Fault
150 °C (302 0 ms °F)
Fault SC
10 °C (50 °F) 5 min
10 h
With a higher deviation less delay time
Fault SC
-10 °C (14 °F)
10 h
With a higher deviation less delay time
Deviation comb. chamber control
5 min
Gas mixer limit stop lean Message
4s
Stop position not reached
Gas mixer start position OK
T494 Exhaust after ATL A
T495 Exhaust after ATL B
Alarm
Alarm
¹ Monitoring must be acknowledged individually
Message
0 ms
Stop position not reached
Alarm
0 ms
Start position not reached on start abort [NATL] Limit value: Par. 15111 / 15113
500 ms Alarm
550 °C (1022 °F)
15 min
Alarm
550 °C (1022 °F)
15 min
500 ms
[NATL]
© GW_620_2020_2.50.13_MWM_en_CPU-P
Limit value: Par. 15111 / 15113
Page 12
TEM Evolution System
List of Limit Values Identification
Sensor monitoring
T286 Exh. after engine
Alarm
RA Monitoring
Alarm T287 Exhaust after KAT
T288 Exhaust after AWT
Fault SC
Alarm
Limit value
Delay
500 ms 550 °C (1022 °F)
2s
500 ms
RA
Level Comment
[NMOT] Limit value: Par. 15111 / 15113 [NKAT]
Fault
550 °C (1022 °F)
2s
Alarm
180 °C (356 2 s °F)
Alarm
50 mbar
500 ms
Limit value: Par. 15111 / 15113 [NAWT]
P157 Exhaust back press. too high
Limit value: Par. 15112 Limit value switch
2 min
Anti-knock governor available
[AKR] Alarm RP
0 ms
Alarm RP
5s
Enable during load run
ZA maximum adjustment ignition point A side
Alarm
0 ms
Sturdy ignition p. adjustment; Limit value: Par. 115036.0°; bit-coded display
ZA maximum adjustment ignition point B side
Alarm
0 ms
Sturdy ignition p. adjustment; Limit value: Par. 115036.0°; bit-coded display
AKR Speed signal
[AKR] Error speed signal [AKR] Sturdy ignition p. adjustment
[AKR] Sturdy ignition p. adjustment
Critical fault! Engine test required!
¹ Monitoring must be acknowledged individually
AKR-Card missing. refer to »system manual operation log error codes«
[AKR] Maximum ZZP-adjustment Alarm
-9.0 °
0 ms
Fault ¹
-9.0 °
0 ms
© GW_620_2020_2.50.13_MWM_en_CPU-P
Limit value: Par. 11502 - 1.0 °; at least -3.0 ° Page 13
TEM Evolution System
List of Limit Values Identification
Sensor monitoring
RA Monitoring
Limit value
Delay
RA
AKR Knock sensor fault bank A
[AKR] Enabling from 50% of load
Alarm RP
10 s
Alarm RP
10 s
Enabling from 50% of load [AKR]
Alarm RP
5s
Refer to system manual »Operation log error codes«
Alarm RP
0 ms
Fault
3s
Alarm
0 ms
Fault
3s
AKR Knock sensor fault bank B
[AKR]
AKR System error
AKR Function block
[AKR] Refer to system manual »Operation log error codes«
Ignition system ignites
Feedback from ZA 10 h
Ignition system error code
Ign. system capacitor discharge bank A
Ign. system capacitor discharge bank B
¹ Monitoring must be acknowledged individually
Level Comment
Ignition does not ignite Fault message from ZA Refer to system manual »Operation log error codes«
10 h
Refer to system manual »Operation log error codes« Error capacitor discharge
Message
0 ms
Alarm
1 min
Refer to system manual »Operation log error codes« Error capacitor discharge
Message
0 ms
Alarm
1 min
© GW_620_2020_2.50.13_MWM_en_CPU-P
Refer to system manual »Operation log error codes«
Page 14
TEM Evolution System
List of Limit Values Identification
Sensor monitoring
RA Monitoring
Limit value
Delay
RA
Level Comment
Ign. system condition serial connection S
Timeout ZA communication Refer to system manual »Operation log error codes« Error ign. system communication
Fault SC
3s
Ign. system condition serial connection W
Message
0 ms
Fault
0 ms
Fault
0 ms
Refer to system manual »Operation log error codes«
Fault SC
0 ms
Refer to system manual »Operation log error codes«
Fault
0 ms
Fault
0 ms
Fault
0 ms
Fault
0 ms
ZA Initialisation of serial connection
Error initialisation ZA interface
ZA Basis initialisation
ZA read telegram
ZA Transmit telegram energies ZA Inquiry telegram ZA Transmit telegram test mode ZA Transmit telegram basic settings P145 Crank case
Fault
0 ms Fault ¹
10.0 mbar
0 ms
After start-up phase; limit value at rated speed 1800 rpm: 20.0 mbar
Alarm
-10.0 mbar
5 min
with engine running
Fault
3
0 ms
xxxx Number of start attempts
¹ Monitoring must be acknowledged individually
© GW_620_2020_2.50.13_MWM_en_CPU-P
10 h Page 15
TEM Evolution System
List of Limit Values Identification
Sensor monitoring
RA Monitoring
Limit value
Delay
RA
Level Comment
Alarm
1725.0 rpm
0 ms
Limit value: Par. 11108 + 15% (resp. +20% for DK-position < 10%), selfacknowledged
Alarm
80.0 rpm
0 ms
Speed bef. start
Fault ¹
1725.0 rpm
200 ms
Limit value: Par. 11108 + 15% (resp. +20% for DK-position < 10%)
Fault
1350.0 rpm
500 ms
S200 Engine speed
S110 Set value speed
Fault
500 ms
G197.Throttle valve position
Fault
0 ms
10 h
X
Limit value depending on condition only with analogue specification of the set speed Position StG; sensor monitoring: Current position is < -30.0 % or > 130.0 %
DZR Calibration Fault
0 ms
10 h
Calibration failed; Refer to system manual »Operation log error codes«
Alarm
5s
Fault
0 ms
Fault
200 ms
Refer to system manual »Operation log error codes«
Fault
0 ms
Refer to system manual »Operation log error codes«
DZR Current derating Enable during load run
DZR Short circuit power stage Speed registration error code
DZR Error code Init 0
¹ Monitoring must be acknowledged individually
© GW_620_2020_2.50.13_MWM_en_CPU-P
Page 16
TEM Evolution System
List of Limit Values Identification
Sensor monitoring
RA Monitoring
Limit value
Delay
RA
DZR TDC sensor error Fault
2s
10 h
Alarm
0 ms
Fault Alarm
2s 0 ms
10 h
Fault
2s
10 h
Alarm
0 ms
Fault
200 ms
Level Comment
TDC signal missing Enable with the engine running Enable with the engine running, auto acknowledgement
DZR Tooth number fault Enable with the engine running Enable with the engine running, auto acknowledgement
DZR TDC mixed up with gear ring
Actuator throttle valve A
G197.6 External actuator
Fault SC
500 ms
E198 Actual power generator
Fault
500 ms
Refer to system manual »Operation log error codes«
X
E198.2 Actual power
¹ Monitoring must be acknowledged individually
Filtered value Fault SC
105.0 %
2 min
Overload; Limit value: Par. 13100 + 5%
Fault
120.0 %
5s
Overload
Fault
-5.0 %
12 s
© GW_620_2020_2.50.13_MWM_en_CPU-P
X
Reverse power; delay Par. 13510
Page 17
TEM Evolution System
List of Limit Values Identification
Sensor monitoring
RA Monitoring
Limit value
Delay
RA
Level Comment
Alarm
410 kW
45 min
Fault
410 kW
60 min
Fault SC
5.0 %
5 min
During start and retrace of the engine: limit value 20%
Alarm
-5.0 %
5s
Exceeding the admissible power in island operation
Fault
-5.0 %
30 s
Exceeding the admissible power in island operation
Fault SC
-5.0 %
5 min
E198.8 Actual power in KW Minimum load; V12: 305kW, V16: 410kW Delay can differ for special plants. X
Minimum load; V12: 305kW, V16: 410kW Delay can differ for special plants.
Deviation power control
Power reduction due to jacket water temperature
Power reduction due to receiver temperature
Message
0.0 %
0 ms
Enable with message T207
Alarm
0.0 %
0 ms
Enable with message T207 and par. 10034=1
Message
0.0 %
0 ms
Enable with message T201/T378
Alarm
0.0 %
0 ms
Enable with message T201/T378 and par. 10034=1
[GK]
Power reduction due to throttle
¹ Monitoring must be acknowledged individually
Limit value: DK position 90 % Message
0.0 %
2 min
island: delay 30s
Alarm
0.0 %
2 min
Enable with par. 10034=1 island: delay 30s
Fault
-40.0 %
0 ms
© GW_620_2020_2.50.13_MWM_en_CPU-P
Page 18
TEM Evolution System
List of Limit Values Identification
Sensor monitoring
RA Monitoring
Limit value
Delay
Power reduction due to CH4-value Message
0.0 %
0 ms
Alarm
0.0 %
0 ms
Power reduction due to AKR 0.0 % 0.0 %
2 min 2 min
Power reduction due to ATL speed
T210 Generator winding V
Level Comment
[CH4] Enable with message Q311 Enable with message Q311 and par. 10034=1 [AKR]
Message Alarm
T209 Generator winding U
RA
island: delay 30s Enable with par. 10034=1 island: Delay. 30s, auto. acknowledgeable, indicator of incorrect parameterisation Par. 11502 [SATL]
Fault SC
Fault SC
¹ Monitoring must be acknowledged individually
Message
0.0 %
2 min
island: delay 30s
Alarm
0.0 %
2 min
Enable with par. 10034=1 island: delay 30s
500 ms Alarm
135.0 °C (275 °F)
10 s
[GK] Limit value: Par. 13500 - 5.0K
Fault ¹
140.0 °C (284 °F)
10 s
Limit value: Par. 13500
Alarm
135.0 °C (275 °F)
10 s
Limit value: Par. 13500 - 5.0K
Fault ¹
140.0 °C (284 °F)
10 s
Limit value: Par. 13500
500 ms
[GK]
© GW_620_2020_2.50.13_MWM_en_CPU-P
Page 19
TEM Evolution System
List of Limit Values Identification
Sensor monitoring
T211 Generator winding W
Fault SC
RA Monitoring
Alarm Fault ¹ T459 Generator bearing A
T460 Generator bearing B
T487 Generator air inlet
Fault SC
Fault SC
Fault SC
Fault SC
Delay
RA
135.0 °C (275 °F) 140.0 °C (284 °F)
10 s 10 s
Limit value: Par. 13500 [GL]
Alarm
55.0 °C (131 2 s °F)
Limit value: Par. 13501 - 5.0K
Fault ¹
60.0 °C (140 2 s °F)
Limit value: Par. 13501
500 ms
[GL] Alarm
55.0 °C (131 2 s °F)
Limit value: Par. 13501 - 5.0K
Fault ¹
60.0 °C (140 2 s °F)
Limit value: Par. 13501
Alarm
75.0 °C (167 2 s °F) 80.0 °C (176 2 s °F)
500 ms
[GLU] Limit value: Par. 13030 - 5.0K Limit value: Par. 13030
500 ms
[GLU] Alarm
75.0 °C (167 2 s °F)
Limit value: Par. 13030 - 5.0K
Fault
80.0 °C (176 2 s °F)
Limit value: Par. 13030
E121 Generator protection
Input security chain Fault
¹ Monitoring must be acknowledged individually
Level Comment
[GK] Limit value: Par. 13500 - 5.0K
500 ms
Fault T488 Generator air outlet
Limit value
500 ms
0 ms
© GW_620_2020_2.50.13_MWM_en_CPU-P
X
Page 20
TEM Evolution System
List of Limit Values Identification
Sensor monitoring
RA Monitoring
Limit value
Delay
RA
Fault
10 min
X
Fault Alarm
30 s 0 ms
Level Comment
Synchronisation E104 mains fault
[NA]
Mains fault sequencial failure
[NA] Fault
E199 Analogous demand
Timeout synchronization
Alarm
0 ms
500 ms
only with demand 4..20mA, deselection in case of a sensor alarm
E199.7 demand active Message
30.0 %
0 ms
Overtemperature net starting device Alarm
500 ms
X
Fault
500 ms
X
Fault
500 ms
X
Fault
500 ms
X
Fault
500 ms
X
Fault
500 ms
X
Fault of the power switch Mains fault Circuit breaker auxiliaries Safety stop valve SAV A Safety stop valve SAV B T291 Heating water flow
Fault SC
¹ Monitoring must be acknowledged individually
500 ms
© GW_620_2020_2.50.13_MWM_en_CPU-P
[HK] Enable with Par. 14008
Page 21
TEM Evolution System
List of Limit Values Identification
Sensor monitoring
T289 Heating water return
Alarm
RA Monitoring
Limit value
Delay
RA
500 ms Message
Level Comment
[HK] Enable with Par. 14009 [NK]; Limit value: Par. 24510
80.0 °C (176 10 s °F)
T290 Heating water before KWT
Alarm
500 ms
[VKWT]
T385 Heating water before AWT
Alarm
500 ms
[VAWT]
T412 Jacket water after AWT
Alarm
500 ms
HK AWT in the engine cooling circuit
T384 Heat. water bef. emerg. cooler Alarm
500 ms
HK AWT in the engine cooling circuit
T386 Heating water before SWT
500 ms
[VSWT]
Alarm
P281 Heating circuit pump
[HK] Fault
S397 HK Control valve position
Alarm
0 ms
X
500 ms
[HKV]
T276 Overtemperature limiter 1
[HK] Input security chain Fault
0 ms
X
Fault
0 ms
X
T277 Safety temperature monitor
[HK] Input security chain
P278 Overpressure limiter
[HK] Input security chain Fault
0 ms
X
P279 Overpressure limiter 1
[HK] Input security chain Fault
0 ms
X
L280 Low water heating circuit
[HK] Input security chain Fault
0 ms
X
P457 Pump coupling circuit
[HK] Input security chain Fault
0 ms
X
Fault
0 ms
X
T435 Overtemperature limiter 2
¹ Monitoring must be acknowledged individually
[HK] Input security chain
© GW_620_2020_2.50.13_MWM_en_CPU-P
Page 22
TEM Evolution System
List of Limit Values Identification
Sensor monitoring
RA Monitoring
Limit value
Delay
RA
P437 Overpressure limiter 2
Level Comment
[HK] Input security chain Fault
0 ms
X
G871 Exhaust bypass AWT limit stop Closed
Message
500 ms
P126 Flow monitoring engine cooling circuit
Fault
0 ms
X
Fault
0 ms
X
[HK+BY]
L123 Low water engine cooling circuit
Input security chain
T419 Emergency cooler-dry cooleroutlet
Alarm
500 ms
[NKS] Enable with Par. 14055
S000 NK Control valve position
Alarm
500 ms
[NKV] position feedback
L458 Low water emergency cooling circuit
P309 Flow monitoring intercooler circuit
[NK] Alarm
500 ms
X [GK]
Fault SC
3s
X
L308 Low water intercooler circuit
[GK] Input security chain Fault
0 ms
X
S000 Intercooler-control valve position T405 Intercooler-dry cooler outlet
Alarm
500 ms
[GKV] Position feedback
Alarm
500 ms
[GKS] Enable with Par. 13085
T404 Cabin air
Alarm
500 ms
[RL1x] Enable with Par. 13092
¹ Monitoring must be acknowledged individually
Message
32.0 °C (89.6 °F)
2s
Limit value: Par. 13900 - 8.0K
Alarm
35.0 °C (95 °F)
2s
Limit value: Par. 13900 - 5.0K
Fault SC
40.0 °C (104 2 s °F)
© GW_620_2020_2.50.13_MWM_en_CPU-P
X
Limit value: Par. 13900
Page 23
TEM Evolution System
List of Limit Values Identification
Sensor monitoring
RA Monitoring
Limit value
Delay
RA
Cabin ventilation P124 Gas pressure gas control system
P125 Leakage check gas control system A
P127 Gas pressure gas control system B
[RL] delay during start 60s
Fault SC
3s
X
Fault
0 ms
X
Alarm
0 ms
[ZG ZGM] for gas type change [DK]
Fault
1 min
Timeout leakage check
Fault
0 ms
T147 Temperature monitor gas control system
Level Comment
[CH4] Auto acknowledgement (Par. 12900)
[ZG ZGM] Fault
P128 Leakage check gas control system B
T131 Temperature monitor gas control system B
Q311 CH4-value
Fault SC
¹ Monitoring must be acknowledged individually
0 ms
X
[CH4] Auto acknowledgement (Par. 12900) [ZG+DK]
Fault
1 min
Fault
0 ms
Timeout leakage check [ZG]
2s
[CH4] Message
0.0 %
30 s
Deselection; enabling/limit value: Par. 12810, Par. 12811
Message
30.0 %
0 ms
Message
38.0 %
0 ms
[ZGM] Gas type change; Limit value: Par. 12806 - 8.0% Limit value: Par. 12806
Message
50.0 %
5 min
Fault SC
38.0 %
5 min
© GW_620_2020_2.50.13_MWM_en_CPU-P
Power reduction; Limit value: Par. 12803; island: delay 30s X
Limit value: Par. 12806
Page 24
TEM Evolution System
List of Limit Values Identification
Sensor monitoring
RA Monitoring
Limit value
Delay
RA
Stop due to CH4 calibration
H108.2 ZGM analogue external demand gas type B
Alarm
500 ms
Fault SC
75 min
Alarm
75 min
X
[CH4K] Timeout calibration, manual Timeout calibration, auto [ZGM]
Gas type change impossible
[ZG ZGM] Alarm
G602.0 Throttle valve gas type A actual
Alarm
G602.6 Control deviation throttle valve gas type A
G603.0 Throttle valve gas type B actual G603.6 Control deviation throttle valve gas type B
X
Level Comment
Alarm
500 ms
0 ms
X
[ZGM] [ZGM]
500 ms
Alarm
10.0 %
5s
Alarm
-10.0 %
5s
X
delay during start and engine running 50 x Par. 12522, otherwise 600 x Par. 12522 delay during start and engine running 50 x Par. 12522, otherwise 600 x Par. 12522 [ZGM] [ZGM]
Alarm
10.0 %
5s
delay during start and engine running 50 x Par. 12522, otherwise 600 x Par. 12522
Alarm
-10.0 %
5s
delay during start and engine running 50 x Par. 12522, otherwise 600 x Par. 12522
Alarm
30.0 V
0 ms
Alarm
20.0 V
0 ms
E149 Voltage supply
¹ Monitoring must be acknowledged individually
© GW_620_2020_2.50.13_MWM_en_CPU-P
Page 25
TEM Evolution System
List of Limit Values Identification
Sensor monitoring
Exxx Earth leakage monitor switching cabinet
RA Monitoring
Alarm
Limit value
Delay
10 kOhm
5s
RA
H141 Internal quick stop
Input security chain Fault
0 ms
H117 Ext. quick stop without heat removal
Fault
0 ms
H116 Ext. quick stop with heat removal
Fault
0 ms
Input security chain Input security chain X
Security chain G143 Circuit breaker TEM swtiching cabinet
Level Comment
Security chain open Fault
0 ms
X
Fault
0 ms
Fault
0 ms
Fault
0 ms
Fault
0 ms
Refer to system manual »Operation log error codes«
Fault
0 ms
Refer to system manual »Operation log error codes«
Fault
0 ms
Refer to system manual »Operation log error codes«
System reset Refer to system manual »Operation log error codes«
PLC program status X
Refer to system manual »Operation log error codes«
Collective fault VME32AI (card 1)
Collective fault VME32AI (card 2)
Collective fault VME32IO (card 1)
¹ Monitoring must be acknowledged individually
© GW_620_2020_2.50.13_MWM_en_CPU-P
Page 26
TEM Evolution System
List of Limit Values Identification
Sensor monitoring
RA Monitoring
Limit value
Delay
RA
Level Comment
CAN-Bus collective-fault Fault
0 ms
Refer to system manual »Operation log error codes«
Alarm
0 ms
Can be applied to all CMxxx-n exemplarily; Refer to system manual »Operation log error codes«
I/O-Controller: Module CM16DI-1
Stepper motor card
error stepper motor card Alarm
0 ms
Refer to system manual »Operation log error codes«
Parameterisable message 01
[xM] Par. message; free text Message
Parameterisable measured value 01 Alarm
0 ms
X
500 ms
Limit value, delay, type, enabling parameterisable [xMW] Par. measured value; free text
Message
0
0 ms
X
Limit value, delay, type, enabling parameterisable
Message
0
0 ms
X
Limit value, delay, type, enabling parameterisable
Control deviation parameterisable controllers 1
[xPR] control deviation par. governor; XX=1..3 Message
10
0 ms
X
Limit value, delay, type, enabling parameterisable
Test fault Fault
¹ Monitoring must be acknowledged individually
0 ms
© GW_620_2020_2.50.13_MWM_en_CPU-P
Entry created by service test functions
Page 27
TEM Evolution System
List of Limit Values Identification
Sensor monitoring
RA Monitoring
Limit value
Delay
RA
Level Comment
Test fault SC Fault SC
0 ms
Entry created by service test functions
Alarm RP
0 ms
Entry created by service test functions
Test alarm RP
Internal voltage (1.5 V)
Refer to system manual »Operation log error codes« Alarm
1.58 V
15 s
Alarm
1.42 V
15 s
Internal voltage (2.5 V)
Refer to system manual »Operation log error codes« Alarm Alarm
2.63 V 2.37 V
15 s 15 s
Internal voltage (3.3 V)
Refer to system manual »Operation log error codes« Alarm
3.47 V
15 s
Alarm
3.13 V
15 s
Internal voltage (3.3 V INT)
Refer to system manual »Operation log error codes« Alarm
3.63 V
15 s
Alarm
2.97 V
15 s
Internal voltage (5.0 V)
¹ Monitoring must be acknowledged individually
Refer to system manual »Operation log error codes« Alarm
5.25 V
15 s
Alarm
4.75 V
15 s
© GW_620_2020_2.50.13_MWM_en_CPU-P
Page 28
TEM Evolution System
List of Limit Values Identification
Sensor monitoring
RA Monitoring
Limit value
Delay
Internal temperature (INT)
RA
Level Comment
Refer to system manual »Operation log error codes« Alarm
75.0 °C (167 1 min °F)
Alarm
-10,0 °C
1 min
Internal temperature (V16)
Refer to system manual »Operation log error codes« Alarm
75.0 °C (167 1 min °F)
Alarm
-10,0 °C
1 min
Internal temperature (V17)
Refer to system manual »Operation log error codes« Alarm
75.0 °C (167 1 min °F)
Alarm
-10,0 °C
1 min
Alarm
3.30 V
1 min
Alarm
2.00 V
1 min
Voltage back-up battery
¹ Monitoring must be acknowledged individually
© GW_620_2020_2.50.13_MWM_en_CPU-P
Page 29