UPS O UPS Overview verview
What’s UPS?
Why need UPS?
Function of UPS
Classification of UPS
3 Em Emer erso son n Con Confi fide dent ntia iall
What’s UPS ? A device that can uninterruptible provide AC power pow er to user.
UPS - Uninterruptible Power Supply
AC mains load battery
4 Em Emer erso son n Con Confi fide dent ntia iall
UPS history
UPS develop through two periods: Rotary UPS and Static UPS.
5 Emerson Confidential
Rotary UPS DC motor; diesel engine; fl wheel generator; rectifier and battery.
6 Emerson Confidential
UPS history UPS
2、Static UPS-- is consisted of semiconductor power devices.
7 Emerson Confidential
UPS Overview UPS
What’s UPS?
Why need UPS?
Function of UPS
Classification of UPS
8 Emerson Confidential
Why need UPS ?- P -Power ower Problem
Surge
noise
spike
transient over voltage
Frequency drift
9 Emerson Confidential
low voltage
sag
blackout
Why need UPS ? Power problem surges
Cause
phenomenon
Huge equipment turn off or lighting strike
spikes
Lighting, electric switch on/off, electric welding
Higher than 110% rated Value,last many cycle. 6000V, last time is 10 ~100ms
Transient Like spike over voltage
20000V,last time 0.1ms
sag
smaller than 80-85% rated value,last many cycle.
Huge equipment turn on, AC mains change
10 Emerson Confidential
Why need UPS ? Power problem noise
Cause
phenomenon
High frequency interference.
Wireless and microwave equipment
Frequency drift
hydropower,generator
Frequency change over 3HZ.
low voltage
Huge equipment start, overload
Smaller than rated value and last long time.
blackout
AC cut off、circuit breaker trip.
Zero voltage last over 2 cycles.
11 Emerson Confidential
Why need UPS? Above AC power problems will damage equipment, lose data and interrupt operations.
12 Emerson Confidential
UPS Overview UPS
What’s UPS?
Why need UPS?
Function of UPS
Classification of UPS
13 Emerson Confidential
UPS Function UPS 1. High reliable and --Keep power continuous uninterruptible power --
3. Battery management --Prolong battery life 4. Monitoring
14 Emerson Confidential
--Help UPS maintenance
UPS Overview UPS
What’s UPS?
Why need UPS?
Function of UPS
Classification of UPS
15 Emerson Confidential
UPS Classification UPS By principle: back-up UPS line-interactive UPS on-line UPS
By power mode: three phase input/single phase output UPS three phase input/ three phase output UPS
By output power: small power(<10 kVA) medium power(10 to 30kVA) large power(>30 kVA) 16 Emerson Confidential
UPS Classification ( c ontinued ) (continued By transformer: high frequency UPS industrial frequency UPS
B waveform: square wave UPS sine wave UPS
17 Emerson Confidential
Content
UPS Overview
UPS Principle
UPS Key Technology
UPS Technical Data
UPS Battery
UPS Monitoring System
18 Emerson Confidential
Back- Back -Up Up UPS Principle When AC power normal, load power comes directly from the AC mains, when AC power fails, a battery powered inverter almost immediately turns on to continue to supply power. load AC mains charger
inverter
battery
19 Emerson Confidential
Line- Line -interactive interactive UPS principle 264-276V Back- Back -Up Up UPS Principle 150-264V 150-175V
AC mains double converter AC normal/rectify AC fail/invert
battery
20 Emerson Confidential
load
On- On -Line Line UPS UPS Principle Whether AC mains is normal or not, inverter is always operating.
21 Emerson Confidential
UPS Comparing UPS Back-up
Line-interactive
On-line
Inverter state
Back up
Hot back up
operating
Output quality
Low
Middle
High
Transferrin g time
5~12ms
4ms
0
Cost
Low
Middle
High
22 Emerson Confidential
Content
UPS Overview
UPS Principle
UPS Key Technology
UPS Technical Data
UPS Battery
UPS Monitoring System
23 Emerson Confidential
UPS Key Technology UPS
Double Conversion
Digital Control
R
Battery Management
24 Emerson Confidential
n
n
Double Conver Conversion sion
AC-DC
Rectify
DC-AC
Invert
25 Emerson Confidential
3- 3 -Phase Phase SCR Bridge Rectifier
+ 1
3
5
4
6
2
A C
_
6 pulse
26 Emerson Confidential
12- 12 -Pulse Pulse Rectifier
L o a d
Battery and Inverter
30°
Two 6 6-Pulse Rectifiers Phase shift Transformer
27 Emerson Confidential
Boost Circuit ( P FC Circuit ) (PFC £
L
«
D T
V i
£ £
1
£
C
£
«
V
-
-
£
« O
-
L £
«
£
«
L
V i £
£
£
-
C
£
«
£
-
V
«
O
-
£
-
L £
«
V i £
£
-
iL
-
28 Emerson Confidential
£
£
«
C
£
«
£
-
V
O
£
-
«
3- 3 -Phase Phase IGBT Rectifier
29 Emerson Confidential
Comparing
Input power factor:0.7-0.85,harmonic current>30%
Input power factor>0.99,harmonic current<3%
30 Emerson Confidential
Single Phase half bridge invert Circuit U +380
+
C1
Q1
D1
-380
L
+380V
L C3 N
220V
N C2
-380V
-
31 Emerson Confidential
Q2
D2
Inverter Control Signal - S PWM -SPWM SPWM signal generation
32 Emerson Confidential
3- 3 -Phase Phase Bridge Inverter + R
S
T
R R S T
S
T
N
_
33 Emerson Confidential
3- 3 -Phase Phase SCR Rectifier UPS
旁路输 bypass
main 主 路输
34 Emerson Confidential
输 出 output
3- 3 -Phase Phase IGBT Rectifier UPS
bypass
main
output
35 Emerson Confidential
UPS Key Technology UPS
Double Conversion
Digital Control
R
Battery Management
36 Emerson Confidential
n
n
Digital Control Digital signal Processor(DSP) Microprocessor Provide all kinds of driving signal to ,
37 Emerson Confidential
.
DSP •Speed: 10-20 times that of micro-processor • improve integrated degree, •Directly give PWM signal , •Avoid device parameter shifting, ensure product accordance. •No need any hardware adjusting .
Third generation generation: :DSP
Second generation:micro-processor First generation:device+IC
38 Emerson Confidential
UPS Key Technology UPS
Double Conversion
Digital Control
R
Battery Management
39 Emerson Confidential
n
n
Series Connection standby main
UPS1
AC mains
load
bypass
standby
UPS2
Solution for medium power case, easy installation, but power is NOT extended.
40 Emerson Confidential
Parallel Connection AC mains
UPS1
load
Parallel logic control
UPS2
Solution for large power case, each UPS shares load, high reliability,but requires complex technology.
41 Emerson Confidential
Double Power Bus AC PPC
UPS1
Bus1
battery
STS
LBS
UPS
UPS2 Bus2
AC PPC battery 42 Emerson Confidential
load
feed load
UPS Key Technology UPS
Double Conversion
Digital Control
R
Battery Management
43 Emerson Confidential
n
n
Battery FC/EC 1. Current limit
0.1C
:
2. FC to EC:Ic≥0.05C or C≤ 80% EC to FC:Ic ≤ 0.01C FC: Floating Charge EC: Equalizing Charge
44 Emerson Confidential
Content
UPS Overview
UPS Principle
UPS Key Technology
UPS Technical Data
UPS Battery
UPS Monitoring System
45 Emerson Confidential
Technical Data
Input Specification Output Specification
46 Emerson Confidential
Input Voltage Range
adaptability to the power network. The wider the better.
47 Emerson Confidential
Bypass Voltage Range
Typical range : ±10%
48 Emerson Confidential
Input Frequency Range adaptability to the power network. The wider the better. 50Hz±4%
49 Emerson Confidential
Input Power Factor Power Factor = active power /apparent power The higher the better. Smaller PF means lar er reactive ower, more harmonic current , which will pollute AC mains network.
50 Emerson Confidential
Total Harmonic Distortion
THD =harmonic current/Base×100% The smaller the better.
51 Emerson Confidential
Technical Data
Input Specification Output Specification
52 Emerson Confidential
Output Voltage Stability
Input voltage in 220V±25%,output voltage fluctuation range when load change from 0 to .
53 Emerson Confidential
Output Frequency Stability Output Frequency Stability≤0.5% UPS local oscillation frequency stability In battery mode, it comes from crystal oscillator.
54 Emerson Confidential
Frequency Regulation and Frequency Slew Rate Frequency Regulation :50Hz±4%, Frequency Slew Rate≤1Hz/s For Frequency Regulation, the wider the better. Frequency Slew Rate:speed of Output frequency tracing input frequency.
55 Emerson Confidential
Overload Capability
Withstanding duration at 125% rated load, after that, transfers to bypass.
56 Emerson Confidential
Output Current Crest Factor Crest Factor =current peak value/ RMS value. Index of UPS load capability, the larger the better.
For PC、Server, the factor is between 2.5 to 3.0. RMS: Root Mean Square 57 Emerson Confidential
Output Power Factor 0.7 or 0.8 NOT the higher the better. nee no on y ac ve power u a so reactive power. So unit is VA not W.
58 Emerson Confidential
Voltage Distortion
Voltage Distortion = harmonic /Base + harmonic×100% The smaller the better.
59 Emerson Confidential
Content
UPS Overview
UPS Principle
UPS Key Technology
UPS Technical Data
UPS Battery
UPS Monitoring System
60 Emerson Confidential
Content
Battery structure and Principle
Battery Characteristic
Battery Capacity Configuration
61 Emerson Confidential
Lead- Lead -Acid Acid Battery Cell v =1cell
Negative plate:
e-
Form 2V cell
Positive plate: Lead dioxide PbO2
Electrolyte : Sulfuric solution H2SO4
Electrical Energy 62 Emerson Confidential
Chemical Energy
Lead- Lead -Acid Acid Battery Battery— —two two general type
◆ Flooded Battery
◆ VRLA Battery
(or “wet type” or “open vented type”) (Valve Regulated Lead-Acid Battery)
63 Emerson Confidential
VRLA Battery— Battery —used used with UPS
UPS UPS
64 Emerson Confidential
Battery Battery
Structure of VRLA Battery ¢Þ ¢Ù ¢Ú ¢Û ¢Ü ¢Ý ¢Ù
① container & cover
¢
② terminal
¢ ③ strap/group bar ④Positive & negative plates ⑤AGM ⑥ safety valve
AGM: Microporous fibre glass acts as both separator and electrolyte absorber.
65 Emerson Confidential
Battery principle discharge
PbO2+2H2SO4+Pb
PbSO4+2H2O+PbSO4 charge
(lead dioxide) (sulfuric acid) (spongy lead)
(sulfate)
active material electrolyte active material active material positive plate
negative plate
positive plate
“Double sulfate”theory
66 Emerson Confidential
(water)
(sulfate)
electrolyte active material negative plate
Content
Battery structure and Principle
Battery Characteristic
Battery Capacity Configuration
67 Emerson Confidential
Discharge Characteristic Discharge Terminal voltage(V/cell)
2.1 2.0 1.9
.
0.3C 10 0.5C 10
1.8 1.0C 10
1.7 1.6
0.6C 10
2.0C 10
1min 2
6 10 30 min 1h 2 3 5 8 10 20 h discharge time
68 Emerson Confidential
0.1C 10
Charge Characteristic d e e g r m u a l h o C V
120
(%)
g n t i n g e r r a r h u C C
(A)
g n e i g g r a a t l h o C V
2.23V Constant Voltage Charging at 25¡ æ
(V)
100 0.1C
2.4
80 0.08C
2.3
60
0.06C
2.2
40
0.04C
2.1
20 0.02C
2.0
Charged Volume
Charging Voltage
After 100% Discharge After 50% Discharge Charging Current
0 0
4
8
12
16
20
24
Charging Time (hours) 69 Emerson Confidential
28 32
36
Relationship between battery discharge capacity and ambient temperature ¡ ª¡ ª low rate discharge £¾1h ------ high rate discharge £¼1h 120
100
© ¥ £ ¨ £ 0
80
60
1
C y t i c a p a c
40
20
0 -30
-20
-10
0
10
20
Temperature£¨ ¡ 棩 70 Emerson Confidential
30
40
Storage Characteristic 100
90
) % ( y t i c a p C e l b a l i a v A
© £ % ¨ £ ¿ Á Ý È à Ó £ Ê
80
70
50 40
30 0
1
2
3
4
5
6
7
8
9
10
±£´æÊ±¼ä£¨Ô£© Storage time (month)
71 Emerson Confidential
11
12
Comparison of UPS battery and PS battery PS
UPS
Design orientation
Long time、small current、 deep discharge
Short time、large current、
Design life
Above 10 years
3~5 years
Lead paste
Long life formulation,
Large power life formulation,
ong cyc e
s or cyc e
e
light discharge
e
separator
long life separator ,thick
large diameter hole, thin. small current and deep discharge will cause life end.
Recovery ability of
good
So-so
Over-discharge
72 Emerson Confidential
Content
Battery structure and Principle
Battery Characteristic
Battery Capacity Configuration
73 Emerson Confidential
Battery Capacity Configuration
P×pf pf× ×T C = V×η×K P: UPS Capacity, VA pf: UPS output power factor, typically 0.7, T: backup time, V: battery string voltage, η:battery inverting efficiency, typically 85%, K: battery discharge coefficient, T=1~3h, K= 0.6 T=3h~5h, K= 0.8 T=5h~10h,K= 0.85 T>10h, K= 1 74 Emerson Confidential
Battery Capacity Configuration Example : 20kVA UL33 UPS,30 battery cells(12V),Carry 35% load,backup time is 4h,how much battery capacity does it need?
C=
= 94.5AH 305V×0.85×0.8
So need 100AH battery.
75 Emerson Confidential
Content
UPS Overview
UPS Principle
UPS Key Technology
UPS Technical Data
UPS Battery
UPS Monitoring System
76 Emerson Confidential
UPS Monitoring System Function 1、know and control real operating state, 2、provide UPS failure report in time, 3、when AC mains abnormal、battery low voltage,automatically shutdown computer, 4、be able to run in LAN、WAN and Internet,
77 Emerson Confidential
Composition of Monitoring System UPS Monitoring System=Intelligent UPS + Network+Monitoring Software Monitoring Software consists of three parts : SNMP Card Centralized Monitoring Software Safe Shutdown Program
78 Emerson Confidential
UPS Networking Scheme
79 Emerson Confidential
Monitoring Screen Display - U -UPS PS Tree
80 Emerson Confidential
Monitoring Screen Display - S tate -State
81 Emerson Confidential
Monitoring Screen Display - D -Data ata Curve
82 Em Emer erso son n Conf Confid iden enti tial al
Monitoring Screen Display - E -Events vents List
83 Em Emer erso son n Conf Confid iden enti tial al
Monitoring Screen Display - E -Event vent Log Query
84 Em Emer erso son n Conf Confid iden enti tial al
Monitoring Screen Display - D -Data ata Log Query
85 Em Emer erso son n Conf Confid iden enti tial al
UPS Events Handling
µ ¯³ ¶ö »Ô ° ¿ò
notifying Administrator
× Pager ¶Ô Ñ ¯ º° ô ·
-µUPS çÔ Ò ´ Events ³ì Ê £¼ Âþ
É ù¹ ¸â ¾ æ¯
audible/visual alarms
¼Ç ÈÈ ëÖ Õ¾
log
ÖÐ ´ ÎÐ ¼ Äþ
executing command file
86 Emerson Confidential
OFF