Beban Pendinginan
Tica C. Nisa Sustia Ag Agustini ustini Prim Arista M. Nizar Aditya A. Syukron
(2409100037) (2409100047) (2409100059) (2409100061) (2409100063)
METODE CLTD/CLF •
Konduksi pada Dinding Luar, Jendela dan Pintu CLTDcorr
(CLTD LM ) K (78 Tr ) (T 0
Dr
2
85)
LM : Faktor koreksi lintang dan bulan K : Faktor koreksi warna permukaan luar dinding Tr : Suhu ruangan (°F) To : Suhu rancangan luar (°F) Dr : daily rate / suhu rata-rata harian ( °F)
•
Beban Akibat Lampu
Q P 3.41 CLF f Q : laju kalor (Btu/h) P : Daya input (watt) CLF : cooling load factor fs : factor ballast
•
Konduksi Atap dan Lantai
Q A U T Q : laju heat loss (Btu/h) U : koefisien transmisi kalor bahan (Btu/ h. °F.ft2) A : luas permukaan bahan (ft2) ∆T : Perbedaan suhu dalam dan luar ruangan ( °F)
•
Beban akibat Penghuni
Qs N sensHG CLF Qs : laju kalor (Btu/h) sensHG : laju kalor sensible per orang CLF : Cooling Load Factor
•
Beban akibat Peralatan
Q A U T Q : Laju heat loss (Btu/h) U : Koefisien transmisi kalor bahan (Btu/ h.F °.ft2) A : Luas permukaan bahan (ft2) ∆T : Perbedaan suhu dalam dan luar ruangan ( °F)
•
Radiasi Matahari melalui Jendela
Q A SC SHGF CLF Q SC SHGF CLF
: laju aliran kalor radiasi pada kaca (Btu/h) : Shading Coefficient : Solar Heat Gain Maximum (Btu/h.ft2) : Cooling Load Factor
Denah ruangan 2,1 m S
kasur T
B
U
box
2 , 7 m
meja
rak buku
Koefisien transmisi kalor bahan dan nilai cltd
Data pendukung To : Tdb = 104 oF, Twb = 95 oF Tr : Tdb = 91.4 o F T
o
F, Twb = 82.4
= To – Tr = 313 – 306 = 7 K
Tkeseharian
= 98,6 F
Dr
= 21,6 oF
P
= 5 watt
Sens HG
= 315 Btu
Jumlah orang
= 3 orang
Perhitungan CLTD Nilai Cooling Load Temperature Different (CLTD) dari berbagai sisi adalah :
CLTD corrected = [10 + (91.4 – 82.4) + (104 – ((104 – 82.4)/2) – 98,6] = 13,6 oF = 262,7 K
CLTD corrected = [19 + (91.4 – 82.4) + (104 – ((104 – 82.4)/2) – 98,6] = 22,6oF = 267,7 K
CLTD corrected = [14 + (91.4 – 82.4) + (104 – ((104 – 82.4)/2) – 98,6] = 17,6 oF = 265 K
CLTD corrected = [19 + (91.4 – 82.4) + (104 – ((104 – 82.4)/2) – 98,6] = 22,6 oF = 267,7 K
SISI UTARA
SISI TIMUR
SISI BARAT Q dinding kosong selatan = Adinding x Udinding x T = (2,7 x 2.75) x 8,35 x 7 = 433,9 Watt
SISI SELATAN Q dinding kosong selatan = Adinding x Udinding x T = (2,1 x 2,75) x 8,35 x 7 = 337,5 Watt
Konduksi Atap dan Lantai Qatap = Aatap x Uasbes x CLTDtimur = 5.67 x 27 x 267,7 = 40982,2 Watt Qlantai = Alantai x Ukeramik x T = 5,67 x 113,6 x 7 = 4508,7 Watt Qtotal = Qatap
Qlantai = 45490,984 Watt
Beban Akibat Penghuni = Jumlah orang x sensHG x CLF = 3 x 315 Btu x 1 = 945 Btu/h
Beban Akibat LAMPU Q = 1 x P x 3,41 x CLF x fs
= 1 x 5 x 3,41 (-1) x 1 = -17,5 Btu/h
Beban TOTAL
KESIMPULAN Total keseluruhan nilai Q adalah : 305522,684 Watt = 290,24 btu/hr = 0,25 PK Untuk PK di pasaran = 0,03
Dari hasil perhitungan cooling load yang telah dilakukan secara manual dengan metode CLTF/CLF, didapatkan nilai Qtotal sebesar 305522,684 Watt. Dengan Qtotal tersebut, jika dikonversi kedalam bentuk satuan PK maka dihasilkan nilai 0,25 PK. Jadi, untuk kamar kos E29 sebenarnya membutuhkan membutuhkan AC dengan nilai 0,25 PK. Namun jika di pasaran nilai 0,25 PK itu sebenarnya adalah 0,03 PK dan untuk AC nilai tersebut tidak ada. Jadi, kamar E29 tidak begitu membutuhkan AC untuk pendinginan.