RET 670 Transformer Protection Restricted Earthfault
©
ABB Power Technologies AB, 2007
Substation Automation and Protection Training
2008-05-23
Substation Automation and Protection Training
1
RET 670 – Restricted Earthfault Protection
Restricted earthfault protection (PDIF, 87N)
Up to three instances available
Low impedance type
Can be used on all directly or low impedance earthed windings
Up to 4 three-phase CT inputs REF1REFPDIF_87N
©
ABB Power Technologies AB, 2007
I3P I3PW1CT1 I3PW1CT2 I3PW2CT1 I3PW2CT2
2008-05-23 2
Substation Automation and Protection Training
RET 670 – Restricted Earthfault Protection
Restricted earthfault protection (PDIF, 87N)
Able to handle multiple circuit breaker applications as well as autotransformers in 1½ CB applications
I3P I3PW1CT1 I3PW1CT2 I3PW2CT1 I3PW2CT2
©
ABB Power Technologies AB, 2007
I3P I3PW1CT1 I3PW1CT2 I3PW2CT1 I3PW2CT2
2008-05-23
Substation Automation and Protection Training
3
RET 670 – Restricted Earthfault Protection
Restricted earthfault protection (PDIF, 87N)
Functionality
Zero sequence differential protection with a percentage biased operate/restrain characteristic, plus an additional zero sequence current directional comparison criterion
Requires no current magnitude or phase correction, even when OLTC present
Insensitive to inrush and overexcitation currents
Only danger is eventual CT saturation 2nd harmonic restraint (reactor energizing)
©
ABB Power Technologies AB, 2007
2008-05-23 4
Substation Automation and Protection Training
RET 670 – Restricted Earthfault Protection
Restricted earthfault protection (PDIF, 87N)
Functionality
Three-section operate/restrain characteristic Idiff
Settings: operate
Idmin
1st slope 70%
IdMin
2nd slope 100%
restrain
©
ABB Power Technologies AB, 2007
Ibias
2008-05-23
Substation Automation and Protection Training
5
RET 670 – Restricted Earthfault Protection
Restricted earthfault protection (PDIF, 87N)
Functionality
Operate/restrain characteristic
Differential current – vector sum of the fundamental frequency neutral current and the fundamental frequency residual current (calculated from the three line-side fundamental frequency phase currents) Idiff = IN + 3I0
I3PW1 = I3PW1CT1 + I1PW1CT2
ABB Power Technologies AB, 2007
©
For multiple circuit breaker applications, the two contributing residual currents are internally summed to produce the overall line-side residual current
2008-05-23 6
Substation Automation and Protection Training
I3P I3PW1CT1 I3PW1CT2 I3PW2CT1 I3PW2CT2
RET 670 – Restricted Earthfault Protection
Restricted earthfault protection (PDIF, 87N)
Functionality
©
ABB Power Technologies AB, 2007
2008-05-23
Operate/restrain characteristic
The bias current stabilizes the restricted earthfault protection
It is a measure of how high the currents are (i.e. a measure of how difficult the conditions are under which the CTs are operating)
The higher the currents, the more difficult the conditions, and the higher the probability that the calculated differential current has a false component, primarily due to CT saturation
The bias current is calculated as the highest fundamental frequency current amongst all the input currents (three phases / neutral) to the restricted earthfault protection
Included in the bias current calculation is an enhanced feature that ensures security when external faults are disconnected
Substation Automation and Protection Training
7
RET 670 – Restricted Earthfault Protection
Restricted earthfault protection (PDIF, 87N)
Functionality
Operate/restrain characteristic
Single circuit breaker applications – ordinary power trfrs
I3P I3PW1CT1 I3PW1CT2 I3PW2CT1 I3PW2CT2
curr(x) = MAX [I3PW1CT1]
©
ABB Power Technologies AB, 2007
curr(z) = IN i.e. Ibias = MAX [curr(x); curr(z)]
2008-05-23 8
Substation Automation and Protection Training
RET 670 – Restricted Earthfault Protection
Restricted earthfault protection (PDIF, 87N)
Functionality
Operate/restrain characteristic
Multiple circuit breaker applications – ordinary power trfrs
I3P I3PW1CT1 I3PW1CT2 I3PW2CT1 I3PW2CT2
curr(a) = MAX [I3PW1CT1] / CTFactorPri1
©
ABB Power Technologies AB, 2007
curr(b) = MAX [I3PW1CT2] / CTFactorPri2 curr(x) = MAX [I3PW1CT1 + I3PW1CT2] curr(z) = IN i.e. Ibias = MAX [curr(a); curr(b); curr(x); curr(z)] 2008-05-23
Substation Automation and Protection Training
9
RET 670 – Restricted Earthfault Protection
Restricted earthfault protection (PDIF, 87N)
Functionality
Operate/restrain characteristic
Multiple circuit breaker applications
CTFactor = Irated pri_CT / Irated_W
The CTFactor is generally chosen so that when 1pu primary current flows through the CT, this would contribute a 1pu component to the bias calculation – e.g. Irated pri_CT = 1000A Irated_W = 500A contribution to bias calculation = 1000 / (1000/500) = 500A
©
ABB Power Technologies AB, 2007
Ibias (pu) = Ibias (pri A) / IBase, where IBase = Irated_W
2008-05-23 10
Substation Automation and Protection Training
Without CTFactor, a 1pu CT primary current would contribute a 1000A component to the bias calculation (i.e. 2pu)
RET 670 – Restricted Earthfault Protection
Restricted earthfault protection (PDIF, 87N)
Functionality Operate/restrain characteristic
Multiple circuit breaker applications
Applying the CTFactor gives a gain in the sensitivity for internal faults (by reducing the contribution to the bias from the T-side CTs), but still ensures adequate biasing for through fault conditions
©
ABB Power Technologies AB, 2007
2008-05-23
Substation Automation and Protection Training
11
RET 670 – Restricted Earthfault Protection
Restricted earthfault protection (PDIF, 87N)
Functionality
Operate/restrain characteristic
Single circuit breaker applications – autotransformers
I3P I3PW1CT1 I3PW1CT2 I3PW2CT1 I3PW2CT2
curr(x) = MAX [I3PW1CT1] curr(y) = MAX [I3PW2CT1]
©
ABB Power Technologies AB, 2007
curr(z) = IN i.e. Ibias = MAX [curr(x); curr(y); curr(z)]
Note: set IBase = highest winding rated current, normally Irated_MV
2008-05-23 12
Substation Automation and Protection Training
RET 670 – Restricted Earthfault Protection
Restricted earthfault protection (PDIF, 87N)
Functionality
Operate/restrain characteristic
Multiple circuit breaker applications – autotransformers
©
ABB Power Technologies AB, 2007
I3P I3PW1CT1 I3PW1CT2 I3PW2CT1 I3PW2CT2
2008-05-23
Substation Automation and Protection Training
13
RET 670 – Restricted Earthfault Protection
Restricted earthfault protection (PDIF, 87N)
Functionality
Operate/restrain characteristic
Multiple circuit breaker autotransformer applications curr(a) = MAX [I3PW1CT1] / CTFactorPri1 curr(b) = MAX [I3PW1CT2] / CTFactorPri2 curr(c) = MAX [I3PW2CT1] / CTFactorSec1 curr(d) = MAX [I3PW2CT2] / CTFactorSec2 curr(x) = MAX [I3PW1CT1 + I3PW1CT2] curr(y) = MAX [I3PW2CT1 + I3PW2CT2] curr(z) = IN
©
ABB Power Technologies AB, 2007
i.e. Ibias = MAX [curr(a);…….curr(z)]
2008-05-23 14
Substation Automation and Protection Training
I3P I3PW1CT1 I3PW1CT2 I3PW2CT1 I3PW2CT2
RET 670 – Restricted Earthfault Protection
Restricted earthfault protection (PDIF, 87N)
Directional criterion – external earth fault zone of protection
s o A (L1) u r B (L2) c C (L3) e Uzs
zs voltage is max. at the earth fault
I zs1
I a0=
a (L1)
I zs1
I b0=
b (L2)
I zs1
c= 0
c (L3)
I
3Io=3I zs1
IN = -3Izs1
IN
Current in the neutral (IN) serves as a directional reference because it has the same direction for both internal and external faults.
For external fault ROA
©
ABB Power Technologies AB, 2007
3I0 IN
Reference is neutral current
ROA
Restrain for external fault
2008-05-23
Currents 3Io and IN are theoretically 180o out of phase for any external earth fault.
MTA
Operate for internal fault
Substation Automation and Protection Training
15
RET 670 – Restricted Earthfault Protection
Restricted earthfault protection (PDIF, 87N)
Directional criterion – internal earth fault power system contribution to fault current
s o u r c e
zone of protection
A (L1) B (L2) C (L3)
Izs2
Izs1
I
a= 0
a (L1)
Izs2
Izs1
I
b= 0
b (L2)
Izs2
Izs1
I
c= 0
c (L2)
Ifault
Uz s
3Io = -3Izs2
IN
IN = - 3Izs1 Return path for 3Izs2
Return path for 3Izs1
©
ABB Power Technologies AB, 2007
ROA
For internal fault 3I0
IN ROA
Restrain for external fault 2008-05-23 16
Substation Automation and Protection Training
Current in the neutral (IN) serves as a directional reference because it has the same direction for both internal and external faults.
MTA
Reference is neutral current
Operate for internal fault
currents 3Io and IN are approximately in phase for an internal earth fault.
RET 670 – Restricted Earthfault Protection
Restricted earthfault protection (PDIF, 87N)
Directional criterion
The directional criterion is applied in order to positively distinguish between internal and external earth faults – this check is an additional criterion, with the purpose of enhancing the security against maloperations for heavy external earth faults, and during the disconnection of such faults by other protections
For an external earth fault the residual current 3I0 and the neutral current IN are theoretically equal in magnitude and 180 degrees out of phase
For an internal earth fault
©
ABB Power Technologies AB, 2007
the residual current 3I0 and the neutral current IN are approximately in phase
2008-05-23
The current in the neutral (IN) serves as the directional reference because it has the same direction for all earth faults, both internal and external – current polarized
Substation Automation and Protection Training
17
RET 670 – Restricted Earthfault Protection
Restricted earthfault protection (PDIF, 87N)
Directional criterion
a start has been registered from the operate-restrain characteristic
the magnitude of the line-side residual current (3I0) is at least 3% of IBase
If a directional check is not executed (due to too small currents), then the internal directional requirement is cancelled as a condition for trip
If a directional check is executed, then a trip output is only allowed if the currents 3I0 and IN are both within the operating (internal) region
Relay Characteristic Angle (RCA)
ABB Power Technologies AB, 2007
©
A directional check is only executed if
Relay Operate Angle (ROA)
2008-05-23 18
Constant (fixed) 0° (determined by where the line-side residual current (3I0) should lie with respect to the directional reference (neutral current) for an internal earth fault) Settable 60° to 90°
Substation Automation and Protection Training
RET 670 – Restricted Earthfault Protection
Restricted earthfault protection (PDIF, 87N)
2nd harmonic analysis / blocking
Required primarily to prevent unwanted operation on reactor energizing due to possible line-side CT saturation caused by a high dc component of long duration
©
ABB Power Technologies AB, 2007
The current through the neutral CT does not have the same dccomponent, or the same amplitude, and consequently the risk of saturation in this CT is much less
2008-05-23
The differential current that appears as a result of the saturation may be so high that it reaches the operate area of the characteristic
Calculation of 2nd harmonic content in the neutral current is made when certain criteria are fulfilled
If the ratio between 2nd harmonic and fundamental exceeds 60%, the function is blocked
Substation Automation and Protection Training
19
RET 670 – Restricted Earthfault Protection
Restricted earthfault protection (PDIF, 87N)
Overview of restricted earthfault protection function 3I0 < 3% of Ibase 3I0 > 3% of Ibase
©
ABB Power Technologies AB, 2007
Directional check
IN > 50% of Idmin 2008-05-23 20
Substation Automation and Protection Training
≥1
&
TRIP
&
START
RET 670 – Restricted Earthfault Protection
Restricted earthfault protection (PDIF, 87N)
Function block
‘Analog’ quantity inputs
©
ABB Power Technologies AB, 2007
‘Analog’ quantity outputs
2008-05-23
Substation Automation and Protection Training
21
©
ABB Power Technologies AB, 2007
RET 670 – Restricted Earthfault Protection - Settings
2008-05-23 22
Substation Automation and Protection Training
RET 670 – Restricted Earthfault Protection - Settings Settings Settings group N1 Differential protection LowImpREF(PDIF,87N)
©
ABB Power Technologies AB, 2007
Off; On
2008-05-23
Substation Automation and Protection Training
23
RET 670 – Restricted Earthfault Protection
Restricted earthfault protection (PDIF, 87N) Service values
©
ABB Power Technologies AB, 2007
2008-05-23 24
Substation Automation and Protection Training
RET 670 – Restricted Earthfault Protection
Restricted earthfault protection (PDIF, 87N) Service values
©
ABB Power Technologies AB, 2007
2008-05-23
Substation Automation and Protection Training
©
ABB Power Technologies AB, 2007
25
2008-05-23 26
Substation Automation and Protection Training