RET 670 Transformer Protection Differential
©
ABB Power Technologies AB, 2007
Substation Automation and Protection Training
2008-05-23
Substation Automation and Protection Training
1
RET 670 – Transformer Differential Protection
Transformer differential protection (PDIF, 87T)
Two-winding or three-winding
Two-winding variant up to 4 three-phase CT inputs
Three-winding variant up to 6 three-phase CT inputs T2D1T2WPDIF
©
ABB Power Technologies AB, 2007
I3PW1CT1 I3PW1CT2 I3PW2CT1 I3PW2CT2
2008-05-23 2
Substation Automation and Protection Training
T3D1T3WPDIF I3PW1CT1 I3PW1CT2 I3PW2CT1 I3PW2CT2 I3PW3CT1 I3PW3CT2
RET 670 – Transformer Differential Protection
Transformer differential protection (PDIF, 87T)
Two-winding connections
Single CT on both sides T2D1T2WPDIF
©
ABB Power Technologies AB, 2007
I3PW1CT1 I3PW1CT2 I3PW2CT1 I3PW2CT2
2008-05-23
Substation Automation and Protection Training
3
RET 670 – Transformer Differential Protection
Transformer differential protection (PDIF, 87T)
Two-winding connections
2 CTs, on one or both sides T2D1T2WPDIF
©
ABB Power Technologies AB, 2007
I3PW1CT1 I3PW1CT2 I3PW2CT1 I3PW2CT2
2008-05-23 4
Substation Automation and Protection Training
RET 670 – Transformer Differential Protection
Transformer differential protection (PDIF, 87T)
Up to two instances
Can protect two objects with one RET 670 IED, or one object that changes status
Two transformers
Generator / transformer separately
Generating status / pumping status for pump storage unit
Internal adaptation to power transformer vector group, turns ratio and CT ratios
Tap changer position monitoring for increased sensitivity
©
ABB Power Technologies AB, 2007
2008-05-23
Substation Automation and Protection Training
5
RET 670 – Transformer Differential Protection
Transformer differential protection (PDIF, 87T)
Unbalance currents due to factors other than faults
Currents that flow on only one side of the power transformer
Magnetizing currents that flow on only the power source side
Normal magnetizing currents
Inrush magnetizing currents
Overexcitation magnetizing currents
Currents that cannot be transformed to the other windings
©
ABB Power Technologies AB, 2007
2008-05-23 6
Zero sequence currents
Error in the power transformer turns ratio due to OLTC
Inequality of the instrument current transformers
Different ratings of current transformers
Different types of current transformers
Substation Automation and Protection Training
RET 670 – Transformer Differential Protection
Transformer differential protection (PDIF, 87T)
Unbalance currents due to factors other than faults (cont.)
Different relative loads on instrument transformers
Different relative currents on CT primaries
Different relative burdens on CT secondaries
Different DC time constants of the fault currents Different time of occurrence, and degree, of CT saturation
©
ABB Power Technologies AB, 2007
2008-05-23
Substation Automation and Protection Training
7
RET 670 – Transformer Differential Protection
Transformer differential protection (PDIF, 87T)
Functionality
Fundamental frequency differential currents (per phase) – calculated as the vector sum of the fundamental frequency current contributions from all sides of the transformer – all current contributions are referred to a common reference first
©
ABB Power Technologies AB, 2007
2008-05-23 8
Phase reference: first star-connected winding (HV→MV → LV), otherwise if no star winding, first delta-connected winding (HV → MV → LV)
For example, if the power transformer is Yd1, the HV winding (Y) is taken as the phase reference winding; if the power transformer is Dy1, then the LV winding (y) is taken as the phase reference; if there is no star-connected winding, such as in Dd0, then the HV delta-connected winding (D) is automatically chosen as the phase reference
All current contributions are phase shifted with reference to the phase reference side
Substation Automation and Protection Training
RET 670 – Transformer Differential Protection
Transformer differential protection (PDIF, 87T)
Functionality Magnitude reference: first winding (usually HV)
The magnitudes of all current contributions are referred to the magnitude reference side (i.e. W1), i.e. the magnitudes of all current contributions from all other sides are always transferred to the W1 side
It is for this reason that all differential currents are normally expressed in HV-side primary Amperes
©
ABB Power Technologies AB, 2007
2008-05-23
Substation Automation and Protection Training
9
RET 670 – Transformer Differential Protection
Transformer differential protection (PDIF, 87T) Functionality
In numerical differential protections, conversion of all current contributions to the phase and magnitude reference sides is performed mathematically by pre-programmed coefficient matrices, which depend on the protected power transformer transformation ratio and vector group connection
Once the power transformer vector group, rated currents and rated voltages have been entered by the user, the differential protection calculates off-line the matrix coefficients, which are then used in the on-line calculations
©
ABB Power Technologies AB, 2007
2008-05-23 10
Substation Automation and Protection Training
RET 670 – Transformer Differential Protection
Transformer differential protection (PDIF, 87T)
Functionality
Differential currents (in W1-side primary amperes)
ABB Power Technologies AB, 2007
©
Two-winding transformer
2008-05-23
Contribution from W1 side to differential currents
Contribution from W2 side to differential currents
DCCL1_W1
DCCL1_W2
DCCL2_W1
DCCL2_W2
DCCL3_W1
DCCL3_W2
Substation Automation and Protection Training
11
RET 670 – Transformer Differential Protection
Transformer differential protection (PDIF, 87T)
Functionality
Differential currents (in W1-side primary amperes)
ABB Power Technologies AB, 2007
©
Three-winding transformer
2008-05-23 12
Substation Automation and Protection Training
Contribution from W1 side to differential currents
Contribution from W2 side to differential currents
Contribution from W3 side to differential currents
DCCL1_W1
DCCL1_W2
DCCL1_W3
DCCL2_W1
DCCL2_W2
DCCL2_W3
DCCL3_W1
DCCL3_W2
DCCL3_W3
RET 670 – Transformer Differential Protection
Transformer differential protection (PDIF, 87T)
Functionality Values for the A, B, C matrix coefficients depend on
Winding connection type, i.e. star (Y/y) or delta (D/d)
Transformer vector group, i.e. Yd1, Dy11 (which introduces a phase shift between winding currents in multiples of 30°)
Zero sequence current elimination set On / Off
©
ABB Power Technologies AB, 2007
2008-05-23
Substation Automation and Protection Training
13
RET 670 – Transformer Differential Protection
Transformer differential protection (PDIF, 87T)
Functionality On-line compensation for on-load tap-changer (OLTC) movement
The OLTC is a mechanical device that is used to stepwise change the number of turns within one power transformer winding – consequently the overall turns ratio of the transformer is changed
Typically the OLTC is located on the HV winding (i.e. W1) – by stepwise increasing or decreasing the number of HV winding turns, it is possible to stepwise regulate the LV-side voltage
As the turns ratio (transformation ratio) changes from the nominal, the actual primary currents flowing will automatically adjust in accordance with the actual turns ratio
©
ABB Power Technologies AB, 2007
Turns ratio = NLV/NHV and │IHVNHV│ = │ILVNLV│ 2008-05-23 14
Substation Automation and Protection Training
RET 670 – Transformer Differential Protection
Transformer differential protection (PDIF, 87T)
Functionality
On-line compensation for on-load tap-changer (OLTC) movement
However, as the transformation ratio changes from the nominal NLV/NHV = Ur_W2 / Ur_W1 the differential function will calculate a resulting differential current if the ratio Ur_W2 / Ur_W1 is fixed in the calculation
©
ABB Power Technologies AB, 2007
2008-05-23
The differential function in IED 670 has a built-in feature to continuously monitor the tap position and to dynamically compensate on-line for changes in the power transformer turns ratio
Substation Automation and Protection Training
15
RET 670 – Transformer Differential Protection
Transformer differential protection (PDIF, 87T)
Functionality On-line compensation for on-load tap-changer (OLTC) movement
Setting parameters define on which winding the OLTC is located, and what the no-load voltage change is for a tap step
By knowing the actual tap position, the differential function can then calculate the correct no-load voltage for the winding on which the OLTC is located
For example, if the OLTC is located on the HV winding (W1), the no-load voltage Ur_W1 will be treated as a function of the actual tap position, and therefore for every tap position the corresponding value for Ur_W1 will be calculated and used in the differential current calculation
©
ABB Power Technologies AB, 2007
2008-05-23 16
Substation Automation and Protection Training
RET 670 – Transformer Differential Protection
Transformer differential protection (PDIF, 87T)
Functionality On-line compensation for on-load tap-changer (OLTC) movement
By doing this, complete on-line compensation for OLTC movement is achieved – the differential protection will be ideally balanced for every tap position and no false differential current will appear irrespective of the actual tap position
Typically, the minimum differential protection pickup for power transformers with OLTC is set between 30% to 40% - however, with the OLTC compensation feature it is possible to set the differential protection in IED 670 to more sensitive pickup values of 15% to 20%
©
ABB Power Technologies AB, 2007
2008-05-23
Substation Automation and Protection Training
17
RET 670 – Transformer Differential Protection
Transformer differential protection (PDIF, 87T)
Functionality On-line compensation for on-load tap-changer (OLTC) movement
Two-winding differential protection in IED 670 can compensate on-line for one OLTC on the protected power transformer
Three-winding differential protection in IED 670 can compensate on-line for up to two OLTCs on the protected power transformer
©
ABB Power Technologies AB, 2007
2008-05-23 18
Substation Automation and Protection Training
RET 670 – Transformer Differential Protection
Transformer differential protection (PDIF, 87T)
Functionality On-line compensation for on-load tap-changer (OLTC) movement
OLTC position is determined within IEC 670 by function block YLTC
Within this function block, the OLTC position value is continuously monitored to ensure its integrity – if any error with the OLTC position value is detected an alarm will be given which should be connected to the applicable OLTCxAL input of the differential protection function block
Whenever an OLTCxAL input has a logical value 1, the differential protection minimum pickup, originally defined by setting parameter IdMin, will be increased by the set range of the OLTC
©
ABB Power Technologies AB, 2007
2008-05-23
Substation Automation and Protection Training
19
RET 670 – Transformer Differential Protection
Transformer differential protection (PDIF, 87T)
Functionality
©
ABB Power Technologies AB, 2007
2008-05-23 20
Differential current alarm
The fundamental frequency differential current level is monitored all the time within the differential function – as soon as all three fundamental frequency differential currents are above a set threshold, defined by setting parameter IDiffAlarm, a delay on pickup timer is started; when the pre-set time, defined by setting parameter tAlarmDelay, expires, the differential current alarm will be generated and the output signal IDALARM will be set to logical value 1
This feature can be effectively used to provide an alarm when OLTC position compensation is used and something in the whole compensation chain goes wrong
This alarm can also be used to desensitize the differential function (with some additional IED configuration logic that connects the IDALARM output to an OLTCxAL input)
Substation Automation and Protection Training
RET 670 – Transformer Differential Protection
Transformer differential protection (PDIF, 87T)
Functionality
Bias current
Single circuit breaker applications
Calculated as the highest fundamental frequency current amongst all the current contributions to the differential current calculation
This highest individual current contribution is taken as the single common bias current for all three phases DCCL1_W1 DCCL2_W1 +
DCCL2_W2
DCCL3_W1
DCCL3_W2
©
ABB Power Technologies AB, 2007
=
DCCL1_W2
2008-05-23
Substation Automation and Protection Training
21
RET 670 – Transformer Differential Protection
Transformer differential protection (PDIF, 87T)
Functionality
Bias current
Single circuit breaker applications
The current contributions from all windings are already referred to the magnitude reference (W1) side (for this reason, the bias current is usually expressed in HV-side primary Amperes) and can therefore be directly compared regarding their magnitudes
©
ABB Power Technologies AB, 2007
i.e. Ibias = MAX [DCCLx_W1; DCCLx_W2]
2008-05-23 22
Substation Automation and Protection Training
RET 670 – Transformer Differential Protection
Transformer differential protection (PDIF, 87T)
Functionality
Through-fault stability for multi-breaker arrangements
Ideal CTs, external current summation
+A
+B
-A -B
Idiff
To Diff Prot +A -A -B → -B IDIFF = +B -B = 0 IBIAS = MAX(-B; +B)
©
ABB Power Technologies AB, 2007
Ibias
2008-05-23
Substation Automation and Protection Training
23
RET 670 – Transformer Differential Protection
Transformer differential protection (PDIF, 87T)
Functionality
Through-fault stability for multi-breaker arrangements
Real CTs, external current summation
+A
-A -B
+B
Idiff
To Diff Prot +A -A -B ±error → -B ±error IDIFF = +B -B ±error = ±error
©
ABB Power Technologies AB, 2007
IBIAS = MAX(-B ±error; +B)
2008-05-23 24
Substation Automation and Protection Training
Ibias
RET 670 – Transformer Differential Protection
Transformer differential protection (PDIF, 87T) Functionality
Through-fault stability for multi-breaker arrangements
Real CTs, internal current summation
+A
Idiff
+B
-A -B
To RET 670 +A -A -B ±error
T2D1
Ibias
©
ABB Power Technologies AB, 2007
to IBIAS calculation
Σ
to IDIFF & IBIAS calculation IDIFF = +A -A -B ±error +B = ±error IBIAS = MAX(-B ±error; +B; +A; -A -B ±error)
2008-05-23
Substation Automation and Protection Training
25
RET 670 – Transformer Differential Protection
Transformer differential protection (PDIF, 87T)
Functionality
Bias current
Multiple circuit breaker applications, on any or all sides
©
ABB Power Technologies AB, 2007
From any side, the current contributions from the two T-side CTs are included in the bias current calculation, as well as the resultant current contribution for that transformer winding (which is the calculated sum of the two separate CT contributions)
to IBIAS calculation
Σ 2008-05-23 26
Substation Automation and Protection Training
to IDIFF & IBIAS calculation
RET 670 – Transformer Differential Protection
Transformer differential protection (PDIF, 87T)
Functionality
Bias current
Multiple circuit breaker applications, on any or all sides
A*
From W1 CT1:
IL1_W1CT1 IL2_W1CT1
DCCL1_W1CT1
=
IL3_W1CT1
A*
From W1 CT2:
DCCL3_W1CT1
IL1_W1CT2 IL2_W1CT2
DCCL1_W1CT2
=
IL3_W1CT2
©
ABB Power Technologies AB, 2007
From W2 CT1:
(Ur_W2 / Ur_W1) *
B
*
DCCL1_W2CT1
=
IL3_W2CT1
From W2 CT2:
B
*
IL2_W2CT2 IL3_W2CT2
2008-05-23
DCCL2_W2CT1 DCCL3_W2CT1
IL1_W2CT2 (Ur_W2 / Ur_W1) *
DCCL2_W1CT2 DCCL3_W1CT2
IL1_W2CT1 IL2_W2CT1
DCCL2_W1CT1
DCCL1_W2CT2
=
DCCL2_W2CT2 DCCL3_W2CT2
Substation Automation and Protection Training
27
RET 670 – Transformer Differential Protection
Transformer differential protection (PDIF, 87T)
Functionality
Bias current
Multiple circuit breaker applications, on any or all sides
Therefore, in principle, want to include the following contributions in the bias current calculation DCCLx_W1CT1/2; DCCLx_W2CT1/2; DCCLx_W1CT1+DCCLxW1CT2; DCCLxW2CT1+DCCLxW2CT2
However, for applications with two restraint CT inputs on one side (such as for breaker-and-a-half applications), the primary ratings of the CTs can be much higher than the rating of the protected power transformer
In order to determine the bias current for such Tconfigurations, the currents flowing on the T-side can be separately scaled by an additional setting – this is done in order to prevent unwanted de-sensitizing (over-biassing) of the overall differential protection
©
ABB Power Technologies AB, 2007
2008-05-23 28
Substation Automation and Protection Training
RET 670 – Transformer Differential Protection
Transformer differential protection (PDIF, 87T)
Functionality
Bias current
Multiple circuit breaker applications, on any or all sides
When 1pu primary current flows through the T-side CT, want this to contribute a 1pu component to the bias calculation – e.g. Irated pri_CT = 1000A Irated_W1 = 500A Irated_W1 = 500A
©
ABB Power Technologies AB, 2007
1000/1
2008-05-23
Substation Automation and Protection Training
29
RET 670 – Transformer Differential Protection
Transformer differential protection (PDIF, 87T)
Functionality
Bias current
Multiple circuit breaker applications, on any or all sides
If no other action were taken, the contribution to the bias calculation from the 1000A (= 1pu of the CT primary rating) flowing through the T-side CT would be = 1000A (= 2pu!!!)
©
ABB Power Technologies AB, 2007
Ibias (pu) = Ibias (pri A) / IBase, where IBase = Irated_W
Therefore, a scaling factor needs to be introduced (setting parameters CT1RatingW1, CT2RatingW1, CT1RatingW2, CT2RatingW2)
By applying the scaling factor, the contribution to the bias calculation from the 1000A flowing through the T-side CT is then determined as follows: (I / CT1RatingW1)*Irated_W1 = (1000/1000)*500 = 500A (=1pu!!!)
2008-05-23 30
Substation Automation and Protection Training
RET 670 – Transformer Differential Protection
Transformer differential protection (PDIF, 87T)
Functionality
Bias current
Multiple circuit breaker applications, on any or all sides curr(1) = MAX [DCCLx_W1CT1 + DCCLx_W1CT2] curr(2) = MAX [DCCLx_W2CT1 + DCCLx_W2CT2] curr(3) = MAX [DCCLx_W1CT1] * (1 / CT1RatingW1) * RatedCurrentW1 curr(4) = MAX [DCCLx_W1CT2] * (1 / CT2RatingW1) * RatedCurrentW1 curr(5) = MAX [DCCLx_W2CT1] * (Ur_W1 / Ur_W2) * (1 / CT1RatingW2) * RatedCurrentW1 curr(6) = MAX [DCCLx_W2CT2] * (Ur_W1 / Ur_W2) * (1 / CT2RatingW2) * RatedCurrentW1
©
ABB Power Technologies AB, 2007
i.e. Ibias = MAX [curr(1);…….curr(6)]
2008-05-23
Substation Automation and Protection Training
31
RET 670 – Transformer Differential Protection
Transformer differential protection (PDIF, 87T)
Functionality
Zero sequence current elimination
Selectable (per winding) – Setting: On / Off per winding
Elimination of the zero sequence currents is necessary to avoid unwanted trips for external earth faults whenever The protected power transformer cannot transform the zero sequence currents to the other side
The zero sequence currents can only flow on one side of the protected power transformer
The zero sequence currents should be subtracted from the side of the power transformer where the zero sequence currents can flow for external earth faults
©
ABB Power Technologies AB, 2007
2008-05-23 32
Substation Automation and Protection Training
RET 670 – Transformer Differential Protection
Transformer differential protection (PDIF, 87T)
Functionality Zero sequence current elimination
In most cases power transformers do not properly transform the zero sequence currents to the other side – a typical example is a power transformer of the star-delta type (e.g. YNd1)
Transformers of this type do not transform the zero sequence currents, but zero sequence currents can flow in the earthed starconnected winding (e.g. an external earth fault on the star-side causes zero sequence currents to flow on the star-side, but not on the delta-side)
©
ABB Power Technologies AB, 2007
2008-05-23
Substation Automation and Protection Training
33
RET 670 – Transformer Differential Protection
Transformer differential protection (PDIF, 87T)
Functionality
©
ABB Power Technologies AB, 2007
2008-05-23 34
Zero sequence current elimination
This results in false differential currents that consist exclusively of the zero sequence currents – if high enough, these false differential currents can result in the unwanted operation of the differential function (and unwanted disconnection of the healthy power transformer)
The star-winding zero sequence currents must therefore be subtracted from the fundamental frequency differential currents if an unwanted trip is to be avoided
For delta-windings, this feature should be enabled only if an earthing transformer exists within the differential zone on the delta-side of the protected power transformer
Substation Automation and Protection Training
RET 670 – Transformer Differential Protection
Transformer differential protection (PDIF, 87T)
Functionality Zero sequence current elimination
If the zero sequence currents are subtracted from the current contribution of any side to the differential currents, they are automatically eliminated from the bias current contribution as well
Removing the zero sequence current from the differential currents decreases to some extent the sensitivity of the differential protection for internal earth faults
However, the automatic subtraction of the zero sequence currents from the bias current as well counteracts this effect to some degree
©
ABB Power Technologies AB, 2007
=
2008-05-23
DCCL1_W1
DCCL1_W2
DCCL2_W1 +
DCCL2_W2
DCCL3_W1
DCCL3_W2
Substation Automation and Protection Training
35
RET 670 – Transformer Differential Protection
Transformer differential protection (PDIF, 87T)
Functionality
Three-section operate/restrain characteristic
Highset unrestrained limit
Reset ratio 0.95
Idiff
Section 1
Section 2
Section 3 Settings:
Idunre
IdMin IdUnre
©
ABB Power Technologies AB, 2007
Slope Section 2
Slope Section 3
EndSection1 EndSection2 SlopeSection2
Idmin
SlopeSection3 End of Section 1 2008-05-23 36
Substation Automation and Protection Training
End of Section 2
Ibias
RET 670 – Transformer Differential Protection
Transformer differential protection (PDIF, 87T)
Functionality Unrestrained (i.e. non-stabilized) limit
This limit determines the pickup (operate) threshold for big differential currents for which there should be no doubt that the fault is internal
This limit is constant
For measured differential currents greater than this limit, instantaneous tripping is allowed, i.e. no supervision by blocking criteria (waveform or harmonic restrain) is applied
©
ABB Power Technologies AB, 2007
2008-05-23
Substation Automation and Protection Training
37
RET 670 – Transformer Differential Protection
Transformer differential protection (PDIF, 87T)
Functionality
©
ABB Power Technologies AB, 2007
2008-05-23 38
Restrained (i.e. stabilized) characteristic
This characteristic determines the pickup (operate) threshold for differential currents with magnitude less than the unrestrained limit – it is possible for these differential currents to occur and cause pickup for reasons other than internal faults
The pickup (operate) threshold is mostly not constant, as after Section 1 it increases with increasing bias current magnitude – in this way the magnitudes of the individual fundamental frequency differential currents are compared to an adaptive limit that is dependent on the bias (i.e. restrain) current magnitude
Following a start (pickup), blocking criteria (waveform and harmonic restrain) are applied before tripping is permitted, i.e. a trip will only be released if not prevented by one of the blocking criteria
Substation Automation and Protection Training
RET 670 – Transformer Differential Protection
Transformer differential protection (PDIF, 87T)
Functionality
Restrained (i.e. stabilized) characteristic
©
ABB Power Technologies AB, 2007
2008-05-23
Section 1
Most sensitive part
Characteristic a straight line
Current flow normal load current
Typical reason for existence of false differential currents in this section is non compensation for tap position
Section 2
First slope (low percentage)
Caters for false differential currents when higher than normal currents flow through the current transformers
Substation Automation and Protection Training
39
RET 670 – Transformer Differential Protection
Transformer differential protection (PDIF, 87T)
Functionality
Restrained (i.e. stabilized) characteristic
Second slope (higher percentage)
Provides higher tolerance to substantial current transformer saturation for high through fault currents, which can be expected in this section
The characteristic settings should be made such that
for internal faults, the differential currents are always safely above the characteristic
for external faults, any unwanted (false) differential currents are always safely below the characteristic
©
ABB Power Technologies AB, 2007
Section 3
2008-05-23 40
Substation Automation and Protection Training
RET 670 – Transformer Differential Protection
Transformer differential protection (PDIF, 87T)
Functionality Blocking criteria (phase segregated)
The two blocking criteria are the waveform restrain and the harmonic restrain – these two criteria have the power to block (i.e. to prevent) a trip command being given by the differential protection whose operate-restrain characteristic has measured an operate condition (registered a start)
Instantaneous differential currents are calculated on which the waveform and harmonic analyses are performed – the same matrix equations are used as for the fundamental frequency currents, except now instantaneous values (i.e. sampled values) are used instead
©
ABB Power Technologies AB, 2007
2008-05-23
Substation Automation and Protection Training
41
RET 670 – Transformer Differential Protection
Transformer differential protection (PDIF, 87T)
Functionality
Blocking criteria
Waveform restrain
©
ABB Power Technologies AB, 2007
2008-05-23 42
Substation Automation and Protection Training
Based on waveform recognition – looks for the intervals within each power system cycle with low rate-of-change in the instantaneous differential currents that are typical to power transformer inrush currents
RET 670 – Transformer Differential Protection
Transformer differential protection (PDIF, 87T)
Functionality
Blocking criteria Waveform restrain
The waveform restrain function will activate a restrain signal in those phases where this wave shape is detected
If the operate-restrain characteristic registers a start in a particular phase, then the status of the waveform restrain output for the same phase will be assessed, and if activated, a block signal for that phase will be established
The BLKWAVLx output from the function block will only become logic 1 if the waveform restrain output in phase Lx is activated, and the operate-restrain characteristic has registered a start in the same phase
©
ABB Power Technologies AB, 2007
2008-05-23
Substation Automation and Protection Training
43
RET 670 – Transformer Differential Protection
Transformer differential protection (PDIF, 87T)
Functionality
Blocking criteria Harmonic restrain
Required to prevent unwanted tripping due to magnetizing inrush currents, or due to magnetizing currents caused by overvoltages – magnetizing currents flow only on one side of a power transformer, and are therefore always a cause of false differential currents
Harmonic analysis (2nd and 5th harmonic) is performed on the instantaneous differential currents, but only after the operaterestrain characteristic has registered a start – i.e. if the operate-restrain characteristic registers a start in a particular phase, then the harmonic analysis on the instantaneous differential current in that phase will be started (phase segregated)
©
ABB Power Technologies AB, 2007
2008-05-23 44
Substation Automation and Protection Training
RET 670 – Transformer Differential Protection
Transformer differential protection (PDIF, 87T)
Functionality
Blocking criteria
Harmonic restrain For example, if the operate-restrain characteristic has registered a start in phase L1, then the harmonic analysis on the instantaneous differential current in phase L1 will be started – if the content of the 2nd harmonic in the instantaneous differential current of this phase is above the setting I2/I1Ratio, then a block signal for this phase will be established
©
ABB Power Technologies AB, 2007
2008-05-23
Substation Automation and Protection Training
45
RET 670 – Transformer Differential Protection
Transformer differential protection (PDIF, 87T)
Functionality
Blocking criteria
Cross-blocking between phases
If a blocking condition is established in any phase, this phase can ‘cross’ this blocking condition to the other phases, i.e. a phase may only cross-block the other phases if it itself is blocked (and it can only be blocked if its operate-restrain characteristic first registered a start)
IdiffL2/3
©
ABB Power Technologies AB, 2007
IdiffL1 Phase L1 blocked
cross-block
Ibias 2008-05-23 46
Substation Automation and Protection Training
Ibias
RET 670 – Transformer Differential Protection
Transformer differential protection (PDIF, 87T)
Functionality
Blocking criteria
Waveform – inrush
2nd harmonic – inrush, CT saturation
Settings: settable level in % of fundamental
5th harmonic – overexcitation
Settings: None
Settings: settable level in % of fundamental
Cross-blocking between phases Setting: On / Off
©
ABB Power Technologies AB, 2007
2008-05-23
Substation Automation and Protection Training
47
RET 670 – Transformer Differential Protection
Transformer differential protection (PDIF, 87T)
Overview of traditional transformer differential protection function
Blocking condition: 2nd harmonic, 5th harmonic waveblock, cross block
restrained
&
≥1
TRIP
©
ABB Power Technologies AB, 2007
unrestrained
START
2008-05-23 48
Substation Automation and Protection Training
RET 670 – Transformer Differential Protection
Transformer differential protection (PDIF, 87T)
Functionality Switch on to fault feature
The transformer differential function in IED 670 has a built-in switch on to fault feature that ensures quick differential protection tripping in cases where a transformer is energized with an internal fault
This feature can be enabled or disabled by a setting parameter SOTFMode
The principle of operation is based on the fact that a current gap will exist within the first power system cycle when a healthy power transformer is energized, and conversely will not exist if the power transformer is unhealthy (is switched on to a fault)
©
ABB Power Technologies AB, 2007
2008-05-23
Substation Automation and Protection Training
49
RET 670 – Transformer Differential Protection
Transformer differential protection (PDIF, 87T)
Functionality
©
ABB Power Technologies AB, 2007
2008-05-23 50
Switch on to fault feature
If this gap does not exist, the waveblock criterion will reset quickly, i.e. within a time window that started when the transformer was switched in
This quick resetting (within the time window) of the waveblock criterion will temporarily disable the second harmonic blocking feature, which then ensures fast operation of the transformer differential function for a switch on to fault condition
This feature is only active during initial power transformer energizing
When the switch on to fault feature is disabled, or once the time window following switch-in has elapsed, the waveblock and second harmonic blocking features work in parallel and are completely independent of each other
Substation Automation and Protection Training
RET 670 – Transformer Differential Protection
Transformer differential protection (PDIF, 87T) Internal / External fault discriminator
Fault position (internal / external) can be determined by comparing the direction of flow of the negative sequence currents on all sides of the transformer
This is done by simply determining the position of the source of the negative sequence currents with respect to the zone of protection – the source of the negative sequence currents is at the point of fault
External fault: the negative sequence currents will have a relative phase displacement of 180°
Internal fault: the negative sequence currents will have a relative phase displacement of about 0°
©
ABB Power Technologies AB, 2007
2008-05-23
Substation Automation and Protection Training
51
RET 670 – Transformer Differential Protection
Transformer differential protection (PDIF, 87T) Internal / External fault discriminator
What about transformation ratio and phase shift?
Before comparison, the negative sequence current contributions must first be referred to the same phase reference, and put to the same magnitude reference
Modern numerical transformer differential relays use matrix equations to compensate for vector group and turns ratio
Negative sequence differential current contributions can be calculated using the same matrix equations – in this way all negative sequence current contributions are automatically compensated for power transformer vector group and turns ratio
The 0° / 180° criterion is then still valid
©
ABB Power Technologies AB, 2007
2008-05-23 52
Substation Automation and Protection Training
RET 670 – Transformer Differential Protection Transformer differential protection (PDIF, 87T)
Internal / External fault discriminator
Example YNd5 transformer
⎡ IDL1 _ NS ⎤ ⎡ 2 −1 −1⎤ ⎡ INS _ W 1 ⎤ ⎡ −1 0 1 ⎤ ⎡ INS _ W 2 ⎤ ⎢ IDL 2 _ NS ⎥ = 1 ⋅ ⎢ −1 2 −1⎥ ⋅ ⎢ a ⋅ INS _ W 1 ⎥ + Ur _ W 2 ⋅ 1 ⋅ ⎢ 1 −1 0 ⎥ ⋅ ⎢ a ⋅ INS _ W 2 ⎥ ⎢ ⎥ 3 ⎢ ⎥ ⎢ ⎥ Ur _ W 1 3 ⎢ ⎥ ⎢ ⎥ ⎢⎣ IDL3 _ NS ⎥⎦ ⎢⎣ −1 −1 2 ⎥⎦ ⎢⎣ a 2 ⋅ INS _ W 1⎥⎦ ⎢⎣ 0 1 −1⎥⎦ ⎢⎣ a 2 ⋅ INS _ W 2 ⎥⎦ NS contribution from W1 side to NS differential currents
NS contribution from W2 side to NS differential currents
©
ABB Power Technologies AB, 2007
NS differential current
2008-05-23
Substation Automation and Protection Training
53
RET 670 – Transformer Differential Protection
Transformer differential protection (PDIF, 87T)
Internal / External fault discriminator
Two-winding transformers
Three-winding transformers
Operation of the internal / external fault discriminator is based on similar principles
Three directional comparisons are made
©
ABB Power Technologies AB, 2007
Operation of the internal / external fault discriminator is based on the relative position of the two phasors representing the HV/LV (W1/W2) negative sequence current contributions, i.e. on a directional comparison between these two phasors
2008-05-23 54
Substation Automation and Protection Training
RET 670 – Transformer Differential Protection
Transformer differential protection (PDIF, 87T)
Internal / External fault discriminator The Internal / External fault discriminator works equally well for symmetrical 3-phase faults
When a symmetrical 3-phase fault occurs, negative sequence currents (the negative sequence current source) will be present until the dc component in the fault currents die out
This interval of time is long enough for the internal / external fault discriminator to declare either an internal or an external fault
©
ABB Power Technologies AB, 2007
2008-05-23
Substation Automation and Protection Training
55
RET 670 – Transformer Differential Protection
Transformer differential protection (PDIF, 87T)
Internal / External fault discriminator
Characteristic
Settings: IMinNegSeq
©
ABB Power Technologies AB, 2007
NegSeqROA
2008-05-23 56
Substation Automation and Protection Training
RET 670 – Transformer Differential Protection
Transformer differential protection (PDIF, 87T)
Internal / External fault discriminator
©
ABB Power Technologies AB, 2007
2008-05-23
Operation (two-winding transformer)
The LV-side phasor is positioned along the zero degree line – then the relative position of the HV-side phasor in the complex plain is determined
To perform the directional comparison, the magnitudes of both phasors must be high enough to ensure that they are due to a fault, i.e. both must be greater than the settable limit IminNegSeq
To guarantee good sensitivity, this IminNegSeq limit must not be set too high
If the magnitude of any one of the phasors is below the limit, no directional comparison will be made – the internal / external fault discriminator will not operate during transformer energization (inrush)
The settable relay operate angle NegSeqROA determines the boundary between the internal and external fault regions
Substation Automation and Protection Training
57
RET 670 – Transformer Differential Protection
Transformer differential protection (PDIF, 87T)
Internal / External fault discriminator CT saturation
During heavy faults, CT saturation might cause the measured phase angle to differ from 180° for external faults, and from about 0° for internal faults
Effective means to counteract the negative effects of main CT saturation have been integrated into the algorithm
At heavy faults, approximately 5ms time-to-saturation of the main CT is sufficient in order to produce a correct discrimination between internal and external faults
©
ABB Power Technologies AB, 2007
2008-05-23 58
Substation Automation and Protection Training
RET 670 – Transformer Differential Protection
Transformer differential protection (PDIF, 87T)
Internal / External fault discriminator
Discriminates between internal and external faults with very high dependability
Detects even minor faults with high sensitivity and high speed
High performance differential protection is achieved by combining the good properties of traditional differential protection with advanced features of the internal / external fault discriminator
Unrestrained negative sequence differential protection
Sensitive negative sequence protection
©
ABB Power Technologies AB, 2007
Features of Internal / External fault discriminator
2008-05-23
Substation Automation and Protection Training
59
RET 670 – Transformer Differential Protection
Transformer differential protection (PDIF, 87T)
Internal / External fault discriminator
©
ABB Power Technologies AB, 2007
2008-05-23 60
Unrestrained negative sequence differential protection
A start from the ordinary differential protection is required to activate the unrestrained negative sequence differential protection
If the internal / external fault discriminator categorizes this same fault as internal, the blocking supervision is bypassed, and the trip output is generated without any further delay
This logic guarantees a fast operating time, even for heavy internal faults with severely saturated current transformers – harmonic distortions do not slow down the differential protection operation
If the fault is categorized as external, the traditional differential protection is NOT blocked, but additional trip criteria are posed to ensure high external fault stability
Substation Automation and Protection Training
RET 670 – Transformer Differential Protection
Transformer differential protection (PDIF, 87T)
Overview of unrestrained negative sequence differential protection in conjunction with traditional transformer differential protection
Blocking condition: 2nd harmonic, 5th harmonic waveblock, cross block Neg Seq Int / Ext Fault Discriminator
internal
&
&
restrained
≥1
TRIP
©
ABB Power Technologies AB, 2007
unrestrained
START
2008-05-23
Substation Automation and Protection Training
61
RET 670 – Transformer Differential Protection
Transformer differential protection (PDIF, 87T)
Internal / External fault discriminator
©
ABB Power Technologies AB, 2007
2008-05-23 62
Sensitive negative sequence protection
Gives sensitive turn-to-turn fault protection
Independent from the traditional differential protection
No start from the ordinary differential protection is required to activate the sensitive negative sequence differential protection
If the internal / external fault discriminator categorizes the disturbance as internal, a separate trip request is placed – this trip request must be confirmed several times in succession before the final trip request is placed – this security feature results in an increase in the operating time
Nevertheless, an operating time of about 30-50ms is achieved for very low-level turn-to-turn faults
Substation Automation and Protection Training
RET 670 – Transformer Differential Protection
Transformer differential protection (PDIF, 87T)
Overview of sensitive negative sequence protection
Blocking condition: 2nd harmonic, 5th harmonic waveblock, cross block Neg Seq Int / internal Ext Fault I- start & Discriminator internal
&
&
restrained
≥1
TRIP
©
ABB Power Technologies AB, 2007
unrestrained
START
2008-05-23
Substation Automation and Protection Training
63
RET 670 – Transformer Differential Protection
Transformer differential protection (PDIF, 87T)
Functionality
Open CT detection feature
The purpose of the open CT detection feature is to prevent a maloperation of the transformer differential function if a loaded main CT connected to the differential protection is by mistake open-circuited in just one phase on the secondary side
©
ABB Power Technologies AB, 2007
2008-05-23 64
Note: This feature is able to detect an open CT condition (interruption) in one phase only – it is not able to detect the simultaneous interruption in two or three phases, for which the differential function will operate and give a trip output if the false differential current is high enough
This feature can be enabled or disabled by the setting parameter OpenCTEnable
Substation Automation and Protection Training
RET 670 – Transformer Differential Protection
Transformer differential protection (PDIF, 87T)
Functionality Open CT detection feature
In order to prevent an unwanted operation of the differential function for an open-circuit condition, the open CT detection feature must operate within 10ms, to ensure in-time blocking of the differential function
It is required to work only during normal load conditions, and is automatically disabled during external faults, big overloads and inrush conditions
Its principle of operation is based on the fact that, for an interruption in one phase, the current in that phase will suddenly drop to zero, while the currents in the other two phases will continue as before
©
ABB Power Technologies AB, 2007
2008-05-23
Substation Automation and Protection Training
65
RET 670 – Transformer Differential Protection
Transformer differential protection (PDIF, 87T)
Functionality Open CT detection feature
If the load currents are very low, or zero, an open CT condition cannot be detected – the open CT algorithm will only detect an open CT condition if the load on the power transformer is in the range 10 – 110% of the rated load
The search for an open CT condition starts 60 seconds (50 seconds in 60 Hz systems) after the bias current enters the 10 – 110% range
©
ABB Power Technologies AB, 2007
2008-05-23 66
Substation Automation and Protection Training
RET 670 – Transformer Differential Protection
Transformer differential protection (PDIF, 87T)
Functionality Open CT detection feature
If an open CT is detected, all the differential functions, except the unrestrained (instantaneous) level, will be blocked immediately
The unrestrained level will also be blocked after a settable time delay tOCTUnrstDelay
An alarm signal will be given after a settable delay tOCTAlarmDelay
The open CT algorithm provides detailed information about the location of the open CT secondary circuit
©
ABB Power Technologies AB, 2007
Transformer side,
CT input, and
Phase
in which the open CT condition was detected 2008-05-23
Substation Automation and Protection Training
67
RET 670 – Transformer Differential Protection
Transformer differential protection (PDIF, 87T)
Functionality Open CT detection feature
A detected open CT condition will be reset automatically by the differential function itself once the condition has been repaired – it is not possible to externally reset the open CT detection
After reset, the open CT detection algorithm will again start to search for an open CT condition within the protected zone
©
ABB Power Technologies AB, 2007
2008-05-23 68
Substation Automation and Protection Training
RET 670 – Transformer Differential Protection
Transformer differential protection (PDIF, 87T)
Functionality
Open CT detection feature
The automatic reset of the open CT detection requires the following conditions to be fulfilled
The bias current must be in the range 10 – 110% of the rated load for at least one minute
The current asymmetry must disappear, i.e. the open CT condition must be repaired Note: not only must the current asymmetry disappear, but current symmetry must be detected
©
ABB Power Technologies AB, 2007
2008-05-23
The above two conditions must be fulfilled for the time interval defined by the setting parameter tOCTResetDelay – the differential functions will remain blocked until this time delay has elapsed (the reason for this is to prevent a maloperation immediately following the reconnection of the open CT circuit)
Substation Automation and Protection Training
69
RET 670 – Transformer Differential Protection Transformer differential protection (PDIF, 87T)
©
ABB Power Technologies AB, 2007
2008-05-23 70
Substation Automation and Protection Training
RET 670 – Transformer Differential Protection
Transformer differential protection (PDIF, 87T) Simplified logic diagram for phase L1
©
ABB Power Technologies AB, 2007
2008-05-23
Substation Automation and Protection Training
71
RET 670 – Transformer Differential Protection
Transformer differential protection (PDIF, 87T)
Simplified logic diagram for internal / external fault discriminator Internal/ External Fault discrimin ator
IDNSMAG
Constant
a
INTFAULT
AND
OpNegSeqDiff=On IBIAS
EXTFAULT
t
TRNSSENS
b>a
b
BLKNSSEN BLKNSUNR BLOCK ABB Power Technologies AB, 2007
©
AND
STL1 STL2 STL3
2008-05-23 72
Substation Automation and Protection Training
OR
TRNSUNR
RET 670 – Transformer Differential Protection
Transformer differential protection (PDIF, 87T)
Internal grouping of Trip signals TRIPRESL1 TRIPRESL2 TRIPRESL3
OR
TRIPRES
OR
TRIPUNRE
TRIPUNREL1 TRIPUNREL2 TRIPUNREL3
TRIP
OR
TRNSSENS
©
ABB Power Technologies AB, 2007
TRNSUNR
2008-05-23
Substation Automation and Protection Training
73
RET 670 – Transformer Differential Protection
Transformer differential protection (PDIF, 87T)
Internal grouping of Start and Block signals STL1 STL2 STL3
OR
START
OR
BLK2H
OR
BLK5H
OR
BLKWAV
BLK2HL1 BLK2HL2 BLK2HL3 BLK5HL1 BLK5HL2 BLK5HL3 BLKWAVL1 BLKWAVL2
©
ABB Power Technologies AB, 2007
BLKWAVL3
2008-05-23 74
Substation Automation and Protection Training
RET 670 – Transformer Differential Protection
Transformer differential protection (PDIF, 87T) Differential current alarm
©
ABB Power Technologies AB, 2007
2008-05-23
Substation Automation and Protection Training
75
RET 670 – Transformer Differential Protection
Transformer differential protection (PDIF, 87T)
Functions blocks for two- and three-winding functions
‘Analog’ quantity Inputs for 2-W OLTC inputs Block inputs
Trip outputs Start outputs
‘Analog’ quantity Inputs for 3-W OLTC inputs
Block outputs
Diff current alarm CT output Open CT outputs
©
ABB Power Technologies AB, 2007
‘Analog’ quantity outputs
2008-05-23 76
Substation Automation and Protection Training
©
ABB Power Technologies AB, 2007
RET 670 – Transformer Differential Protection - Settings
2008-05-23
Substation Automation and Protection Training
77
RET 670 – Transformer Differential Protection - Settings
©
ABB Power Technologies AB, 2007
Settings General settings Differential protection TransformerDiff3Wind(PDIF,87T)
2008-05-23 78
Substation Automation and Protection Training
RET 670 – Transformer Differential Protection - Settings
©
ABB Power Technologies AB, 2007
Settings General settings Differential protection TransformerDiff3Wind(PDIF,87T)
2008-05-23
Substation Automation and Protection Training
79
©
ABB Power Technologies AB, 2007
RET 670 – Transformer Differential Protection - Settings
2008-05-23 80
Substation Automation and Protection Training
RET 670 – Transformer Differential Protection - Settings
WYE (Y); Delta (D)
©
ABB Power Technologies AB, 2007
0 [0 deg]; 1 [30 deg lag]; 2 [60 deg lag]; 3 [90 deg lag]; 4 [120 deg lag]; 5 [150 deg lag]; 6 [180 deg]; 7 [150 deg lead]; 8 [120 deg lead]; 9 [90 deg lead]; 10 [60 deg lead]; 11 [30 deg lead]
2008-05-23
Substation Automation and Protection Training
81
RET 670 – Transformer Differential Protection - Settings
©
ABB Power Technologies AB, 2007
Off; On
2008-05-23 82
Substation Automation and Protection Training
RET 670 – Transformer Differential Protection - Settings
No; Yes
©
ABB Power Technologies AB, 2007
No; Yes
No; Yes
2008-05-23
Substation Automation and Protection Training
83
RET 670 – Transformer Differential Protection - Settings
©
ABB Power Technologies AB, 2007
Not Used Winding 1 (W1) Winding 2 (W2) Winding 3 (W3)
2008-05-23 84
Substation Automation and Protection Training
RET 670 – Transformer Differential Protection - Settings
©
ABB Power Technologies AB, 2007
Not Used Winding 1 (W1) Winding 2 (W2) Winding 3 (W3)
2008-05-23
Substation Automation and Protection Training
85
RET 670 – Transformer Differential Protection - Settings Settings Settings group N1 Differential protection TransformerDiff3Wind(PDIF,87T)
Off; On Off; On
©
ABB Power Technologies AB, 2007
Off; On Off; On
Off; On
2008-05-23 86
Substation Automation and Protection Training
RET 670 – Transformer Differential Protection
Transformer differential protection (PDIF, 87T) Service values
©
ABB Power Technologies AB, 2007
2008-05-23
Substation Automation and Protection Training
87
RET 670 – Transformer Differential Protection
Transformer differential protection (PDIF, 87T) Service values
©
ABB Power Technologies AB, 2007
2008-05-23 88
Substation Automation and Protection Training
RET 670 – Transformer Differential Protection
Transformer differential protection (PDIF, 87T) Service values
©
ABB Power Technologies AB, 2007
2008-05-23
Substation Automation and Protection Training
89
RET 670 – Transformer Differential Protection
Transformer differential protection (PDIF, 87T) Service values
©
ABB Power Technologies AB, 2007
2008-05-23 90
Substation Automation and Protection Training
ABB Power Technologies AB, 2007
©
2008-05-23 91
Substation Automation and Protection Training