FireFinder-XLS Wiri rin ng Compati tib bilityGuide
INTR IN TROD ODUC UCTI TION ON
This wi This wiri ring ng gu guid ide e co cont ntai ains ns in inffor orma mati tion on co conc ncer erni ning ng ci circ rcui uits ts th that at le lea ave th the e Fi Fire reFi Find nder er XL XLS S system enclosure. Table 6 contains specific ratings for each circuit and other data that is useful when planning field wiring. The Wiring Compatibility Matrix covers the requirements when multiple circuits share the same conduit or raceway. raceway. In all cases the wiring must comply with all local and national codes. Table 1 shows the allowable resistance to ensure no more than a 1.5dB loss in the wire for speaker circuits. While a 1.5dB loss does not represent a significant loss in sound pressure level, it cannot be used to guarantee acceptable sound pressure in all cases. Table 2 lists the typical resistance for copper wire at 75 degrees Celsius per NFPA 70 Table 8. The stated values are for a single conductor. If a more precise value is desired, contact the manufacturer of your cable and obtain the value for the specific cable being used.
Use of existing wire is allowed (provided it complies with the requirements of this guide) - pending approval of local AHJ. The use of multiple circuits, even of the same type, within the same jacketed cable is not allowed. When existing wire is to be used, it is recommended to conduct a wiring survey to determine the quality of the existing wire - prior to committing to use the wire.
TABLE 1: MAXIMUM SPEAKER ZONE WIRE RESISTANCE FOR -1.5dB LOSS 10W
20W
30W
40W
50W
75W
96W
125W
150W
180W
25V
12
5.9
3.9
2.9
2.4
1.6
1.2
0.9
0.8
0.7
70.7V
94
47
32
23
19
13
9.8
7.5
6.3
5.2
NOTES: 1. A ll r esistances i nclude both wi r es f or C lass B or all f our wir es f or Class A. 2. For Bulk ampli f i ed zones, subtr act the r i ser r esi stance f r om the value in the table. Multi ply the r emai nder by the number of connected zones. Thi s i s the maxi mum r esi stance f or each connected zone. Thi s calculati on assumes that each zone suppor ts the same wattage.
TAB LE 2: T YPICAL WIRE RESISTANC E AT 75°C (167°F) FOR 1000 FEET (1 WIRE)
Ohms
P/N 315-034786-3
22 AWG
20 AWG
18 AWG
16 AWG
14 AWG
12 AWG
19.6
12.3
7.77
4.89
3.07
1.93
Siemen s Industry Siemens Industry,, Inc. Building Tec vision echnologies Division hnologies Di
Tables 3 through 5 are to be used when designing spea ker and NAC circui circuits ts with the HCP. When designing design ing speaker circuits use Table Table 1 to calculate maximum riser loss and Table 4 or 5 to calculate speaker zone loss.
TABLE 3: MAXIMUM ALLOWAB LE HCP OUTPUT CIRCU IT LINE RESISTAN CE FOR SPECIFIED D C R ISER CURR ENT AN D LINE RESISTANCE MAXIMU M D C RISER C URRE NT (in Amps)
0.1 Ohm
0.25 Ohm
0.5 Ohm
0.75 Ohm
1 Ohm
1.5 Ohms
4
2.73
2.33
1.67
1.00
.33
—
3
2.80
2.50
2.00
1.50
1.00
—
2
2.86
2.67
2.33
2.00
1.67
1.00
1
2.93
2.83
2.67
2.50
2.33
2.00
.5
2.96
2.92
2.83
2.75
2.67
2.50
DC RISER RESISTANCE (in Ohms)
M AXIMUM LOOP RESIST ANCE FOR E ACH HCP ON RISER NOTES: 1. Resi stances specif i ed ar e f or all wi r es. 2. If the total cur r ent r equir ement exceeds 4 A, local auxi li ar y 24 VDC suppli es that ar e UL listed f or f ir e pr otection si gnali ng use, such as Si emens P AD-3, may be used.
TABLE 5: HCP USED FOR 25V RMS OPTION
TABLE 4: HCP USED FOR 70.7V RMS OPTION 0
0
APPROXIMATE SPEAKER ZONE WIRE LOSS IN DECIBELS FOR VARIOUS GAUGE WIRES VERSUS TOTALSPEAKER ZONE WIRE LENGTH (FEET), WHICH IS TWICE THE WIRE RUN LENGTH.
APPROXIMATE SPEAKER SPEAKER ZONE WIRE LOSS IN DECIBELS FOR VARIOUS GAUGE WIRES VERSUS TOTALSPEAKER ZONE WIRE LENGTH (FEET), WHICH IS TWICE THE WIRE RUN LENGTH.
-.5
-0.05
1 4 4 AW G
-1.0
-0.10 S S O L B d
S S O L B d
1 6 A W G
-0.15
-1.5
1 8 A W G
SPEAKER LOAD: 25 WATTSAT 70.7V RMS LOCATEDAT END OF RUN
1 6 A W G
DOES NOT INCLUDEANY LOSS IN RISER RUN
DOES NOT INCLUDEANY LOSS IN RISER RUN
-0.20
-2.0
-0.25
-2.5
100
200
300
400
1 8 A W G
SPEAKER LOAD: 25 WATTS AT 25V RMS LOCATED AT END OF RUN
500
600
700
800
900
100
1000
200
300
400
500
600
700
800
900
TOTALSPEAKER ZONE WIRE LENGTH (FEET)
TOTALSPEAKER ZONE WIRE LENGTH (FEET)
The following cable was tested during the creation of this wiring guide. This information is provided for reference reference only. The use of #24 AWG cable is not allowed due to restrictions associated with Power Power Limited Circuits. Substitute an equivalent #22 AWG cable as needed.
CAT 5e #24awg (4 pair Shielded) CAT 5e #24awg (4 pair Unshielded) THHN #12awg (stranded) Twisted #14awg (FPLR) Twisted #18awg (FPLR) Twisted/Shielded #14awg (FPLR) Twisted/Shielded #18awg (FPLR) THHN #14awg (twisted pair) Siemens Industry, Inc. Building Technologies Division
Olympic Wire P/N 3378M5-9 Olympic Wire P/N 3078M5U Olympic Wire P/N 12 THHN Olympic Wire P/N 2342L Olympic Wire P/N 2202L Olympic Wire P/N 2893L Olympic Wire P/N 2886L Olympic Wire P/N 14STR THHN-0&2
2
P/N 315-034786-3
1000
Figures 1 through 3 illustrate how to calculate the total wire resistance t hat is specified in the MAX. LINE RESISTANCE RESISTANCE column of Table 6. These figures apply to all circuits that are classified as Class A, Class B or Class X. For the DLC ONLY, Class B circuits may be T-Tapped. WIRE 1
DEVICE
EOLR
DEVICE
WIRE 2
TYPICAL TYPIC AL CLAS CLASS S B CIRCU CIRCUIT IT MAXIMUM LINE RESISTANCE SPECIFIED IN TABLE 6 IS THE SUM OF THE LENGTH OF WIRE 1 + WIRE 2.
Figure 1 WIRE 1
WIRE 2
EOLR
DEVICE
DEVICE
WIRE 3
WIRE 4
TYPICA TYP ICAL L CLA CLASS SS A CIR CIRCUI CUIT T MAXIMUM LINE RESISTANCE SPECIFIED IN TABLE 6 IS THE SUM OF THE LENGTH OF WIRE 1 + WIRE 2 + WIRE 3 + WIRE 4.
Figure 2 DEVICE
WIRE 1
WIRE 2
DEVICE
WIRE 1
WIRE 1
WIRE 1
WIRE 2
WIRE 1
WIRE 1
DEVICE
WIRE 2
WIRE 2
WIRE 2 WIRE 1
DEVICE
DEVICE
DEVICE
WIRE 2
WIRE 2 DEVICE
CLASS B DLC LOOP WITH T-TAPS NOTALLOWED FOR CLASS A LOOPS LOOPS.. MAXIMUM LINE RESISTANCE RESISTANCE SPECIFIED SPECIFIED IN TABLE 6 IS THE SUM OF THE THE LENGTH OFALL WIRE 1 SEGMENTS SEGMENTS + ALL WIRE 2 SEGMENTS. SEGMENTS.
Figure 3 Siemens Industry, Inc. Building Technologies Division
3
P/N 315-034786-3
TABLE 6: SPECIFICATIONS AND AND LIMITATIONS
MODULE
CIRCUIT / BUS NAME
CIRCUIT TYPE
ALCC
Global Paging Riser
CDC-4
WIRING CLASSES SUPPORTED
TYPE OF WIRE ALLOWED
ACCEPTABLE WIRE GAUGE
FIBER OPTIC CABLE
MAX. CIRCUIT CURRENT DRAW
POWER LIMITED
MAX. LINE RESISTANCE (All Wires)
Notification Appliance Circuit/Zone
Class B or Class A
Twisted Pair or Twisted Shielded Pair
12AWG 12AWG to to 18AWG 18AWG
Not suppo supporte rted d
.57A (40W @ 70.7V)
YES
80 Ohms
Conventional Detector Initiating Device Circuit Zone
Class B or Class A
UL Approved Single Conductor, Twisted Pair or Twisted Shielded Pair
12AWG to 18AW G
Not supported
175mA / zone
YES
70 Ohms (No Accessories) 40 Ohms (With Accessories)
Yes - use DFM/DFM-BRK
NA
YES
22 AWG, 75 Ohms 20 AWG, 47 Ohms 18AWG, 30 Ohms 16AWG, 19 Ohms 14AWG, 12 Ohms 12AWG, 7 Ohms CAT3 (0.6mm), 38 Ohms CAT3 (0.8mm), 21 Ohms CAT5 (0.51mm), 157 Ohms
12AWG to 22AW G
Not supported
NA
YES
15 Ohms
UL Approved Single Conductor, Twisted Pair or Twisted Shielded Pair
12AW G to 22AW G
Not supported
375m A
YES
252 Devices, 50 Ohms 200 Devices, 62 Ohms 100 Devices,126 Ohms 0-50 Devices, 250 Ohms
Twisted Pair or Twisted Shielded Pair
12AW G to 22AW G
Not supported
NA
YES
100 Ohms
UL Approved Single Conductor, Twisted Pair or Twisted Shielded Pair
12AWG to 18AW G
Not supported
1.5A
YES
See TABLE 3
UL Approved Single Conductor, Twisted Pair or Twisted Shielded Pair
12AWG to 18AW G
Not supported
35mA
YES
24 Ohms
Class B (Style Y) or Class A (Style Z)
UL Approved Single Conductor, Twisted Pair or Twisted Shielded Pair
12AW G to 18AW G
Not supported
25W(25V) =1A
YES
See TABLES 4 & 5
Class B or Class A
UL Approved Single Conductor, Twisted Pair or Twisted Shielded Pair
14AWG to 18AW G
Not supported
6mA
YES
NA
Class B or Class A
UL Approved Single Conductor, Twisted Pair or Twisted Shielded Pair
12AWG to 18AW G
Not supported
34mA
YES
35 Ohms
Twisted Pair, CAT-3 (22AWG) or 12AWG to 22AWG CAT-5 (22AWG) (FPL/FPLR/FPLP) Shielded wire is allowed with CAT-3 or CAT-5, CAT-3/CAT-5 but the distance is cut in (22AWG) half.
DNET (Digital (Digital Audio) Audio)
Signaling Signaling Line Circuit Circuit
Class B (Style 4) or Class X (Style 7)
CAN CAN (Lo (Loca call Net Netwo work rk))
Sign Signali aling n g Line Line Circu Circuit it
Clas Class s B (St (Style yle 4)
Twisted Pair or Twisted Shielded Pair
DLC
P2 Detect Detector or Loop Loop
Signali Signaling ng Line Line Circui Circuitt
Class B (Style 4) or Class A (Style 6)
FMT
T el el ep ep ho ho ne ne Ri se se r
T el el ep ep ho ho ne ne R is is er er
Class B or Class A (with FMT-A ADPT)
Steady NAC
Notification Appliance Circuit/Zone
T el el ep epho ne ne Z on one
T el el ep ep ho ho ne ne Zo Zo ne ne
Speaker Zone 25V, 70V
Notification Appliance Circuit/Zone
Addressable Control Control Point
Initiating Device Circuit
DAC-NET
HCP (Output)
HTRI -S/-D/-R/-M INPUT
Class B (Style Y) or Class A (Style Z)
Class B
HZM
Conventional Detector Initiating Device Circuit Zone
LVM
Remote Microphone / Speaker Circuit
Remote Microphone & Monitor Speaker
Class B
Twisted Shielded Pair
12AWG to 22AW G
Not supported
NA
YES
15 Ohms
HNET (Local Network)
Signaling Line Circuit
Class B (Style 4) or Class X (Style 7)
Twisted Pair or Twisted Shielded Pair
12AWG to 22AWG
Yes - use D2300CPS or D2325CPS
NA
YES
78.4 Ohms (22 AW G)
CAN CAN (Lo (Loca call Net Netwo work rk))
Sign Signali aling n g Line Line Circu Circuit it
Clas Class s B (St (Style yle 4)
Twisted Pair or Twisted Shielded Pair
12AWG to 22AW G
Not supported
NA
YES
15 Ohms
XNET (Peer to Peer Network)
Signaling Line Circuit
Class B (Style 4) or Class X (Style 7)
Twisted Pair or Twisted Shielded Pair
12AWG to 22AWG
Yes - use D2300CPS or D2325CPS
NA
YES
78.4 Ohms (22 AW G)
NIC-C
Siemens Industry, Inc. Building Technologies Division
4
P/N 315-034786-3
TABLE 6: SPECIFICATIONS AND LIMITATIONS
MAX. CAPACITANCE LINE TO LINE
.33uF Line to Line .66uF Line to Earth
NA
END OF LINE DEVICE
MAXIMUM WIRING DISTANCES ( @ 50pF/ft. line to line )
12AWG, 6600 feet (Class A, ZAC-40 Feed to Return) (Class B, ZAC-40 to last ALCC) (limited by capacitance) 68K Ohm 18AWG, 5100 feet (Class A, ZAC-40 Feed to Return) (Class B, ZAC-40 to last ALCC) (limited by resistance)
50uF @ 50V or 4.7K Ohms
18,000 feet (Feed to Return, 12AWG,Class A, no accessories) (limited by resistance) 2500 feet (18AWG,ClassB,with accessories) (limited by resistance)
980 feet CAT3 unshielded 490 feet CAT3 shielded 2900 feet CAT5 unshielded 1450 feet CAT5 shielded 1900 feet 12-22AWG Twisted Pair (between DACNET modules) (Class A or B)
.1uF (reference only, see MAXIMUM WIRING DISTANCE column)
Not required
.1uF TP .05uF TSP
120 Ohm at each end
2000 feet max. (12AWG) (Class B) (limited by capacitance)
.5uF line to line, 1uF line to chassis
Not required
10,000 feet (12 AWG) (Class B) 252 Devices installed (limited by capacitance)
.5uF
10 K Ohms
NA
.125uF
NA
.02uF Line to Line .04uF Line to Earth
NA
SPECIAL FE FEATURES
Class B requires (2 pairs/4 wires) Class A requires (4 pairs/8 wires)
WIRING OUTSIDE THE BUILDING
RATINGS IN THIS GUIDE SUPERSEDE INSTALLATION INSTRUCTION REVISION
MODULE
Underground wiring is permissible if all National and Local code requirements are met and the circuit is installed in an appropriate raceway. Transient protection devices should be installed in accordance with NFPA 70. Overhead exterior wiring is not permitted.
0
ALCC
Underground wiring is permissible if all National and Local code requirements are met and the circuit is installed in an appropriate raceway. Transient protection devices should be installed in accordance with NFPA 70. Overhead exterior wiring is not permitted.
5 or lower
CDC-4
Underground wiring is permissible if all National and Local code requirements are met and the circuit is installed in an appropriate raceway. Transient protection devices should be installed in accordance with NFPA 70. Overhead exterior wiring is not permitted.
8 or lower DAC-NET
Not allowed
SureWire - polarity insensitive loop wiring. T-Tapping allowed (Class B ONLY) PCB Rev 3 and Firmware Rev 05.03.0006 or higher is required to achieve the ratings in this guide.
Underground wiring is permissible if all National and Local code requirements are met and the circuit is installed in an appropriate raceway. Transient protection devices should be installed in accordance with NFPA 70. Overhead exterior wiring is not permitted.
10 or lower
DLC
10,000 feet (12 AWG) (Class B) (limited by capacitance)
Underground wiring is permissible if all National and Local code requirements are met and the circuit is installed in an appropriate raceway. Transient protection devices should be installed in accordance with NFPA 70. Overhead exterior wiring is not permitted.
7 or lower
FMT
24K Ohm
See TABLE 3
Underground wiring is permissible if all National and Local code requirements are met and the circuit is installed in an appropriate raceway. Transient protection devices should be installed in accordance with NFPA 70. Overhead exterior wiring is not permitted.
75K Ohm
2500 feet (12AWG)(Class B) (limited by capacitance)
Underground wiring is permissible if all National and Local code requirements are met and the circuit is installed in an appropriate raceway. Transient protection devices should be installed in accordance with NFPA 70. Overhead exterior wiring is not permitted.
9 or lower
HCP (Output)
24K Ohm
See TABLES 4 & 5
Underground wiring is permissible if all National and Local code requirements are met and the circuit is installed in an appropriate raceway. Transient protection devices should be installed in accordance with NFPA 70. Overhead exterior wiring is not permitted.
470 Ohms
200 Feet All AWG (regardless of resistance or capacitance)
Underground wiring is permissible if all National and Local code requirements are met and the circuit is installed in an appropriate raceway. Transient protection devices should be installed in accordance with NFPA 70. Overhead exterior wiring is not permitted.
HTRI-M 3 or lower lower HTRI-S/D/R 5 or lower lower
HTRI -S/-D/-R/-M INPUT
Underground wiring is permissible if all National and Local code requirements are met and the circuit is installed in an appropriate raceway. Transient protection devices should be installed in accordance with NFPA 70. Overhead exterior wiring is not permitted.
4 or lower
HZM
7 or lower
LVM
8 or lower
NIC-C
4.7K Ohm
12AWG, 9000 feet (Class A) 18AWG, 2250 feet (Class B) Panel Feed to Panel Return (Class A) Panel to Last Device (Class B) (all limited by resistance)
3.3K Internal to the LVM
2000 feet max. (12AWG) (Class B) (limited by capacitance)
Up to 5 LVMs per LPB
.25uF TP .15uF TSP
Not required
2000 feet (regardless of AWG) between nodes (Class A or B)
Short circuit isolation between Nodes. Network repeater built-in
.1uF TP .05uF TSP
120 Ohm at each end
2000 feet max. (12AWG) (Class B) (limited by capacitance)
Not required
2000 feet (regardless of AWG) between nodes (Class A or B)
.1uF
.25uF TP .15uF TSP
Siemens Industry, Inc. Building Technologies Division
Not Allowed
Underground wiring is permissible if all National and Local code requirements are met and the circuit is installed in an appropriate raceway. Transient protection devices should be installed in accordance with NFPA 70. Overhead exterior wiring is not permitted.
Not allowed
Short circuit isolation between Nodes. Network repeater built-in
5
Underground wiring is permissible if all National and Local code requirements are met and the circuit is installed in an appropriate raceway. Transient protection devices should be installed in accordance with NFPA 70. Overhead exterior wiring is not permitted.
P/N 315-034786-3
TABLE 6: SPECIFICATIONS AND AND LIMITATIONS CONTINUED
MODULE
CIRCUIT / BUS NAME
CIRCUIT TYPE
WIRING CLASSES SUPPORTED
TYPE OF WIRE ALLOWED
ACCEPTABLE WIRE GAUGE
FIBER OPTIC CABLE
MAX. CIRCUIT CURRENT DRAW
POWER LIMITED
MAX. LINE RESISTANCE (All Wires)
TZC-8B
Telephone Zone
Telephone Zone
Class B
Twisted Pair or Twisted Shielded Pair
12AWG to 22AW G
Not supported
35mA per Zone
YES
100 Ohms
Speaker Zone
Notification Appliance Circuit/Zone
Class B (Style Y) or Class A (Style Z) Zone can be wired Split/Interleaved/ A/B (2 Class B zones)
UL Approved Single Conductor, Twisted Pair or Twisted Shielded Pair
12AWG 12AWG to to 18AWG 18AWG
Not suppo supporte rted d
40W(25V) load = 1.6A 20W(25V0 load = 0.8A 10W(25V) load = 0.4A
YES
See TABLE 1
Bulk Amplifier/ Audio Source
Notification Appliance Circuit/Zone
UL Approved Single Conductor, Twisted Pair or Twisted Shielded Pair
12AWG 12AWG to to 18AWG 18AWG
Not suppo supporte rted d
40W(25V) load = 1.6A 20W(25V0 load = 0.8A 10W(25V) load = 0.4A
YES
See TABLE 1
Speaker Zone
Notification Appliance Circuit/Zone
UL Approved Single Conductor, Twisted Pair or Twisted Shielded Pair
12AWG 12AWG to to 18AWG 18AWG
Not suppo supporte rted d
180W(25V) load = 7.2A 90W(25V) load = 3.6A 45W(25V) load = 1.8A
NO
See TABLE 1
Bulk Amplifier/ Audio Source
Notification Appliance Circuit/Zone
Class B (Style Y) or Class A (Style Z)
UL Approved Single Conductor, Twisted Pair or Twisted Shielded Pair
12AWG 12AWG to to 18AWG 18AWG
Not suppo supporte rted d
180W(25V) load = 7.2A 90W(25V) load = 3.6A 45W(25V) load = 1.8A
NO
See TABLE 1
NAC Steady
Notification Appliance Circuit/Zone
Class B (Style Y) or Class A (Style Z)
UL Approved Single Conductor, Twisted Pair or Twisted Shielded Pair
YES
.5A load = 7.9 Ohm 1.0A load = 3.4 Ohm 1.5A load = 1.9 Ohm 2.0A load = 1.2 Ohm 2.5A load = 1.0 Ohm 3.0A load = .8 Ohm
Class B (Style Y) or Class A (Style Z)
UL Approved Single Conductor, Twisted Pair or Twisted Shielded Pair
YES
.5A load = 7.9 Ohm 1.0A load = 3.4 Ohm 1.5A load = 1.9 Ohm 2.0A load = 1.2 Ohm 2.5A load = 1.0 Ohm 3.0A load = .8 Ohm
12AWG to 18AW G
Not supported
3A per zone
YES
.5A load = 7.9 Ohm 1.0A load = 3.4 Ohm 1.5A load = 1.9 Ohm 2.0A load = 1.2 Ohm 2.5A load = 1.0 Ohm 3.0A load = .8 Ohm
ZAC-40
Class B (Style Y) or Class A (Style Z)
Class B (Style Y) or Class A (Style Z) Zone can be wired Split/Interleaved/ A/B (2 Class B zones)
ZAM-180
NAC Coded
Notification Appliance Circuit/Zone
12AWG to 18AW G
12AWG to 18AW G
Not supported
Not supported
3A per zone
3A per zone
ZIC-4A
Sync Strobe
Notification Appliance Circuit/Zone
Class B (Style Y) or Class A (Style Z)
UL Approved Single Conductor, Twisted Pair or Twisted Shielded Pair
Speaker Zone 25V, 70V
Notification Appliance Circuit/Zone
Class B (Style Y) or Class A (Style Z)
UL Approved Single Conductor, Twisted Pair or Twisted Shielded Pair
12AWG to 18AW G
Not supported
96W(25V) = 3.84A
YES
See TABLE 1
NAC Steady
Notification Appliance Circuit/Zone
Class B (Style Y)
UL Approved Single Conductor, Twisted Pair or Twisted Shielded Pair
12AWG to 18AW G
Not supported
2A per zone
YES
.5A load = 6.9 Ohm 1.0A load = 3.3 Ohm 1.5A load = 2.1 Ohm 2.0A load = 1.5 Ohm
NAC Coded
Notification Appliance Circuit/Zone
Class B (Style Y)
UL Approved Single Conductor, Twisted Pair or Twisted Shielded Pair
12AWG to 18AW G
Not supported
2A per zone
YES
.5A load = 6.9 Ohm 1.0A load = 3.3 Ohm 1.5A load = 2.1 Ohm 2.0A load = 1.5 Ohm
Sync Strobe
Notification Appliance Circuit/Zone
Class B (Style Y)
UL Approved Single Conductor, Twisted Pair or Twisted Shielded Pair
12AWG to 18AW G
Not supported
2A per zone
YES
.5A load = 6.9 Ohm 1.0A load = 3.3 Ohm 1.5A load = 2.1 Ohm 2.0A load = 1.5 Ohm
Speaker Zone 25V, 70V
Notification Appliance Circuit/Zone
Class B (Style Y)
UL Approved Single Conductor, Twisted Pair or Twisted Shielded Pair
12AWG 12AWG to to 18AWG 18AWG
Not suppo supporte rted d
25W(25V) = 1A 30W(70V) = 0.43A
YES
See TABLE 1
ZIC-8B
Siemens Industry, Inc. Building Technologies Division
6
P/N 315-034786-3
TABLE 6: SPECIFICATIONS AND AND LIMITATIONS CONTINUED
MAX. CAPACITANCE LINE TO LINE
.5uF
NA
END OF LINE DEVICE
MAXIMUM WIRING DISTANCES ( @ 50pF/ft. line to line )
10K Ohm
68K Ohm
SPECIAL FEATURES
WIRING OU OUT SIDE THE BUILDING
10,000 feet (12 AWG) (Class B) (limited by capacitance)
Provides dial and busy tones
Underground wiring is permissible if all National and Local code requirements are met and the circuit is installed in an appropriate raceway. Transient protection devices should be installed in accordance with NFPA 70. Overhead exterior wiring is not permitted.
See TABLE 1
Zone is supervised when active can be used for non-emergency use (Convenience page or background music)
Underground wiring is permissible if all National and Local code requirements are met and the circuit is installed in an appropriate raceway. Transient protection devices should be installed in accordance with NFPA 70. Overhead exterior wiring is not permitted.
RATINGS IN THIS GUIDE SUPERSEDE INSTALLATION INSTRUCTION REVISION
MODULE
5 or lower
TZC-8B
5 or lower
ZAC-40
NA
NA
68K Ohm
68K Ohm
Underground wiring is permissible if all National and Local code requirements are met and the circuit is installed in an appropriate raceway. Transient protection devices should be installed in accordance with NFPA 70. Overhead exterior wiring is not permitted.
See TABLE 1
See TABLE 1
Zone is supervised when active can be used for non-emergency use (Convenience page or background music)
Underground wiring is permissible if all National and Local code requirements are met and the circuit is installed in an appropriate raceway. Transient protection devices should be installed in accordance with NFPA 70. Overhead exterior wiring is not permitted.
6 or lower
ZAM-180
NA
NA
68K Ohm
24K Ohm
Underground wiring is permissible if all National and Local code requirements are met and the circuit is installed in an appropriate raceway. Transient protection devices should be installed in accordance with NFPA 70. Overhead exterior wiring is not permitted.
See TABLE 1
Underground wiring is permissible if all National and Local code requirements are met and the circuit is installed in an appropriate raceway. Transient protection devices should be installed in accordance with NFPA 70. Overhead exterior wiring is not permitted.
3A, 12AWG, 200 feet (Class B) 1A, 14AWG, 550feet (Class B) (all limited by resistance)
NA
24K Ohm
3A, 12AWG, 200 feet (Class B) 1A, 14AWG, 550feet (Class B)
Single circuit can sound (3) unique codes- based on logic
(all limited by resistance)
Underground wiring is permissible if all National and Local code requirements are met and the circuit is installed in an appropriate raceway. Transient protection devices should be installed in accordance with NFPA 70. Overhead exterior wiring is not permitted.
7 or lower
ZIC-4A
NA
24K Ohm
3A, 12AWG, 200 feet (Class B) 1A, 14AWG, 550feet (Class B)
All strobe circuits on a given ZIC-4A are synchronized.
(all limited by resistance)
NA
NA
24K Ohm
24K Ohm
Underground wiring is permissible if all National and Local code requirements are met and the circuit is installed in an appropriate raceway. Transient protection devices should be installed in accordance with NFPA 70. Overhead exterior wiring is not permitted.
See TABLE 1
Underground wiring is permissible if all National and Local code requirements are met and the circuit is installed in an appropriate raceway. Transient protection devices should be installed in accordance with NFPA 70. Overhead exterior wiring is not permitted.
2A, 12AWG, 380feet (Class B) 1A, 14AWG, 530feet (Class B) (all limited by resistance)
NA
24K Ohm
2A, 12AWG, 380feet (Class B) 1A, 14AWG, 530feet (Class B)
Underground wiring is permissible if all National and Local code requirements are met and the circuit is installed in an appropriate raceway. Transient protection devices should be installed in accordance with NFPA 70. Overhead exterior wiring is not permitted.
Single circuit can sound (3) unique codes- based on logic
(all limited by resistance)
Underground wiring is permissible if all National and Local code requirements are met and the circuit is installed in an appropriate raceway. Transient protection devices should be installed in accordance with NFPA 70. Overhead exterior wiring is not permitted.
6 or lower ZIC-8B
NA
24K Ohm
2A, 12AWG, 380feet (Class B) 1A, 14AWG, 530feet (Class B)
All strobe circuits on a given ZIC-8B are synchronized.
(all limited by resistance)
NA
24K Ohm
Siemens Industry, Inc. Building Technologies Division
Underground wiring is permissible if all National and Local code requirements are met and the circuit is installed in an appropriate raceway. Transient protection devices should be installed in accordance with NFPA 70. Overhead exterior wiring is not permitted.
Underground wiring is permissible if all National and Local code requirements are met and the circuit is installed in an appropriate raceway. Transient protection devices should be installed in accordance with NFPA 70. Overhead exterior wiring is not permitted.
See TABLE 1