YASNAC MRC ver. 3.144B
Trouble Shooting Guide, YASNAC MRC
MOTOMAN ROBOTICS AB a subsidiary of YASKAWA Electric Corporation
Notes
MOTOMAN ROBOTICS AB
Alarm 0010
Trouble Shooting YASNAC MRC Page: 1
CPU Board Insertion Error Alarm Occurrence Turn power OFF, and then ON again.
NO
Alarm re-occurs?
YES
Remove the SV board corresponding to the display, and then re-install it
Resume use
Alarm re-occurs?
YES
NO Resume use
Remove the MCP01 board, and then re-install it NO Resume use
Alarm re-occurs?
YES
Replace the ROM of the board corresponding to the display NO
Alarm re-occurs?
YES Replace the board corresponding to the display
ROM failure
YES
Alarm re-occurs?
Board failure
Replace all boards
NO Board failure
Skapad: 98-10-09
Ändrad: 98-11-26
Alarm re-occurs?
NO
YES Contact MOTOMAN-service
Filnamn: T:\M-ROBOT\ENGELSK\TROUBLE_SHOOTING.FM
Trouble Shooting YASNAC MRC
MOTOMAN ROBOTICS AB
Page: 2
Alarm 0020
CPU Communication Error Alarm Occurrence Turn power OFF, and then ON again.
NO Resume use
Alarm re-occurs?
YES
Remove the SV board corresponding to the display, and then re-install it Alarm re-occurs?
YES
NO Resume use
Remove all boards, and then re-install them
NO
Alarm re-occurs?
Resume use
YES
Replace the ROM of the board corresponding to the display NO
Alarm re-occurs?
YES Replace the board corresponding to the display
ROM failure
YES
Alarm re-occurs?
Board failure
Replace all boards
NO Board failure
Skapad: 98-10-09
Ändrad: 98-11-26
Alarm re-occurs?
NO
YES Contact MOTOMAN-service
Filnamn: T:\M-ROBOT\ENGELSK\TROUBLE_SHOOTING.FM
MOTOMAN ROBOTICS AB
Alarm 0030
Trouble Shooting YASNAC MRC Page: 3
ROM Error Alarm Occurrence Turn power OFF, and then ON again.
NO Resume use
Alarm re-occurs?
YES
Replace the ROM of the board corresponding to the display NO ROM failure
Alarm re-occurs?
YES Replace the board corresponding to the display
YES Contact MOTOMAN-service
Skapad: 98-10-09
Ändrad: 98-11-26
Alarm re-occurs?
NO Board failure
Filnamn: T:\M-ROBOT\ENGELSK\TROUBLE_SHOOTING.FM
Trouble Shooting YASNAC MRC
MOTOMAN ROBOTICS AB
Page: 4
Alarm 0040
RAM Error (local) Alarm Occurrence Turn power OFF, and then ON again.
NO
Alarm re-occurs?
Resume use
YES
Remove the board corresponding to the display, and then re-install it NO Resume use
Alarm re-occurs?
YES Replace the board corresponding to the display
YES
Contact MOTOMAN-service
Skapad: 98-10-09
Ändrad: 98-11-26
Alarm re-occurs?
NO Board failure
Filnamn: T:\M-ROBOT\ENGELSK\TROUBLE_SHOOTING.FM
MOTOMAN ROBOTICS AB
Alarm 0050
Trouble Shooting YASNAC MRC Page: 5
RTC Error) Alarm Occurrence Turn power OFF, and then ON again.
NO Resume use
Alarm re-occurs?
YES
Remove the board corresponding to the display, and then re-install it NO Resume use
Alarm re-occurs?
YES Replace the board corresponding to the display
YES
Contact MOTOMAN-service
Skapad: 98-10-09
Ändrad: 98-11-26
Alarm re-occurs?
NO Board failure
Filnamn: T:\M-ROBOT\ENGELSK\TROUBLE_SHOOTING.FM
Trouble Shooting YASNAC MRC
MOTOMAN ROBOTICS AB
Page: 6
Alarm 0060
RAM Error (A-bus Common) Alarm Occurrence Turn power OFF, and then ON again.
NO
Alarm re-occurs?
Resume use
YES
Remove the board corresponding to the display, and then re-install it YES
Alarm re-occurs?
NO
Remove all boards and re-install again
NO
Alarm re-occurs?
Resume use
YES Replace the board corresponding to the display
Resume use
YES
Alarm re-occurs?
Board failure
Replace all boards NO
Alarm re-occurs?
Board failure
Skapad: 98-10-09
NO
YES Contact MOTOMAN-service
Ändrad: 98-11-26
Filnamn: T:\M-ROBOT\ENGELSK\TROUBLE_SHOOTING.FM
MOTOMAN ROBOTICS AB
Alarm 0070
Trouble Shooting YASNAC MRC Page: 7
RAM Error (D-Bus 2-Port) Alarm Occurrence Turn power OFF, and then ON again.
NO Resume use
Alarm re-occurs?
YES
Remove the SV board corresponding to the display, and then re-install it YES
Alarm re-occurs?
NO
Remove all boards and re-install again NO Resume use
Alarm re-occurs?
Resume use
YES
Replace the SV board corresponding to the display NO
Alarm re-occurs?
SV board failure
YES Replace the MCP02 board
YES
Alarm re-occurs?
Replace all boards NO Board failure
Skapad: 98-10-09
Ändrad: 98-11-26
Alarm re-occurs?
NO
Board failure YES
Contact MOTOMAN-service
Filnamn: T:\M-ROBOT\ENGELSK\TROUBLE_SHOOTING.FM
Trouble Shooting YASNAC MRC
MOTOMAN ROBOTICS AB
Page: 8
Alarm 0080
RAM Error (S-Bus 2-Port) Alarm Occurrence Turn power OFF, and then ON again. Alarm re-occurs?
NO Resume use
YES
Remove the board corresponding to the display, and then re-install it Alarm re-occurs?
YES
NO
Remove MCP01 and re-install again Alarm re-occurs?
NO Resume use
Resume use
YES Replace the board corresponding to the display Alarm re-occurs?
YES Replace the MCP01 board Alarm re-occurs?
NO MCP01 board failure
Skapad: 98-10-09
Ändrad: 98-11-26
NO Board failure
YES
Contact MOTOMAN-service
Filnamn: T:\M-ROBOT\ENGELSK\TROUBLE_SHOOTING.FM
MOTOMAN ROBOTICS AB
Alarm 0090
Trouble Shooting YASNAC MRC Page: 9
I/O Module Communication Error Alarm Occurrence Turn power OFF, and then ON again.
NO
Alarm re-occurs?
YES Confirm the setting of the I/O module
Resume use
Alarm re-occurs?
YES
NO Resume use
Check the wiring of the cable between MIF01 and MBB02 NO Resume use
Alarm re-occurs?
YES
Remove the I/O module corresponding to the display, and then re-install it Alarm re-occurs?
YES
NO Resume use
Replace the I/O module NO
Alarm re-occurs?
YES Replace MIF01 board
I/O module failure YES
Contact MOTOMAN-service
Skapad: 98-10-09
Ändrad: 98-11-26
Alarm re-occurs?
NO MIF01 board failure
Filnamn: T:\M-ROBOT\ENGELSK\TROUBLE_SHOOTING.FM
Trouble Shooting YASNAC MRC
MOTOMAN ROBOTICS AB
Page: 10
Alarm 0100
IAMP Communication Error Alarm Occurrence Turn power OFF, and then ON again. Alarm re-occurs?
NO Resume use
YES
Remove the cable connector between the MSV board and IAMP Alarm re-occurs?
YES Check the wiring of the cable between MSV board and IAMP Alarm re-occurs?
NO
Resume use
YES
Resume use
Confirm the setting of the servopack Alarm re-occurs?
YES Replace the servopack NO
Alarm re-occurs?
NO Resume use
YES Replace the MSV board
Servopack failure YES
Contact MOTOMAN-service
Skapad: 98-10-09
NO
Ändrad: 98-11-26
Alarm re-occurs?
NO MSV board failure
Filnamn: T:\M-ROBOT\ENGELSK\TROUBLE_SHOOTING.FM
MOTOMAN ROBOTICS AB
Alarm 0110
Trouble Shooting YASNAC MRC Page: 11
IAMP Parameter Modification Error Alarm Occurrence Turn power OFF, and then ON again.
NO Resume use
Alarm re-occurs?
YES
Remove the cable connector between the MSV board and IAMP and re-install Alarm re-occurs?
YES
NO
Check the wiring of the cable between MSV board and IAMP
NO
Alarm re-occurs?
Resume use
YES Replace the servopack
Resume use NO
Alarm re-occurs?
YES Replace the MSV board
Servopack failure YES
Contact MOTOMAN-service
Skapad: 98-10-09
Ändrad: 98-11-26
Alarm re-occurs?
NO
MSV Board failure
Filnamn: T:\M-ROBOT\ENGELSK\TROUBLE_SHOOTING.FM
Trouble Shooting YASNAC MRC
MOTOMAN ROBOTICS AB
Page: 12
Alarm 0120
Encoder communication error Alarm Occurrence Turn power OFF, and then ON again.
Resume use
NO
Alarm re-occurs?
YES
Remove the cable connector between encoder and IAMP, and then re-install it
Remove the cable connector between the MSV board and IAMP and re-install Alarm re-occurs?
YES
NO
Resume use Resume use
NO
Alarm re-occurs?
YES
Check the cable ground between encoder and IAMP Cable failure
NO
Remove the cable connector between encoder and IAMP, and then install to another axis
YES
Alarm re-occurs?
Replace the servopack
Alarm re-occurs? YES
NO
Check the wiring of the cable between MSV board and IAMP
Cable failure
NO
YES
Alarm re-occurs?
YES
Alarm re-occurs?
Alarm re-occurs? YES Replace the MSV board
Contact MOTOMAN-service
Reset the absolute encoder YES
Servopack failure
Alarm re-occurs? YES
Replace the motor
NO
NO
Resume use
Alarm re-occurs? NO BSV Board failure
Contact MOTOMAN-service
NO Motor failure Skapad: 98-10-09
Ändrad: 98-11-26
Filnamn: T:\M-ROBOT\ENGELSK\TROUBLE_SHOOTING.FM
MOTOMAN ROBOTICS AB
Alarm 0130
Trouble Shooting YASNAC MRC Page: 13
Encoder Overspeed Alarm Occurrence Turn power OFF, and then ON again.
NO
Alarm re-occurs?
Resume use
YES After the motor stops, control power ON.
YES
Alarm re-occurs?
Reset the absolute encoder
NO
Alarm re-occurs?
Resume use
Resume use
YES Replace servo motor
YES
Contact MOTOMAN-service
Skapad: 98-10-09
NO
Ändrad: 98-11-26
Alarm re-occurs?
NO Motor failure
Filnamn: T:\M-ROBOT\ENGELSK\TROUBLE_SHOOTING.FM
Trouble Shooting YASNAC MRC
MOTOMAN ROBOTICS AB
Page: 14
Alarm 0131
Encoder Data Error Alarm Occurrence Turn power OFF, and then ON again.
NO
Alarm re-occurs?
Resume use
YES Reset the absolute encoder
NO
Alarm re-occurs?
YES Replace the motor
Resume use YES
Alarm re-occurs?
Motor failure
Contact MOTOMAN-service
Alarm 0132
NO
Encoder Back-up Error Alarm Occurrence
Change the battery, reset the alarm and then set home position NO
Alarm re-occurs?
Resume use
YES Reset the absolute encoder
NO
Alarm re-occurs?
Replace the motor
Resume use YES Contact MOTOMAN-service Skapad: 98-10-09
Ändrad: 98-11-26
YES
Alarm re-occurs?
NO Motor failure
Filnamn: T:\M-ROBOT\ENGELSK\TROUBLE_SHOOTING.FM
MOTOMAN ROBOTICS AB
Alarm 0133
Trouble Shooting YASNAC MRC Page: 15
Encoder Checksum Error Alarm Occurrence
Change the battery, reset the alarm and then set home position. NO
Alarm re-occurs?
Resume use
YES
Reset the absolute encoder NO
Alarm re-occurs?
Resume use
Replace servo motor
YES Contact MOTOMAN-service
Skapad: 98-10-09
Ändrad: 98-11-26
YES
Alarm re-occurs?
NO Motor failure
Filnamn: T:\M-ROBOT\ENGELSK\TROUBLE_SHOOTING.FM
Trouble Shooting YASNAC MRC
MOTOMAN ROBOTICS AB
Page: 16
Alarm 0134
Encoder Battery Error Alarm Occurrence
Change the battery
NO
Alarm re-occurs?
Resume use
YES
Check Internal wiring YES
Alarm re-occurs?
Resume use
Reset the absolute encoder
NO
Alarm re-occurs?
Resume use
YES Replace the motor
YES
Alarm re-occurs?
NO Motor failure
Contact MOTOMAN-service
Alarm 0135
NO
Encoder Overheat Alarm Occurrence After cooling, turn the power ON again
NO
Alarm re-occurs?
Resume use
Check Internal wiring
YES Contact MOTOMAN-service Skapad: 98-10-09
YES
Ändrad: 98-11-26
Alarm re-occurs?
NO Internal wire failure
Filnamn: T:\M-ROBOT\ENGELSK\TROUBLE_SHOOTING.FM
MOTOMAN ROBOTICS AB
Alarm 0200
Trouble Shooting YASNAC MRC Page: 17
Fault (Parameter) Alarm Occurrence Turn power OFF, and then ON again.
NO
Alarm re-occurs?
YES
Resume use
Contact MOTOMANservice before initializing the parameter file
Alarm 0210
Fault (System Config-Data) Alarm Occurrence
Contact MOTOMANservice before initializing the parameter file
Alarm 0220
Fault (Job Management Data) Alarm Occurrence Turn power OFF, and then ON agian.
NO
Alarm re-occurs?
Resume use
Initialize the job file YES Contact MOTOMAN-service
Skapad: 98-10-09
YES
Ändrad: 98-11-26
Alarm re-occurs?
NO Job file destroyed
Filnamn: T:\M-ROBOT\ENGELSK\TROUBLE_SHOOTING.FM
Trouble Shooting YASNAC MRC Page: 18
Alarm 0230
MOTOMAN ROBOTICS AB
Fault (CIO Ladder) Alarm Occurrence Initialize the CIO Ladder Alarm re-occurs?
NO
YES
Contact MOTOMAN-service
CIO Ladder destroyed
Alarm 0300
Verify Error (System Config-Data) Alarm Occurrence
Contact MOTOMANservice before initializing the system config.
Alarm 0310
Verify Error (CMOS Memory Size) Alarm Occurrence Confirm the extension CMOS board NO
Alarm re-occurs?
The extension CMOS board is not mounted
Skapad: 98-10-09
Ändrad: 98-11-26
YES Contact MOTOMANservice before initializing the system config.
Filnamn: T:\M-ROBOT\ENGELSK\TROUBLE_SHOOTING.FM
MOTOMAN ROBOTICS AB
Alarm 0320
Trouble Shooting YASNAC MRC Page: 19
Verify Error (I/O module) Alarm Occurrence
Remove the I/O-module that corresponds to the display, then re-install the module Alarm re-occurs?
NO
YES
Resume use
Confirm the setting of the I/O module Alarm re-occurs?
YES Replace the I/O module corresponding to the display
NO
Alarm re-occurs?
I/O module failure
Alarm 0330
NO Resume use
YES
Contact MOTOMAN-service
Illegal Parameter Alarm Occurrence Reset original parameter value
NO
Alarm re-occurs?
Resume use
Skapad: 98-10-09
YES
Contact MOTOMAN-service
Ändrad: 98-11-26
Filnamn: T:\M-ROBOT\ENGELSK\TROUBLE_SHOOTING.FM
Trouble Shooting YASNAC MRC Page: 20
Alarm 0340
MOTOMAN ROBOTICS AB
Verify Error (Servopack Type) Alarm Occurrence
Set the parameter to match the mounted servopack type NO
Alarm re-occurs?
YES
Resume use
Contact MOTOMANservice before initializing the system config.
Alarm 0350
Verify Error (Encoder Type) Alarm Occurrence
Set the parameter to match the mounted encoder type NO
Alarm re-occurs?
Resume use
Alarm 0360
YES
Contact MOTOMANservice before initializing the system config.
Verify Error (Application) Alarm Occurrence
Contact MOTOMAN-service before initializing the system config.
Alarm 0370
Verify Error (Sensor Function) Alarm Occurrence
Contact MOTOMAN-service before initializing the system config.
Skapad: 98-10-09
Ändrad: 98-11-26
Filnamn: T:\M-ROBOT\ENGELSK\TROUBLE_SHOOTING.FM
MOTOMAN ROBOTICS AB
Alarm 0400
Trouble Shooting YASNAC MRC Page: 21
Parameter Transmission Error Alarm Occurrence Turn power OFF, and then ON agian.
NO
Alarm re-occurs?
Resume use
YES
Replace the board corresponding to the display
NO
Alarm re-occurs?
Board failure
Replace all boards YES Contact MOTOMAN-service
Alarm 0410
YES
Alarm re-occurs?
NO
Board failure
Mode Change Error Alarm Occurrence Turn power OFF, and then ON again.
NO
Alarm re-occurs?
Resume use
Skapad: 98-10-09
YES Contact MOTOMAN-service
Ändrad: 98-11-26
Filnamn: T:\M-ROBOT\ENGELSK\TROUBLE_SHOOTING.FM
Trouble Shooting YASNAC MRC Page: 22
MOTOMAN ROBOTICS AB
Alarm 0900 - 0920 Watch Dog Timer Error Turn power OFF, and then ON agian.
Alarm Occurrence
Alarm re-occurs? NO
YES Remove the board corresponding to the display, then re-install it
Resume use Remove all boards, then re-install them
Alarm re-occurs?
YES
NO
Alarm re-occurs? NO
Resume use YES
Resume use
Replace the EPROM of the board corresponding to the display Replace board corresponding to the display
YES
Alarm re-occurs? NO
Alarm re-occurs? YES
NO
Replace all boards
Board failure Alarm re-occurs?
EPROM failure
YES
NO Contact MOTOMAN-service
Board failure
AL-0900
MCP02
AL-0901
Skapad: 98-10-09
AL-0906
MCP01
AL-0914
MSV#5
AL-0907
MIF01
AL-0915
MSV#6 MSV#7
AL-0902
MSL#1
AL-0910
MSV#1
AL-0916
AL-0903
MSL#2
AL-0911
MSV#2
AL-0917
AL-0904
AL-0912
MSV#3
AL-0920
AL-0905
AL-0913
MSV#3
Ändrad: 98-11-26
MIF02
Filnamn: T:\M-ROBOT\ENGELSK\TROUBLE_SHOOTING.FM
Trouble Shooting YASNAC MRC
MOTOMAN ROBOTICS AB
Page: 23
Alarm 0930 - 0937 Access Error Turn power OFF, and then ON agian.
Alarm Occurrence
Alarm re-occurs? NO
YES Remove the board corresponding to the display, then re-install it
Resume use Remove all boards, then re-install them
Alarm re-occurs?
YES
NO
Alarm re-occurs? NO
Resume use YES
Resume use
Replace the EPROM of the board corresponding to the display Replace board corresponding to the display
YES
Alarm re-occurs? NO
Alarm re-occurs? YES
NO
Replace all boards
Board failure Alarm re-occurs?
EPROM failure
YES
NO Contact MOTOMAN-service
Board failure
AL-0930
MIF02
AL-0931 AL-0932
Skapad: 98-10-09
AL-0933 AL-0934
MSL#1
Ändrad: 98-11-26
MSL#2
AL-0936
MCP01
AL-0937
MIF01
AL-0935
Filnamn: T:\M-ROBOT\ENGELSK\TROUBLE_SHOOTING.FM
Trouble Shooting YASNAC MRC Page: 24
MOTOMAN ROBOTICS AB
Alarm 0940 - 0947 A-Bus Error Turn power OFF, and then ON agian.
Alarm Occurrence
Alarm re-occurs? NO
YES Remove the board corresponding to the display, then re-install it
Resume use Remove all boards, then re-install them
Alarm re-occurs?
YES
NO
Alarm re-occurs? NO
Resume use YES
Resume use
Replace the EPROM of the board corresponding to the display Replace board corresponding to the display
YES
Alarm re-occurs? NO
Alarm re-occurs? YES
NO
Replace all boards
Board failure Alarm re-occurs?
EPROM failure
YES
NO Contact MOTOMAN-service
Board failure
AL-0940
MIF02
AL-0941 AL-0942
Skapad: 98-10-09
AL-0943 AL-0944
MSL#1
Ändrad: 98-11-26
MSL#2
AL-0946
MCP01
AL-0947
MIF01
AL-0945
Filnamn: T:\M-ROBOT\ENGELSK\TROUBLE_SHOOTING.FM
MOTOMAN ROBOTICS AB
Alarm 0999
Trouble Shooting YASNAC MRC Page: 25
NMI Error Alarm Occurrence Turn power OFF, and then ON agian. Alarm re-occurs? YES
NO Resume use
Remove all boards and then re-install them Alarm re-occurs? YES
NO
Replace EPROM of all boards
Resume use
Alarm re-occurs? NO
EPROM failure
Replace all boards Alarm re-occurs?
Skapad: 98-10-09
YES
NO
Contact MOTOMAN-service
Board failure
Ändrad: 98-11-26
Filnamn: T:\M-ROBOT\ENGELSK\TROUBLE_SHOOTING.FM
Trouble Shooting YASNAC MRC Page: 26
Alarm 1010
MOTOMAN ROBOTICS AB
ROM Error (Syscon) Alarm Occurrence Turn power OFF, and then ON agian. Alarm re-occurs?
NO
YES
Resume use
Remove the EPROM board on the MCP01 board and then re-install them Alarm re-occurs? YES
NO
Replace EPROM board on the MCP01 board
Make sure connector has no loose connections, and then resume use
Alarm re-occurs? NO
MMM02 failure
Replace MCP01 board Alarm re-occurs?
Skapad: 98-10-09
YES
NO
Contact MOTOMAN-service
Board failure
Ändrad: 98-11-26
Filnamn: T:\M-ROBOT\ENGELSK\TROUBLE_SHOOTING.FM
MOTOMAN ROBOTICS AB
Alarm 1020
Trouble Shooting YASNAC MRC Page: 27
ROM Error (Motion) Alarm Occurrence Turn power OFF, and then ON agian. Alarm re-occurs?
NO
YES
Resume use
Remove the EPROM board on the MCP02 board and then re-install them Alarm re-occurs? YES
NO
Replace EPROM board on the MCP02 board
Make sure connector has no loose connections, and then resume use
Alarm re-occurs? NO
MMM04 failure
Replace MCP02 board Alarm re-occurs?
Skapad: 98-10-09
YES
NO
Contact MOTOMAN-service
Board failure
Ändrad: 98-11-26
Filnamn: T:\M-ROBOT\ENGELSK\TROUBLE_SHOOTING.FM
Trouble Shooting YASNAC MRC
MOTOMAN ROBOTICS AB
Page: 28
Alarm 1030
ROM Error (CIO) Alarm Occurrence Turn power OFF, and then ON agian. Alarm re-occurs? YES
NO Resume use
Remove the EPROM board on the MIF01 board and then re-install them Alarm re-occurs? YES
NO
Replace EPROM board on the MCP01 board
Make sure connector has no loose connections, and then resume use
Alarm re-occurs? NO
EPROM failure
Replace MIF01 board Alarm re-occurs?
Skapad: 98-10-09
YES
NO
Contact MOTOMAN-service
Board failure
Ändrad: 98-11-26
Filnamn: T:\M-ROBOT\ENGELSK\TROUBLE_SHOOTING.FM
Trouble Shooting YASNAC MRC
MOTOMAN ROBOTICS AB
Alarm 1040
Page: 29
System Error (Syscon) Alarm Occurrence Turn power OFF, and then ON agian. Alarm re-occurs?
NO
YES
Resume use
Replace MCP01 board Alarm re-occurs? YES
NO
Contact MOTOMAN-service
Board failure
1
Skapad: 98-10-09
6
Multi Task Specification Error
2
Motion Interrupt Not Done
7
Lack of Command Saving Area
3
Syscon Error
8
EMS Error
4
Command Processing
9
5
Undefined Interrupt
10
Ändrad: 98-11-26
SL Interrupt Not Done
Filnamn: T:\M-ROBOT\ENGELSK\TROUBLE_SHOOTING.FM
Trouble Shooting YASNAC MRC
MOTOMAN ROBOTICS AB
Page: 30
Alarm 1050
ROM Error (Sensor) Alarm Occurrence Turn power OFF, and then ON agian. Alarm re-occurs?
NO
YES
Resume use
Remove the EPROM board on the MSL board and then re-install it Alarm re-occurs? YES
NO
Replace EPROM board on the MSL board
Make sure connector has no loose connections, and then resume use
Alarm re-occurs? NO
YES
EPROM failure
Replace MSL board corresponding to the display Alarm re-occurs?
Skapad: 98-10-09
YES
NO
Contact MOTOMAN-service
Board failure
Ändrad: 98-11-26
Filnamn: T:\M-ROBOT\ENGELSK\TROUBLE_SHOOTING.FM
MOTOMAN ROBOTICS AB
Alarm 1060
Trouble Shooting YASNAC MRC Page: 31
System Error (CIO) Alarm Occurrence Turn power OFF, and then ON agian. Alarm re-occurs?
NO
YES
Resume use
Replace MIF01 board Alarm re-occurs? NO
Contact MOTOMAN-service
Board failure
01
05
Command Error SYSCONCIO
02
06
System Error
04
Skapad: 98-10-09
YES
FA Communication Bus Error
Ändrad: 98-11-26
Filnamn: T:\M-ROBOT\ENGELSK\TROUBLE_SHOOTING.FM
Trouble Shooting YASNAC MRC Page: 32
Alarm 1070
MOTOMAN ROBOTICS AB
Fault (Parameter) Alarm Occurrence Turn power OFF, and then ON agian. Alarm re-occurs? YES
NO Resume use
Initialize
the parameter file Alarm re-occurs?
Skapad: 98-10-09
YES
NO
Contact MOTOMANservice before initializing the system config.
Board failure
0
RC parameters
8
AP parameters
1
RO parameters
9
RS parameters
2
SV paramerters
10
SP parameters
3
SVM parameters
11
CM parameters
4
SC parameters
12
SE parameters
5
SD parameters
13
VC parameters
6
CIO parameters
14
RSM parameters
7
FD parameters
Ändrad: 98-11-26
Filnamn: T:\M-ROBOT\ENGELSK\TROUBLE_SHOOTING.FM
MOTOMAN ROBOTICS AB
Alarm 1080
Trouble Shooting YASNAC MRC Page: 33
Fault (Job data) Alarm Occurrence Turn power OFF, and then ON agian. Alarm re-occurs? YES
NO Resume use
Initialize
the job file Alarm re-occurs?
Alarm 1090
YES
NO
Contact MOTOMANservice before initializing the system config.
Job file destroyed
File Failure (Motion) Alarm Occurrence Turn power OFF, and then ON agian. Alarm re-occurs?
NO
YES
Resume use
Contact MOTOMANservice before initializing the system config.
Skapad: 98-10-09
Ändrad: 98-11-26
Filnamn: T:\M-ROBOT\ENGELSK\TROUBLE_SHOOTING.FM
Trouble Shooting YASNAC MRC
MOTOMAN ROBOTICS AB
Page: 34
Alarm 1100
File Total Checksum Error (Motion) Turn power OFF, and then ON agian.
Alarm Occurrence
Alarm re-occurs? NO
YES
Resume use
Replace MCP02 board Alarm re-occurs?
Alarm 1110
YES
NO
Contact MOTOMAN-service
Board failure
Set-up Process Error (Syscon) Turn power OFF, and then ON agian.
Alarm Occurrence
Alarm re-occurs? NO
YES
Resume use
Replace MCP02 board Alarm re-occurs?
1
Skapad: 98-10-09
YES
NO
Contact MOTOMAN-service
Board failure
Motion Section Set-up incomplete
Ändrad: 98-11-26
Filnamn: T:\M-ROBOT\ENGELSK\TROUBLE_SHOOTING.FM
MOTOMAN ROBOTICS AB
Alarm 1120
Trouble Shooting YASNAC MRC Page: 35
Wrong Segment Clock Value Turn power OFF, and then ON agian.
Alarm Occurrence
Alarm re-occurs? NO
YES
Resume use
Reset phase offset data file Alarm re-occurs?
Alarm 1130
YES
NO
Contact MOTOMAN-service
CMOS file breakdown
MMM Error Turn power OFF, and then ON agian.
Alarm Occurrence
Alarm re-occurs? NO
YES
Resume use
Contact MOTOMAN-service
0 1
Process Definition Table Not Set
2
Entry Table Overflow
Skapad: 98-10-09
Ändrad: 98-11-26
3
Process Not Set
4
Process Control Code Not Set
Filnamn: T:\M-ROBOT\ENGELSK\TROUBLE_SHOOTING.FM
Trouble Shooting YASNAC MRC Page: 36
Alarm 1140
MOTOMAN ROBOTICS AB
MMM Error Alarm Occurrence Turn power OFF, and then ON agian. Alarm re-occurs?
NO
YES
Resume use
Contact MOTOMAN-service
Alarm 1150
Fault Alarm Occurrence Turn power OFF, and then ON agian. Alarm re-occurs?
NO
YES
Resume use
Contact MOTOMAN-service
Skapad: 98-10-09
Ändrad: 98-11-26
Filnamn: T:\M-ROBOT\ENGELSK\TROUBLE_SHOOTING.FM
MOTOMAN ROBOTICS AB
Alarm 1160
Trouble Shooting YASNAC MRC Page: 37
High Temperature (in Control Box) Alarm Occurrence Turn power OFF, and then ON agian. Alarm re-occurs?
NO
YES
Resume use
Turn the power off, let the controller cool inside, and then turn power on again Alarm re-occurs? YES
NO
Check movement of cooling fan
Resume use
Alarm re-occurs? YES
NO
Check wiring cooling fan Faulty? YES
NO Replace fan Replace power unit (CPS-18F)
Contact MOTOMAN-service
Alarm re-occurs?
YES
NO Alarm re-occurs?
Fan failure NO Power unit failure
YES Contact MOTOMAN-service
Skapad: 98-10-09
Ändrad: 98-11-26
Filnamn: T:\M-ROBOT\ENGELSK\TROUBLE_SHOOTING.FM
Trouble Shooting YASNAC MRC
MOTOMAN ROBOTICS AB
Page: 38
Alarm 1170
Overrun Limit Switch Released Alarm Occurrence Turn power OFF, and then ON agian. Alarm re-occurs?
NO
YES
Resume use
Check the OVERRUN RECOVERY switch Alarm re-occurs?
Skapad: 98-10-09
YES
NO
Contact MOTOMAN-service
Switch failure
Ändrad: 98-11-26
Filnamn: T:\M-ROBOT\ENGELSK\TROUBLE_SHOOTING.FM
MOTOMAN ROBOTICS AB
Trouble Shooting YASNAC MRC Page: 39
Alarm 1180 - 1186 Servo Monitor System Error Alarm Occurrence Turn power OFF, and then ON agian. Alarm re-occurs? NO
YES
Resume use
Replace MSV board corresponding to the display Alarm re-occurs? YES
NO
Board failure
Replace MCP01 board Alarm re-occurs? NO
YES
Board failure
Replace MCP02 board Alarm re-occurs?
Skapad: 98-10-09
YES
NO
Contact MOTOMAN-service
Board failure
AL-1180
MSV#1
AL-1183
MSV#4
AL-1181
MSV#2
AL-1184
MSV#5
AL-1182
MSV#3
AL-1185
MSV#6
Ändrad: 98-11-26
AL-1186
MSV#7
Filnamn: T:\M-ROBOT\ENGELSK\TROUBLE_SHOOTING.FM
Trouble Shooting YASNAC MRC
MOTOMAN ROBOTICS AB
Page: 40
Alarm 1190 - 1196 Servo System Error Alarm Occurrence Turn power OFF, and then ON agian. Alarm re-occurs? NO
YES
Resume use
Replace MSV board corresponding to the display Alarm re-occurs? YES
NO
Board failure
Replace MCP01 board Alarm re-occurs? NO
YES
Board failure
Replace MCP02 board Alarm re-occurs?
Skapad: 98-10-09
YES
NO
Contact MOTOMAN-service
Board failure
AL-1190
MSV#1
AL-1193
MSV#4
AL-1191
MSV#2
AL-1194
MSV#5
AL-1192
MSV#3
AL-1195
MSV#6
Ändrad: 98-11-26
AL-1196
MSV#7
Filnamn: T:\M-ROBOT\ENGELSK\TROUBLE_SHOOTING.FM
Trouble Shooting YASNAC MRC
MOTOMAN ROBOTICS AB
Page: 41
Alarm 1200 - 1206 Overcurrent Alarm Occurrence
Condition at the time of alarm?
At control power ON
Replace servopack corresponding to the display
Running
Alarm re-occurs?
Check first grounding terminal
Go to point A
NO YES Contact MOTOMAN-service
At servo power ON
Servopack failure
Faulty grounding YES
NO
Replace servopack corresponding to the display
B Check second ground terminal
Alarm re-occurs? NO
Faulty grounding YES
NO
Check internal wiring
NO
Servopack failure
Replace motor corresponding to the display
Alarm re-occurs? YES
YES
Contact MOTOMAN-service
Alarm re-occurs? NO YES
Internal wiring failure
Servomotor failure Contact MOTOMAN-service
Skapad: 98-10-09
Ändrad: 98-11-26
Filnamn: T:\M-ROBOT\ENGELSK\TROUBLE_SHOOTING.FM
Trouble Shooting YASNAC MRC Page: 42
MOTOMAN ROBOTICS AB
Alarm 1200 - 1206 Overcurrent (...continued) A Check movement of servopack cooling fan Abnormal? YES
NO
Replace cooling fan
Check robot load
Alarm re-occurs?
Fan failure
NO
Load condition? OK
YES
Overload Alarm occurs at a specific point?
Contact MOTOMAN-service
Decrease weight
NO YES Check first grounding terminal
YES
Faulty grounding
NO
NO
Servopack failure
Go to point B
Replace servopack corresponding to the display Alarm re-occurs?
YES
Skapad: 98-10-09
Contact MOTOMAN-service
AL-1200
MSV#1
AL-1203
MSV#4
AL-1201
MSV#2
AL-1204
MSV#5
AL-1202
MSV#3
AL-1205
MSV#6
Ändrad: 98-11-26
AL-1206
MSV#7
Filnamn: T:\M-ROBOT\ENGELSK\TROUBLE_SHOOTING.FM
Trouble Shooting YASNAC MRC
MOTOMAN ROBOTICS AB
Page: 43
Alarm 1210 - 1216 MCCB Tripped Alarm Occurrence At control power ON
Condition at the time of alarm?
Turn ON the MCCB Alarm re-occurs? YES
NO
At servo power ON
Running
Check first grounding terminal
Resume use Go to point A
Replace servopack corresponding to the display Alarm re-occurs?
Servopack failure
NO
Faulty grounding
Replace servopack corresponding to the display
YES B Contact MOTOMAN service
YES
NO
Check second ground terminal
Alarm re-occurs? NO
Faulty grounding YES
NO
Replace internal wiring
YES
NO
Servopack failure
Replace motor corresponding to the display
Alarm re-occurs?
YES
Contact MOTOMAN-service
Alarm re-occurs? NO
Internal wiring failure
YES
Motor failure Contact MOTOMAN-service
Skapad: 98-10-09
Ändrad: 98-11-26
Filnamn: T:\M-ROBOT\ENGELSK\TROUBLE_SHOOTING.FM
Trouble Shooting YASNAC MRC Page: 44
MOTOMAN ROBOTICS AB
Alarm 1210 - 1216 MCCB Tripped (...continued) A
Check robot load Load condition? OK Overload Alarm occurs at a specific point?
Decrease weight
NO YES Check first grounding terminal
YES
Faulty grounding
NO
NO
Servopack failure
Go to point B
Replace servopack corresponding to the display Alarm re-occurs?
YES
Skapad: 98-10-09
Contact MOTOMAN-service
AL-1210
MSV#1
AL-1213
MSV#4
AL-1211
MSV#2
AL-1214
MSV#5
AL-1212
MSV#3
AL-1215
MSV#6
Ändrad: 98-11-26
AL-1216
MSV#7
Filnamn: T:\M-ROBOT\ENGELSK\TROUBLE_SHOOTING.FM
Trouble Shooting YASNAC MRC
MOTOMAN ROBOTICS AB
Page: 45
Alarm 1220 - 1226 Ground Fault Alarm Occurrence
Condition at the time of alarm?
At control power ON
Replace servopack corresponding to the display
Running
Alarm re-occurs?
Check first grounding terminal
Go to point A
NO YES Contact MOTOMAN-service
At servo power ON
Servopack failure
Faulty grounding YES
NO
Replace servopack corresponding to the display Check second ground terminal
Alarm re-occurs? NO
Faulty grounding YES
NO
Check internal wiring
NO
Servopack failure
Replace motor corresponding to the display
Alarm re-occurs? YES
YES
Contact MOTOMAN-service
Alarm re-occurs? NO YES
Internal wiring failure
Servo motor failure Contact MOTOMAN-service
Skapad: 98-10-09
Ändrad: 98-11-26
Filnamn: T:\M-ROBOT\ENGELSK\TROUBLE_SHOOTING.FM
Trouble Shooting YASNAC MRC
MOTOMAN ROBOTICS AB
Page: 46
Alarm 1220 - 1226 Ground Fault (...continued) A
Alarm occurs at a specific point?
NO
YES
Check first grounding terminal Faulty grounding
Check second ground terminal
NO
YES
Faulty grounding YES
Replace servopack corresponding to the display
NO
Check internal wiring Alarm re-occurs? NO YES Internal wiring failure
Replace motor corresponding to the display
Contact MOTOMAN-service
Alarm re-occurs?
Alarm re-occurs?
YES
NO
Contact MOTOMAN-service
Skapad: 98-10-09
Servopack failure
NO
YES
Motor failure
Contact MOTOMAN-service
AL-1220
MSV#1
AL-1223
MSV#4
AL-1221
MSV#2
AL-1224
MSV#5
AL-1222
MSV#3
AL-1225
MSV#6
Ändrad: 98-11-26
AL-1226
MSV#7
Filnamn: T:\M-ROBOT\ENGELSK\TROUBLE_SHOOTING.FM
Trouble Shooting YASNAC MRC
MOTOMAN ROBOTICS AB
Page: 47
Alarm 1230 - 1236 Defective Current Offset Alarm Occurrence
Replace servopack corresponding to the display
Alarm re-occurs?
Skapad: 98-10-09
NO
YES
Servopack failure
Contact MOTOMAN-service
AL-1230
MSV#1
AL-1233
MSV#4
AL-1231
MSV#2
AL-1234
MSV#5
AL-1232
MSV#3
AL-1235
MSV#6
Ändrad: 98-11-26
AL-1236
MSV#7
Filnamn: T:\M-ROBOT\ENGELSK\TROUBLE_SHOOTING.FM
Trouble Shooting YASNAC MRC
MOTOMAN ROBOTICS AB
Page: 48
Alarm 1240- 1246 Encoder Transmission Error Turn power OFF, and then ON again.
Alarm Occurrence
Alarm re-occurs?
Remove the cable between MSV board and IAMP, then re-install it
YES
NO Resume use
Remove the cable between encoder and IAMP, then re-install it
Resume use
NO
Alarm re-occurs?
YES
NO
Alarm re-occurs? YES
Resume use
Check the cable ground between encoder and IAMP
Remove the cable between the encoder and IAMP, then install connector from another axis
Alarm re-occurs? YES
NO
Alarm re-occurs?
YES
Check the cable between encoder and IAMP Alarm re-occurs?
NO
NO
Servopack failure
Reset absolute encoder
Replace the servopack
Cable failure NO
Alarm re-occurs? YES
Alarm re-occurs?
YES
NO
Replace the servomotor
Replace MSV board
Alarm re-occurs?
NO
YES
Board failure
Alarm re-occurs?
NO
Resume use
YES
Motor failure Contact MOTOMAN-service
Skapad: 98-10-09
AL-1240
MSV#1
AL-1243
MSV#4
AL-1241
MSV#2
AL-1244
MSV#5
AL-1242
MSV#3
AL-1245
MSV#6
Ändrad: 98-11-26
AL-1246
MSV#7
Filnamn: T:\M-ROBOT\ENGELSK\TROUBLE_SHOOTING.FM
MOTOMAN ROBOTICS AB
Trouble Shooting YASNAC MRC Page: 49
Alarm 1250 - 1256 Defective Encoder Internal Data Alarm Occurrence Turn power OFF, and then ON again. Alarm re-occurs? NO
YES
Resume use
Reset absolute encoder corresponding to the displayed axis Alarm re-occurs? YES
NO
Replace motor corresponding to the displayed axis
Resume use
Alarm re-occurs? NO
YES
Motor failure
Contact MOTOMAN-service
Skapad: 98-10-09
AL-1250
MSV#1
AL-1253
MSV#4
AL-1251
MSV#2
AL-1254
MSV#5
AL-1252
MSV#3
AL-1255
MSV#6
Ändrad: 98-11-26
AL-1256
MSV#7
Filnamn: T:\M-ROBOT\ENGELSK\TROUBLE_SHOOTING.FM
Trouble Shooting YASNAC MRC
MOTOMAN ROBOTICS AB
Page: 50
Alarm 1260 - 1266 Defective Encoder Absolute Data Alarm Occurrence Turn power OFF, and then ON again. Alarm re-occurs? NO
YES
Resume use
Reset absolute encoder corresponding to the displayed axis Alarm re-occurs? YES
NO
Replace motor corresponding to the displayed axis
Resume use
Alarm re-occurs? NO
YES
Motor failure
Contact MOTOMAN-service
Skapad: 98-10-09
AL-1260
MSV#1
AL-1263
MSV#4
AL-1261
MSV#2
AL-1264
MSV#5
AL-1262
MSV#3
AL-1265
MSV#6
Ändrad: 98-11-26
AL-1266
MSV#7
Filnamn: T:\M-ROBOT\ENGELSK\TROUBLE_SHOOTING.FM
Trouble Shooting YASNAC MRC
MOTOMAN ROBOTICS AB
Page: 51
Alarm 1270 - 1276 Encoder Overheat Alarm Occurrence
Condition at the time of alarm?
At control power ON
Running
If motor has cooling fan check if fan is working
A Check Robot load Reset absolute encoder corresponding to the displayed axis
NO
YES
Load condition?
Check wiring
Overload
Alarm re-occurs? YES
NO
Abnormal?
Decrease weight
Resume use
Faulty wiring? NO
Replace internal wiring
Replace motor Alarm re-occurs?
Replace cooling fan
YES
NO
YES
Alarm re-occurs? NO
Alarm re-occurs? YES
Motor failure
Fan failure
Contact MOTOMAN-service
Skapad: 98-10-09
Go to point A
AL-1270
MSV#1
AL-1273
MSV#4
AL-1271
MSV#2
AL-1274
MSV#5
AL-1272
MSV#3
AL-1275
MSV#6
Ändrad: 98-11-26
Internal wiring failure
NO
AL-1276
MSV#7
Filnamn: T:\M-ROBOT\ENGELSK\TROUBLE_SHOOTING.FM
Trouble Shooting YASNAC MRC
MOTOMAN ROBOTICS AB
Page: 52
Alarm 1280- 1286 Servo Monitor Transmission Error Alarm Occurrence Turn power OFF, and then ON again. Alarm re-occurs? NO
YES
Resume use
Remove the cable between MSV board and IAMP, then re-install it Alarm re-occurs? YES
NO
Check the cable wiring between MSV board and IAMP
Resume use
Faulty wiring YES
NO
Replace cable
Replace the servopack
Alarm re-occurs?
YES Alarm re-occurs?
NO
YES
NO Cable failure
Replace MSV board Servopack failure
Skapad: 98-10-09
Alarm re-occurs? YES
NO
Contact MOTOMAN-service
Board failure
AL-1280
MSV#1
AL-1283
MSV#4
AL-1281
MSV#2
AL-1284
MSV#5
AL-1282
MSV#3
AL-1285
MSV#6
Ändrad: 98-11-26
AL-1286
MSV#7
Filnamn: T:\M-ROBOT\ENGELSK\TROUBLE_SHOOTING.FM
MOTOMAN ROBOTICS AB
Trouble Shooting YASNAC MRC Page: 53
Alarm 1290 -1296 Servo CPU Synchronizing Error Alarm Occurrence Replace MSV board Alarm re-occurs? NO
YES
Board failure
Contact MOTOMAN-service
AL-1290
MSV#1
AL-1293
MSV#4
AL-1291
MSV#2
AL-1294
MSV#5
AL-1292
MSV#3
AL-1295
MSV#6
AL-1296
MSV#7
AL-1306
MSV#7
Alarm 1300 -1306 DSP Program Checksum Error Alarm Occurrence Replace MSV board Alarm re-occurs? NO
YES
Board failure
Contact MOTOMAN-service
Skapad: 98-10-09
AL-1300
MSV#1
AL-1303
MSV#4
AL-1301
MSV#2
AL-1304
MSV#5
AL-1302
MSV#3
AL-1305
MSV#6
Ändrad: 98-11-26
Filnamn: T:\M-ROBOT\ENGELSK\TROUBLE_SHOOTING.FM
Trouble Shooting YASNAC MRC Page: 54
MOTOMAN ROBOTICS AB
Alarm 1310 -1316 Mon Pgrm Total Checksum Error Alarm Occurrence Replace MSV board Alarm re-occurs? NO
YES
Board failure
Contact MOTOMAN-service
Skapad: 98-10-09
AL-1310
MSV#1
AL-1313
MSV#4
AL-1311
MSV#2
AL-1314
MSV#5
AL-1312
MSV#3
AL-1315
MSV#6
Ändrad: 98-11-26
AL-1316
MSV#7
Filnamn: T:\M-ROBOT\ENGELSK\TROUBLE_SHOOTING.FM
Trouble Shooting YASNAC MRC
MOTOMAN ROBOTICS AB
Page: 55
Alarm 1320- 1326 Servopack Failure Alarm Occurrence Turn power OFF, and then ON again. Alarm re-occurs? NO
YES
Resume use
Remove the cable between MSV board and IAMP, then re-install it Alarm re-occurs? YES
NO
Check the cable wiring between MSV board and IAMP
Resume use
Faulty wiring YES
NO
Replace cable
Replace the servopack
Alarm re-occurs?
YES Alarm re-occurs?
NO
YES
NO Cable failure
Replace MSV board Servopack failure
Skapad: 98-10-09
Alarm re-occurs? YES
NO
Contact MOTOMAN-service
Board failure
AL-1320
MSV#1
AL-1323
MSV#4
AL-1321
MSV#2
AL-1324
MSV#5
AL-1322
MSV#3
AL-1325
MSV#6
Ändrad: 98-11-26
AL-1326
MSV#7
Filnamn: T:\M-ROBOT\ENGELSK\TROUBLE_SHOOTING.FM
Trouble Shooting YASNAC MRC
MOTOMAN ROBOTICS AB
Page: 56
Alarm 1330- 1336 Position Error Alarm Occurrence
Condition at the time of alarm?
At control power ON
Go to point A
Running
At servo power ON Replace the cable between encoder and IAMP with a cable from another axis Moved to another axis?
NO Replace MSV board
YES Alarm re-occurs?
Check wiring
YES
NO Board failure Faulty wiring YES
NO
Replace cable Alarm re-occurs?
YES
NO
Replace the servo motor Alarm re-occurs?
YES
Contact MOTOMAN-service
Cable failure NO Motor failure
Skapad: 98-10-09
Ändrad: 98-11-26
Filnamn: T:\M-ROBOT\ENGELSK\TROUBLE_SHOOTING.FM
Trouble Shooting YASNAC MRC
MOTOMAN ROBOTICS AB
Page: 57
Alarm 1330- 1336 Position Error (... continued)
A
Is there a noise source around?
NO
YES Remove the noise source Alarm re-occurs?
YES
NO Resume use
Check wiring Faulty wiring YES Replace cable Replace the servo motor
YES
Alarm re-occurs?
NO NO
Alarm re-occurs?
Motor failure
Cable failure YES Replace MSV board Alarm re-occurs?
YES
Contact MOTOMAN-service
NO Board failure
Skapad: 98-10-09
AL-1330
MSV#1
AL-1333
MSV#4
AL-1331
MSV#2
AL-1334
MSV#5
AL-1332
MSV#3
AL-1335
MSV#6
Ändrad: 98-11-26
AL-1336
MSV#7
Filnamn: T:\M-ROBOT\ENGELSK\TROUBLE_SHOOTING.FM
Trouble Shooting YASNAC MRC
MOTOMAN ROBOTICS AB
Page: 58
Alarm 1340- 1346 Overload 1 Alarm Occurrence
Condition at the time of alarm?
At control power ON
Replace MSV board Right away
Running
How long after Servo ON does alarm occur?
After several minutes
Check for interference
Check Robot load Load condition?
Interference? YES NO
Overload
OK
Modify teaching Alarm re-occurs?
Reduce load YES
NO
Check motor wiring Faulty wiring
NO
Teaching error YES Alarm re-occurs?
Go to point A
Replace wiring NO
YES
Alarm re-occurs?
Board failure
YES
NO
Contact MOTOMAN-service
Cable failure
Skapad: 98-10-09
AL-1340
MSV#1
AL-1343
MSV#4
AL-1341
MSV#2
AL-1344
MSV#5
AL-1342
MSV#3
AL-1345
MSV#6
Ändrad: 98-11-26
AL-1346
MSV#7
Filnamn: T:\M-ROBOT\ENGELSK\TROUBLE_SHOOTING.FM
Trouble Shooting YASNAC MRC
MOTOMAN ROBOTICS AB
Page: 59
Alarm 1340- 1346 Overload 1 (...continued) Is brake release audiable?
NO
A
Check brake circuit YES Input voltage abnormal
Abnormal condition?
NO
Input voltage normal
Check brake lead wiring
Replace SVM
Faulty wiring
Replace MTU board
NO
Alarm re-occurs?
YES
NO
Check motor brake
Replace wiring
YES Resume use
Alarm re-occurs?
Alarm re-occurs?
NO YES
YES
NO
Resume use Contact MOTOMAN-service
Resume use
NO Check if mechanically locked
YES Replace the servo motor
Movable?
NO
Defective?
Alarm re-occurs?
Fix mechanical problem
YES
YES NO
Alarm re-occurs?
YES
Contact MOTOMAN-service
Resume use
NO Resume use
Skapad: 98-10-09
Ändrad: 98-11-26
Filnamn: T:\M-ROBOT\ENGELSK\TROUBLE_SHOOTING.FM
Trouble Shooting YASNAC MRC
MOTOMAN ROBOTICS AB
Page: 60
Alarm 1350- 1356 Overload 2 Alarm Occurrence
Condition at the time of alarm?
At control power ON
Replace MSV board Right away
Running
How long after Servo ON does alarm occur?
After several minutes
Check for interference
Check robot load
Interference?
Load condition?
YES NO
Overload
OK
Modify teaching Alarm re-occurs?
Reduce load YES
NO
Check motor wiring Faulty wiring
NO
Teaching error YES Alarm re-occurs?
Go to point A
Replace wiring NO
YES
Alarm re-occurs?
Board failure
YES
NO
Contact MOTOMAN-service
Cable failure
Skapad: 98-10-09
AL-1350
MSV#1
AL-1353
MSV#4
AL-1351
MSV#2
AL-1354
MSV#5
AL-1352
MSV#3
AL-1355
MSV#6
Ändrad: 98-11-26
AL-1356
MSV#7
Filnamn: T:\M-ROBOT\ENGELSK\TROUBLE_SHOOTING.FM
Trouble Shooting YASNAC MRC
MOTOMAN ROBOTICS AB
Page: 61
Alarm 1350- 1356 Overload 2 (...continued) Is brake release audiable?
NO
A
Check brake circuit YES Input voltage abnormal
Abnormal condition?
Replace MTU board
NO
Output voltage abnormal
Check brake lead wiring
Replace SVM
Faulty wiring NO
Alarm re-occurs?
YES
NO
Check motor brake
Replace wiring
YES Resume use
Alarm re-occurs?
Alarm re-occurs?
NO YES
YES
NO
Resume use Contact MOTOMAN-service
Resume use
NO Check if mechanically locked
YES Replace the servo motor
Movable?
NO
Defective?
Alarm re-occurs?
Fix mechanical problem
YES
YES NO
Alarm re-occurs?
YES
Contact MOTOMAN-service
Resume use
NO Resume use
Skapad: 98-10-09
Ändrad: 98-11-26
Filnamn: T:\M-ROBOT\ENGELSK\TROUBLE_SHOOTING.FM
Trouble Shooting YASNAC MRC
MOTOMAN ROBOTICS AB
Page: 62
Alarm 1360-1366
Broken PG Line Alarm Occurrence
At control power on
Condition at the time of alarm?
Replace cable between encoder & IAMP with cable from another axis
At servo power on
Move to other axis?
Replace MSV board
NO
YES
Alarm re-occurs?
Running
1
YES
Check wiring NO MSV board failure Faulty wiring?
YES
Replace servopack Alarm re-occurs?
Replace cable YES
NO Replace motor
YES
NO
Alarm re-occurs?
Servopack failure
Replace cable between IAMP and MSV Alarm re-occurs?
NO
NO YES
Cable failure
Cable failure Replace motor Alarm re-occurs?
NO Motor failure
Alarm re-occurs?
NO
YES YES Contact MOTOMAN-service
Skapad: 98-10-09
Ändrad: 98-11-26
Motor failure
Contact MOTOMAN-service
Filnamn: T:\M-ROBOT\ENGELSK\TROUBLE_SHOOTING.FM
Trouble Shooting YASNAC MRC
MOTOMAN ROBOTICS AB
Alarm 1360-1366
Page: 63
Broken PG Line (...continued)
1 Is there a noise source around?
YES
Remove noise source
YES
Alarm re-occurs?
NO Check wiring Faulty wiring?
YES
NO
Resume use
NO
Cable failure
Replace cable
NO Alarm re-occurs?
YES
Replace motor Alarm re-occurs?
YES
NO
MSV board failure Alarm re-occurs?
NO
YES
Motor failure Replace servopack
MSV board failure
Alarm re-occurs?
YES
NO Servopack failure
Replace cable between IAMP and MSV NO
Alarm re-occurs?
Cable failure
YES
Replace motor
YES
Alarm re-occurs?
Contact MOTOMAN-service
Skapad: 98-10-09
AL-1360
MSV#1
AL-1363
MSV#4
AL-1361
MSV#2
AL-1364
MSV#5
AL-1362
MSV#3
AL-1365
MSV#6
Ändrad: 98-11-26
AL-1366
NO Motor failure
MSV#7
Filnamn: T:\M-ROBOT\ENGELSK\TROUBLE_SHOOTING.FM
Trouble Shooting YASNAC MRC
MOTOMAN ROBOTICS AB
Page: 64
Alarm 1370-1376
Over Speed Alarm Occurrence Is there a noise source around?
NO
Check wiring
YES
Faulty wiring?
NO
YES
Alarm re-occurs?
Condition at the time of alarm
Replace cable Alarm re-occurs?
NO Resume use
At servo power on
1
Remove noise source
YES
Running
At servo power on NO
Cable failure 1
NO
Alarm occurs at specific point?
YES YES 1 NO
Replace MSV board Alarm re-occurs?
YES
MSV board failure
NO
YES
Point of alarm taught by MOVJ?
Reduce speed
YES
Multiple axes moving at the same time?
Replace motor NO Alarm re-occurs?
NO
Motor failure
Alarm re-occurs?
YES
1
YES NO Contact MOTOMAN-service
Skapad: 98-10-09
Resume use
AL-1370
MSV#1
AL-1373
MSV#4
AL-1371
MSV#2
AL-1374
MSV#5
AL-1372
MSV#3
AL-1375
MSV#6
Ändrad: 98-11-26
AL-1376
MSV#7
Filnamn: T:\M-ROBOT\ENGELSK\TROUBLE_SHOOTING.FM
Trouble Shooting YASNAC MRC
MOTOMAN ROBOTICS AB
Alarm 1380-1386
Page: 65
Servo Tracking Error
Alarm Occurrence
Condition at the time of alarm?
Running Check if robot interferes with work or fixture
At control power on Modify teaching
YES
Interference?
NO
Alarm re-occurs?
YES
Check motor wiring
OK
Check load Load condition?
NO
Overload
Teaching error Decrease weight Replace MSV board Alarm re-occurs?
Faulty wiring?
NO
NO
1
YES
1
YES YES
MSV board failure Replace wiring harness
Contact MOTOMAN-service
Alarm re-occurs? NO Wiring failure
Skapad: 98-10-09
AL-1380
MSV#1
AL-1383
MSV#4
AL-1381
MSV#2
AL-1384
MSV#5
AL-1382
MSV#3
AL-1385
MSV#6
Ändrad: 98-11-26
AL-1386
MSV#7
Filnamn: T:\M-ROBOT\ENGELSK\TROUBLE_SHOOTING.FM
Trouble Shooting YASNAC MRC
MOTOMAN ROBOTICS AB
Page: 66
Alarm 1380-1386
Servo Tracking Error (...continued) 1 Is brake release audible?
NO
YES
Check brake circuit Abnormal condition?
Input voltage abnormal Replace MTU board
Output voltage abnormal Replace SVM Alarm re-occurs?
NO Resume use Alarm re-occurs?
YES
Check brake lead wiring Faulty wiring?
NO
NO
YES
Alarm re-occurs? YES
Resume use
NO Resume use
Contact MOTOMAN-service Check if mechanically locked NO
Alarm re-occurs?
NO
Defective? YES
Movable?
Replace motor
Fix mechanical problem
Skapad: 98-10-09
Check motor brake
Replace wiring harness
Contact MOTOMAN service
YES
NO
YES YES
Contact MOTOMAN-service
YES
Alarm re-occurs?
NO
NO
Resume use
Resume use
Ändrad: 98-11-26
Filnamn: T:\M-ROBOT\ENGELSK\TROUBLE_SHOOTING.FM
Trouble Shooting YASNAC MRC
MOTOMAN ROBOTICS AB
Page: 67
Alarm 1390-1396 Speed (Monitor) Alarm Occurrence
Is there a noise source around?
NO
Check wiring
YES
Remove noise source Alarm re-occurs?
YES
Faulty wiring?
Resume use
NO At control power on
1
YES
Condition at the time of alarm?
Replace cable Alarm re-occurs?
NO
Running
At servo power on NO
Cable failure 1
NO
Alarm occurs at specific point?
YES YES 1 NO
Replace MSV board
Point of alarm taught by MOVJ YES
Alarm re-occurs?
NO
MSV board failure
YES
Multiple axes moving at the same time?
Replace motor
NO
Reduce speed
Alarm re-occurs?
NO
Alarm re-occurs?
Motor failure
YES
NO
Contact MOTOMAN service
Resume use
Skapad: 98-10-09
AL-1390
MSV#1
AL-1393
MSV#4
AL-1391
MSV#2
AL-1394
MSV#5
AL-1392
MSV#3
AL-1395
MSV#6
Ändrad: 98-11-26
YES
YES
AL-1396
1
MSV#7
Filnamn: T:\M-ROBOT\ENGELSK\TROUBLE_SHOOTING.FM
Trouble Shooting YASNAC MRC
MOTOMAN ROBOTICS AB
Page: 68
Alarm 3000-3006
Not Ready For Servo System Alarm Occurrence Turn the power off and then on again
Resume use
Alarm re-occurs?
NO
YES Check MTU board
NO
Defective?
NO
Is SVM working?
Defective?
Alarm re-occurs?
Replace MTU board
YES
Check primary power voltage
Replace SVM
YES
Alarm re-occurs?
YES
YES
YES Primary power failure
1
NO
NO
Resume use
Check cable between servopack and MSV board YES
1
Defective?
NO
1
Replace cable
NO Resume use
Alarm re-occurs?
YES
1
NO Cable failure
Skapad: 98-10-09
AL-3000
MSV#1
AL-3003
MSV#4
AL-3001
MSV#2
AL-3004
MSV#5
AL-3002
MSV#3
AL-3005
MSV#6
Ändrad: 98-11-26
AL-3006
MSV#7
Filnamn: T:\M-ROBOT\ENGELSK\TROUBLE_SHOOTING.FM
Trouble Shooting YASNAC MRC
MOTOMAN ROBOTICS AB
Alarm 3000-3006
Page: 69
Not Ready For Servo System (...continued)
1
Check cable between servopack and SVM Defective?
YES
Replace cable
NO Replace servopack
YES
Alarm re-occurs?
Alarm re-occurs?
YES
Replace MSV board Alarm re-occurs?
NO Servopack failure
NO
Cable failure
YES
Contact MOTOMAN service
NO MSV board failure
Skapad: 98-10-09
Ändrad: 98-11-26
Filnamn: T:\M-ROBOT\ENGELSK\TROUBLE_SHOOTING.FM
Trouble Shooting YASNAC MRC
MOTOMAN ROBOTICS AB
Page: 70
Alarm 3010-3016
Servo Defective Speed
Alarm Occurrence
Are you trying to turn power on while axis is moving
YES
Try power on while axis is stopped
NO Replace MSV board
YES
Alarm re-occurs?
Alarm re-occurs?
NO
MSV board failure
NO
Resume use
YES Contact MOTOMAN service
Skapad: 98-10-09
AL-3010
MSV#1
AL-3013
MSV#4
AL-3011
MSV#2
AL-3014
MSV#5
AL-3012
MSV#3
AL-3015
MSV#6
Ändrad: 98-11-26
AL-3016
MSV#7
Filnamn: T:\M-ROBOT\ENGELSK\TROUBLE_SHOOTING.FM
Trouble Shooting YASNAC MRC
MOTOMAN ROBOTICS AB
Alarm 3020-3026
Page: 71
Servo Defective DB
Alarm Occurrence Turn the power off and then on again Alarm re-occurs?
YES
Replace servopack Alarm re-occurs?
NO
NO
Servopack failure
NO
MSV board failure
Resume use YES Replace MSV board Alarm re-occurs? YES Contact MOTOMAN service
Skapad: 98-10-09
AL-3020
MSV#1
AL-3023
MSV#4
AL-3021
MSV#2
AL-3024
MSV#5
AL-3022
MSV#3
AL-3025
MSV#6
Ändrad: 98-11-26
AL-3026
MSV#7
Filnamn: T:\M-ROBOT\ENGELSK\TROUBLE_SHOOTING.FM
Trouble Shooting YASNAC MRC
MOTOMAN ROBOTICS AB
Page: 72
Alarm 3030-3036
Regenerative Trouble
Alarm Occurrence At servo power on
Condition at the time of alarm? At control power on Replace servopack Alarm re-occurs?
Check regeneration resistor NO
YES
Defective? Contact MOTOMAN-service
Replace regeneration resistor
YES
YES
Alarm re-occurs?
NO
NO
Servopack failure
Regeneration resistor failure
Skapad: 98-10-09
AL-3030
MSV#1
AL-3033
MSV#4
AL-3031
MSV#2
AL-3034
MSV#5
AL-3032
MSV#3
AL-3035
MSV#6
Ändrad: 98-11-26
AL-3036
MSV#7
Filnamn: T:\M-ROBOT\ENGELSK\TROUBLE_SHOOTING.FM
Trouble Shooting YASNAC MRC
MOTOMAN ROBOTICS AB
Alarm 3040-3046
Page: 73
Overvoltage
Alarm Occurrence
Condition at the time of alarm?
At servo power on
At control power on
Check primary power voltage Abnormal?
Primary power failure
YES
NO Check regeneration resistor Replace servopack
NO
Alarm re-occurs?
YES
Defective?
Replace regeneration resistor
YES
Contact MOTOMAN-service
YES
Alarm re-occurs?
NO
NO
Servopack failure
Regeneration resistor failure
Skapad: 98-10-09
AL-3040
MSV#1
AL-3043
MSV#4
AL-3041
MSV#2
AL-3044
MSV#5
AL-3042
MSV#3
AL-3045
MSV#6
Ändrad: 98-11-26
AL-3046
MSV#7
Filnamn: T:\M-ROBOT\ENGELSK\TROUBLE_SHOOTING.FM
Trouble Shooting YASNAC MRC
MOTOMAN ROBOTICS AB
Page: 74
Alarm 3050-3056
Voltage Drop
Alarm Occurrence At servo power on
Condition at the time of alarm? At control power on
Check primary power voltage
Replace servopack
NO
Alarm re-occurs?
YES
Abnormal?
YES
Primary power failure
Contact MOTOMAN-service
NO Servopack failure
Skapad: 98-10-09
AL-3050
MSV#1
AL-3053
MSV#4
AL-3051
MSV#2
AL-3054
MSV#5
AL-3052
MSV#3
AL-3055
MSV#6
Ändrad: 98-11-26
AL-3056
MSV#7
Filnamn: T:\M-ROBOT\ENGELSK\TROUBLE_SHOOTING.FM
Trouble Shooting YASNAC MRC
MOTOMAN ROBOTICS AB
Alarm 3060-3066
Page: 75
Heat sink overheat
Alarm Occurrence At servo power on
Condition at the time of alarm? At control power on
Check primary power voltage
Replace servopack
NO
Alarm re-occurs?
YES
Abnormal?
YES
Primary power failure
Contact MOTOMAN-service
NO Servopack failure
Skapad: 98-10-09
AL-3060
MSV#1
AL-3063
MSV#4
AL-3061
MSV#2
AL-3064
MSV#5
AL-3062
MSV#3
AL-3065
MSV#6
Ändrad: 98-11-26
AL-3066
MSV#7
Filnamn: T:\M-ROBOT\ENGELSK\TROUBLE_SHOOTING.FM
Trouble Shooting YASNAC MRC
MOTOMAN ROBOTICS AB
Page: 76
Alarm 3070-3076
Servo Blown Fuse
Alarm Occurrence At servo power on
Condition at the time of alarm? At control power on Replace servopack Alarm re-occurs?
Check motor cable NO
YES
Abnormal? Contact MOTOMAN-service
YES
Replace wiring harness Alarm re-occurs?
YES
NO
NO
Servopack failure
Wiring failure
Skapad: 98-10-09
AL-3070
MSV#1
AL-3073
MSV#4
AL-3071
MSV#2
AL-3074
MSV#5
AL-3072
MSV#3
AL-3075
MSV#6
Ändrad: 98-11-26
AL-3076
MSV#7
Filnamn: T:\M-ROBOT\ENGELSK\TROUBLE_SHOOTING.FM
MOTOMAN ROBOTICS AB
Trouble Shooting YASNAC MRC Page: 77
Alarm 3080-3086 Broken Current Ref Cable Alarm Occurrence Check cable between servopack and MSV board Defective?
YES
Replace cable
Replace servopack
YES
Alarm re-occurs?
Alarm re-occurs?
YES
Replace MSV board
NO
NO
Alarm re-occurs?
Servopack failure
NO
Cable failure
YES
Contact MOTOMAN-service
NO MSV board failure
Skapad: 98-10-09
AL-3080
MSV#1
AL-3083
MSV#4
AL-3081
MSV#2
AL-3084
MSV#5
AL-3082
MSV#3
AL-3085
MSV#6
Ändrad: 98-11-26
AL-3086
MSV#7
Filnamn: T:\M-ROBOT\ENGELSK\TROUBLE_SHOOTING.FM
Trouble Shooting YASNAC MRC Page: 78
Alarm 3090-3096
MOTOMAN ROBOTICS AB
Open Phase
Alarm Occurrence Check primary power voltage Abnormal?
YES
NO
Check if contactor is stuck or not Abnormal?
Primary power failure
Replace contactor
YES
Alarm re-occurs?
NO Check cable for SVM contactor
Replace cable
YES
YES
NO
Abnormal?
Contactor failure
NO Alarm re-occurs?
YES
Replace servopack Alarm re-occurs?
NO
YES
Replace MSV board
Cable failure NO
Abnormal?
Servopack failure YES
NO
MSV board failure
Contact MOTOMAN-service
Skapad: 98-10-09
AL-3090
MSV#1
AL-3093
MSV#4
AL-3091
MSV#2
AL-3094
MSV#5
AL-3092
MSV#3
AL-3095
MSV#6
Ändrad: 98-11-26
AL-3096
MSV#7
Filnamn: T:\M-ROBOT\ENGELSK\TROUBLE_SHOOTING.FM
Trouble Shooting YASNAC MRC
MOTOMAN ROBOTICS AB
Alarm 4000
Page: 79
Not Ready Alarm Occurrence Reset alarm, and then execute the operation again Alarm re-occurs?
NO Resume use
Alarm 4010
YES Contact MOTOMAN-service
Current Position Set Program Error Alarm Occurrence Reset alarm, and then execute the operation again Alarm re-occurs?
NO Resume use
Alarm 4020
YES Contact MOTOMAN-service
Servo Power On Sequence Error Alarm Occurrence Reset alarm, and then execute the operation again NO Resume use
Skapad: 98-10-09
Ändrad: 98-11-26
Alarm re-occurs?
YES Contact MOTOMAN-service
Filnamn: T:\M-ROBOT\ENGELSK\TROUBLE_SHOOTING.FM
Trouble Shooting YASNAC MRC
MOTOMAN ROBOTICS AB
Page: 80
Alarm 4030
Servo Power Off Sequence Error Alarm Occurrence Reset alarm, and then execute the operation again NO
Alarm re-occurs?
Resume use
Alarm 4040
YES Contact MOTOMAN-service
Home Calibration Error Alarm Occurrence Reset alarm, and then execute the operation again NO
Alarm re-occurs?
Resume use
Alarm 4050
YES Contact MOTOMAN-service
Absolute Data Change Error Alarm Occurrence Reset alarm, and then execute the operation again NO Resume use
Skapad: 98-10-09
Ändrad: 98-11-26
Alarm re-occurs?
YES Contact MOTOMAN-service
Filnamn: T:\M-ROBOT\ENGELSK\TROUBLE_SHOOTING.FM
Trouble Shooting YASNAC MRC
MOTOMAN ROBOTICS AB
Alarm 4060
Page: 81
Segment Data Output Error Alarm Occurrence Reset alarm, and then execute the operation again NO
Alarm re-occurs?
Resume use
Alarm 4070
YES Contact MOTOMAN-service
Axis Parameter Error Alarm Occurrence Initialize parameter setting NO
Alarm re-occurs?
Resume use
Alarm 4080
YES Contact MOTOMAN-service
Table Parameter Error For Actual Axis Alarm Occurrence Initialize parameter setting NO Resume use
Skapad: 98-10-09
Ändrad: 98-11-26
Alarm re-occurs?
YES Contact MOTOMAN-service
Filnamn: T:\M-ROBOT\ENGELSK\TROUBLE_SHOOTING.FM
Trouble Shooting YASNAC MRC
MOTOMAN ROBOTICS AB
Page: 82
Alarm 4090
Sequence Task Control Error Alarm Occurrence Reset alarm, and then execute the operation again NO
Alarm re-occurs?
Resume use
Alarm 4100
YES Contact MOTOMAN-service
Data Refresh Error Alarm Occurrence Reset alarm, and then execute the operation again NO
Alarm re-occurs?
Resume use
Alarm 4110
YES Contact MOTOMAN-service
Undefined Command (Arith) Alarm Occurrence Reset alarm, and then execute the operation again NO Resume use
Skapad: 98-10-09
Ändrad: 98-11-26
Alarm re-occurs?
YES Contact MOTOMAN-service
Filnamn: T:\M-ROBOT\ENGELSK\TROUBLE_SHOOTING.FM
Trouble Shooting YASNAC MRC
MOTOMAN ROBOTICS AB
Alarm 4120
Page: 83
System Error (Arith) Alarm Occurrence Reset alarm, and then execute the operation again Alarm re-occurs?
NO Resume use
Alarm 4130
YES Contact MOTOMAN-service
Arithmetic Error Alarm Occurrence Reset alarm, and then execute the operation again Alarm re-occurs?
NO Resume use
Alarm 4140
YES Contact MOTOMAN-service
Select Error (Parameter) Alarm Occurrence Reset alarm, and then execute the operation again NO Resume use
Skapad: 98-10-09
Ändrad: 98-11-26
Alarm re-occurs?
YES Contact MOTOMAN-service
Filnamn: T:\M-ROBOT\ENGELSK\TROUBLE_SHOOTING.FM
Trouble Shooting YASNAC MRC
MOTOMAN ROBOTICS AB
Page: 84
Alarm 4150
Group Axis Control Error Alarm Occurrence Reset alarm, and then execute the operation again NO
Alarm re-occurs?
Resume use
Alarm 4160
YES Contact MOTOMAN-service
Two Steps Same Position (Circle) Alarm Occurrence
Confirm the taught program, and then input three different points NO
Alarm re-occurs?
Resume use
Alarm 4170
YES Contact MOTOMAN-service
Two Steps Same Position (Spline) Alarm Occurrence
Confirm the taught program, and then input three different points NO Resume use
Skapad: 98-10-09
Ändrad: 98-11-26
Alarm re-occurs?
YES Contact MOTOMAN-service
Filnamn: T:\M-ROBOT\ENGELSK\TROUBLE_SHOOTING.FM
Trouble Shooting YASNAC MRC
MOTOMAN ROBOTICS AB
Alarm 4180
Page: 85
Two Steps Same Position (3 steps) Alarm Occurrence
Confirm the taught program, and then input three different points NO
Alarm re-occurs?
YES
Resume use
Alarm 4190
Contact MOTOMAN-service
Two Steps Same Position (weave) Alarm Occurrence
Confirm the taught program, and then input three different points NO
Alarm re-occurs?
YES
Resume use
Alarm 4200
Contact MOTOMAN-service
Teach Error (Spline) Alarm Occurrence Confirm the taught program, and then provide instructions to position taught points correctly
NO Resume use
Skapad: 98-10-09
Ändrad: 98-11-26
Alarm re-occurs?
YES Contact MOTOMAN-service
Filnamn: T:\M-ROBOT\ENGELSK\TROUBLE_SHOOTING.FM
Trouble Shooting YASNAC MRC
MOTOMAN ROBOTICS AB
Page: 86
Alarm 4210
Impossible Linear Motion (L/U) Alarm Occurrence
Confirm the taught program so the pattern of L and U axes is the same
NO
Alarm re-occurs?
Resume use
Alarm 4220
YES Contact MOTOMAN-service
Impossible Linear Motion (S/L) Alarm Occurrence
Confirm the taught program so the pattern of S and L axes is the same
NO Resume use
Skapad: 98-10-09
Ändrad: 98-11-26
Alarm re-occurs?
YES Contact MOTOMAN-service
Filnamn: T:\M-ROBOT\ENGELSK\TROUBLE_SHOOTING.FM
MOTOMAN ROBOTICS AB
Alarm 4230
Trouble Shooting YASNAC MRC Page: 87
Excessive Segment (Low speed) Alarm Occurrence Decrease the speed of the step where the alarm occured NO
Alarm re-occurs?
YES
Set form of axes S and L, and provide a new instruction
Resume use
Alarm re-occurs?
NO Resume use
Alarm 4240
YES Contact MOTOMAN-service
Excessive Segment (High speed) Alarm Occurrence Decrease the speed of the step where the alarm occured NO
Alarm re-occurs?
YES Set form of axes S and L, and provide a new instruction
Resume use
NO Resume use
Skapad: 98-10-09
Ändrad: 98-11-26
Alarm re-occurs?
YES Contact MOTOMAN-service
Filnamn: T:\M-ROBOT\ENGELSK\TROUBLE_SHOOTING.FM
Trouble Shooting YASNAC MRC
MOTOMAN ROBOTICS AB
Page: 88
Alarm 4250-4300
Soft Limit Over Alarm Occurrence
Reset alarm using soft-limit-over reset method, and then provide another instruction Alarm re-occurs?
NO
YES
Resume use
Contact MOTOMAN-service
AL-4250
Pulse limit over: minimum
AL-4280
Cube limit over: maximum
AL-4260
Pulse limit over: maximum
AL-4290
Special soft limit over: minimum
AL-4270
Cube limit over: minimum
AL-4300
Special soft limit over: maximum
Alarm 4310-4340
Mechanical Interference Alarm Occurrence
Reset alarm using soft-limit-over reset method, and then provide another instruction.
NO
Alarm re-occurs?
YES Contact MOTOMAN-service
Resume use
AL-4310
Mechanical interference: minimum
AL-4330
Special mechanical interference: maximum
AL-4320
Mechanical interference: maximum
AL-4340
Special mechanical interference: minimum
Skapad: 98-10-09
Ändrad: 98-11-26
Filnamn: T:\M-ROBOT\ENGELSK\TROUBLE_SHOOTING.FM
Trouble Shooting YASNAC MRC
MOTOMAN ROBOTICS AB
Alarm 4350-4360
Page: 89
Pulse Mechanical limit Alarm Occurrence
Reset alarm using soft-limit-over reset method, and then provide another instruction.
Alarm re-occurs?
NO
YES
Resume use
AL-4350
Contact MOTOMAN-service
Pulse mechanical limit: minimum
Alarm 4370
AL-4360
Pulse mechanical limit: maximum
Station Axis Data Input Error Alarm Occurrence
Reset alarm, and then execute the operation again
NO Resume use
Skapad: 98-10-09
Ändrad: 98-11-26
Alarm re-occurs?
YES Contact MOTOMAN-service
Filnamn: T:\M-ROBOT\ENGELSK\TROUBLE_SHOOTING.FM
Trouble Shooting YASNAC MRC
MOTOMAN ROBOTICS AB
Page: 90
Alarm 4380
Segment Control Error Alarm Occurrence Reset alarm, and then execute the operation again
NO
Alarm re-occurs?
Resume use
Alarm 4390
YES Contact MOTOMAN-service
Sub-segment Control Error Alarm Occurrence Reset alarm, and then execute the operation again
NO
Alarm re-occurs?
Resume use
Alarm 4400
YES Contact MOTOMAN-service
Wrong Specified Control Group Alarm Occurrence
Reset alarm, and then execute the operation again NO Resume use
Skapad: 98-10-09
Ändrad: 98-11-26
Alarm re-occurs?
YES Contact MOTOMAN-service
Filnamn: T:\M-ROBOT\ENGELSK\TROUBLE_SHOOTING.FM
Trouble Shooting YASNAC MRC
MOTOMAN ROBOTICS AB
Alarm 4410
Page: 91
CPU Communication Error Alarm Occurrence
Reset alarm, and then execute the operation again Alarm re-occurs?
NO
YES
Resume use
Alarm 4420
Contact MOTOMAN-service
Failed To Select Over SP Level Alarm Occurrence
Reset alarm, and then execute the operation again NO
Alarm re-occurs?
YES
Resume use
Turn the power off, and then on again YES
Alarm re-occurs?
Replace MSV board NO MSV board failure
Skapad: 98-10-09
Ändrad: 98-11-26
Alarm re-occurs?
NO Resume use
YES Contact MOTOMAN-service
Filnamn: T:\M-ROBOT\ENGELSK\TROUBLE_SHOOTING.FM
Trouble Shooting YASNAC MRC
MOTOMAN ROBOTICS AB
Page: 92
Alarm 4430
Averaging Number Change Error Alarm Occurrence
Reset alarm, and then execute the operation again NO
Alarm re-occurs?
YES
Resume use
Turn the power off, and then on again Alarm re-occurs?
YES
Replace MSV board NO
Alarm re-occurs?
Resume use YES
MSV board failure
Alarm 4440
NO
Contact MOTOMAN-service
Torque Limit Change Error Alarm Occurrence
Reset alarm, and then execute the operation again NO
Alarm re-occurs?
YES
Resume use
Turn the power off, and then on again YES
Alarm re-occurs?
Replace MSV board NO MSV board failure
Skapad: 98-10-09
Ändrad: 98-11-26
Alarm re-occurs?
NO Resume use
YES Contact MOTOMAN-service
Filnamn: T:\M-ROBOT\ENGELSK\TROUBLE_SHOOTING.FM
Trouble Shooting YASNAC MRC
MOTOMAN ROBOTICS AB
Alarm 4450
Page: 93
JMS Error Alarm Occurrence
Reset alarm, and then execute the operation again Alarm re-occurs?
NO Resume use
YES Contact MOTOMAN-service
1/255
Parameter
11/245
Sequence number error
2/254
Access time over
12/244
Step numer error
3/253
Access error
13/243
4/252
Job name error
14/242
5/251
Existing job open
15/241
6/250
Memory over
16/240
Lack of handle
7/249
Not existing
17/239
Write Protected
8/248
Acess not permitted
18/238
Maximum instruction
9/247
Handling number error
19/237
Maximum step
10/246
System error
99/157
Job failure
Alarm 4460
Code error
JHM Error Alarm Occurrence Turn the power off, and then on again NO Resume use
Skapad: 98-10-09
Ändrad: 98-11-26
Alarm re-occurs?
YES Contact MOTOMAN-service
Filnamn: T:\M-ROBOT\ENGELSK\TROUBLE_SHOOTING.FM
Trouble Shooting YASNAC MRC
MOTOMAN ROBOTICS AB
Page: 94
Alarm 4470
Instruction Interpreter Error Alarm Occurrence Turn the power off, and then on again NO
Alarm re-occurs?
Resume use
Alarm 4480
YES Contact MOTOMAN-service
Undefined Global Variable Alarm Occurrence
Reset the parameter, and then execute the operation again NO
Alarm re-occurs?
Resume use
Alarm 4490
YES Contact MOTOMAN-service
Var-Scoreboard Control Error Alarm Occurrence
Reset alarm, and then execute the operation again NO Resume use
Skapad: 98-10-09
Ändrad: 98-11-26
Alarm re-occurs?
YES Contact MOTOMAN-service
Filnamn: T:\M-ROBOT\ENGELSK\TROUBLE_SHOOTING.FM
Trouble Shooting YASNAC MRC
MOTOMAN ROBOTICS AB
Alarm 4500
Page: 95
Undefined Local Variable Alarm Occurrence
Set the local variable to the job heade and then execute the operation again NO
Alarm re-occurs?
Resume use
Alarm 4510
YES Contact MOTOMAN-service
Less Than 3 Steps (circular) Alarm Occurrence
Confirm the taught program, and then input instructions to provide more than three steps continuously
NO
Alarm re-occurs?
Resume use
Alarm 4520
YES Contact MOTOMAN-service
Cannot Interpolate Circular Motion Alarm Occurrence
Confirm the taught program, and then input instructions to provide more than three steps continuously
NO Resume use
Skapad: 98-10-09
Ändrad: 98-11-26
Alarm re-occurs?
YES Contact MOTOMAN-service
Filnamn: T:\M-ROBOT\ENGELSK\TROUBLE_SHOOTING.FM
Trouble Shooting YASNAC MRC
MOTOMAN ROBOTICS AB
Page: 96
Alarm 4530
Undefined Job Alarm Occurrence
Reset alarm, end then execute the operation again Alarm re-occurs?
NO
YES
Resume use
Alarm 4540
Contact MOTOMAN-service
Undefined Label Alarm Occurrence Check the taught point, and then teach the point again NO
Alarm re-occurs?
YES
Resume use
Alarm 4550
Contact MOTOMAN-service
Undefined Return Job Alarm Occurrence Start from the original job NO Resume use
Alarm re-occurs?
YES Check the taught point, and then teach the point again NO
Resume use
Skapad: 98-10-09
Ändrad: 98-11-26
Alarm re-occurs?
YES
Contact MOTOMAN-service
Filnamn: T:\M-ROBOT\ENGELSK\TROUBLE_SHOOTING.FM
Trouble Shooting YASNAC MRC
MOTOMAN ROBOTICS AB
Alarm 4560
Page: 97
Lack Of Local-Variable Area Alarm Occurrence
Decrease the use of local variables Alarm re-occurs?
NO Resume use
Alarm 4570
YES Contact MOTOMAN-service
Local-Variable Control Error Alarm Occurrence
Reset alarm, and then execute the operation again Alarm re-occurs?
NO Resume use
Alarm 4580
YES Contact MOTOMAN-service
Job Call Stack Error Alarm Occurrence
Reset alarm, and then execute the operation again NO Resume use
Skapad: 98-10-09
Ändrad: 98-11-26
Alarm re-occurs?
YES Contact MOTOMAN-service
Filnamn: T:\M-ROBOT\ENGELSK\TROUBLE_SHOOTING.FM
Trouble Shooting YASNAC MRC
MOTOMAN ROBOTICS AB
Page: 98
Alarm 4590
Feedback Pulse Making Error Alarm Occurrence
Reset alarm, and then execute the operation again Alarm re-occurs?
NO Resume use
Alarm 4600
YES Contact MOTOMAN-service
Unsuccessful Fine Positioning Alarm Occurrence Reset alarm, and then execute the operation again NO
Alarm re-occurs?
YES
Resume use
Turn the power off, and then on again Alarm re-occurs?
YES Replace MSV board NO
Alarm re-occurs?
MSV board failure
Skapad: 98-10-09
Ändrad: 98-11-26
NO Resume use
YES Contact MOTOMAN-service
Filnamn: T:\M-ROBOT\ENGELSK\TROUBLE_SHOOTING.FM
Trouble Shooting YASNAC MRC
MOTOMAN ROBOTICS AB
Alarm 4610
Page: 99
Pending Block-End Error Alarm Occurrence
Reset alarm, and then execute the operation again Alarm re-occurs?
NO Resume use
Alarm 4620
YES Contact MOTOMAN-service
Data Preset Error Alarm Occurrence
Reset alarm, and then execute the operation again Alarm re-occurs?
NO Resume use
Alarm 4630
YES Contact MOTOMAN-service
Variable Data Type Error Alarm Occurrence
Reset alarm, and then execute the operation again NO Resume use
Skapad: 98-10-09
Ändrad: 98-11-26
Alarm re-occurs?
YES Contact MOTOMAN-service
Filnamn: T:\M-ROBOT\ENGELSK\TROUBLE_SHOOTING.FM
Trouble Shooting YASNAC MRC
MOTOMAN ROBOTICS AB
Page: 100
Alarm 4640
Over Variable Limit Alarm Occurrence Change value of variable type that exceeds numerical range limits. NO
Alarm re-occurs?
Resume use
Alarm 4650
(B**) ‘0-255 (I**) -32768~32767 (D**) -2147483648 ~214748 (R**) -1.70141E+38 ~1.70141E
YES Contact MOTOMAN-service
Defective Taught Point (circular) Alarm Occurrence Check taught point, and then teach three points not in a straight line NO
Alarm re-occurs?
Resume use
Alarm 4660
YES Contact MOTOMAN-service
Weaving Control Error Alarm Occurrence
Reset alarm, and then check weave file and REFP points NO Resume use
Skapad: 98-10-09
Ändrad: 98-11-26
Alarm re-occurs?
YES Contact MOTOMAN-service
Filnamn: T:\M-ROBOT\ENGELSK\TROUBLE_SHOOTING.FM
Trouble Shooting YASNAC MRC
MOTOMAN ROBOTICS AB
Alarm 4670-4671
Page: 101
Overrun In Axis
Alarm Occurrence Recover from overtravel then try again Alarm re-occurs?
NO Resume use
YES
Set the swith again
Check short switch on MBB02
YES
Abnormal? NO
Alarm re-occurs?
NO Swith setting failure
Check the over run limit switch
YES
Replace switch
YES
Defective? NO
Alarm re-occurs?
NO
YES
Check the wiring of the overrun limit switch Alarm re-occurs?
Switch failure
YES
Replace wiring harness
NO Replace MTU board Replace MBB02 (IOBB) board
YES
Alarm re-occurs?
Alarm re-occurs?
YES
NO Lead failure
NO
Alarm re-occurs?
NO
YES
Board failure MBB02 (IOBB) failure
AL-4670
At robot axes occurrence
Skapad: 98-10-09
Ändrad: 98-11-26
Contact MOTOMAN-service
AL-4671
At external axes occurrence
Filnamn: T:\M-ROBOT\ENGELSK\TROUBLE_SHOOTING.FM
Trouble Shooting YASNAC MRC
MOTOMAN ROBOTICS AB
Page: 102
Alarm 4680-4730
File Fault Alarm Occurrence
Reset alarm, and then execute the operation again Alarm re-occurs?
NO Resume use
YES
Load the file corresponding to the screen, and then try again Alarm re-occurs?
NO
YES Contact MOTOMAN-service
Resume use
AL-4680
Tool file
AL-4710
Weaving file
AL-4690
User frame file
AL-4720
Home position absolute data file
AL-4700
Servo monitor signal file
AL-4730
Second home position data file
Alarm 4740
Posn File Data Read-Out Error Alarm Occurrence
Reset alarm, and then execute the operation again NO Resume use
Skapad: 98-10-09
Ändrad: 98-11-26
Alarm re-occurs?
YES Contact MOTOMAN-service
Filnamn: T:\M-ROBOT\ENGELSK\TROUBLE_SHOOTING.FM
Trouble Shooting YASNAC MRC
MOTOMAN ROBOTICS AB
Alarm 4750
Page: 103
Unmatched Posn Var Data Type Alarm Occurrence Change position variable data type (pulse - XYZ). Alarm re-occurs?
NO Resume use
Alarm 4760
YES Contact MOTOMAN-service
File No. Error Alarm Occurrence
Reset alarm, and then execute the operation again Alarm re-occurs?
NO Resume use
Alarm 4770
YES Contact MOTOMAN-service
Undefined Reference Point Alarm Occurrence
Register the reference point
NO Resume use
Skapad: 98-10-09
Ändrad: 98-11-26
Alarm re-occurs?
YES Contact MOTOMAN-service
Filnamn: T:\M-ROBOT\ENGELSK\TROUBLE_SHOOTING.FM
Trouble Shooting YASNAC MRC
MOTOMAN ROBOTICS AB
Page: 104
Alarm 4780
Stack More Than 8 (job call) Alarm Occurrence
Check program, and modify so that stack does not exceed 8 calls NO
Alarm re-occurs?
Resume use
Alarm 4790
YES Contact MOTOMAN-service
Arithmetic Section Request Error Alarm Occurrence
Reset alarm, and then execute the operation again NO
Alarm re-occurs?
Resume use
Alarm 4800
YES Contact MOTOMAN-service
Request-To-Send Error Alarm Occurrence
Reset alarm, and then execute the operation again NO Resume use
Skapad: 98-10-09
Ändrad: 98-11-26
Alarm re-occurs?
YES Contact MOTOMAN-service
Filnamn: T:\M-ROBOT\ENGELSK\TROUBLE_SHOOTING.FM
Trouble Shooting YASNAC MRC
MOTOMAN ROBOTICS AB
Alarm 4810
Page: 105
Over Variable No. (B000~B039) (I000~I039) D000~D039) R000~R039) P000~P127) BP000~BP127) EX000~EX127)
Alarm Occurrence Check program, and change variable number within limit Alarm re-occurs?
NO
YES
Resume use
Alarm 4820
Contact MOTOMAN-service
Position Data Management Error Alarm Occurrence
Reset alarm, and then execute the operation again NO
Alarm re-occurs?
Resume use
YES Contact MOTOMAN-service
1
Not enough area
9
Control information destroyed
2
Number of axis zero
10
Irregular position number
3
Position not kept
11
Position data not set
4
Number of position over
12
Undefined position
5
Area not specified
13
Undefined control group
6
File destroyed
14
Initialization not done
7
Memory over
15
Number of axis over
8
Position data destroyed
Skapad: 98-10-09
Ändrad: 98-11-26
Filnamn: T:\M-ROBOT\ENGELSK\TROUBLE_SHOOTING.FM
Trouble Shooting YASNAC MRC
MOTOMAN ROBOTICS AB
Page: 106
Alarm 4830-4850
Undefined Condition File Alarm Occurrence Complete the setting of the file NO
Alarm re-occurs?
YES
Resume use
Contact MOTOMAN-service
AL-4830
Welder condition file
AL-4840
Arc start condition file
Alarm 4860
AL-4850
Arc end condition file
Wrong Welder Selection Alarm Occurrence
Match unit of voltage selection to welder type NO Resume use
Skapad: 98-10-09
Ändrad: 98-11-26
Alarm re-occurs?
YES Contact MOTOMAN-service
Filnamn: T:\M-ROBOT\ENGELSK\TROUBLE_SHOOTING.FM
Trouble Shooting YASNAC MRC
MOTOMAN ROBOTICS AB
Alarm 4870-4900
Page: 107
Condition File Fault Alarm Occurrence
Reset alarm, and then execute the operation again Alarm re-occurs?
NO
YES Load file, and the try again
Resume use NO
Alarm re-occurs?
Resume use
YES Contact MOTOMAN-service
AL-4870
Welder condition file
AL-4890
Arc end condition file
AL-4880
Arc start condition file
AL-4900
Arc condition supp. file
Alarm 4910
AX-CPU Command Area Error Alarm Occurrence
Reset alarm, and then execute the operation again NO Resume use
Skapad: 98-10-09
Ändrad: 98-11-26
Alarm re-occurs?
YES Contact MOTOMAN-service
Filnamn: T:\M-ROBOT\ENGELSK\TROUBLE_SHOOTING.FM
Trouble Shooting YASNAC MRC
MOTOMAN ROBOTICS AB
Page: 108
Alarm 4920-4950
File Fault Alarm Occurrence
Reset alarm, and then execute the operation again Alarm re-occurs?
NO
YES
Resume use
Load file, and then try again NO
Alarm re-occurs?
Resume use
YES Contact MOTOMAN-service
AL-4920
COM-ARC 3 Condition file
AL-4940
Correction condition file
AL-4930
COM-ARC 3 Data file
AL-4950
Phase offset data file
Alarm 4960
System Change Alarm Occurrence Turn the power off, and then on again
NO Resume use
Skapad: 98-10-09
Ändrad: 98-11-26
Alarm re-occurs?
YES Contact MOTOMAN-service
Filnamn: T:\M-ROBOT\ENGELSK\TROUBLE_SHOOTING.FM
Trouble Shooting YASNAC MRC
MOTOMAN ROBOTICS AB
Alarm 4970
Page: 109
Equation Exception Error Alarm Occurrence
Reset alarm, and then execute the operation again Alarm re-occurs?
NO
YES
Resume use
Alarm 4980
Contact MOTOMAN-service
Excessive Instruction Equation Alarm Occurrence
Check the program, and make the expression short Alarm re-occurs?
NO
YES
Resume use
Alarm 4990
Contact MOTOMAN-service
Encoder Battery Error Alarm Occurrence
Reset alarm, and then execute the operation again NO
Alarm re-occurs?
Battery failure
YES
Replace battery board for encoder
NO MFC board failure
Skapad: 98-10-09
Ändrad: 98-11-26
Alarm re-occurs?
YES
Contact MOTOMAN-service
Filnamn: T:\M-ROBOT\ENGELSK\TROUBLE_SHOOTING.FM
Trouble Shooting YASNAC MRC
MOTOMAN ROBOTICS AB
Page: 110
Alarm 5000
Encoder Overheat
Alarm Occurrence Turn the power off, let encoder cool, and then turn the power on Alarm re-occurs? YES If motor has cooling fan, check if fan is working properly Is fan working?
YES
NO Check the wiring of fan Defective?
NO
YES Replace fan wiring Alarm re-occurs?
Check load YES
NO
Load condition?
Replace fan Alarm re-occurs?
Lead failure
OK
Overload
YES
Decrease weight NO Replace motor
Fan failure Contact MOTOMAN-service
YES
Alarm re-occurs? NO Motor failure
Skapad: 98-10-09
Ändrad: 98-11-26
Filnamn: T:\M-ROBOT\ENGELSK\TROUBLE_SHOOTING.FM
Trouble Shooting YASNAC MRC
MOTOMAN ROBOTICS AB
Alarm 5010
Page: 111
Illegal Parameter Alarm Occurrence
Change the parameter back to original Alarm re-occurs?
NO
YES
Resume use
Load parameter file, and then try again NO
Alarm re-occurs?
Contact MOTOMAN-service
Resume use
Alarm 5020
YES
Zero Divisor Occurrence Alarm Occurrence
Change the program so that the number will not be divided by zero NO Resume use
Skapad: 98-10-09
Ändrad: 98-11-26
Alarm re-occurs?
YES Contact MOTOMAN-service
Filnamn: T:\M-ROBOT\ENGELSK\TROUBLE_SHOOTING.FM
Trouble Shooting YASNAC MRC Page: 112
Alarm 5030
MOTOMAN ROBOTICS AB
Global-Variable Area Parameter Error Alarm Occurrence
Change the parameter back to original value Alarm re-occurs?
NO
YES
Resume use
Load parameter file, and then try again NO
Alarm re-occurs?
Contact MOTOMAN-service
Resume use
Alarm 5040
YES
Out Of Range (abso data)
Alarm Occurrence
Reset alarm by checking second home position Alarm re-occurs?
YES
NO
Check battery wiring to encodeers Defective?
YES
Replace battery
Resume use NO Replace motor Motor failure
NO
Alarm re-occurs? YES
YES
Alarm re-occurs? NO Battery failure
Contact MOTOMAN-service
Skapad: 98-10-09
Ändrad: 98-11-26
Filnamn: T:\M-ROBOT\ENGELSK\TROUBLE_SHOOTING.FM
Trouble Shooting YASNAC MRC
MOTOMAN ROBOTICS AB
Alarm 5060
Page: 113
Undefined Auto-Weld Release Cond Alarm Occurrence
Set welding release condition time, and then try again Alarm re-occurs?
NO Resume use
Alarm 5070
YES Contact MOTOMAN-service
Undefined Position For Arc Retry Alarm Occurrence
Add step, and then try again
NO
Alarm re-occurs?
Resume use
Alarm 5080
YES Contact MOTOMAN-service
Overspeed Limit Alarm Occurrence
Check setting for MFC04 board, and then try again NO Resume use
Skapad: 98-10-09
Ändrad: 98-11-26
Alarm re-occurs?
YES Contact MOTOMAN-service
Filnamn: T:\M-ROBOT\ENGELSK\TROUBLE_SHOOTING.FM
Trouble Shooting YASNAC MRC
MOTOMAN ROBOTICS AB
Page: 114
Alarm 5090
DC 24V Power Supply Failure
Alarm Occurrence
Check 24V power voltage supplied to IOBB Defective?
YES
Replace DC 24V power supply
NO Check fuse on IOBB
YES
Alarm re-occurs?
YES
Replace fuse
Replace IOBB
YES
Alarm re-occurs?
Alarm re-occurs?
NO
Board failure
Defective?
NO
Power supply failure
NO
Fuse failure
NO
YES Contact MOTOMAN-service
Skapad: 98-10-09
Ändrad: 98-11-26
Filnamn: T:\M-ROBOT\ENGELSK\TROUBLE_SHOOTING.FM
Trouble Shooting YASNAC MRC
MOTOMAN ROBOTICS AB
Alarm 5100
Page: 115
Shock Sensor Action Alarm Occurrence Remove interference between the tool and the fixture, etc
Remove interference, and then try again
YES
Interference? NO
Alarm re-occurs?
Check the shock sensor cable
YES
NO
Defective?
YES
Replace cable
YES
Alarm re-occurs?
Resume use NO Check the shock sensor operation Check the setting of IOBB short pin switch Abnormal?
NO
Abnormal? Set the short pin switch
YES
Replace MTU board
MTU board failure
YES
NO Sensor failure
YES Contact MOTOMAN-service
Setting failure
Replace MRY board Alarm re-occurs?
Skapad: 98-10-09
Replace shock sensor
Alarm re-occurs?
YES
NO Alarm re-occurs?
Cable failure
YES
Alarm re-occurs?
NO
NO
Replace IOBB YES
Alarm re-occurs?
NO
YES
MRY board failure
Contact MOTOMAN-service
Ändrad: 98-11-26
NO
IOBB failure
Filnamn: T:\M-ROBOT\ENGELSK\TROUBLE_SHOOTING.FM
Trouble Shooting YASNAC MRC Page: 116
Alarm 5110
MOTOMAN ROBOTICS AB
Brake Fuse Blown Alarm Occurrence Check the brake lead wiring for short to ground Short? Check the brake fuse
Replace the brake fuse
YES
YES
Replace lead wire for brake
YES
Alarm re-occurs? NO
Fuse blown?
Lead wire failure NO Alarm re-occurs?
YES
Replace the MTU board Alarm re-occurs?
NO
NO
Board failure
Fuse failure YES Contact MOTOMAN-service
Skapad: 98-10-09
Ändrad: 98-11-26
Filnamn: T:\M-ROBOT\ENGELSK\TROUBLE_SHOOTING.FM
Trouble Shooting YASNAC MRC
MOTOMAN ROBOTICS AB
Alarm 5120
Page: 117
Parity Error Alarm Occurrence Check the parameter for parity check function Invalid parameter?
YES
Set the parameter correctly
NO Check input Check the input program
YES
NO
Abnormal?
YES
Parameter setting failure
NO Alarm re-occurs?
YES
Alarm re-occurs?
Replace the MTU board Alarm re-occurs?
NO
NO
Board failure
Abnormal input YES Contact MOTOMAN-service
Skapad: 98-10-09
Ändrad: 98-11-26
Filnamn: T:\M-ROBOT\ENGELSK\TROUBLE_SHOOTING.FM
Trouble Shooting YASNAC MRC Page: 118
Alarm 5130
MOTOMAN ROBOTICS AB
Over BCD Range Alarm Occurrence
Check the BCD function parameter Invalid parameter?
YES
Set the parameter correctly
NO Check input/output Check the input/ output program
YES
YES
NO
Abnormal?
Parameter setting failure
NO Alarm re-occurs?
YES
Replace IO module board Alarm re-occurs?
NO Input/output failure
Alarm re-occurs?
NO
Board failure
YES Contact MOTOMAN-service
Skapad: 98-10-09
Ändrad: 98-11-26
Filnamn: T:\M-ROBOT\ENGELSK\TROUBLE_SHOOTING.FM
Trouble Shooting YASNAC MRC
MOTOMAN ROBOTICS AB
Alarm 5140
Page: 119
Over Binary Range (parity check) Alarm Occurrence Check parity check - BCD function parameter Invalid parameter?
YES
Set the parameter correctly
NO Check output Check the output program
NO
Abnormal?
YES
Parameter setting failure
NO Alarm re-occurs?
Alarm re-occurs?
YES
Replace IO module board
YES
Alarm re-occurs?
NO Output failure
NO
Board failure
YES Contact MOTOMAN-service
Alarm 5150
Offline Undefined Command (Arith) Alarm Occurrence Reset alarm, and then execute the operation again NO Resume use
Skapad: 98-10-09
Ändrad: 98-11-26
Alarm re-occurs?
YES Contact MOTOMAN-service
Filnamn: T:\M-ROBOT\ENGELSK\TROUBLE_SHOOTING.FM
Trouble Shooting YASNAC MRC
MOTOMAN ROBOTICS AB
Page: 120
Alarm 5160
Offline System Error (Arith) Alarm Occurrence Reset alarm, and then execute the operation again NO
Alarm re-occurs?
YES
Resume use
Alarm 5170
Contact MOTOMAN-service
Robot Calibration Data Error Alarm Occurrence Reset alarm, and then execute the operation again NO
Alarm re-occurs?
Resume use
Alarm 5180
YES Contact MOTOMAN-service
Robot Calibration Frame Error Alarm Occurrence Reset alarm, and then execute the operation again NO Resume use
Skapad: 98-10-09
Ändrad: 98-11-26
Alarm re-occurs?
YES Contact MOTOMAN-service
Filnamn: T:\M-ROBOT\ENGELSK\TROUBLE_SHOOTING.FM
Trouble Shooting YASNAC MRC
MOTOMAN ROBOTICS AB
Alarm 5190
Page: 121
Arithmetic Section Init Error Alarm Occurrence Reset alarm, and then execute the operation again Alarm re-occurs?
NO Resume use
Alarm 5200
YES Contact MOTOMAN-service
Set-Up Process Error (motion) Alarm Occurrence Reset alarm, and then execute the operation again Alarm re-occurs?
NO Resume use
Alarm 5210
YES Contact MOTOMAN-service
System Error (motion) Alarm Occurrence Reset alarm, and then execute the operation again NO Resume use
Skapad: 98-10-09
Ändrad: 98-11-26
Alarm re-occurs?
YES Contact MOTOMAN-service
Filnamn: T:\M-ROBOT\ENGELSK\TROUBLE_SHOOTING.FM
Trouble Shooting YASNAC MRC
MOTOMAN ROBOTICS AB
Page: 122
Alarm 5220
Servo Ready Monitoring Error Alarm Occurrence Reset alarm, and then execute the operation again NO
Alarm re-occurs?
Resume use
Alarm 5230
YES Contact MOTOMAN-service
Calibration Data Error Alarm Occurrence Reset alarm, and then execute the operation again NO
Alarm re-occurs?
Resume use
Alarm 5240
YES Contact MOTOMAN-service
Tool Calibration Data Error Alarm Occurrence Reset alarm, and then execute the operation again NO Resume use
Skapad: 98-10-09
Ändrad: 98-11-26
Alarm re-occurs?
YES Contact MOTOMAN-service
Filnamn: T:\M-ROBOT\ENGELSK\TROUBLE_SHOOTING.FM
Trouble Shooting YASNAC MRC
MOTOMAN ROBOTICS AB
Alarm 5250-5300
Page: 123
File Fault Alarm Occurrence Reset alarm, and then execute the operation again Alarm re-occurs?
NO Resume use
YES
Load the file corresponding to the display, and then try again
NO
Alarm re-occurs?
YES Contact MOTOMAN-service
Resume use
AL-5250
Robot calibration file
AL-5280
Arc end cond guide file
AL-5260
Tool calibration file
AL-5290
Welder user-defined file
AL-5270
Arc start cond guide file
AL-5300
Ladder program file
Alarm 5310
Arithmetic Alarm Reset Error Alarm Occurrence Reset alarm, and then execute the operation again NO Resume use
Skapad: 98-10-09
Ändrad: 98-11-26
Alarm re-occurs?
YES Contact MOTOMAN-service
Filnamn: T:\M-ROBOT\ENGELSK\TROUBLE_SHOOTING.FM
Trouble Shooting YASNAC MRC
MOTOMAN ROBOTICS AB
Page: 124
Alarm 5320
Wrong Control Group Axis Alarm Occurrence Check program and modify it (include control group to the original job). NO
Alarm re-occurs?
Resume use
Alarm 5330
YES Contact MOTOMAN-service
Cannot Execute Job (no robot) Alarm Occurrence Check program and modify it (include control group to the original job). NO
Alarm re-occurs?
Resume use
Alarm 5340
YES Contact MOTOMAN-service
Sensing Data Request Error Alarm Occurrence Reset alarm, and then execute the operation again NO Resume use
Skapad: 98-10-09
Ändrad: 98-11-26
Alarm re-occurs?
YES Contact MOTOMAN-service
Filnamn: T:\M-ROBOT\ENGELSK\TROUBLE_SHOOTING.FM
Trouble Shooting YASNAC MRC
MOTOMAN ROBOTICS AB
Alarm 5350
Page: 125
Main Contactor On Reply Error Alarm Occurrence Reset alarm, and then execute the operation again NO
Alarm re-occurs?
Resume use
YES Check if main contactor is working or not
NO
Working?
YES
Check voltage for main contactor coil NO
Abnormal?
YES
Replace main contactor Alarm re-occurs?
YES
Check MTU board Defective?
NO
YES
Replace MTU board
NO
Contactor failure
Contact MOTOMAN-service
YES
Alarm re-occurs? NO MTU board failure
Skapad: 98-10-09
Ändrad: 98-11-26
Filnamn: T:\M-ROBOT\ENGELSK\TROUBLE_SHOOTING.FM
Trouble Shooting YASNAC MRC
MOTOMAN ROBOTICS AB
Page: 126
Alarm 5360
Main Contactor Off Reply Error Alarm Occurrence Reset alarm, and then execute the operation again NO
Alarm re-occurs?
Resume use
YES Check if main contactor is working or not
NO
Working?
YES
Check voltage for main contactor coil NO
Abnormal?
YES
Replace main contactor Alarm re-occurs?
YES
Check MTU board Defective?
NO Contactor failure
YES
Replace MTU board
NO Contact MOTOMAN-service
YES
Alarm re-occurs? NO MTU board failure
Skapad: 98-10-09
Ändrad: 98-11-26
Filnamn: T:\M-ROBOT\ENGELSK\TROUBLE_SHOOTING.FM
Trouble Shooting YASNAC MRC
MOTOMAN ROBOTICS AB
Alarm 5370
Page: 127
Braking Lock Reply Error Alarm Occurrence Reset alarm, and then execute the operation again NO
Alarm re-occurs?
Resume use
YES Check if main contactor is working or not
NO
Working?
YES
Check voltage for main contactor coil NO
Abnormal?
YES
Replace main contactor Alarm re-occurs?
YES
Check MTU board Defective?
NO
YES
Replace MTU board
NO
Contactor failure
Contact MOTOMAN-service
YES
Alarm re-occurs? NO MTU board failure
Skapad: 98-10-09
Ändrad: 98-11-26
Filnamn: T:\M-ROBOT\ENGELSK\TROUBLE_SHOOTING.FM
Trouble Shooting YASNAC MRC
MOTOMAN ROBOTICS AB
Page: 128
Alarm 5380
Braking Release Reply Error Alarm Occurrence Reset alarm, and then execute the operation again NO
Alarm re-occurs?
Resume use
YES Check if main contactor is working or not
NO
Working?
YES
Check voltage for main contactor coil NO
Abnormal?
YES
Replace main contactor Alarm re-occurs?
YES
Check MTU board Defective?
NO Contactor failure
YES
Replace MTU board
NO Contact MOTOMAN-service
YES
Alarm re-occurs? NO MTU board failure
Skapad: 98-10-09
Ändrad: 98-11-26
Filnamn: T:\M-ROBOT\ENGELSK\TROUBLE_SHOOTING.FM
Trouble Shooting YASNAC MRC
MOTOMAN ROBOTICS AB
Alarm 5390
Page: 129
Servo-Ready On Error Alarm Occurrence Reset alarm, and then execute the operation again NO
Alarm re-occurs?
Resume use
YES Check if main contactor is working or not
NO
Working?
YES
1
YES
Replace MTU board
Check voltage for main contactor coil NO
Abnormal?
YES
Replace main contactor Alarm re-occurs?
YES
Check MTU board Defective?
NO
NO
Contactor failure
Contact MOTOMAN-service
YES
Alarm re-occurs? NO MTU board failure
Skapad: 98-10-09
Ändrad: 98-11-26
Filnamn: T:\M-ROBOT\ENGELSK\TROUBLE_SHOOTING.FM
Trouble Shooting YASNAC MRC Page: 130
Alarm 5390
MOTOMAN ROBOTICS AB
Servo-Ready On Error (...continued) 1
Check change LED on servopack YES
Lit? NO Turn off power, and then turn it on again Alarm re-occurs?
NO
Resume use
YES Check wiring between contactor and servopack
Defective?
Replace wiring between contactor and servopack
YES
NO Check wiring between MSV board and servopack Defective?
YES
YES
Alarm re-occurs?
NO
Wiring failure
Replace wiring between MSV board and servopack
NO Replace servopack Alarm re-occurs? NO
YES YES
Alarm re-occurs?
NO
Wiring failure
NO
MSV board failure
Replace MSV board Alarm re-occurs?
Servopack failure YES Contact MOTOMAN-service Skapad: 98-10-09
Ändrad: 98-11-26
Filnamn: T:\M-ROBOT\ENGELSK\TROUBLE_SHOOTING.FM
Trouble Shooting YASNAC MRC
MOTOMAN ROBOTICS AB
Alarm 5400
Page: 131
Servo-Ready Off Error Alarm Occurrence Reset alarm, and then execute the operation again NO
Alarm re-occurs?
Resume use
YES Check if main contactor is working or not
NO
Working?
YES
1
YES
Replace MTU board
Check voltage for main contactor coil NO
Abnormal?
YES
Replace main contactor Alarm re-occurs?
YES
Check MTU board Defective?
NO
NO
Contactor failure
Contact MOTOMAN-service
YES
Alarm re-occurs? NO MTU board failure
Skapad: 98-10-09
Ändrad: 98-11-26
Filnamn: T:\M-ROBOT\ENGELSK\TROUBLE_SHOOTING.FM
Trouble Shooting YASNAC MRC Page: 132
Alarm 5400
MOTOMAN ROBOTICS AB
Servo-Ready Off Error (...continued) 1
Check change LED on servopack YES
Lit? NO Turn off power, and then turn it on again Alarm re-occurs?
NO
Resume use
YES Check wiring between contactor and servopack
Defective?
Replace wiring between contactor and servopack
YES
NO Check wiring between MSV board and servopack Defective?
YES
YES
Alarm re-occurs?
NO
Wiring failure
Replace wiring between MSV board and servopack
NO Replace servopack Alarm re-occurs? NO
YES YES
Alarm re-occurs?
NO
Wiring failure
NO
MSV board failure
Replace MSV board Alarm re-occurs?
Servopack failure YES Contact MOTOMAN-service Skapad: 98-10-09
Ändrad: 98-11-26
Filnamn: T:\M-ROBOT\ENGELSK\TROUBLE_SHOOTING.FM
Trouble Shooting YASNAC MRC
MOTOMAN ROBOTICS AB
Alarm 5410
Page: 133
Base-Block On Error Alarm Occurrence Reset alarm, and then execute the operation again Alarm re-occurs?
NO
Resume use
NO
Resume use
YES Turn off power, and then turn it on again Alarm re-occurs? YES Check wiring between MSV board and servopack Defective?
YES
Replace wiring between MSV board and servopack
NO Replace servopack Alarm re-occurs? NO
YES YES
Alarm re-occurs?
NO
Wiring failure
NO
MSV board failure
Replace MSV board Alarm re-occurs?
Servopack failure YES Contact MOTOMAN-service
Skapad: 98-10-09
Ändrad: 98-11-26
Filnamn: T:\M-ROBOT\ENGELSK\TROUBLE_SHOOTING.FM
Trouble Shooting YASNAC MRC Page: 134
Alarm 5420
MOTOMAN ROBOTICS AB
Base-Block Off Error Alarm Occurrence Reset alarm, and then execute the operation again Alarm re-occurs?
NO
Resume use
NO
Resume use
YES Turn off power, and then turn it on again Alarm re-occurs? YES Check wiring between MSV board and servopack Defective?
YES
Replace wiring between MSV board and servopack
NO Replace servopack Alarm re-occurs? NO
YES YES
Alarm re-occurs?
NO
Wiring failure
NO
MSV board failure
Replace MSV board Alarm re-occurs?
Servopack failure YES Contact MOTOMAN-service
Skapad: 98-10-09
Ändrad: 98-11-26
Filnamn: T:\M-ROBOT\ENGELSK\TROUBLE_SHOOTING.FM
Trouble Shooting YASNAC MRC
MOTOMAN ROBOTICS AB
Alarm 5430
Page: 135
Dynamic Brake On Error Alarm Occurrence Reset alarm, and then execute the operation again Alarm re-occurs?
NO
Resume use
NO
Resume use
YES Turn off power, and then turn it on again Alarm re-occurs? YES Check wiring between MSV board and servopack Defective?
YES
Replace wiring between MSV board and servopack
NO Replace servopack Alarm re-occurs? NO
YES YES
Alarm re-occurs?
NO
Wiring failure
NO
MSV board failure
Replace MSV board Alarm re-occurs?
Servopack failure YES Contact MOTOMAN-service
Skapad: 98-10-09
Ändrad: 98-11-26
Filnamn: T:\M-ROBOT\ENGELSK\TROUBLE_SHOOTING.FM
Trouble Shooting YASNAC MRC Page: 136
Alarm 5440
MOTOMAN ROBOTICS AB
Dynamic Brake Off Error Alarm Occurrence Reset alarm, and then execute the operation again Alarm re-occurs?
NO
Resume use
NO
Resume use
YES Turn off power, and then turn it on again Alarm re-occurs? YES Check wiring between MSV board and servopack Defective?
YES
Replace wiring between MSV board and servopack
NO Replace servopack Alarm re-occurs? NO
YES YES
Alarm re-occurs?
NO
Wiring failure
NO
MSV board failure
Replace MSV board Alarm re-occurs?
Servopack failure YES Contact MOTOMAN-service
Skapad: 98-10-09
Ändrad: 98-11-26
Filnamn: T:\M-ROBOT\ENGELSK\TROUBLE_SHOOTING.FM
MOTOMAN ROBOTICS AB
Alarm 5450
Trouble Shooting YASNAC MRC Page: 137
Unused (on) Alarm Occurrence Reset alarm, and then execute the operation again NO
Alarm re-occurs?
Resume use
YES Contact MOTOMAN-service
Alarm 5460
Unused (off) Alarm Occurrence Reset alarm, and then execute the operation again NO
Alarm re-occurs?
Resume use
YES Contact MOTOMAN-service
Alarm 5470
Cannot Edit (edit lock job) Alarm Occurrence
Release Edit-lock, and then execute the operation again NO
Alarm re-occurs?
Resume use
Skapad: 98-10-09
YES Contact MOTOMAN-service
Ändrad: 98-11-26
Filnamn: T:\M-ROBOT\ENGELSK\TROUBLE_SHOOTING.FM
Trouble Shooting YASNAC MRC Page: 138
Alarm 5480
MOTOMAN ROBOTICS AB
Select Error (application 1) Alarm Occurrence Reset alarm, and then execute the operation again NO
Alarm re-occurs?
YES
Resume use
Contact MOTOMAN-service
Alarm 5490
Select Error (application 2) Alarm Occurrence Reset alarm, and then execute the operation again NO
Alarm re-occurs?
YES
Resume use
Contact MOTOMAN-service
Alarm 5500
Select Error (sensor 1) Alarm Occurrence Reset alarm, and then execute the operation again NO
Alarm re-occurs?
Resume use
Skapad: 98-10-09
Ändrad: 98-11-26
YES Contact MOTOMAN-service
Filnamn: T:\M-ROBOT\ENGELSK\TROUBLE_SHOOTING.FM
MOTOMAN ROBOTICS AB
Alarm 5510
Trouble Shooting YASNAC MRC Page: 139
Select Error (sensor 2) Alarm Occurrence Reset alarm, and then execute the operation again Alarm re-occurs?
NO Resume use
YES Contact MOTOMAN-service
Alarm 5520
Wrong Port Out (analog output) Alarm Occurrence Reset alarm, and then execute the operation again Alarm re-occurs?
NO Resume use
Data 1
Contact MOTOMAN-service
Application 1
Skapad: 98-10-09
YES
Ändrad: 98-11-26
Data 2
Application 2
Filnamn: T:\M-ROBOT\ENGELSK\TROUBLE_SHOOTING.FM
Trouble Shooting YASNAC MRC
MOTOMAN ROBOTICS AB
Page: 140
Alarm 5530
Pass Over
Alarm Occurrence Is COM-ARC III’s function normal?
Check workpiece deviation
YES
NO Check the cable between the current detection unit and the sensor board
Defective?
Deviation?
Small
Large
Position a workpiece
Check the current detection unit
NO
YES
Defective?
YES
Replace the current detection unit
Change the cable NO Replace the sensor board Sensor board failure
Alarm re-occurs?
NO
YES
YES
Alarm re-occurs? NO Current detection unit failure
Contact MOTOMAN-service
Alarm 5540
Wrong Selection (sensor) Alarm Occurrence Reset alarm, and then execute the operation again NO
Alarm re-occurs?
Resume use
Skapad: 98-10-09
Ändrad: 98-11-26
YES Contact MOTOMAN-service
Filnamn: T:\M-ROBOT\ENGELSK\TROUBLE_SHOOTING.FM
MOTOMAN ROBOTICS AB
Alarm 5550
Trouble Shooting YASNAC MRC Page: 141
Wrong Mech Parameter File Alarm Occurrence Reset alarm, and then execute the operation again NO
Alarm re-occurs?
Resume use
YES Contact MOTOMAN-service
Alarm 5560
Incompleted PT Frame Alarm Occurrence Reset alarm, and then execute the operation again NO
Alarm re-occurs?
Resume use
YES Contact MOTOMAN-service
Alarm 5570
Defective Taught Point (cutting) Alarm Occurrence Reset alarm, and then execute the operation again NO
Alarm re-occurs?
Resume use
Data 1
Contact MOTOMAN-service
CW axis position is not 0.
Skapad: 98-10-09
YES
Ändrad: 98-11-26
Data 2
Cutting radius is 0.
Filnamn: T:\M-ROBOT\ENGELSK\TROUBLE_SHOOTING.FM
Trouble Shooting YASNAC MRC Page: 142
Alarm 5580
MOTOMAN ROBOTICS AB
Defective Taught Point (endless) Alarm Occurrence Reset alarm, and then execute the operation again NO
Alarm re-occurs?
YES
Resume use
Data 1 Data 2
Contact MOTOMAN-service
Linear motion error (MRESET not executed. Endless on base axes
Alarm 5590
Data 3
Endless not selected on T-axis.
Data 4
Command position exceeds limit (214748367 pulse).
Correctional Direction Data Alarm Occurrence Reset alarm, and then execute the operation again NO
Alarm re-occurs?
YES
Resume use
Contact MOTOMAN-service
Alarm 5600
Position Correction Data Alarm Occurrence Reset alarm, and then execute the operation again NO
Alarm re-occurs?
Resume use
Skapad: 98-10-09
Ändrad: 98-11-26
YES Contact MOTOMAN-service Filnamn: T:\M-ROBOT\ENGELSK\TROUBLE_SHOOTING.FM
MOTOMAN ROBOTICS AB
Alarm 5610
Trouble Shooting YASNAC MRC Page: 143
Over Tool File No. Alarm Occurrence Reset alarm, and then execute the operation again NO
Alarm re-occurs?
Resume use
YES Contact MOTOMAN-service
Alarm 5620
Defective Taught Point (weav) Alarm Occurrence
Check the REFP, and then teach the REFP again NO
Alarm re-occurs?
Resume use
Data 1
YES Contact MOTOMAN-service
Weaving atart point and end point is the same
Alarm 5630
Data 2
Weaving REFP 1 or 2 is on the path
Undefined Robot Calibration Alarm Occurrence
Execute robot calibration
NO
Alarm re-occurs
Resume use
Skapad: 98-10-09
YES Contact MOTOMAN-service
Ändrad: 98-11-26
Filnamn: T:\M-ROBOT\ENGELSK\TROUBLE_SHOOTING.FM
Trouble Shooting YASNAC MRC
MOTOMAN ROBOTICS AB
Page: 144
Alarm 5640
Parameter Error Alarm Occurrence Reset the parameter with the original data NO
Alarm re-occurs?
Resume use
YES
Load the parameter file and then try again Alarm re-occurs?
NO
YES
Resume use
Alarm 5650
Contact MOTOMAN-service
Defective Taught Point (Calib) Alarm Occurrence
Check the taught point, and then teach the point again NO
Alarm re-occurs?
Resume use
Data 3 Data 4
Skapad: 98-10-09
YES Contact MOTOMAN-service
Data for station 2nd axis is not same 3, 4, 5 points. Data for station 1st axis is not same 1, 2, 3 points.
Ändrad: 98-11-26
Data 5 Data 6
Data for station 2nd axis is not same 1, 2, 3 points. Data for station 1st axis is not same 3, 4, 5 points.
Filnamn: T:\M-ROBOT\ENGELSK\TROUBLE_SHOOTING.FM
MOTOMAN ROBOTICS AB
Alarm 5660
Trouble Shooting YASNAC MRC Page: 145
DM-Bank Transmission Error Alarm Occurrence Reset alarm, and then execute the operation again NO
Alarm re-occurs?
Resume use
YES Contact MOTOMAN-service
Alarm 5670
Cannot Execute Job (no grp axis) Alarm Occurrence
Set group axes
NO
Alarm re-occurs?
Resume use
YES Contact MOTOMAN-service
Alarm 5680
Univ Data Preset Request Error Alarm Occurrence Reset alarm, and then execute the operation again NO
Alarm re-occurs?
Resume use
Skapad: 98-10-09
YES Contact MOTOMAN-service
Ändrad: 98-11-26
Filnamn: T:\M-ROBOT\ENGELSK\TROUBLE_SHOOTING.FM
Trouble Shooting YASNAC MRC
MOTOMAN ROBOTICS AB
Page: 146
Alarm 5690
Braking Sequence Error Alarm Occurrence Reset alarm, and then execute the operation again NO
Alarm re-occurs?
YES
Resume use
Contact MOTOMAN-service
Alarm 5700
Process Error (Syscon - axis) Alarm Occurrence Reset alarm, and then execute the operation again NO
Alarm re-occurs?
YES
Resume use
Alarm 5710
Contact MOTOMAN-service
Illegal Sv Parameter (online) Alarm Occurrence
Reset the parameter with the original data. NO
Alarm re-occurs?
Resume use
Load the parameter file and then try again
NO Resume use
Skapad: 98-10-09
YES
Ändrad: 98-11-26
Alarm re-occurs?
YES Contact MOTOMAN-service
Filnamn: T:\M-ROBOT\ENGELSK\TROUBLE_SHOOTING.FM
MOTOMAN ROBOTICS AB
Alarm 5720
Trouble Shooting YASNAC MRC Page: 147
Illegal Sv Parameter (online) Alarm Occurrence Reset alarm, and then execute the operation again NO
Alarm re-occurs?
YES
Resume use
Replace the MSV board, and then try again Alarm re-occurs?
NO Resume use
Alarm 5730
YES Contact MOTOMAN-service
Sv Parameter Change Error (online) Alarm Occurrence Reset alarm, and then execute the operation again NO
Alarm re-occurs?
Resume use
Replace the MSV board, and then try again NO Resume use
Skapad: 98-10-09
YES
Ändrad: 98-11-26
Alarm re-occurs?
YES Contact MOTOMAN-service
Filnamn: T:\M-ROBOT\ENGELSK\TROUBLE_SHOOTING.FM
Trouble Shooting YASNAC MRC
MOTOMAN ROBOTICS AB
Page: 148
Alarm 5740
Illegal Max Speed Parameter Alarm Occurrence Reset the parameter with the original data NO
Alarm re-occurs?
Resume use
YES
Load the parameter file and then try again Alarm re-occurs?
NO Resume use
Alarm 5750
YES Contact MOTOMAN-service
Undefined Position Variable Alarm Occurrence
Set the position variable
NO
Alarm re-occurs?
YES
Resume use
Alarm 5760
Contact MOTOMAN-service
Undefined User Frame Alarm Occurrence
Set the user frame
NO
Alarm re-occurs?
Resume use
Skapad: 98-10-09
Ändrad: 98-11-26
YES Contact MOTOMAN-service
Filnamn: T:\M-ROBOT\ENGELSK\TROUBLE_SHOOTING.FM
MOTOMAN ROBOTICS AB
Alarm 5770
Trouble Shooting YASNAC MRC Page: 149
Out Of Range (parallel process) Alarm Occurrence Reset alarm, and then execute the operation again NO
Alarm re-occurs?
Resume use
YES Contact MOTOMAN-service
Alarm 5780
SL Board On-Line Error Alarm Occurrence Reset alarm, and then execute the operation again NO
Alarm re-occurs?
Resume use
YES Contact MOTOMAN-service
Alarm 5790
Interrupt Error (sensor) Alarm Occurrence Reset alarm, and then execute the operation again NO
Alarm re-occurs?
Resume use
Skapad: 98-10-09
YES Contact MOTOMAN-service
Ändrad: 98-11-26
Filnamn: T:\M-ROBOT\ENGELSK\TROUBLE_SHOOTING.FM
Trouble Shooting YASNAC MRC Page: 150
Alarm 5800
MOTOMAN ROBOTICS AB
Out Of Current Detector Range Alarm Occurrence Reset alarm, and then execute the operation again NO
Alarm re-occurs?
YES
Resume use
Contact MOTOMAN-service
Alarm 5810
Command Error (sensor) Alarm Occurrence Reset alarm, and then execute the operation again NO
Alarm re-occurs?
YES
Resume use
Contact MOTOMAN-service
Alarm 5820
Process Error (sensor) Alarm Occurrence Reset alarm, and then execute the operation again NO
Alarm re-occurs?
Resume use
Skapad: 98-10-09
Ändrad: 98-11-26
YES Contact MOTOMAN-service
Filnamn: T:\M-ROBOT\ENGELSK\TROUBLE_SHOOTING.FM
MOTOMAN ROBOTICS AB
Alarm 5830
Trouble Shooting YASNAC MRC Page: 151
Parallel Start Instruction Error Alarm Occurrence Check the program, and then modify it. NO
Alarm re-occurs?
Resume use
YES Contact MOTOMAN-service
Alarm 5840
Cannot Execute Job (grp axis) Alarm Occurrence
Set group axes
NO
Alarm re-occurs?
Resume use
YES Contact MOTOMAN-service
Alarm 5850
Measure Inst Execute Error Alarm Occurrence Reset alarm, and then execute the operation again NO
Alarm re-occurs?
Resume use
Skapad: 98-10-09
YES Contact MOTOMAN-service
Ändrad: 98-11-26
Filnamn: T:\M-ROBOT\ENGELSK\TROUBLE_SHOOTING.FM
Headquarters: MOTOMAN ROBOTICS AB Box 504 l 385 25 Torsås l Sweden Tel: +46-486-48800l Fax: +46-486-41410
Subsidiary: MOTOMAN ROBOTICS UK LTD 1 Swan Industrial Estate l Banbury l OXON OX16 8DJ l England Tel: +44-1295-272755 l Fax: +44-1295-267127
MOTOMAN ROBOTICS ITALIA SRL Via Emilia 1420/16 l I-41100 Modena l ITALY Tel: +39-59280496 l Fax: +39-59280602
MOTOMAN ROBOTICS FRANCE S.A. Rue Nungesser et Coli l D2A Nantes-Atlantique l F-44860 Saint-Aignan-de-Grand-Lieu l France Tel: +33-2-40131919 l Fax: +33-40754147
MOTOMAN ROBOTICS ESPAÑA S.L. Avenida Marina 56 l Parcela 90 l ES-08830 ST. Boi de Llobregat l Spain Tel: +34-36303478 l Fax: +34-36543459
Distributors: ELECTRO-ARCO S.A. Rua Vice Almirante Azevedo Coutinho, 4 l Venda Nova l PT-2700 Amadora l Portugal Tel: +351-14968160 l Fax: +351-14990696
HN AUTOMATIC A/S Hjulmagervej 4 l DK-7100 Vejle l Denmark Tel: +45-79428000 l Fax: +45-79428001
LINCOLN-KD S.A. Ctra, Laureà Miró 396-398 l E-08980 Sant Feliu de Llobregat l Spain Tel: +34-36859600 l Fax: +34-36859633
MOTOMAN ROBOTIT OY Kärsämäentie 8 l SF-20300 Turku l Finland Tel: +358-22145600 l Fax: +358-22145660
ROBOT-TEKNIKK AS Øvre Eikervei 177 l N-3048 Drammen l Norway Tel: +47-32217830 l Fax: +47-32217840
SIAD S.p.a. Via S. Bernardino, 92 l I-24126 Bergamo l Italy Tel: +39-35-328111 l Fax: +39-35-320183
MOTOMAN ROBOTICS AB a subsidiary of YASKAWA Electric Corporation