Overload Relay Trip Curves Selection Index Class 2510, 8536, 9065
Using Thermal Overload Relay Trip Curves . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2 Class 2510 AC and DC Manual Starters . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6 Class 8536 AC Magnetic Starters with Melting Alloy Overload Relay . . . . . . . . . . . . . . . . . . . . . . . . . 7 with Bimetallic Overload Relay . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9
Class 9065 Separately Mounted Overload Relays Melting Alloy . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11 Bimetallic . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12
Class 9065 Solid-State Overload Relays Motor Logic ® SSOLR, Type SF, SR, SS, ST . . . . . . . . . . . . . . . . 13 Motor Logic ® Plus Programmable SSOLR, Type SP . . . . . . . . . . 14
Overload Relay Trip Curves
5/2005
USING THERMAL OVERLOAD RELAY TRIP CURVES Overview
Overload relay trip curves present trip time as a function of overload current. To use them properly, you must understand their application, construction, and limitations. Trip curves for Square D ® products assume a cold start with the coil energized at the rated voltage in an ambient temperature of 40 °C (104 °F). Different trip times would result under different conditions— conditions— if the starter coil were not energized, for example, or if the controller door were open. Ambient temperature affects the performance of the thermal overload relay (OLR). Trip times increase in temperatures below 40 °C and decrease above 40 °C. But since motor capacity also varies with temperature in about the same proportion, this variation is not normally a factor in OLR selection. Most motors are also rated on the basis of a 40 °C ambient temperature, so the 40 °C OLR trip curves allow direct comparison with motor characteristics.
Application
Trip curves are most commonly used to determine whether protection against locked rotor current (LRC) is adequate should the motor stall or fail to start. Consult the manufacturer to determine the value of the locked rotor current and the length of time that the motor can withstand this condition. Then, compare this data to the OLR trip curve to ensure that the device will trip before the motor is damaged. Trip curves can also indicate whether the OLR allows normal starting of a motor without tripping, especially in applications with a long acceleration period. For this type of analysis, calculate the rms (heating) value of the load current on the trip curve at cumulative intervals during and following the starting period. Plotting the actual motor current on the trip curve is not sufficient, because the OLR may trip even if the motor current curve does not intersect the OLR trip curve. Although the starting current falls off as the motor reaches full speed, the heat produced in the OLR (and in the motor) does not immediately dissipate. The effect of this thermal inertia can inertia can be approximated by calculating the rms current over several cumulative time periods. For an accelerating time of 15 s, for instance, rms current values might be calculated for the following time periods: 0–5 s, 0–10 s, 0–15 s, and so forth. These rms current values can then be plotted; and if the resulting curve does not intersect the OLR trip curve, then no trip should occur during startup. NOTE: If the curves do intersect at some point point beyond the motor accelerating period, period, the OLRs may or may not trip during startup. The above calculation ignores heat losses, and therefore may give a false indication that the OLRs will trip. In such cases, we recommend conducting a trial.
Curve Construction
Square D trip curves come in two basic versions:
•
Curves with one solid line (maximum) and one dashed line (average) apply (average) apply to present-production melting-alloy thermal units (plain brass nameplate only) and present-production bimetallic thermal units.
•
Curves with two solid lines (with lines (with or without shaded area) apply to older-design melting-alloy thermal units (red enamel nameplate) and older-design bimetallic thermal units.
The width of the band curve does not represent repeat accuracy of a particular thermal unit, nor does it imply a variation between thermal units of the same size. However, the thermal units of different sizes do have slightly different characteristics. These differences result in a band of values (or maximum and average values, depending on the type of curve) when data for several sizes of thermal units are included in one curve. The load scale is expressed in three ways:
• •
Multiples of trip current rating is rating is obtained by dividing the overload current by the trip current rating.
•
Percent of thermal unit number, element number, or relay rating is rating is obtained by dividing the overload current by the number stamped on the thermal unit nameplate and multiplying by 100. (For a B19.5 thermal unit, 100% corresponds to 19.5.)
1
2
Percent of trip current rating is rating is obtained by dividing the overload current by the trip current rating1 and multiplying by 100.
Also called the rated trip current or the ultimate trip current.
© 2005 Schneider Electric All Rights Reserved
5/2005
Calculating the Trip Current Rating
Overload Relay Trip Curves
The trip current rating is a nominal value approximating the minimum current that will trip an OLR in an ambient temperature of 40 °C. To calculate the trip current rating: 1. Refer to the thermal thermal unit unit selection selection table specifie specified d for the controller. controller. 2. Locate the minimum full-load full-load current (FLC) for the applicable thermal unit. unit. 3. Multiply the the minimum FLC by 1.25 (1.15 for Class 8198). The result is the trip current rating. This procedure applies to controllers with bimetallic OLRs if the trip adjustment is set to 100%.
Calculating the Trip Current for Ambient Temperatures Other Than 40 °C
When the controller is in an ambient temperature other than 40 °C, calculate the trip current using the correction factor shown in Fi Figu gure re 2. Trip rip Curr Curren entt
=
M × tri trip cur curre rent nt rat rating ing at 40 °C
where M is the multiplier corresponding to the temperature. NOTE: Ambient temperature is the the temperature surrounding the starter enclosure. Normal Normal temperature rise inside the enclosure is accounted for in the thermal unit selection tables.
Limitations
For most magnetic starters, the trip curves are different for OLRs mounted in small enclosures than for those mounted in large enclosures. While curves for open-type starters are theoretically correct only for devices mounted without an enclosure, these curves provide a reasonable approximation of performance using a large enclosure.
•
Small enclosure trip curves are for use with devices of the following Classes: — 8536 (start (starter er in its own own enclosure) enclosure) — 8904 (non-comb (non-combinat ination ion or non-rever non-reversing) sing) — 8998, 899 8999, 9, I-Line, I-Line, and QMB (motor (motor control centers) centers)
•
Large enclosure trip curves are for use with devices of the following Classes: — 8536 (start (starter er in its own own enclosure) enclosure) — 8539 (combinat (combination ion starter, starter, non-revers non-reversing) ing) — 8606, 8630, 8630, 8640 8640 (reduced (reduced voltage voltage starter starter)) — 8736, 8739 (reversing (reversing starter) starter) — 8810, 8811, 8811, 8812 8812 (multi-sp (multi-speed eed starter) starter) — 8940, 8941 (pump controller controller)) — any other other starter starter in a large enclosu enclosure re
Curve accuracy should be sufficient for most applications. The curves are more accurate for high currents than for low currents. In particular, overload currents below 300% may yield different trip times. Conditions in the field may differ from those in a laboratory; the longer the trip time period, the more pronounced the differences. Continued on next page
© 2005 Schneider Electric All Rights Rights Reserved
3
Overload Relay Trip Curves
Examples
5/2005
Motor 7.5 hp, 200 V, 3-phase, 1.15 SF, 22.6 A FLC, 136 A LRC Starter Class 8536 Type SCG3 with B45 thermal units Ambient Temperature 40 °C (104 °F)
Question
What is the average OLR trip time with a locked rotor current of 136 A (6 ti mes FLC)?
Calculations
In a 40 °C ambient temperature, the trip current rating is 125% of the minimum current in the thermal unit selection table. For the Class 8536 Type SCG3 starter, B45 thermal units were selected from the 22.0–24.4 A FLC range shown in Thermal Unit Table 13 on pag age e 5. Based on the minimum FLC for the thermal unit, the Trip Current Rating = 1.25 × 22 27.5 =
With a locked rotor current of 136 A, the Multiple of Trip Current Rating = 136 ÷ 27.5
=
4.95
Solution
The trip curve index shows that curve 30068-407 should be used for a Class 8536 Type SCG3 starter in a small enclosure. For a multiple of 4.95, the average trip time shown in the curve is 19 seconds.
Question
If the ambient temperature were 50 °C (122 °F), what would the average trip time be?
Calculations
Figure Figu re 2 on page page 5 shows that the ambient temperature correction factor at 50 °C is 0.9. Trip Current Rating 1.25 × 22 × 0.9 24.75 =
=
With a locked rotor current of 136 A, the Multiple of Trip Current Rating = 136 ÷ 24.75
=
5.5
Solution
For a multiple of 5.5, the average trip time shown in curve 30068-407 is 16 seconds.
Question
If the load current were twice the FLC (45.2 A), and the ambient temperature were 40 °C (104 °F), what would the average trip time be?
Calculations
Trip Current Rating = 1.25 × 22
=
27.5
Multiple of Trip Current Rating = 45.2 ÷ 27.5
=
1.65
Solution
For a multiple of 1.65, the average trip time shown in curve 30068-407 is 170 seconds.
Question
If the load current were 28 A, what would the average trip time be?
Calculations
Trip Current Rating = 1.25 × 22
=
27.5
Multiple of Trip Current Rating = 28 ÷ 27.5 Solution
4
=
1.018
For a load current this close to the trip current rating, the trip time is difficult to predict. It would likely take hours for the OLR to trip.
© 2005 Schneider Electric All Rights Reserved
5/2005
Overload Relay Trip Curves
Figu Figure re 1:
Exce Excerp rptt from from The Therm rmal al Uni Unitt Tabl Table e 13
Motor Full-Load Current (A)
Thermal Unit Number
1 T.U.
2 T.U.
3 T.U.
5.20-5.73 5.74-6.39 6.40-7.13 7.14-7.90 7.91-8.55
5.20-5.73 5.74-6.39 6.40-7.13 7.14-7.90 7.91-8.55
4.94-5.21 5.22-5.84 5.85-6.67 6.68-7.54 7.55-8.14
B B B B B
8.20 9.10 10.2 10.2 11.5 11.5 12.8 12.8
8.56-9.53 9.54-10.6 10.7-11.8 11.9-13.2 13.3-14.9
8.56-9.53 9.54-10.6 10.7-11.8 11.9-12.0 …
8.15-8.72 8.73-9.66 9.67-10.5 10.6-11.3 11.4-12.0
B B B B B
14 15.5 15.5 17.5 17.5 19.5 19.5 22
15.0-16.6 16.7-18.0
… …
… …
B 25 B 28.0 28.0
Following Selections for Size 1 Only … … … 16.7-18.9 19.0-21.2
11.9-13.2 13.3-14.9 15.0-16.6 16.7-18.9 19.0-21.2
… 11.4-12.7 12.8-14.1 14.2-15.9 16.0-17.5
B B B B B
19.5 19.5 22 25 28.0 28.0 32
21.3-23.0 23.1-25.5 25.6-26.0 …
21.3-23.0 23.1-25.5 25.6-26.0 …
17.6-19.7 19.8-21.9 22.0-24.4 24.5-26.0
B B B B
36 40 45 50
Figu Figure re 2:
Ambi Ambien entt Temp Temper erat atur ure e Corr Correc ectio tion n Curv Curve e for for OLRs OLRs
E D A100 R G I T N E 80 C S E E R 60 G E D E R 40 U T A R E 20 P M E T T N 0 E I B M A -20
AMBIENT TEMPERATURE CORRECTION CURVE FOR THERMAL OVERLOAD RELAYS
212 194 176 158 140 122 104 86
68 50 32 14
0
2 . 0
4 . 0
6 . 0
8 . 0
0 . 1
2 . 1
4 . 1
T I E H N E R A F S E E R G E D E R U T A R E P M E T T N E I B M A
-4
MULTIPLIER M
© 2005 Schneider Electric All Rights Rights Reserved
5
Overload Relay Trip Curves
5/2005
Reference Drawing Number, 30068-xxx
Class 2510 AC and DC Manual Starters Melting Alloy Overload Relay Size FHP
Type F
Series Application A
Open or Enclosed
Thermal Unit Type A 1 TU
2 TU
B 3TU
1 TU
2 TU
FB 3TU
M-0
M-1
MC TC
312 456 456 456 page 30 page page page 72 page page 72 page page 72
490 page 79 page
Large Enclosure
313 457 457 457 page 31 page page page 73 page page 73 page page 73
490 page 79 page
2511, 2512, Small Enclosure
313 page 31 page
Small Enclosure A
279 page 20 page
457 457 457 page 73 page page page 73 page page 73
490 page 79 page
312 456 456 456 page 30 page page page 72 page page 72 page page 72
490 page 79 page
Large Enclosure
313 457 457 457 page 31 page page page 73 page page 73 page page 73
490 page 79 page
2511, 2512, Small Enclosure
313 page 31 page
Small Enclosure A
A
Small Enclosure Large Enclosure
6
1, 2, 3 TU
490 page 79 page
279 page 20 page
Open M-1P
3TU
457 457 457 page 73 page page page 73 page page 73
Open
MC TC
2 TU
447 page pa ge 66
Open
MB TB
1 TU
SB
279 page 20 page
457 page 73 page
490 page 79 page
456 page 72 page
490 page 79 page
457 page pag e 73
490 page pa ge 79
© 2005 Schneider Electric All Rights Reserved
5/2005
Overload Relay Trip Curves
Reference Drawing Number, 30068-xxx
Class 8536 AC Magnetic Starters Melting Alloy Overload Relay Size
Type
A1
Series Application
B,C
00
Thermal Unit Type A 1 TU
2 TU
B 3TU
Open
443 page pag e 62
446 page pa ge 65
8536 Small Enclosure
444 page 63 page
445 page 64 page
Large Enclosure
443 page 62 page
446 page 65 page
1 TU
2 TU
FB 3TU
1 TU
2 TU
SB 3TU
490 page 79 page
Open SA
A Enclosed
314 314 411 page 32 page page page 32 page page 45
490 page 79 page 490 page 79 page
Open 0
SB
A
8536 Small Enclosure
272 272 407 454 454 454 page 15 page page page 15 page page 41 page page 70 page page 70 page page 70
490 page 79 page
Large Enclosure
310 310 408 453 453 453 page 28 page page page 28 page page 42 page page 69 page page 69 page page 69
490 page 79 page 490 page 79 page
Open 8536 Small Enclosure 1
SC
A
272 272 407 454 454 454 page 15 page page page 15 page page 41 page page 70 page page 70 page page 70 319 319 page 37 page page page 37
SC
A
490 page 79 page
Model 3 MCC, QMB, I-Line
272 272 407 454 454 454 page pa ge 15 page page 15 page page 41 page page 70 page page 70 page page 70
490 page pag e 79
Other Larger Enclosure
310 310 408 453 453 453 page 28 page page page 28 page page 42 page page 69 page page 69 page page 69
490 page 79 page 490 page 79 page
8536 Small Enclosure
278 page 19 page
490 page 79 page
Large Enclosure
278 page 19 page
490 page 79 page 490 page 79 page
Open 280 280 409 455 455 455 page 21 page page page 21 page page 43 page page 71 page page 71 page page 71
490 page 79 page
320 320 455 455 455 page 38 page page page 38 page page 71 page page 71 page page 71
490 page 79 page
Model 3 MCC, QMB, I-Line
280 280 409 455 455 455 page 21 page page page 21 page page 43 page page 71 page page 71 page page 71
490 page 79 page
Other Larger Enclosure
315 315 410 463 463 463 page 33 page page page 33 page page 44 page page 78 page page 78 page page 78
490 page 79 page
8536 Small Enclosure 2
1)
SD
A
490 page 79 page
454 454 page 70 page page page 70
Model 4 MCC
Open 1P
1, 2, 3 TU
Model 4 MCC
Non-reversing.
© 2005 Schneider Electric All Rights Rights Reserved
7
Overload Relay Trip Curves
Class 8536 AC Magnetic Starters Melting Alloy Overload Relay Size
Type
Series Application
5/2005
Reference Drawing Number, 30068-xxx Thermal Unit Type B 3 TU
CC 1 TU
2 TU
DD 3TU
1 TU
2 TU
FB (Form Y81) 3TU
SE
SF
3TU
8536 Small Enclosure
317 299 page 35 page page page 22
458 458 page 74 page page page 74
MCC, QMB, I-Line
317 299 page 35 page page page 22
458 458 page 74 page page page 74
Other Larger Enclosure
318 300 page 36 page page page 23
459 459 page 75 page page page 75
A
461 461 page 77 page page page 77
Open
4
2 TU
459 459 page 75 page page page 75
Open
3
1 TU
8536 Small Enclosure
302 page 25 page
460 460 page 76 page page page 76
MCC, QMB, I-Line
302 page 25 page
460 page 76 page
Other Larger Enclosure
303 page 26 page
461 461 page 77 page page page 77
A
Open
5
SG
8536 Small Enclosure
273 page 16 page
MCC, QMB, I-Line
273 page 16 page
Other Larger Enclosure
274 page 17 page
A
Open
5
SG
8536 Small Enclosure
311 page 29 page
MCC, QMB, I-Line
311 page pag e 29
Other Larger Enclosure
311 page 29 page
B
Open
6
8
SH
8536 Small Enclosure
348 page 39 page
MCC, QMB, I-Line
348 page 39 page
Other Larger Enclosure
349 page 40 page
A, B
© 2005 Schneider Electric All Rights Reserved
5/2005
Overload Relay Trip Curves
Reference Drawing Number, 30068-xxx Class 8536 AC Magnetic Starters Bimetallic Overload Relay Size
Type SB Form B
Series Application
SC Form B
SD Form B
2 TU
3TU
Ambient-Temperature Compensated AR 1 TU
2 TU
A
413 page pa ge 46
Large Enclosure (includes Reversing)
413 page 46 page
8536 Small Enclosure
415 page 48 page
Large Enclosure (includes Reversing)
416 page 49 page
8536 Small Enclosure
413 page 46 page
Large Enclosure (includes Reversing)
413 page 46 page
8536 Small Enclosure
415 page 48 page
MCC, QMB, I-Line
415 page 48 page
Large Enclosure (includes Reversing)
416 page 49 page
8536 Small Enclosure
414 page 47 page
Large Enclosure (includes Reversing)
414 page 47 page
A
A
3TU
8536 Small Enclosure
B
2 SD Form B2
1 TU
A
1 SC Form B2
Non-Compensated AR
B
0 SB Form B2
Thermal Unit Type
8536 Small Enclosure
417 page 50 page
MCC, QMB, I-Line
417 page 50 page
Large Enclosure (includes Reversing)
418 page 51 page
Thermal Unit Type Size
Type
Se Series Application
Non-Compensated AU 1 TU
SE Form B5
3
SE Form B5
SE Form Y59
A
B
A
2 TU
3TU
8536 Small Enclosure
438 page 60 page
MCC, QMB, I-Line
438 page 60 page
Large Enclosure (includes Reversing)
439 page 61 page
Non-Compensated E or K 1 TU
2 TU
3TU
8536 Small Enclosure
820 page 82 page
MCC, QMB, I-Line
820 page 82 page
Large Enclosure (includes Reversing)
820 page 82 page
Ambient-Temperature Compensated E or K 1 TU
2 TU
3 TU
8536 Small Enclosure
820 page 82 page
MCC, QMB, I-Line
820 page 82 page
Large Enclosure (includes Reversing)
820 page 82 page
© 2005 Schneider Electric All Rights Rights Reserved
9
Overload Relay Trip Curves
5/2005
Reference Drawing Number, 30068-xxx Class 8536 AC Magnetic Starters Bimetallic Overload Relay Size
Type
SF Form B5
4
SF Form B5
SF Form Y59
Series Application
A
B
A
Thermal Unit Type Non-Compensated AU 1 TU
2 TU
3TU
8536 Small Enclosure
423 page pag e 56
MCC, QMB, I-Line
423 page 56 page
Large Enclosure (includes Reversing)
424 page 57 page
Non-Compensated E or K 1 TU
2 TU
3TU
8536 Small Enclosure
820 page 82 page
MCC, QMB, I-Line
820 page 82 page
Large Enclosure (includes Reversing)
820 page 82 page
Ambient-Temperature Compensated E or K 1 TU
2 TU
3TU
8536 Small Enclosure
820 page 82 page
MCC, QMB, I-Line
820 page 82 page
Large Enclosure (includes Reversing)
820 page 82 page
Thermal Unit Type Size
Type
Se Series Application
Non-Compensated AR 1 TU
SG Form A B2Y500
SG Form BY500
6
419 page 52 page
MCC, QMB, I-Line
419 page 52 page
10
SH Form B2
A, B
2 TU
3TU
413 page 46 page
MCC, QMB, I-Line
413 page 46 page
Standard or Large Enclosure
419 page 52 page
MCC, QMB, I-Line
419 page 52 page
B
B
1 TU
Standard or Large Enclosure A
SG Form B
SH Form B
3TU
Standard or Large Enclosure
5 SG Form B2
2 TU
Ambient-Temperature Compensated AR
Standard or Large Enclosure
413 page 46 page
MCC, QMB, I-Line
413 page 46 page
Standard or Large Enclosure MCC, QMB, I-Line
Trip curves not available for this OLR
Standard or Large Enclosure
413 page 46 page
MCC, QMB, I-Line
413 page 46 page
A, B
© 2005 Schneider Electric All Rights Reserved
5/2005
Overload Relay Trip Curves
Reference Drawing Number, 30068-xxx
Class 9065 Separately Mounted Melting Alloy Overload Relay Size
Type
Series Application
C
A
Open or Enclosed
S
A
Open or Enclosed
T
A
Open or Enclosed
S
A
Open or Enclosed
25 A
45 A
Thermal Unit Type B 1 TU
2 TU
FB 3TU
1 TU
2 TU
SB 3TU
450 page pa ge 67
1 TU
2 TU
3TU
490 page 79 page
490 page 79 page
490 page 79 page
490 page 79 page
490 page pag e 79 311 page 29 page
490 page 79 page
451 page 68 page
490 page 79 page 316 page 34 page
490 page 79 page
Thermal Unit Type Size
Type
Se Series Application
C 1 TU
86 A
U
A
Open or Enclosed
S
A
Open or Enclosed
2 TU
CC 3TU
1 TU
2 TU
3TU 301 page 24 page
Thermal Unit Type Size
Type
Se Series Application
CC 1 TU
133 A
266 A
F
B
Open or Enclosed
S
A
Open or Enclosed
G
A
Open or Enclosed
© 2005 Schneider Electric All Rights Rights Reserved
2 TU
DD 3TU
1 TU
2 TU
3TU
304 page 27 page 275 page 18 page
11
Overload Relay Trip Curves
Class 9065 Separately Mounted Bimetallic Overload Relay Size
Type
Series Ap A pplication
DA
A
Open or Enclosed
DA2
A
Open or Enclosed
GA
A
Open or Enclosed
GA2
A
Open or Enclosed
HA
A
Open or Enclosed
HA2
A
Open or Enclosed
JA
A
Open or Enclosed
JA2
A
Open or Enclosed
25 A
60 A
100 A
180 A
5/2005
Reference Drawing Number, 30068-xxx Thermal Unit Type Ambient-Temperature Compensated E or K 1 TU
2 TU
3TU
Non-Compensated E or K 1 TU
2 TU
3TU
820 page pag e 82 820 page 82 page 820 page 82 page 820 page 82 page 820 page 82 page 820 page 82 page 820 page 82 page 820 page 82 page
Thermal Unit Type Size
Type
Se Series Application
Ambient-Temperature Compensated AR 1 TU
SEO6B
B
Open or Enclosed
SEO6B2 A
Open or Enclosed
SEO9B
A
Open or Enclosed
SEO9B2 A
Open or Enclosed
26 A
45 A
12
2 TU
3TU
Non-Compensated AR 1 TU
2 TU
3TU
413 page pag e 46 419 page 52 page 414 page 47 page 420 page 53 page
© 2005 Schneider Electric All Rights Reserved
5/2005
Overload Relay Trip Curves
MOTOR LOGIC ® Solid State Overload Relays CHARACTERISTIC CHARACTERISTI C CURVE NO. 9065-0001 Class 9065 Type SS, SF, SR and ST 1000
100 S D N O C E S N I
E M I T
10
CLASS 20
CLASS 10
1 1
2
3
4
5
6
7
8
9
10
MULTIPLE OF FLA
© 2000 Schneide r Electricall rights reserved reserved
© 2005 Schneider Electric All Rights Rights Reserved
Curve No. 9065TC0001 March 2000
13
MOTOR LOGIC ® PLUS Programmable Programmable Solid State Overload Relays CHARACTERISTIC CURVE NO. 9065-0002 Class 9065 Type SP 10000
1000
S D N O C E S 100 N I E M I T
CLASS 30 10
CLASS 20 CLASS 15 CLASS 10 CLASS 5
1 0
100
200
300
400
500
600
700
800
900
1000
% OF OC SETTING
© 2000 Schneider Electric all rights eserved r
Curve No. 9065TC0002 March 2000
MULTIPLES OF TRIP CURRENT RATING 10000 9000 8000
5 . 6 . 7 . 8 . 9 . 1
5 . 1
2
3
4
5
6
7
8
0 9 1
5 1
0 2
10000 9000 8000
7000
7000
6000
6000
5000
5000
4000
4000
3000
3000
OVERLOAD RELAY TIME-CURRENT CHARACTERISTICS REFERENCE DRAWING NO. 30068-272B Relay Design
Melting Alloy
Therm hermal al Unit Unit Type ypes
B0.44 0.44– –B45
40 °C ambient cold start trip time characteristics of: 2000
2000
40 ˚C (104 ˚F) AMBIENT COLD START MAXIMUM AVERAGE
1500
1500
Equipment
AC Magnetic Starter
Size
0&1
Type
SB & SC
1000 900 800
Series
A
1000 900 800
Qty Qty. of of The Therm rmal al Unit Units s
1 or or 2
700
700
When installed in:
600
600
500
500
400
400
300
300
200
200
S D N 150 O C E 100 S 90 N 80 I E M I T
150
100 90 80
70
70
60
60
50
50
40
40
30
30
20
20
15
15
10 9
10 9
8
8
7
7
6
6
5
5
4
4
3
3
2
2
1.5
1
• Sma Smallll enclos enclosure ure (Class (Class 8536 only) only) • QMB QMB, I-L I-Lin ine e ® The trip current rating can be determined from the instructions given with the appropriate thermal unit selection table. The characteristics shown do not necessarily apply to equipment manufactured before S the date of the referenced drawing. D N O C E S N I
E M I T
1.5
5 . 6 . 7 . 8 . 9 . 1
5 . 1
2
3
4
5
6
7
8
9 0 1
5 1
1
0 2
MULTIPLES OF TRIP CURRENT RATING
© 2005 2005 Schneider Schneider Electric all rights ghts reserved reserved
Curve No. 8536TC0301 May 2005
CURRENT IN MULTIPLES OF TRIP CURRENT RATING 10000 9000 8000
0
1
2
3
4
5
10000 9000 8000
7000
7000
6000
6000
5000
5000
4000
4000
3000
3000
2000
2000
OVERLOAD RELAY TIME-CURRENT CHARACTERISTICS REFERENCE DRAWING NO. 30068-273
Relay Design
Melting Alloy
Ther Therma mall Unit Unit Types ypes
DD11 DD112– 2–DD DD34 340 0
40 °C ambient cold start trip time characteristics of: 40 ˚C (104 ˚F) AMBIENT COLD START MAXIMUM AVERAGE
1500
1500
Equipment
AC Magnetic Starter
Size
5
Type
SG
Qty Qty. of of The Therm rmal al Unit Units s
3
1000 900 800
1000 900 800
700
700
600
600
• Sma Smallll enclos enclosure ure (Class (Class 8536 only) only)
500
500
400
400
• Motor Motor Cont Control rol Center Center (Class 8998, 8999, QMB, or I-Line ® )
When installed in:
6
300
200
300
200
S D N 150 O C E S 100 90 N I 80 E M I T
7
150
100 90 80
70
70
60
60
50
50
40
40
30
30
20
20
15
15
10 9
10 9
8
8
7
7
6
6
5
5
4
4
3
3
2
2
1.5
1
S D N O C E S N I
Trip current rating can be determined from the instructions given with appropriate thermal unit selection table. The characteristics characteristics shown do not necessarily apply to equipment manufactured before the date of the referenced drawing.
E M I T
1.5
0
1
2
3
4
5
6
1
7
CURRENT IN MULTIPLES OF TRIP CURRENT RATING
© 2005 2005 Schneider Schneider Electric all rights ghts reserved reserved
Curve No. 8536TC0302 May 2005
MULTIPLES OF TRIP CURRENT RATING 10000 9000 8000
5 . 6 . 7 . 8 . 9 . 1
5 . 1
2
3
4
5
6
7
8
0 9 1
5 1
0 2
10000 9000 8000
7000
7000
6000
6000
5000
5000
4000
4000
3000
3000
OVERLOAD RELAY TIME-CURRENT CHARACTERISTICS REFERENCE DRAWING NO. 30068-274A Relay Design
Melting Alloy
Therm hermal al Unit Unit Types ypes
DD1 DD112– 12–DD3 DD320
40 °C ambient cold start trip time characteristics of: 2000
2000
40 ˚C (104 ˚F) AMBIENT COLD START MAXIMUM AVERAGE
1500
1500
Equipment
AC Magnetic Starter
Size
5
Type
SG
1000 900 800
Series
A
1000 900 800
Qty. of of The Therm rma al Un Units its
3
700
700
When installed in:
600
600
500
500
400
400
300
300
200
200
S D N 150 O C E 100 S 90 N 80 I E M I T
150
100 90 80
70
70
60
60
50
50
40
40
30
30
20
20
15
15
10 9
10 9
8
8
7
7
6
6
5
5
4
4
3
3
2
2
1.5
1
• Hinged Hinged door and and all other other (larger (larger)) enclosures enclosures The trip current rating can be determined from the instructions given with the appropriate thermal unit selection table. The characteristics shown do not necessarily apply to equipment manufactured before the date of the referenced drawing. S D N O C E S N I
E M I T
1.5
5 . 6 . 7 . 8 . 9 . 1
5 . 1
2
3
4
5
6
7
8
9 0 1
5 1
1
0 2
MULTIPLES OF TRIP CURRENT RATING
© 2005 2005 Schneider Schneider Electric all rights ghts reserved reserved
Curve No. 8536TC0303 May 2005
MULTIPLES OF TRIP CURRENT RATING 10000 9000 8000
5 . 6 . 7 . 8 . 9 . 1
5 . 1
2
3
4
5
6
7
8
0 9 1
5 1
0 2
10000 9000 8000
7000
7000
6000
6000
5000
5000
4000
4000
3000
3000
OVERLOAD RELAY TIME-CURRENT CHARACTERISTICS REFERENCE DRAWING NO. 30068-275A Relay Design
Melting Alloy
Therm hermal al Unit Unit Types ypes
DD4 DD48–D 8–DD300 300
40 °C ambient cold start trip time characteristics of: 2000
2000
40 ˚C (104 ˚F) AMBIENT COLD START MAXIMUM AVERAGE
1500
1500
Equipment
Separate Overload Relay
Size
300 A (nominal)
Type
GG & GO
1000 900 800
Series
A
1000 900 800
Qty. of of The Therm rma al Un Units its
1
700
700
When installed in:
600
600
500
500
400
400
300
300
200
200
• Hinged Hinged door and and all other other (larger (larger)) enclosures enclosures
S D N 150 O C E 100 S 90 N 80 I E M I T
150
100 90 80
70
70
60
60
50
50
40
40
30
30
20
20
15
15
10 9
10 9
8
8
7
7
6
6
5
5
4
4
3
3
2
2
1.5
1
• Sma Smallll enclos enclosure ure (Class (Class 9065 only) only)
The trip current rating can be determined from the instructions given with the appropriate thermal unit selection table. The characteristics shown do not necessarily apply to equipment manufactured before S the date of the referenced drawing. D N O C E S N I
E M I T
1.5
5 . 6 . 7 . 8 . 9 . 1
5 . 1
2
3
4
5
6
7
8
9 0 1
5 1
1
0 2
MULTIPLES OF TRIP CURRENT RATING
© 2005 2005 Schneider Schneider Electric all rights ghts reserved reserved
Curve No. 9065TC0301 May 2005
MULTIPLES OF TRIP CURRENT RATING 10000 9000 8000
5 . 6 . 7 . 8 . 9 . 1
5 . 1
2
3
4
5
6
7
8
0 9 1
5 1
0 2
10000 9000 8000
7000
7000
6000
6000
5000
5000
4000
4000
3000
3000
OVERLOAD RELAY TIME-CURRENT CHARACTERISTICS REFERENCE DRAWING NO. 30068-278 Relay Design
Melting Alloy
Therm hermal al Unit Unit Type ypes
B1.16 1.16– –B56
40 °C ambient cold start trip time characteristics of: 2000
2000
40 ˚C (104 ˚F) AMBIENT COLD START MAXIMUM AVERAGE
1500
1500
Equipment
AC Magnetic Starter
Size
1P
Type
SC
1000 900 800
Series
A
1000 900 800
Qty. of of The Therm rma al Un Units its
1
700
700
When installed in:
600
600
500
500
400
400
300
300
200
200
• Hinged Hinged door and and all other other (larger (larger)) enclosures enclosures
S D N 150 O C E 100 S 90 N 80 I E M I T
150
100 90 80
70
70
60
60
50
50
40
40
30
30
20
20
15
15
10 9
10 9
8
8
7
7
6
6
5
5
4
4
3
3
2
2
1.5
1
• Sma Smallll enclos enclosure ure (Class (Class 8536 only) only)
The trip current rating can be determined from the instructions given with the appropriate thermal unit selection table. The characteristics shown do not necessarily apply to equipment manufactured before S the date of the referenced drawing. D N O C E S N I
E M I T
1.5
5 . 6 . 7 . 8 . 9 . 1
5 . 1
2
3
4
5
6
7
8
9 0 1
5 1
1
0 2
MULTIPLES OF TRIP CURRENT RATING
© 2005 2005 Schneider Schneider Electric all rights ghts reserved reserved
Curve No. 8536TC0304 May 2005
MULTIPLES OF TRIP CURRENT RATING 10000 9000 8000
5 . 6 . 7 . 8 . 9 . 1
5 . 1
2
3
4
5
6
7
8
0 9 1
5 1
0 2
10000 9000 8000
7000
7000
6000
6000
5000
5000
4000
4000
3000
3000
OVERLOAD RELAY TIME-CURRENT CHARACTERISTICS REFERENCE DRAWING NO. 30068-279 Relay Design
Melting Alloy
Therm hermal al Unit Unit Type ypes
B0.44 0.44– –B50
40 °C ambient cold start trip time characteristics of: 2000
2000
40 ˚C (104 ˚F) AMBIENT COLD START MAXIMUM AVERAGE
1500
1500
Equipment
AC Manual Star ter
Size
M-0, M-1, M-1P
Type
M&T
1000 900 800
Series
A
1000 900 800
Qty. of of The Therm rma al Un Units its
1
700
700
When installed in:
600
600
500
500
400
400
300
300
200
200
S D N 150 O C E 100 S 90 N 80 I E M I T
150
100 90 80
70
70
60
60
50
50
40
40
30
30
20
20
15
15
10 9
10 9
8
8
7
7
6
6
5
5
4
4
3
3
2
2
1.5
1
• Sma Smallll enclos enclosure ure (Class (Class 2510 only) only) The trip current rating can be determined from the instructions given with the appropriate thermal unit selection table. The characteristics shown do not necessarily apply to equipment manufactured before the date of the referenced drawing. S D N O C E S N I
E M I T
1.5
5 . 6 . 7 . 8 . 9 . 1
5 . 1
2
3
4
5
6
7
8
9 0 1
5 1
1
0 2
MULTIPLES OF TRIP CURRENT RATING
© 2005 2005 Schneider Schneider Electric all rights ghts reserved reserved
Curve No. 2510TC0301 May 2005
MULTIPLES OF TRIP CURRENT RATING 10000 9000 8000
5 . 6 . 7 . 8 . 9 . 1
5 . 1
2
3
4
5
6
7
8
0 9 1
5 1
0 2
10000 9000 8000
7000
7000
6000
6000
5000
5000
4000
4000
3000
3000
OVERLOAD RELAY TIME-CURRENT CHARACTERISTICS REFERENCE DRAWING NO. 30068-280A Relay Design
Melting Alloy
Therm hermal al Unit Unit Type ypes
B4.85 4.85– –B70
40 °C ambient cold start trip time characteristics of: 2000
2000
40 ˚C (104 ˚F) AMBIENT COLD START MAXIMUM AVERAGE
1500
1500
Equipment
AC Magnetic Starter
Size
2
Type
SD
1000 900 800
Series
A
1000 900 800
Qty Qty. of of The Therm rmal al Unit Units s
1 or or 2
700
700
When installed in:
600
600
500
500
400
400
300
300
200
200
S D N 150 O C E 100 S 90 N 80 I E M I T
150
100 90 80
70
70
60
60
50
50
40
40
30
30
20
20
15
15
10 9
10 9
8
8
7
7
6
6
5
5
4
4
3
3
2
2
1.5
1
• Sma Smallll enclos enclosure ure (Class (Class 8536 only) only) • QMB QMB, I-L I-Lin ine e ® The trip current rating can be determined from the instructions given with the appropriate thermal unit selection table. The characteristics shown do not necessarily apply to equipment manufactured before S the date of the referenced drawing. D N O C E S N I
E M I T
1.5
5 . 6 . 7 . 8 . 9 . 1
5 . 1
2
3
4
5
6
7
8
9 0 1
5 1
1
0 2
MULTIPLES OF TRIP CURRENT RATING
© 2005 2005 Schneider Schneider Electric all rights ghts reserved reserved
Curve No. 8536TC0305 May 2005
MULTIPLES OF TRIP CURRENT RATING 10000 9000 8000
5 . 6 . 7 . 8 . 9 . 1
5 . 1
2
3
4
5
6
7
8
0 9 1
5 1
0 2
10000 9000 8000
7000
7000
6000
6000
5000
5000
4000
4000
3000
3000
OVERLOAD RELAY TIME-CURRENT CHARACTERISTICS REFERENCE DRAWING NO. 30068-299 Relay Design
Melting Alloy
Therm hermal al Unit Unit Type ypes
CC20 CC20..9–CC 9–CC19 196 6
40 °C ambient cold start trip time characteristics of: 2000
2000
40 ˚C (104 ˚F) AMBIENT COLD START MAXIMUM AVERAGE
1500
1500
Equipment
AC Magnetic Starter
Size
3
Type
SE
1000 900 800
Series
A
1000 900 800
Qty. of of The Therm rma al Un Units its
3
700
700
When installed in:
600
600
500
500
400
400
300
300
200
200
S D N 150 O C E 100 S 90 N 80 I E M I T
150
100 90 80
70
70
60
60
50
50
40
40
30
30
20
20
15
15
10 9
10 9
8
8
7
7
6
6
5
5
4
4
3
3
2
2
1.5
1
• Sma Smallll enclos enclosure ure (Class (Class 8536 only) only) • Motor Motor Contro Controll Cente Centerr (Class 8998, 8999, QMB, or I-Line ® ) The trip current rating can be determined from the instructions given with the appropriate thermal unit selection table. The characteristics shown do not S necessarily apply to equipment manufactured before Dthe date of the referenced drawing. N O C E S N I
E M I T
1.5
5 . 6 . 7 . 8 . 9 . 1
5 . 1
2
3
4
5
6
7
8
9 0 1
5 1
1
0 2
MULTIPLES OF TRIP CURRENT RATING
© 2005 2005 Schneider Schneider Electric all rights ghts reserved reserved
Curve No. 8536TC0306 May 2005
MULTIPLES OF TRIP CURRENT RATING 10000 9000 8000
5 . 6 . 7 . 8 . 9 . 1
5 . 1
2
3
4
5
6
7
8
0 9 1
5 1
0 2
10000 9000 8000
7000
7000
6000
6000
5000
5000
4000
4000
3000
3000
OVERLOAD RELAY TIME-CURRENT CHARACTERISTICS REFERENCE DRAWING NO. 30068-300 Relay Design
Melting Alloy
Therm hermal al Unit Unit Type ypes
CC20 CC20..9–CC 9–CC18 180 0
40 °C ambient cold start trip time characteristics of: 2000
2000
40 ˚C (104 ˚F) AMBIENT COLD START MAXIMUM AVERAGE
1500
1500
Equipment
AC Magnetic Starter
Size
3
Type
SE
1000 900 800
Series
A
1000 900 800
Qty. of of The Therm rma al Un Units its
3
700
700
When installed in:
600
600
500
500
400
400
300
300
200
200
S D N 150 O C E 100 S 90 N 80 I E M I T
150
100 90 80
70
70
60
60
50
50
40
40
30
30
20
20
15
15
10 9
10 9
8
8
7
7
6
6
5
5
4
4
3
3
2
2
1.5
1
• Hinged Hinged door and and all other other (larger (larger)) enclosures enclosures The trip current rating can be determined from the instructions given with the appropriate thermal unit selection table. The characteristics shown do not necessarily apply to equipment manufactured before the date of the referenced drawing. S D N O C E S N I
E M I T
1.5
5 . 6 . 7 . 8 . 9 . 1
5 . 1
2
3
4
5
6
7
8
9 0 1
5 1
1
0 2
MULTIPLES OF TRIP CURRENT RATING
© 2005 2005 Schneider Schneider Electric all rights ghts reserved reserved
Curve No. 8536TC0307 May 2005
MULTIPLES OF TRIP CURRENT RATING 10000 9000 8000
5 . 6 . 7 . 8 . 9 . 1
5 . 1
2
3
4
5
6
7
8
0 9 1
5 1
0 2
10000 9000 8000
7000
7000
6000
6000
5000
5000
4000
4000
3000
3000
OVERLOAD RELAY TIME-CURRENT CHARACTERISTICS REFERENCE DRAWING NO. 30068-301A Relay Design
Melting Alloy
Therm hermal al Unit Unit Type ypes
CC20 CC20..9–CC 9–CC11 112 2
40 °C ambient cold start trip time characteristics of: 2000
2000
40 ˚C (104 ˚F) AMBIENT COLD START MAXIMUM AVERAGE
1500
1500
Equipment
Separate Overload Relay
Size
100 A (nominal)
Type
SEO
1000 900 800
Series
A
1000 900 800
Qty. of of The Therm rma al Un Units its
3
700
700
When installed in:
600
600
500
500
400
400
300
300
200
200
S D N 150 O C E 100 S 90 N 80 I E M I T
150
100 90 80
70
70
60
60
50
50
40
40
30
30
20
20
15
15
10 9
10 9
8
8
7
7
6
6
5
5
4
4
3
3
2
2
1.5
1
• Hinged Hinged door and and all other other (larger (larger)) enclosures enclosures The trip current rating can be determined from the instructions given with the appropriate thermal unit selection table. The characteristics shown do not necessarily apply to equipment manufactured before the date of the referenced drawing. S D N O C E S N I
E M I T
1.5
5 . 6 . 7 . 8 . 9 . 1
5 . 1
2
3
4
5
6
7
8
9 0 1
5 1
1
0 2
MULTIPLES OF TRIP CURRENT RATING
© 2005 2005 Schneider Schneider Electric all rights ghts reserved reserved
Curve No. 9065TC0302 May 2005
MULTIPLES OF TRIP CURRENT RATING 10000 9000 8000
5 . 6 . 7 . 8 . 9 . 1
5 . 1
2
3
4
5
6
7
8
0 9 1
5 1
0 2
10000 9000 8000
7000
7000
6000
6000
5000
5000
4000
4000
3000
3000
OVERLOAD RELAY TIME-CURRENT CHARACTERISTICS REFERENCE DRAWING NO. 30068-302 Relay Design
Melting Alloy
Therm hermal al Unit Unit Type ypes
CC64 CC64..3–CC 3–CC21 219 9
40 °C ambient cold start trip time characteristics of: 2000
2000
40 ˚C (104 ˚F) AMBIENT COLD START MAXIMUM AVERAGE
1500
1500
Equipment
AC Magnetic Starter
Size
4
Type
SF
1000 900 800
Series
A
1000 900 800
Qty. of of The Therm rma al Un Units its
3
700
700
When installed in:
600
600
500
500
400
400
300
300
200
200
S D N 150 O C E 100 S 90 N 80 I E M I T
150
100 90 80
70
70
60
60
50
50
40
40
30
30
20
20
15
15
10 9
10 9
8
8
7
7
6
6
5
5
4
4
3
3
2
2
1.5
1
• Sma Smallll enclos enclosure ure (Class (Class 8536 only) only) • Motor Motor Contro Controll Cente Centerr (Class 8998, 8999, QMB, or I-Line ® ) The trip current rating can be determined from the instructions given with the appropriate thermal unit selection table. The characteristics shown do not S necessarily apply to equipment manufactured before Dthe date of the referenced drawing. N O C E S N I
E M I T
1.5
5 . 6 . 7 . 8 . 9 . 1
5 . 1
2
3
4
5
6
7
8
9 0 1
5 1
1
0 2
MULTIPLES OF TRIP CURRENT RATING
© 2005 2005 Schneider Schneider Electric all rights ghts reserved reserved
Curve No. 8536TC0308 May 2005
MULTIPLES OF TRIP CURRENT RATING 10000 9000 8000
5 . 6 . 7 . 8 . 9 . 1
5 . 1
2
3
4
5
6
7
8
0 9 1
5 1
0 2
10000 9000 8000
7000
7000
6000
6000
5000
5000
4000
4000
3000
3000
OVERLOAD RELAY TIME-CURRENT CHARACTERISTICS REFERENCE DRAWING NO. 30068-303 Relay Design
Melting Alloy
Therm hermal al Unit Unit Type ypes
CC64 CC64..3–CC 3–CC19 196 6
40 °C ambient cold start trip time characteristics of: 2000
2000
40 ˚C (104 ˚F) AMBIENT COLD START MAXIMUM AVERAGE
1500
1500
Equipment
AC Magnetic Starter
Size
4
Type
SF
1000 900 800
Series
A
1000 900 800
Qty. of of The Therm rma al Un Units its
3
700
700
When installed in:
600
600
500
500
400
400
300
300
200
200
S D N 150 O C E 100 S 90 N 80 I E M I T
150
100 90 80
70
70
60
60
50
50
40
40
30
30
20
20
15
15
10 9
10 9
8
8
7
7
6
6
5
5
4
4
3
3
2
2
1.5
1
• Hinged Hinged door and and all other other (larger (larger)) enclosures enclosures The trip current rating can be determined from the instructions given with the appropriate thermal unit selection table. The characteristics shown do not necessarily apply to equipment manufactured before the date of the referenced drawing. S D N O C E S N I
E M I T
1.5
5 . 6 . 7 . 8 . 9 . 1
5 . 1
2
3
4
5
6
7
8
9 0 1
5 1
1
0 2
MULTIPLES OF TRIP CURRENT RATING
© 2005 2005 Schneider Schneider Electric all rights ghts reserved reserved
Curve No. 8536TC0309 May 2005
MULTIPLES OF TRIP CURRENT RATING 10000 9000 8000
5 . 6 . 7 . 8 . 9 . 1
5 . 1
2
3
4
5
6
7
8
0 9 1
5 1
0 2
10000 9000 8000
7000
7000
6000
6000
5000
5000
4000
4000
3000
3000
OVERLOAD RELAY TIME-CURRENT CHARACTERISTICS REFERENCE DRAWING NO. 30068-304 Relay Design
Melting Alloy
Therm hermal al Unit Unit Type ypes
CC64 CC64..3–CC 3–CC19 196 6
40 °C ambient cold start trip time characteristics of: 2000
2000
40 ˚C (104 ˚F) AMBIENT COLD START MAXIMUM AVERAGE
1500
1500
Equipment
Separate Overload Relay
Size
150 A (nominal)
Type
SEO
1000 900 800
Series
A
1000 900 800
Qty. of of The Therm rma al Un Units its
3
700
700
When installed in:
600
600
500
500
400
400
300
300
200
200
S D N 150 O C E 100 S 90 N 80 I E M I T
150
100 90 80
70
70
60
60
50
50
40
40
30
30
20
20
15
15
10 9
10 9
8
8
7
7
6
6
5
5
4
4
3
3
2
2
1.5
1
• Hinged Hinged door and and all other other (larger (larger)) enclosures enclosures The trip current rating can be determined from the instructions given with the appropriate thermal unit selection table. The characteristics shown do not necessarily apply to equipment manufactured before the date of the referenced drawing. S D N O C E S N I
E M I T
1.5
5 . 6 . 7 . 8 . 9 . 1
5 . 1
2
3
4
5
6
7
8
9 0 1
5 1
1
0 2
MULTIPLES OF TRIP CURRENT RATING
© 2005 2005 Schneider Schneider Electric all rights ghts reserved reserved
Curve No. 9065TC0303 May 2005
MULTIPLES OF TRIP CURRENT RATING 10000 9000 8000
5 . 6 . 7 . 8 . 9 . 1
5 . 1
2
3
4
5
6
7
8
0 9 1
5 1
0 2
10000 9000 8000
7000
7000
6000
6000
5000
5000
4000
4000
3000
3000
OVERLOAD RELAY TIME-CURRENT CHARACTERISTICS REFERENCE DRAWING NO. 30068-310A Relay Design
Melting Alloy
Therm hermal al Unit Unit Type ypes
B0.44 0.44– –B40
40 °C ambient cold start trip time characteristics of: 2000
2000
40 ˚C (104 ˚F) AMBIENT COLD START MAXIMUM AVERAGE
1500
1500
Equipment
AC Magnetic Starter
Size
0&1
Type
SB & SC
1000 900 800
Series
A
1000 900 800
Qty Qty. of of The Therm rmal al Unit Units s
1 or or 2
700
700
When installed in:
600
600
500
500
400
400
300
300
200
200
S D N 150 O C E 100 S 90 N 80 I E M I T
150
100 90 80
70
70
60
60
50
50
40
40
30
30
20
20
15
15
10 9
10 9
8
8
7
7
6
6
5
5
4
4
3
3
2
2
1.5
1
• Hinged Hinged door and and all other other (larger (larger)) enclosures enclosures The trip current rating can be determined from the instructions given with the appropriate thermal unit selection table. The characteristics shown do not necessarily apply to equipment manufactured before the date of the referenced drawing. S D N O C E S N I
E M I T
1.5
5 . 6 . 7 . 8 . 9 . 1
5 . 1
2
3
4
5
6
7
8
9 0 1
5 1
1
0 2
MULTIPLES OF TRIP CURRENT RATING
© 2005 2005 Schneider Schneider Electric all rights ghts reserved reserved
Curve No. 8536TC0310 May 2005
MULTIPLES OF TRIP CURRENT RATING 10000 9000 8000
5 . 6 . 7 . 8 . 9 . 1
5 . 1
2
3
4
5
6
7
8
0 9 1
5 1
0 2
10000 9000 8000
7000
7000
6000
6000
5000
5000
4000
4000
3000
3000
OVERLOAD RELAY TIME-CURRENT CHARACTERISTICS REFERENCE DRAWING NO. 30068-311A Relay Design
Melting Alloy
Therm hermal al Unit Unit Type ypes
B0.44 0.44– –B40
40 °C ambient cold start trip time characteristics of: 2000
2000
40 ˚C (104 ˚F) AMBIENT COLD START MAXIMUM AVERAGE
1500
1500
Equipment
Separate Overload Relay
Size
30 A (nominal)
Type
SEG & SEO
1000 900 800
Series
A
1000 900 800
Qty. of of The Therm rma al Un Units its
3
700
700
When installed in:
600
600
500
500
400
400
300
300
200
200
• Hinged Hinged door and and all other other (larger (larger)) enclosures enclosures
S D N 150 O C E 100 S 90 N 80 I E M I T
150
100 90 80
70
70
60
60
50
50
40
40
30
30
20
20
15
15
10 9
10 9
8
8
7
7
6
6
5
5
4
4
3
3
2
2
1.5
1
• Sma Smallll enclos enclosure ure (Class (Class 9065 only) only)
The trip current rating can be determined from the instructions given with the appropriate thermal unit selection table. The characteristics shown do not necessarily apply to equipment manufactured before S the date of the referenced drawing. D N O C E S N I
E M I T
1.5
5 . 6 . 7 . 8 . 9 . 1
5 . 1
2
3
4
5
6
7
8
9 0 1
5 1
1
0 2
MULTIPLES OF TRIP CURRENT RATING
© 2005 2005 Schneider Schneider Electric all rights ghts reserved reserved
Curve No. 9065TC0304 May 2005
MULTIPLES OF TRIP CURRENT RATING 10000 9000 8000
5 . 6 . 7 . 8 . 9 . 1
5 . 1
2
3
4
5
6
7
8
0 9 1
5 1
0 2
10000 9000 8000
7000
7000
6000
6000
5000
5000
4000
4000
3000
3000
OVERLOAD RELAY TIME-CURRENT CHARACTERISTICS REFERENCE DRAWING NO. 30068-312A Relay Design
Melting Alloy
Therm hermal al Unit Unit Type ypes
B0.44 0.44– –B45
40 °C ambient cold start trip time characteristics of: 2000
2000
40 ˚C (104 ˚F) AMBIENT COLD START MAXIMUM AVERAGE
1500
1500
Equipment
AC Manual Star ter
Size
M-0 & M-1
Type
M&T
1000 900 800
Series
A
1000 900 800
Qty. of of The Therm rma al Un Units its
3
700
700
When installed in:
600
600
500
500
400
400
300
300
200
200
S D N 150 O C E 100 S 90 N 80 I E M I T
150
100 90 80
70
70
60
60
50
50
40
40
30
30
20
20
15
15
10 9
10 9
8
8
7
7
6
6
5
5
4
4
3
3
2
2
1.5
1
• Sma Smallll enclos enclosure ure (Class (Class 2510 only) only) The trip current rating can be determined from the instructions given with the appropriate thermal unit selection table. The characteristics shown do not necessarily apply to equipment manufactured before the date of the referenced drawing. S D N O C E S N I
E M I T
1.5
5 . 6 . 7 . 8 . 9 . 1
5 . 1
2
3
4
5
6
7
8
9 0 1
5 1
1
0 2
MULTIPLES OF TRIP CURRENT RATING
© 2005 2005 Schneider Schneider Electric all rights ghts reserved reserved
Curve No. 2510TC0302 May 2005
MULTIPLES OF TRIP CURRENT RATING 10000 9000 8000
5 . 6 . 7 . 8 . 9 . 1
5 . 1
2
3
4
5
6
7
8
0 9 1
5 1
0 2
10000 9000 8000
7000
7000
6000
6000
5000
5000
4000
4000
3000
3000
OVERLOAD RELAY TIME-CURRENT CHARACTERISTICS REFERENCE DRAWING NO. 30068-313A Relay Design
Melting Alloy
Therm hermal al Unit Unit Type ypes
B0.44 0.44– –B45
40 °C ambient cold start trip time characteristics of: 2000
2000
40 ˚C (104 ˚F) AMBIENT COLD START MAXIMUM AVERAGE
1500
1500
Equipment
AC Manual Star ter
Size
M-0 & M-1
Type
M&T
1000 900 800
Series
A
1000 900 800
Qty. of of The Therm rma al Un Units its
6
700
700
When installed in:
600
600
500
500
400
400
300
300
200
200
S D N 150 O C E 100 S 90 N 80 I E M I T
150
100 90 80
70
70
60
60
50
50
40
40
30
30
20
20
15
15
10 9
10 9
8
8
7
7
6
6
5
5
4
4
3
3
2
2
1.5
1
• Sma Smallll enclosur enclosure e (Class (Class 2511, 2512 2512 only) only) The trip current rating can be determined from the instructions given with the appropriate thermal unit selection table. The characteristics shown do not necessarily apply to equipment manufactured before the date of the referenced drawing. S D N O C E S N I
E M I T
1.5
5 . 6 . 7 . 8 . 9 . 1
5 . 1
2
3
4
5
6
7
8
9 0 1
5 1
1
0 2
MULTIPLES OF TRIP CURRENT RATING
© 2005 2005 Schneider Schneider Electric all rights ghts reserved reserved
Curve No. 2510TC0303 May 2005
MULTIPLES OF TRIP CURRENT RATING 10000 9000 8000
5 . 6 . 7 . 8 . 9 . 1
5 . 1
2
3
4
5
6
7
8
0 9 1
5 1
0 2
10000 9000 8000
7000
7000
6000
6000
5000
5000
4000
4000
3000
3000
OVERLOAD RELAY TIME-CURRENT CHARACTERISTICS REFERENCE DRAWING NO. 30068-314A Relay Design
Melting alloy
Therm hermal al Unit Unit Types ypes
B0.44 0.44–B –B1 11.5 1.5
40 °C ambient cold start trip time characteristics of: 2000
2000
40 ˚C (104 ˚F) AMBIENT COLD START MAXIMUM AVERAGE
1500
1500
Equipment
Class 8736 Reversing Starter
Size
00
Type
SA
1000 900 800
Series
A
1000 900 800
Qty Qty. of of The Therm rmal al Unit Units s
1 or or 2
700
700
When installed in:
600
600
500
500
400
400
300
300
200
200
• Hinged Hinged door and and all other other (larger (larger)) enclosures enclosures
S D N 150 O C E 100 S 90 N 80 I E M I T
150
100 90 80
70
70
60
60
50
50
40
40
30
30
20
20
15
15
10 9
10 9
8
8
7
7
6
6
5
5
4
4
3
3
2
2
1.5
1
• Sma Smallll enclos enclosure ure (Class (Class 8736 only) only)
The trip current rating can be determined from the instructions given with the appropriate thermal unit selection table. The characteristics shown do not necessarily apply to equipment manufactured before S the date of the referenced drawing. D N O C E S N I
E M I T
1.5
5 . 6 . 7 . 8 . 9 . 1
5 . 1
2
3
4
5
6
7
8
9 0 1
5 1
1
0 2
MULTIPLES OF TRIP CURRENT RATING
© 2005 2005 Schneider Schneider Electric all rights ghts reserved reserved
Curve No. 8736TC0301 May 2005
MULTIPLES OF TRIP CURRENT RATING 10000 9000 8000
5 . 6 . 7 . 8 . 9 . 1
5 . 1
2
3
4
5
6
7
8
0 9 1
5 1
0 2
10000 9000 8000
7000
7000
6000
6000
5000
5000
4000
4000
3000
3000
OVERLOAD RELAY TIME-CURRENT CHARACTERISTICS REFERENCE DRAWING NO. 30068-315A Relay Design
Melting Alloy
Therm hermal al Unit Unit Type ypes
B4.85 4.85– –B70
40 °C ambient cold start trip time characteristics of: 2000
2000
40 ˚C (104 ˚F) AMBIENT COLD START MAXIMUM AVERAGE
1500
1500
Equipment
AC Magnetic Starter
Size
2
Type
SD
1000 900 800
Series
A
1000 900 800
Qty Qty. of of The Therm rmal al Unit Units s
1 or or 2
700
700
When installed in:
600
600
500
500
400
400
300
300
200
200
S D N 150 O C E 100 S 90 N 80 I E M I T
150
100 90 80
70
70
60
60
50
50
40
40
30
30
20
20
15
15
10 9
10 9
8
8
7
7
6
6
5
5
4
4
3
3
2
2
1.5
1
• Hinged Hinged door and and all other other (larger (larger)) enclosures enclosures The trip current rating can be determined from the instructions given with the appropriate thermal unit selection table. The characteristics shown do not necessarily apply to equipment manufactured before the date of the referenced drawing. S D N O C E S N I
E M I T
1.5
5 . 6 . 7 . 8 . 9 . 1
5 . 1
2
3
4
5
6
7
8
9 0 1
5 1
1
0 2
MULTIPLES OF TRIP CURRENT RATING
© 2005 2005 Schneider Schneider Electric all rights ghts reserved reserved
Curve No. 8536TC0311 May 2005
MULTIPLES OF TRIP CURRENT RATING 10000 9000 8000
5 . 6 . 7 . 8 . 9 . 1
5 . 1
2
3
4
5
6
7
8
0 9 1
5 1
0 2
10000 9000 8000
7000
7000
6000
6000
5000
5000
4000
4000
3000
3000
OVERLOAD RELAY TIME-CURRENT CHARACTERISTICS REFERENCE DRAWING NO. 30068-316A Relay Design
Melting Alloy
Therm hermal al Unit Unit Type ypes
B4.85 4.85– –B62
40 °C ambient cold start trip time characteristics of: 2000
2000
40 ˚C (104 ˚F) AMBIENT COLD START MAXIMUM AVERAGE
1500
1500
Equipment
Separate Overload Relay
Size
50 A (nominal)
Type
SEG & SEO
1000 900 800
Series
A
1000 900 800
Qty. of of The Therm rma al Un Units its
3
700
700
When installed in:
600
600
500
500
400
400
300
300
200
200
• Hinged Hinged door and and all other other (larger (larger)) enclosures enclosures
S D N 150 O C E 100 S 90 N 80 I E M I T
150
100 90 80
70
70
60
60
50
50
40
40
30
30
20
20
15
15
10 9
10 9
8
8
7
7
6
6
5
5
4
4
3
3
2
2
1.5
1
• Sma Smallll enclos enclosure ure (Class (Class 9065 only) only)
The trip current rating can be determined from the instructions given with the appropriate thermal unit selection table. The characteristics shown do not necessarily apply to equipment manufactured before S the date of the referenced drawing. D N O C E S N I
E M I T
1.5
5 . 6 . 7 . 8 . 9 . 1
5 . 1
2
3
4
5
6
7
8
9 0 1
5 1
1
0 2
MULTIPLES OF TRIP CURRENT RATING
© 2005 2005 Schneider Schneider Electric all rights ghts reserved reserved
Curve No. 9065TC0305 May 2005
MULTIPLES OF TRIP CURRENT RATING 10000 9000 8000
5 . 6 . 7 . 8 . 9 . 1
5 . 1
2
3
4
5
6
7
8
0 9 1
5 1
0 2
10000 9000 8000
7000
7000
6000
6000
5000
5000
4000
4000
3000
3000
OVERLOAD RELAY TIME-CURRENT CHARACTERISTICS REFERENCE DRAWING NO. 30068-317A Relay Design
Melting Alloy
Therm hermal al Unit Unit Type ypes
CC20 CC20..9–CC 9–CC19 196 6
40 °C ambient cold start trip time characteristics of: 2000
2000
40 ˚C (104 ˚F) AMBIENT COLD START MAXIMUM AVERAGE
1500
1500
Equipment
AC Magnetic Starter
Size
3
Type
SE
1000 900 800
Series
A
1000 900 800
Qty. of of The Therm rma al Un Units its
2
700
700
When installed in:
600
600
500
500
400
400
300
300
200
200
S D N 150 O C E 100 S 90 N 80 I E M I T
150
100 90 80
70
70
60
60
50
50
40
40
30
30
20
20
15
15
10 9
10 9
8
8
7
7
6
6
5
5
4
4
3
3
2
2
1.5
1
• Sma Smallll enclos enclosure ure (Class (Class 8536 only) only) • Motor Motor Contro Controll Cente Centerr (Class 8998, 8999, QMB, or I-Line ® ) The trip current rating can be determined from the instructions given with the appropriate thermal unit selection table. The characteristics shown do not S necessarily apply to equipment manufactured before Dthe date of the referenced drawing. N O C E S N I
E M I T
1.5
5 . 6 . 7 . 8 . 9 . 1
5 . 1
2
3
4
5
6
7
8
9 0 1
5 1
1
0 2
MULTIPLES OF TRIP CURRENT RATING
© 2005 2005 Schneider Schneider Electric all rights ghts reserved reserved
Curve No. 8536TC0312 May 2005
MULTIPLES OF TRIP CURRENT RATING 10000 9000 8000
5 . 6 . 7 . 8 . 9 . 1
5 . 1
2
3
4
5
6
7
8
0 9 1
5 1
0 2
10000 9000 8000
7000
7000
6000
6000
5000
5000
4000
4000
3000
3000
OVERLOAD RELAY TIME-CURRENT CHARACTERISTICS REFERENCE DRAWING NO. 30068-318A Relay Design
Melting Alloy
Therm hermal al Unit Unit Type ypes
CC20 CC20..9–CC 9–CC15 156 6
40 °C ambient cold start trip time characteristics of: 2000
2000
40 ˚C (104 ˚F) AMBIENT COLD START MAXIMUM AVERAGE
1500
1500
Equipment
AC Magnetic Starter
Size
3
Type
SE
1000 900 800
Series
A
1000 900 800
Qty. of of The Therm rma al Un Units its
2
700
700
When installed in:
600
600
500
500
400
400
300
300
200
200
S D N 150 O C E 100 S 90 N 80 I E M I T
150
100 90 80
70
70
60
60
50
50
40
40
30
30
20
20
15
15
10 9
10 9
8
8
7
7
6
6
5
5
4
4
3
3
2
2
1.5
1
• Hinged Hinged door and and all other other (larger (larger)) enclosures enclosures The trip current rating can be determined from the instructions given with the appropriate thermal unit selection table. The characteristics shown do not necessarily apply to equipment manufactured before the date of the referenced drawing. S D N O C E S N I
E M I T
1.5
5 . 6 . 7 . 8 . 9 . 1
5 . 1
2
3
4
5
6
7
8
9 0 1
5 1
1
0 2
MULTIPLES OF TRIP CURRENT RATING
© 2005 2005 Schneider Schneider Electric all rights ghts reserved reserved
Curve No. 8536TC0313 May 2005
MULTIPLES OF TRIP CURRENT RATING 10000 9000 8000
5 . 6 . 7 . 8 . 9 . 1
5 . 1
2
3
4
5
6
7
8
0 9 1
5 1
0 2
10000 9000 8000
7000
7000
6000
6000
5000
5000
4000
4000
3000
3000
OVERLOAD RELAY TIME-CURRENT CHARACTERISTICS REFERENCE DRAWING NO. 30068-319 Relay Design
Melting Alloy
Therm hermal al Unit Unit Type ypes
B0.44 0.44– –B50
40 °C ambient cold start trip time characteristics of: 2000
2000
40 ˚C (104 ˚F) AMBIENT COLD START MAXIMUM AVERAGE
1500
1500
Equipment
AC Magnetic Starter
Size
1
Type
SC
1000 900 800
Series
A
1000 900 800
Qty Qty. of of The Therm rmal al Unit Units s
2 or or 3
700
700
When installed in:
600
600
500
500
400
400
300
300
200
200
S D N 150 O C E 100 S 90 N 80 I E M I T
150
100 90 80
70
70
60
60
50
50
40
40
30
30
20
20
15
15
10 9
10 9
8
8
7
7
6
6
5
5
4
4
3
3
2
2
1.5
1
• Mode Modell 4 Motor Motor Contr Control ol Center Center only The trip current rating can be determined from the instructions given with the appropriate thermal unit selection table. The characteristics shown do not necessarily apply to equipment manufactured before the date of the referenced drawing. S D N O C E S N I
E M I T
1.5
5 . 6 . 7 . 8 . 9 . 1
5 . 1
2
3
4
5
6
7
8
9 0 1
5 1
1
0 2
MULTIPLES OF TRIP CURRENT RATING
© 2005 2005 Schneider Schneider Electric all rights ghts reserved reserved
Curve No. 8536TC0314 May 2005
MULTIPLES OF TRIP CURRENT RATING 10000 9000 8000
5 . 6 . 7 . 8 . 9 . 1
5 . 1
2
3
4
5
6
7
8
0 9 1
5 1
0 2
10000 9000 8000
7000
7000
6000
6000
5000
5000
4000
4000
3000
3000
OVERLOAD RELAY TIME-CURRENT CHARACTERISTICS REFERENCE DRAWING NO. 30068-320 Relay Design
Melting Alloy
Therm hermal al Unit Unit Type ypes
B5.50 5.50– –B88
40 °C ambient cold start trip time characteristics of: 2000
2000
40 ˚C (104 ˚F) AMBIENT COLD START MAXIMUM AVERAGE
1500
1500
Equipment
AC Magnetic Starter
Size
2
Type
SD
1000 900 800
Series
A
1000 900 800
Qty Qty. of of The Therm rmal al Unit Units s
2 or or 3
700
700
When installed in:
600
600
500
500
400
400
300
300
200
200
S D N 150 O C E 100 S 90 N 80 I E M I T
150
100 90 80
70
70
60
60
50
50
40
40
30
30
20
20
15
15
10 9
10 9
8
8
7
7
6
6
5
5
4
4
3
3
2
2
1.5
1
• Mode Modell 4 Motor Motor Contr Control ol Center Center only The trip current rating can be determined from the instructions given with the appropriate thermal unit selection table. The characteristics shown do not necessarily apply to equipment manufactured before the date of the referenced drawing. S D N O C E S N I
E M I T
1.5
5 . 6 . 7 . 8 . 9 . 1
5 . 1
2
3
4
5
6
7
8
9 0 1
5 1
1
0 2
MULTIPLES OF TRIP CURRENT RATING
© 2005 2005 Schneider Schneider Electric all rights ghts reserved reserved
Curve No. 8536TC0315 May 2005
MULTIPLES OF TRIP CURRENT RATING 10000 9000 8000
5 . 6 . 7 . 8 . 9 . 1
5 . 1
2
3
4
5
6
7
8
0 9 1
5 1
0 2
10000 9000 8000
7000
7000
6000
6000
5000
5000
4000
4000
3000
3000
OVERLOAD RELAY TIME-CURRENT CHARACTERISTICS REFERENCE DRAWING NO. 30068-348 Relay Design
Melting Alloy
Therm hermal al Unit Unit Type ypes
B1.30–B 30–B6 6.25
40 °C ambient cold start trip time characteristics of: 2000
2000
40 ˚C (104 ˚F) AMBIENT COLD START MAXIMUM AVERAGE
1500
1500
Equipment
AC Magnetic Starter
Size
6
Type
SH
1000 900 800
Series
A
1000 900 800
Qty. of of The Therm rma al Un Units its
3
700
700
When installed in:
600
600
500
500
400
400
300
300
200
200
S D N 150 O C E 100 S 90 N 80 I E M I T
150
100 90 80
70
70
60
60
50
50
40
40
30
30
20
20
15
15
10 9
10 9
8
8
7
7
6
6
5
5
4
4
3
3
2
2
1.5
1
• Sma Smallll enclos enclosure ure (Class (Class 8536 only) only) • Motor Motor Contro Controll Cente Centerr (Class 8998, 8999, QMB, or I-Line ® ) The trip current rating can be determined from the instructions given with the appropriate thermal unit selection table. The characteristics shown do not S necessarily apply to equipment manufactured before Dthe date of the referenced drawing. N O C E S N I
E M I T
1.5
5 . 6 . 7 . 8 . 9 . 1
5 . 1
2
3
4
5
6
7
8
9 0 1
5 1
1
0 2
MULTIPLES OF TRIP CURRENT RATING
© 2005 2005 Schneider Schneider Electric all rights ghts reserved reserved
Curve No. 8536TC0316 May 2005
MULTIPLES OF TRIP CURRENT RATING 10000 9000 8000
5 . 6 . 7 . 8 . 9 . 1
5 . 1
2
3
4
5
6
7
8
0 9 1
5 1
0 2
10000 9000 8000
7000
7000
6000
6000
5000
5000
4000
4000
3000
3000
OVERLOAD RELAY TIME-CURRENT CHARACTERISTICS REFERENCE DRAWING NO. 30068-349 Relay Design
Melting Alloy
Therm hermal al Unit Unit Type ypes
B1.30–B 30–B4 4.85
40 °C ambient cold start trip time characteristics of: 2000
2000
40 ˚C (104 ˚F) AMBIENT COLD START MAXIMUM AVERAGE
1500
1500
Equipment
AC Magnetic Starter
Size
6
Type
SH
1000 900 800
Series
A
1000 900 800
Qty. of of The Therm rma al Un Units its
3
700
700
When installed in:
600
600
500
500
400
400
300
300
200
200
S D N 150 O C E 100 S 90 N 80 I E M I T
150
100 90 80
70
70
60
60
50
50
40
40
30
30
20
20
15
15
10 9
10 9
8
8
7
7
6
6
5
5
4
4
3
3
2
2
1.5
1
• Hinged Hinged door and and all other other (larger (larger)) enclosures enclosures The trip current rating can be determined from the instructions given with the appropriate thermal unit selection table. The characteristics shown do not necessarily apply to equipment manufactured before the date of the referenced drawing. S D N O C E S N I
E M I T
1.5
5 . 6 . 7 . 8 . 9 . 1
5 . 1
2
3
4
5
6
7
8
9 0 1
5 1
1
0 2
MULTIPLES OF TRIP CURRENT RATING
© 2005 2005 Schneider Schneider Electric all rights ghts reserved reserved
Curve No. 8536TC0317 May 2005
MULTIPLES OF TRIP CURRENT RATING 10000 9000 8000
5 . 6 . 7 . 8 . 9 . 1
5 . 1
2
3
4
5
6
7
8
0 9 1
5 1
0 2
10000 9000 8000
7000
7000
6000
6000
5000
5000
4000
4000
3000
3000
OVERLOAD RELAY TIME-CURRENT CHARACTERISTICS REFERENCE DRAWING NO. 30068-407 Relay Design
Melting Alloy
Therm hermal al Unit Unit Type ypes
B0.44 0.44– –B50
40 °C ambient cold start trip time characteristics of: 2000
2000
40 ˚C (104 ˚F) AMBIENT COLD START MAXIMUM AVERAGE
1500
1500
Equipment
AC Magnetic Starter
Size
0&1
Type
SB & SC
1000 900 800
Series
A
1000 900 800
Qty. of of The Therm rma al Un Units its
3
700
700
When installed in:
600
600
500
500
400
400
300
300
200
200
S D N 150 O C E 100 S 90 N 80 I E M I T
150
100 90 80
70
70
60
60
50
50
40
40
30
30
20
20
15
15
10 9
10 9
8
8
7
7
6
6
5
5
4
4
3
3
2
2
1.5
1
• Sma Smallll enclos enclosure ure (Class (Class 8536 only) only) • QMB QMB, I-L I-Lin ine e ® The trip current rating can be determined from the instructions given with the appropriate thermal unit selection table. The characteristics shown do not necessarily apply to equipment manufactured before S the date of the referenced drawing. D N O C E S N I
E M I T
1.5
5 . 6 . 7 . 8 . 9 . 1
5 . 1
2
3
4
5
6
7
8
9 0 1
5 1
1
0 2
MULTIPLES OF TRIP CURRENT RATING
© 2005 2005 Schneider Schneider Electric all rights ghts reserved reserved
Curve No. 8536TC0318 May 2005
MULTIPLES OF TRIP CURRENT RATING 10000 9000 8000
5 . 6 . 7 . 8 . 9 . 1
5 . 1
2
3
4
5
6
7
8
0 9 1
5 1
0 2
10000 9000 8000
7000
7000
6000
6000
5000
5000
4000
4000
3000
3000
OVERLOAD RELAY TIME-CURRENT CHARACTERISTICS REFERENCE DRAWING NO. 30068-408 Relay Design
Melting Alloy
Therm hermal al Unit Unit Type ypes
B0.44 0.44– –B45
40 °C ambient cold start trip time characteristics of: 2000
2000
40 C (104 F) AMBIENT COLD START MAXIMUM AVERAGE
1500
1500
Equipment
AC Magnetic Starter
Size
0&1
Type
SB & SC
1000 900 800
Series
A
1000 900 800
Qty. of of The Therm rma al Un Units its
3
700
700
When installed in:
600
600
500
500
400
400
300
300
200
200
S D N 150 O C E 100 S 90 N 80 I E M I T
150
100 90 80
70
70
60
60
50
50
40
40
30
30
20
20
15
15
10 9
10 9
8
8
7
7
6
6
5
5
4
4
3
3
2
2
1.5
1
• Hinged Hinged door and and all other other (larger (larger)) enclosures enclosures The trip current rating can be determined from the instructions given with the appropriate thermal unit selection table. The characteristics shown do not necessarily apply to equipment manufactured before the date of the referenced drawing. S D N O C E S N I
E M I T
1.5
5 . 6 . 7 . 8 . 9 . 1
5 . 1
2
3
4
5
6
7
8
9 0 1
5 1
1
0 2
MULTIPLES OF TRIP CURRENT RATING
© 2005 2005 Schneider Schneider Electric all rights ghts reserved reserved
Curve No. 8536TC0319 May 2005
MULTIPLES OF TRIP CURRENT RATING 10000 9000 8000
5 . 6 . 7 . 8 . 9 . 1
5 . 1
2
3
4
5
6
7
8
0 9 1
5 1
0 2
10000 9000 8000
7000
7000
6000
6000
5000
5000
4000
4000
3000
3000
OVERLOAD RELAY TIME-CURRENT CHARACTERISTICS REFERENCE DRAWING NO. 30068-409 Relay Design
Melting Alloy
Therm hermal al Unit Unit Type ypes
B4.85 4.85– –B88
40 °C ambient cold start trip time characteristics of: 2000
2000
40 ˚C (104 ˚F) AMBIENT COLD START MAXIMUM AVERAGE
1500
1500
Equipment
AC Magnetic Starter
Size
2
Type
SD
1000 900 800
Series
A
1000 900 800
Qty. of of The Therm rma al Un Units its
3
700
700
When installed in:
600
600
500
500
400
400
300
300
200
200
S D N 150 O C E 100 S 90 N 80 I E M I T
150
100 90 80
70
70
60
60
50
50
40
40
30
30
20
20
15
15
10 9
10 9
8
8
7
7
6
6
5
5
4
4
3
3
2
2
1.5
1
• Sma Smallll enclos enclosure ure (Class (Class 8536 only) only) • QMB QMB, I-L I-Lin ine e ® The trip current rating can be determined from the instructions given with the appropriate thermal unit selection table. The characteristics shown do not necessarily apply to equipment manufactured before S the date of the referenced drawing. D N O C E S N I
E M I T
1.5
5 . 6 . 7 . 8 . 9 . 1
5 . 1
2
3
4
5
6
7
8
9 0 1
5 1
1
0 2
MULTIPLES OF TRIP CURRENT RATING
© 2005 2005 Schneider Schneider Electric all rights ghts reserved reserved
Curve No. 8536TC0320 May 2005
MULTIPLES OF TRIP CURRENT RATING 10000 9000 8000
5 . 6 . 7 . 8 . 9 . 1
5 . 1
2
3
4
5
6
7
8
0 9 1
5 1
0 2
10000 9000 8000
7000
7000
6000
6000
5000
5000
4000
4000
3000
3000
OVERLOAD RELAY TIME-CURRENT CHARACTERISTICS REFERENCE DRAWING NO. 30068-410 Relay Design
Melting Alloy
Therm hermal al Unit Unit Type ypes
B4.85 4.85– –B79
40 °C ambient cold start trip time characteristics of: 2000
2000
40 ˚C (104 ˚F) AMBIENT COLD START MAXIMUM AVERAGE
1500
1500
Equipment
AC Magnetic Starter
Size
2
Type
SD
1000 900 800
Series
A
1000 900 800
Qty. of of The Therm rma al Un Units its
3
700
700
When installed in:
600
600
500
500
400
400
300
300
200
200
S D N 150 O C E 100 S 90 N 80 I E M I T
150
100 90 80
70
70
60
60
50
50
40
40
30
30
20
20
15
15
10 9
10 9
8
8
7
7
6
6
5
5
4
4
3
3
2
2
1.5
1
• Hinged Hinged door and and all other other (larger (larger)) enclosures enclosures The trip current rating can be determined from the instructions given with the appropriate thermal unit selection table. The characteristics shown do not necessarily apply to equipment manufactured before the date of the referenced drawing. S D N O C E S N I
E M I T
1.5
5 . 6 . 7 . 8 . 9 . 1
5 . 1
2
3
4
5
6
7
8
9 0 1
5 1
1
0 2
MULTIPLES OF TRIP CURRENT RATING
© 2005 2005 Schneider Schneider Electric all rights ghts reserved reserved
Curve No. 8536TC0321 May 2005
MULTIPLES OF TRIP CURRENT RATING 10000 9000 8000
5 . 6 . 7 . 8 . 9 . 1
5 . 1
2
3
4
5
6
7
8
0 9 1
5 1
0 2
10000 9000 8000
7000
7000
6000
6000
5000
5000
4000
4000
3000
3000
OVERLOAD RELAY TIME-CURRENT CHARACTERISTICS REFERENCE DRAWING NO. 30068-411 Relay Design
Melting alloy
Therm hermal al Unit Unit Types ypes
B0.44 0.44–B –B1 10.2 0.2
40 °C ambient cold start trip time characteristics of: 2000
2000
40 ˚C (104 ˚F) AMBIENT COLD START MAXIMUM AVERAGE
1500
1500
Equipment
Class 8736 Reversing Starter
Size
00
Type
SA
1000 900 800
Series
A
1000 900 800
Qty. of of The Therm rma al Un Units its
3
700
700
When installed in:
600
600
500
500
400
400
300
300
200
200
• Hinged Hinged door and and all other other (larger (larger)) enclosures enclosures
S D N 150 O C E 100 S 90 N 80 I E M I T
150
100 90 80
70
70
60
60
50
50
40
40
30
30
20
20
15
15
10 9
10 9
8
8
7
7
6
6
5
5
4
4
3
3
2
2
1.5
1
• Sma Smallll enclos enclosure ure (Class (Class 8736 only) only)
The trip current rating can be determined from the instructions given with the appropriate thermal unit selection table. The characteristics shown do not necessarily apply to equipment manufactured before S the date of the referenced drawing. D N O C E S N I
E M I T
1.5
5 . 6 . 7 . 8 . 9 . 1
5 . 1
2
3
4
5
6
7
8
9 0 1
5 1
1
0 2
MULTIPLES OF TRIP CURRENT RATING
© 2005 2005 Schneider Schneider Electric all rights ghts reserved reserved
Curve No. 8736TC0302 May 2005
MULTIPLES OF TRIP CURRENT RATING 10000 9000 8000
5 . 6 . 7 . 8 . 9 . 1
5 . 1
2
3
4
5
6
7
8
0 9 1
5 1
0 2
10000 9000 8000
7000
7000
6000
6000
5000
5000
4000
4000
3000
3000
2000
2000
OVERLOAD RELAY TIME-CURRENT CHARACTERISTICS REFERENCE DRAWING NO. 30068-413 Relay Design
Bimetallic, Temperature-compensated
Therm hermal al Unit Unit Type ypes
AR.44–A 44–AR R40
40 °C ambient cold start trip time characteristics of: 40 ˚C (104 ˚F) AMBIENT COLD START MAXIMUM AVERAGE
1500
1500
Equipment
AC Magnetic Starter
Size
0&1
Type
SB & SC
Series
B
Form
B
Qty. of of The Therm rma al Un Units its
3
1000 900 800
1000 900 800
700
700
600
600
500
500
400
400
• Sma Smallll enclos enclosure ure (Class (Class 8536 only) only)
300
300
• Motor Motor Contro Controll Cente Centerr (Class 8998, 8999, QMB, or I-Line ® )
200
200
S D N 150 O C E 100 S 90 N 80 I E M I T
150
100 90 80
70
70
60
60
50
50
40
40
30
30
20
20
15
15
10 9
10 9
8
8
7
7
6
6
5
5
4
4
3
3
2
2
1.5
1
When installed in:
• Hinged Hinged door and and all other other (larger (larger)) enclosures enclosures S DThe trip current rating can be determined from the N Oinstructions given with the appropriate thermal unit Cselection table. The characteristics shown do not E S necessarily apply to equipment manufactured before Nthe date of the referenced drawing. I
E NOTE:Curves NOTE: Curves also apply for Class 9065 Type SEO6B M I Series B separately mounted overload relays. T
1.5
5 . 6 . 7 . 8 . 9 . 1
5 . 1
2
3
4
5
6
7
8
9 0 1
5 1
1
0 2
MULTIPLES OF TRIP CURRENT RATING
© 2005 2005 Schneider Schneider Electric all rights ghts reserved reserved
Curve No. 8536TC0322 May 2005
MULTIPLES OF TRIP CURRENT RATING 10000 9000 8000
5 . 6 . 7 . 8 . 9 . 1
5 . 1
2
3
4
5
6
7
8
0 9 1
5 1
0 2
10000 9000 8000
7000
7000
6000
6000
5000
5000
4000
4000
3000
3000
2000
2000
OVERLOAD RELAY TIME-CURRENT CHARACTERISTICS REFERENCE DRAWING NO. 30068-414 Relay Design
Bimetallic, Temperature-compensated
Therm hermal al Unit Unit Types ypes
AR8.5– 8.5–A AR94
40 °C ambient cold start trip time characteristics of: 40 ˚C (104 ˚F) AMBIENT COLD START MAXIMUM AVERAGE
1500
1500
Equipment
AC Magnetic Starter
Size
2
Type
SD
Series
A
Form
B
Qty. of of The Therm rma al Un Units its
3
1000 900 800
1000 900 800
700
700
600
600
500
500
400
400
• Sma Smallll enclos enclosure ure (Class (Class 8536 only) only)
300
300
• Motor Motor Contro Controll Cente Centerr (Class 8998, 8999, QMB, or I-Line ® )
200
200
S D N 150 O C E 100 S 90 N 80 I E M I T
150
100 90 80
70
70
60
60
50
50
40
40
30
30
20
20
15
15
10 9
10 9
8
8
7
7
6
6
5
5
4
4
3
3
2
2
1.5
1
When installed in:
• Hinged Hinged door and and all other other (larger (larger)) enclosures enclosures S DThe trip current rating can be determined from the N Oinstructions given with the appropriate thermal unit Cselection table. The characteristics shown do not E S necessarily apply to equipment manufactured before Nthe date of the referenced drawing. I
E NOTE:Curves NOTE: Curves also apply for Class 9065 Type SEO9B M I Series A separately mounted overload relays. T
1.5
5 . 6 . 7 . 8 . 9 . 1
5 . 1
2
3
4
5
6
7
8
9 0 1
5 1
1
0 2
MULTIPLES OF TRIP CURRENT RATING
© 2005 2005 Schneider Schneider Electric all rights ghts reserved reserved
Curve No. 8536TC0323 May 2005
MULTIPLES OF TRIP CURRENT RATING 10000 9000 8000
5 . 6 . 7 . 8 . 9 . 1
5 . 1
2
3
4
5
6
7
8
0 9 1
5 1
0 2
10000 9000 8000
7000
7000
6000
6000
5000
5000
4000
4000
3000
3000
OVERLOAD RELAY TIME-CURRENT CHARACTERISTICS REFERENCE DRAWING NO. 30068-415 Relay Design
Bimetallic
Therm hermal al Unit Unit Type ypes
AR.45–A 45–AR R40
40 °C ambient cold start trip time characteristics of: 2000
2000
40 ˚C (104 ˚F) AMBIENT COLD START MAXIMUM AVERAGE
1500
1500
1000 900 800
1000 900 800
700
700
600
600
500
500
400
400
300
300
200
200 150
100 90 80
70
70
60
60
50
50
40
40
30
30
20
20
15
15
10 9
10 9
8
8
7
7
6
6
5
5
4
4
3
3
2
2
1.5
1
AC Magnetic Starter
Size
0&1
Type
SB & SC
Series
A
Form
B2
Qty. of of The Therm rma al Un Units its
3
When installed in: • Sma Smallll enclos enclosure ure (Class (Class 8536 only) only)
S D N 150 O C E 100 S 90 N 80 I E M I T
Equipment
• Motor Motor Contro Controll Cente Centerr (Class 8998, 8999, QMB, or I-Line ® ) The trip current rating can be determined from the instructions given with the appropriate thermal unit S Dselection table. The characteristics shown do not Nnecessarily apply to equipment manufactured before Othe date of the referenced drawing. C E S N I
E M I T
1.5
5 . 6 . 7 . 8 . 9 . 1
5 . 1
2
3
4
5
6
7
8
9 0 1
5 1
1
0 2
MULTIPLES OF TRIP CURRENT RATING
© 2005 2005 Schneider Schneider Electric all rights ghts reserved reserved
Curve No. 8536TC0324 May 2005
MULTIPLES OF TRIP CURRENT RATING 10000 9000 8000
5 . 6 . 7 . 8 . 9 . 1
5 . 1
2
3
4
5
6
7
8
0 9 1
5 1
0 2
10000 9000 8000
7000
7000
6000
6000
5000
5000
4000
4000
3000
3000
OVERLOAD RELAY TIME-CURRENT CHARACTERISTICS REFERENCE DRAWING NO. 30068-416 Relay Design
Bimetallic
Therm hermal al Unit Unit Type ypes
AR.45–A 45–AR R40
40 °C ambient cold start trip time characteristics of: 2000
2000
40 ˚C (104 ˚F) AMBIENT COLD START MAXIMUM AVERAGE
1500
1500
1000 900 800
1000 900 800
700
700
600
600
500
500
400
400
300
300
200
200 150
100 90 80
70
70
60
60
50
50
40
40
30
30
20
20
15
15
10 9
10 9
8
8
7
7
6
6
5
5
4
4
3
3
2
2
1.5
1
AC Magnetic Starter
Size
0&1
Type
SB & SC
Series
A
Form
B2
Qty. of of The Therm rma al Un Units its
3
When installed in: • Hinged Hinged door and and all other other (larger (larger)) enclosures enclosures
S D N 150 O C E 100 S 90 N 80 I E M I T
Equipment
The trip current rating can be determined from the instructions given with the appropriate thermal unit selection table. The characteristics shown do not necessarily apply to equipment manufactured before S the date of the referenced drawing. D N O C E S N I
E M I T
1.5
5 . 6 . 7 . 8 . 9 . 1
5 . 1
2
3
4
5
6
7
8
9 0 1
5 1
1
0 2
MULTIPLES OF TRIP CURRENT RATING
© 2005 2005 Schneider Schneider Electric all rights ghts reserved reserved
Curve No. 8536TC0325 May 2005
MULTIPLES OF TRIP CURRENT RATING 10000 9000 8000
5 . 6 . 7 . 8 . 9 . 1
5 . 1
2
3
4
5
6
7
8
0 9 1
5 1
0 2
10000 9000 8000
7000
7000
6000
6000
5000
5000
4000
4000
3000
3000
OVERLOAD RELAY TIME-CURRENT CHARACTERISTICS REFERENCE DRAWING NO. 30068-417 Relay Design
Bimetallic
Therm hermal al Unit Unit Types ypes
AR8.5– 8.5–A AR86
40 °C ambient cold start trip time characteristics of: 2000
2000
40 ˚C (104 ˚F) AMBIENT COLD START MAXIMUM AVERAGE
1500
1500
1000 900 800
1000 900 800
700
700
600
600
500
500
400
400
300
300
200
200 150
100 90 80
70
70
60
60
50
50
40
40
30
30
20
20
15
15
10 9
10 9
8
8
7
7
6
6
5
5
4
4
3
3
2
2
1.5
1
AC Magnetic Starter
Size
2
Type
SD
Series
A
Form
B2
Qty. of of The Therm rma al Un Units its
3
When installed in: • Sma Smallll enclos enclosure ure (Class (Class 8536 only) only)
S D N 150 O C E 100 S 90 N 80 I E M I T
Equipment
• Motor Motor Contro Controll Cente Centerr (Class 8998, 8999, QMB, or I-Line ® ) The trip current rating can be determined from the instructions given with the appropriate thermal unit S Dselection table. The characteristics shown do not Nnecessarily apply to equipment manufactured before Othe date of the referenced drawing. C E S N I
E M I T
1.5
5 . 6 . 7 . 8 . 9 . 1
5 . 1
2
3
4
5
6
7
8
9 0 1
5 1
1
0 2
MULTIPLES OF TRIP CURRENT RATING
© 2005 2005 Schneider Schneider Electric all rights ghts reserved reserved
Curve No. 8536TC0326 May 2005
MULTIPLES OF TRIP CURRENT RATING 10000 9000 8000
5 . 6 . 7 . 8 . 9 . 1
5 . 1
2
3
4
5
6
7
8
0 9 1
5 1
0 2
10000 9000 8000
7000
7000
6000
6000
5000
5000
4000
4000
3000
3000
OVERLOAD RELAY TIME-CURRENT CHARACTERISTICS REFERENCE DRAWING NO. 30068-418 Relay Design
Bimetallic
Therm hermal al Unit Unit Types ypes
AR8.5– 8.5–A AR86
40 °C ambient cold start trip time characteristics of: 2000
2000
40 ˚C (104 ˚F) AMBIENT COLD START MAXIMUM AVERAGE
1500
1500
1000 900 800
1000 900 800
700
700
600
600
500
500
400
400
300
300
200
200 150
100 90 80
70
70
60
60
50
50
40
40
30
30
20
20
15
15
10 9
10 9
8
8
7
7
6
6
5
5
4
4
3
3
2
2
1.5
1
AC Magnetic Starter
Size
2
Type
SD
Series
A
Form
B2
Qty. of of The Therm rma al Un Units its
3
When installed in: • Hinged Hinged door and and all other other (larger (larger)) enclosures enclosures
S D N 150 O C E 100 S 90 N 80 I E M I T
Equipment
The trip current rating can be determined from the instructions given with the appropriate thermal unit selection table. The characteristics shown do not necessarily apply to equipment manufactured before S the date of the referenced drawing. D N O C E S N I
E M I T
1.5
5 . 6 . 7 . 8 . 9 . 1
5 . 1
2
3
4
5
6
7
8
9 0 1
5 1
1
0 2
MULTIPLES OF TRIP CURRENT RATING
© 2005 2005 Schneider Schneider Electric all rights ghts reserved reserved
Curve No. 8536TC0327 May 2005
MULTIPLES OF TRIP CURRENT RATING 10000 9000 8000
5 . 6 . 7 . 8 . 9 . 1
5 . 1
2
3
4
5
6
7
8
0 9 1
5 1
0 2
10000 9000 8000
7000
7000
6000
6000
5000
5000
4000
4000
3000
3000
OVERLOAD RELAY TIME-CURRENT CHARACTERISTICS REFERENCE DRAWING NO. 30068-419A Relay Design
Bimetallic
Therm hermal al Unit Unit Type ypes
AR.45–A 45–AR R35
40 °C ambient cold start trip time characteristics of: 2000
2000
40 ˚C (104 ˚F) AMBIENT COLD START MAXIMUM AVERAGE
1500
1500
Equipment
Separate Overload Relay
Size
26 A (nominal)
Type
SEO6B2
1000 900 800
Series
A
1000 900 800
Qty. of of The Therm rma al Un Units its
3
700
700
When installed in:
600
600
500
500
400
400
300
300
200
200
S D N 150 O C E 100 S 90 N 80 I E M I T
150
100 90 80
70
70
60
60
50
50
40
40
30
30
20
20
15
15
10 9
10 9
8
8
7
7
6
6
5
5
4
4
3
3
2
2
1.5
1
• Hinged Hinged door and and all other other (larger (larger)) enclosures enclosures The trip current rating can be determined from the instructions given with the appropriate thermal unit selection table. The characteristics shown do not necessarily apply to equipment manufactured before the date of the referenced drawing. S D N O C E S N I
E M I T
1.5
5 . 6 . 7 . 8 . 9 . 1
5 . 1
2
3
4
5
6
7
8
9 0 1
5 1
1
0 2
MULTIPLES OF TRIP CURRENT RATING
© 2005 2005 Schneider Schneider Electric all rights ghts reserved reserved
Curve No. 9065TC0306 May 2005
MULTIPLES OF TRIP CURRENT RATING 10000 9000 8000
5 . 6 . 7 . 8 . 9 . 1
5 . 1
2
3
4
5
6
7
8
0 9 1
5 1
0 2
10000 9000 8000
7000
7000
6000
6000
5000
5000
4000
4000
3000
3000
OVERLOAD RELAY TIME-CURRENT CHARACTERISTICS REFERENCE DRAWING NO. 30068-420 Relay Design
Bimetallic
Therm hermal al Unit Unit Types ypes
AR8.5– 8.5–A AR86
40 °C ambient cold start trip time characteristics of: 2000
2000
40 ˚C (104 ˚F) AMBIENT COLD START MAXIMUM AVERAGE
1500
1500
Equipment
Separate Overload Relay
Size
45 A (nominal)
Type
SEO9B2
1000 900 800
Series
A
1000 900 800
Qty. of of The Therm rma al Un Units its
3
700
700
When installed in:
600
600
500
500
400
400
300
300
200
200
S D N 150 O C E 100 S 90 N 80 I E M I T
150
100 90 80
70
70
60
60
50
50
40
40
30
30
20
20
15
15
10 9
10 9
8
8
7
7
6
6
5
5
4
4
3
3
2
2
1.5
1
• Hinged Hinged door and and all other other (larger (larger)) enclosures enclosures The trip current rating can be determined from the instructions given with the appropriate thermal unit selection table. The characteristics shown do not necessarily apply to equipment manufactured before the date of the referenced drawing. S D N O C E S N I
E M I T
1.5
5 . 6 . 7 . 8 . 9 . 1
5 . 1
2
3
4
5
6
7
8
9 0 1
5 1
1
0 2
MULTIPLES OF TRIP CURRENT RATING
© 2005 2005 Schneider Schneider Electric all rights ghts reserved reserved
Curve No. 9065TC0307 May 2005
MULTIPLES OF TRIP CURRENT RATING 10000 9000 8000
5 . 6 . 7 . 8 . 9 . 1
5 . 1
2
3
4
5
6
7
8
0 9 1
5 1
0 2
10000 9000 8000
7000
7000
6000
6000
5000
5000
4000
4000
3000
3000
OVERLOAD RELAY TIME-CURRENT CHARACTERISTICS REFERENCE DRAWING NO. 30068-421 Relay Design
Bimetallic
Therm herma al Uni Unitt Types pes
AR.45– 45–AR9. R9.3
40 °C ambient cold start trip time characteristics of: 2000
2000
40 ˚C (104 ˚F) AMBIENT COLD START MAXIMUM AVERAGE
1500
1500
1000 900 800
1000 900 800
700
700
600
600
500
500
400
400
300
300
200
200
150
100 90 80
70
70
60
60
50
50
40
40
30
30
20
20
15
15
10 9
10 9
8
8
7
7
6
6
5
5
4
4
3
3
2
2
1.5
1
Class 8736 Reversing Starter
Size
00
Type
SA
Series
A
Form
B2
Qty. of of The Therm rma al Un Units its
3
When installed in: • Sma Smallll enclos enclosure ure (Class (Class 8736 only) only)
S D N 150 O C E 100 S 90 N 80 I E M I T
Equipment
• Hinged Hinged door and and all other other (larger (larger)) enclosures enclosures The trip current rating can be determined from the instructions given with the appropriate thermal unit selection table. The characteristics shown do not S Dnecessarily apply to equipment manufactured before Nthe date of the referenced drawing. O C E S N I
E M I T
1.5
5 . 6 . 7 . 8 . 9 . 1
5 . 1
2
3
4
5
6
7
8
9 0 1
5 1
1
0 2
MULTIPLES OF TRIP CURRENT RATING
© 2005 2005 Schneider Schneider Electric all rights ghts reserved reserved
Curve No. 8736TC0303 May 2005
MULTIPLES OF TRIP CURRENT RATING 10000 9000 8000
5 . 6 . 7 . 8 . 9 . 1
5 . 1
2
3
4
5
6
7
8
0 9 1
5 1
0 2
10000 9000 8000
7000
7000
6000
6000
5000
5000
4000
4000
3000
3000
2000
2000
OVERLOAD RELAY TIME-CURRENT CHARACTERISTICS REFERENCE DRAWING NO. 30068-422 Relay Design
Bimetallic, Temperature-compensated
Therm hermal al Unit Unit Type ypes
AR.45–A 45–AR R10. 10.2
40 °C ambient cold start trip time characteristics of: 40 ˚C (104 ˚F) AMBIENT COLD START MAXIMUM AVERAGE
1500
1500
Equipment
Class 8736 Reversing Starter
Size
00
Type
SA
Series
A
Form
B
Qty. of of The Therm rma al Un Units its
3
1000 900 800
1000 900 800
700
700
600
600
500
500
400
400
• Sma Smallll enclos enclosure ure (Class (Class 8736 only) only)
300
300
• Hinged Hinged door and and all other other (larger (larger)) enclosures enclosures
200
200
S D N 150 O C E 100 S 90 N 80 I E M I T
150
100 90 80
70
70
60
60
50
50
40
40
30
30
20
20
15
15
10 9
10 9
8
8
7
7
6
6
5
5
4
4
3
3
2
2
1.5
1
When installed in:
The trip current rating can be determined from the instructions given with the appropriate thermal unit S Dselection table. The characteristics shown do not Nnecessarily apply to equipment manufactured before Othe date of the referenced drawing. C E S N I
E M I T
1.5
5 . 6 . 7 . 8 . 9 . 1
5 . 1
2
3
4
5
6
7
8
9 0 1
5 1
1
0 2
MULTIPLES OF TRIP CURRENT RATING
© 2005 2005 Schneider Schneider Electric all rights ghts reserved reserved
Curve No. 8736TC0304 May 2005
MULTIPLES OF TRIP CURRENT RATING 10000 9000 8000
5 . 6 . 7 . 8 . 9 . 1
5 . 1
2
3
4
5
6
7
8
0 9 1
5 1
0 2
10000 9000 8000
7000
7000
6000
6000
5000
5000
4000
4000
3000
3000
OVERLOAD RELAY TIME-CURRENT CHARACTERISTICS REFERENCE DRAWING NO. 30068-423 Relay Design
Bimetallic
Therm hermal al Unit Unit Type ypes
AU44–A 44–AU2 U235 35
40 °C ambient cold start trip time characteristics of: 2000
2000
40 ˚C (104 ˚F) AMBIENT COLD START MAXIMUM AVERAGE
1500
1500
1000 900 800
1000 900 800
700
700
600
600
500
500
400
400
300
300
200
200 150
100 90 80
70
70
60
60
50
50
40
40
30
30
20
20
15
15
10 9
10 9
8
8
7
7
6
6
5
5
4
4
3
3
2
2
1.5
1
AC Magnetic Starter
Size
4
Type
SF
Series
A
Form
B5
Qty. of of The Therm rma al Un Units its
3
When installed in: • Sma Smallll enclos enclosure ure (Class (Class 8536 only) only)
S D N 150 O C E 100 S 90 N 80 I E M I T
Equipment
• Motor Motor Contro Controll Cente Centerr (Class 8998, 8999, QMB, or I-Line ® ) The trip current rating can be determined from the instructions given with the appropriate thermal unit S Dselection table. The characteristics shown do not Nnecessarily apply to equipment manufactured before Othe date of the referenced drawing. C E S N I
E M I T
1.5
5 . 6 . 7 . 8 . 9 . 1
5 . 1
2
3
4
5
6
7
8
9 0 1
5 1
1
0 2
MULTIPLES OF TRIP CURRENT RATING
© 2005 2005 Schneider Schneider Electric all rights ghts reserved reserved
Curve No. 8536TC0328 May 2005
MULTIPLES OF TRIP CURRENT RATING 10000 9000 8000
5 . 6 . 7 . 8 . 9 . 1
5 . 1
2
3
4
5
6
7
8
0 9 1
5 1
0 2
10000 9000 8000
7000
7000
6000
6000
5000
5000
4000
4000
3000
3000
OVERLOAD RELAY TIME-CURRENT CHARACTERISTICS REFERENCE DRAWING NO. 30068-424 Relay Design
Bimetallic
Therm hermal al Unit Unit Type ypes
AU44–A 44–AU1 U183 83
40 °C ambient cold start trip time characteristics of: 2000
2000
40 ˚C (104 ˚F) AMBIENT COLD START MAXIMUM AVERAGE
1500
1500
1000 900 800
1000 900 800
700
700
600
600
500
500
400
400
300
300
200
200 150
100 90 80
70
70
60
60
50
50
40
40
30
30
20
20
15
15
10 9
10 9
8
8
7
7
6
6
5
5
4
4
3
3
2
2
1.5
1
AC Magnetic Starter
Size
4
Type
SF
Series
A
Form
B5
Qty. of of The Therm rma al Un Units its
3
When installed in: • Hinged Hinged door and and all other other (larger (larger)) enclosures enclosures
S D N 150 O C E 100 S 90 N 80 I E M I T
Equipment
The trip current rating can be determined from the instructions given with the appropriate thermal unit selection table. The characteristics shown do not necessarily apply to equipment manufactured before S the date of the referenced drawing. D N O C E S N I
E M I T
1.5
5 . 6 . 7 . 8 . 9 . 1
5 . 1
2
3
4
5
6
7
8
9 0 1
5 1
1
0 2
MULTIPLES OF TRIP CURRENT RATING
© 2005 2005 Schneider Schneider Electric all rights ghts reserved reserved
Curve No. 8536TC0329 May 2005
MULTIPLES OF TRIP CURRENT RATING 10000 9000 8000
5 . 6 . 7 . 8 . 9 . 1
5 . 1
2
3
4
5
6
7
8
0 9 1
5 1
0 2
10000 9000 8000
7000
7000
6000
6000
5000
5000
4000
4000
3000
3000
OVERLOAD RELAY TIME-CURRENT CHARACTERISTICS REFERENCE DRAWING NO. 30068-426 Relay Design
Bimetallic
Therm hermal al Unit Unit Type ypes
AU44–A 44–AU1 U152 52
40 °C ambient cold start trip time characteristics of: 2000
2000
40 ˚C (104 ˚F) AMBIENT COLD START MAXIMUM AVERAGE
1500
1500
Equipment
Separate Overload Relay
Size
4
Type
SAF & AF
1000 900 800
Series
A
1000 900 800
Qty. of of The Therm rma al Un Units its
1
700
700
When installed in:
600
600
500
500
400
400
300
300
200
200
S D N 150 O C E 100 S 90 N 80 I E M I T
150
100 90 80
70
70
60
60
50
50
40
40
30
30
20
20
15
15
10 9
10 9
8
8
7
7
6
6
5
5
4
4
3
3
2
2
1.5
1
• Hinged Hinged door and and all other other (larger (larger)) enclosures enclosures The trip current rating can be determined from the instructions given with the appropriate thermal unit selection table. The characteristics shown do not necessarily apply to equipment manufactured before the date of the referenced drawing. S D N O C E S N I
E M I T
1.5
5 . 6 . 7 . 8 . 9 . 1
5 . 1
2
3
4
5
6
7
8
9 0 1
5 1
1
0 2
MULTIPLES OF TRIP CURRENT RATING
© 2005 2005 Schneider Schneider Electric all rights ghts reserved reserved
Curve No. 9065TC0308 May 2005
MULTIPLES OF TRIP CURRENT RATING 10000 9000 8000
5 . 6 . 7 . 8 . 9 . 1
5 . 1
2
3
4
5
6
7
8
0 9 1
5 1
0 2
10000 9000 8000
7000
7000
6000
6000
5000
5000
4000
4000
3000
3000
OVERLOAD RELAY TIME-CURRENT CHARACTERISTICS REFERENCE DRAWING NO. 30068-427 Relay Design
Bimetallic
Therm hermal al Unit Unit Type ypes
AU44–A 44–AU1 U152 52
40 °C ambient cold start trip time characteristics of: 2000
2000
40 ˚C (104 ˚F) AMBIENT COLD START MAXIMUM AVERAGE
1500
1500
Equipment
Separate Overload Relay
Size
4
Type
SAF & AF
1000 900 800
Series
A
1000 900 800
Qty. of of The Therm rma al Un Units its
1
700
700
When installed in:
600
600
500
500
400
400
300
300
200
200
S D N 150 O C E 100 S 90 N 80 I E M I T
150
100 90 80
70
70
60
60
50
50
40
40
30
30
20
20
15
15
10 9
10 9
8
8
7
7
6
6
5
5
4
4
3
3
2
2
1.5
1
• Sma Smallll enclos enclosure ure (Class (Class 9065 only) only) The trip current rating can be determined from the instructions given with the appropriate thermal unit selection table. The characteristics shown do not necessarily apply to equipment manufactured before the date of the referenced drawing. S D N O C E S N I
E M I T
1.5
5 . 6 . 7 . 8 . 9 . 1
5 . 1
2
3
4
5
6
7
8
9 0 1
5 1
1
0 2
MULTIPLES OF TRIP CURRENT RATING
© 2005 2005 Schneider Schneider Electric all rights ghts reserved reserved
Curve No. 9065TC0309 May 2005
MULTIPLES OF TRIP CURRENT RATING 10000 9000 8000
5 . 6 . 7 . 8 . 9 . 1
5 . 1
2
3
4
5
6
7
8
0 9 1
5 1
0 2
10000 9000 8000
7000
7000
6000
6000
5000
5000
4000
4000
3000
3000
OVERLOAD RELAY TIME-CURRENT CHARACTERISTICS REFERENCE DRAWING NO. 30068-438 Relay Design
Bimetallic
Therm hermal al Unit Unit Type ypes
AU20–A 20–AU1 U123 23
40 °C ambient cold start trip time characteristics of: 2000
2000
40 ˚C (104 ˚F) AMBIENT COLD START MAXIMUM AVERAGE
1500
1500
1000 900 800
1000 900 800
700
700
600
600
500
500
400
400
300
300
200
200 150
100 90 80
70
70
60
60
50
50
40
40
30
30
20
20
15
15
10 9
10 9
8
8
7
7
6
6
5
5
4
4
3
3
2
2
1.5
1
AC Magnetic Starter
Size
3
Type
SE
Series
A
Form
B5
Qty. of of The Therm rma al Un Units its
3
When installed in: • Sma Smallll enclos enclosure ure (Class (Class 8536 only) only)
S D N 150 O C E 100 S 90 N 80 I E M I T
Equipment
• Motor Motor Contro Controll Cente Centerr (Class 8998, 8999, QMB, or I-Line ® ) The trip current rating can be determined from the instructions given with the appropriate thermal unit S Dselection table. The characteristics shown do not Nnecessarily apply to equipment manufactured before Othe date of the referenced drawing. C E S N I
E M I T
1.5
5 . 6 . 7 . 8 . 9 . 1
5 . 1
2
3
4
5
6
7
8
9 0 1
5 1
1
0 2
MULTIPLES OF TRIP CURRENT RATING
© 2005 2005 Schneider Schneider Electric all rights ghts reserved reserved
Curve No. 8536TC0330 May 2005
MULTIPLES OF TRIP CURRENT RATING 10000 9000 8000
5 . 6 . 7 . 8 . 9 . 1
5 . 1
2
3
4
5
6
7
8
0 9 1
5 1
0 2
10000 9000 8000
7000
7000
6000
6000
5000
5000
4000
4000
3000
3000
OVERLOAD RELAY TIME-CURRENT CHARACTERISTICS REFERENCE DRAWING NO. 30068-439 Relay Design
Bimetallic
Therm hermal al Unit Unit Type ypes
AU20–A 20–AU1 U110 10
40 °C ambient cold start trip time characteristics of: 2000
2000
40 ˚C (104 ˚F) AMBIENT COLD START MAXIMUM AVERAGE
1500
1500
1000 900 800
1000 900 800
700
700
600
600
500
500
400
400
300
300
200
200 150
100 90 80
70
70
60
60
50
50
40
40
30
30
20
20
15
15
10 9
10 9
8
8
7
7
6
6
5
5
4
4
3
3
2
2
1.5
1
AC Magnetic Starter
Size
3
Type
SE
Series
A
Form
B5
Qty. of of The Therm rma al Un Units its
3
When installed in: • Hinged Hinged door and and all other other (larger (larger)) enclosures enclosures
S D N 150 O C E 100 S 90 N 80 I E M I T
Equipment
The trip current rating can be determined from the instructions given with the appropriate thermal unit selection table. The characteristics shown do not necessarily apply to equipment manufactured before S the date of the referenced drawing. D N O C E S N I
E M I T
1.5
5 . 6 . 7 . 8 . 9 . 1
5 . 1
2
3
4
5
6
7
8
9 0 1
5 1
1
0 2
MULTIPLES OF TRIP CURRENT RATING
© 2005 2005 Schneider Schneider Electric all rights ghts reserved reserved
Curve No. 8536TC0331 May 2005
MULTIPLES OF TRIP CURRENT RATING 10000 9000 8000
5 . 6 . 7 . 8 . 9 . 1
5 . 1
2
3
4
5
6
7
8
0 9 1
5 1
0 2
10000 9000 8000
7000
7000
6000
6000
5000
5000
4000
4000
3000
3000
OVERLOAD RELAY TIME-CURRENT CHARACTERISTICS REFERENCE DRAWING NO. 30068-443 Relay Design
Melting Alloy
Therm herma al Unit nit Types pes
A.49–A 9–A11.0
40 °C ambient cold start trip time characteristics of: 2000
2000
40 ˚C (104 ˚F) AMBIENT COLD START MAXIMUM AVERAGE
1500
1500
Equipment
AC Magnetic Starter
Size
00
Type
A
1000 900 800
Series
B&C
1000 900 800
Qty. of of The Therm rma al Un Units its
1
700
700
When installed in:
600
600
500
500
400
400
300
300
200
200
S D N 150 O C E 100 S 90 N 80 I E M I T
150
100 90 80
70
70
60
60
50
50
40
40
30
30
20
20
15
15
10 9
10 9
8
8
7
7
6
6
5
5
4
4
3
3
2
2
1.5
1
• Hinged Hinged door and and all other other (larger (larger)) enclosures enclosures The trip current rating can be determined from the instructions given with the appropriate thermal unit selection table. The characteristics shown do not necessarily apply to equipment manufactured before the date of the referenced drawing. S D N O C E S N I
E M I T
1.5
5 . 6 . 7 . 8 . 9 . 1
5 . 1
2
3
4
5
6
7
8
9 0 1
5 1
1
0 2
MULTIPLES OF TRIP CURRENT RATING
© 2005 2005 Schneider Schneider Electric all rights ghts reserved reserved
Curve No. 8536TC0332 May 2005
MULTIPLES OF TRIP CURRENT RATING 10000 9000 8000
5 . 6 . 7 . 8 . 9 . 1
5 . 1
2
3
4
5
6
7
8
0 9 1
5 1
0 2
10000 9000 8000
7000
7000
6000
6000
5000
5000
4000
4000
3000
3000
OVERLOAD RELAY TIME-CURRENT CHARACTERISTICS REFERENCE DRAWING NO. 30068-444 Relay Design
Melting Alloy
Therm herma al Unit nit Types pes
A.49–A 9–A11.0
40 °C ambient cold start trip time characteristics of: 2000
2000
40 ˚C (104 ˚F) AMBIENT COLD START MAXIMUM AVERAGE
1500
1500
Equipment
AC Magnetic Starter
Size
00
Type
A
1000 900 800
Series
B&C
1000 900 800
Qty. of of The Therm rma al Un Units its
1
700
700
When installed in:
600
600
500
500
400
400
300
300
200
200
S D N 150 O C E 100 S 90 N 80 I E M I T
150
100 90 80
70
70
60
60
50
50
40
40
30
30
20
20
15
15
10 9
10 9
8
8
7
7
6
6
5
5
4
4
3
3
2
2
1.5
1
• Sma Smallll enclos enclosure ure (Class (Class 8536 only) only) The trip current rating can be determined from the instructions given with the appropriate thermal unit selection table. The characteristics shown do not necessarily apply to equipment manufactured before the date of the referenced drawing. S D N O C E S N I
E M I T
1.5
5 . 6 . 7 . 8 . 9 . 1
5 . 1
2
3
4
5
6
7
8
9 0 1
5 1
1
0 2
MULTIPLES OF TRIP CURRENT RATING
© 2005 2005 Schneider Schneider Electric all rights ghts reserved reserved
Curve No. 8536TC0333 May 2005
MULTIPLES OF TRIP CURRENT RATING 10000 9000 8000
5 . 6 . 7 . 8 . 9 . 1
5 . 1
2
3
4
5
6
7
8
0 9 1
5 1
0 2
10000 9000 8000
7000
7000
6000
6000
5000
5000
4000
4000
3000
3000
OVERLOAD RELAY TIME-CURRENT CHARACTERISTICS REFERENCE DRAWING NO. 30068-445 Relay Design
Melting Alloy
Therm herma al Unit nit Types pes
A.49–A 9–A11.0
40 °C ambient cold start trip time characteristics of: 2000
2000
40 ˚C (104 ˚F) AMBIENT COLD START MAXIMUM AVERAGE
1500
1500
Equipment
AC Magnetic Starter
Size
00
Type
A
1000 900 800
Series
C
1000 900 800
Qty. of of The Therm rma al Un Units its
3
700
700
When installed in:
600
600
500
500
400
400
300
300
200
200
S D N 150 O C E 100 S 90 N 80 I E M I T
150
100 90 80
70
70
60
60
50
50
40
40
30
30
20
20
15
15
10 9
10 9
8
8
7
7
6
6
5
5
4
4
3
3
2
2
1.5
1
• Sma Smallll enclos enclosure ure (Class (Class 8536 only) only) The trip current rating can be determined from the instructions given with the appropriate thermal unit selection table. The characteristics shown do not necessarily apply to equipment manufactured before the date of the referenced drawing. S D N O C E S N I
E M I T
1.5
5 . 6 . 7 . 8 . 9 . 1
5 . 1
2
3
4
5
6
7
8
9 0 1
5 1
1
0 2
MULTIPLES OF TRIP CURRENT RATING
© 2005 2005 Schneider Schneider Electric all rights ghts reserved reserved
Curve No. 8536TC0334 May 2005
MULTIPLES OF TRIP CURRENT RATING 10000 9000 8000
5 . 6 . 7 . 8 . 9 . 1
5 . 1
2
3
4
5
6
7
8
0 9 1
5 1
0 2
10000 9000 8000
7000
7000
6000
6000
5000
5000
4000
4000
3000
3000
OVERLOAD RELAY TIME-CURRENT CHARACTERISTICS REFERENCE DRAWING NO. 30068-446 Relay Design
Melting Alloy
Therm herma al Unit nit Types pes
A.49–A 49–A9 9.85
40 °C ambient cold start trip time characteristics of: 2000
2000
40 ˚C (104 ˚F) AMBIENT COLD START MAXIMUM AVERAGE
1500
1500
Equipment
AC Magnetic Starter
Size
00
Type
A
1000 900 800
Series
C
1000 900 800
Qty. of of The Therm rma al Un Units its
3
700
700
When installed in:
600
600
500
500
400
400
300
300
200
200
S D N 150 O C E 100 S 90 N 80 I E M I T
150
100 90 80
70
70
60
60
50
50
40
40
30
30
20
20
15
15
10 9
10 9
8
8
7
7
6
6
5
5
4
4
3
3
2
2
1.5
1
• Hinged Hinged door and and all other other (larger (larger)) enclosures enclosures The trip current rating can be determined from the instructions given with the appropriate thermal unit selection table. The characteristics shown do not necessarily apply to equipment manufactured before the date of the referenced drawing. S D N O C E S N I
E M I T
1.5
5 . 6 . 7 . 8 . 9 . 1
5 . 1
2
3
4
5
6
7
8
9 0 1
5 1
1
0 2
MULTIPLES OF TRIP CURRENT RATING
© 2005 2005 Schneider Schneider Electric all rights ghts reserved reserved
Curve No. 8536TC0335 May 2005
MULTIPLES OF TRIP CURRENT RATING 10000 9000 8000
5 . 6 . 7 . 8 . 9 . 1
5 . 1
2
3
4
5
6
7
8
0 9 1
5 1
0 2
10000 9000 8000
7000
7000
6000
6000
5000
5000
4000
4000
3000
3000
OVERLOAD RELAY TIME-CURRENT CHARACTERISTICS REFERENCE DRAWING NO. 30068-447 Relay Design
Melting Alloy
Therm herma al Unit nit Types pes
A.49–A 9–A25.2
40 °C ambient cold start trip time characteristics of: 2000
2000
40 ˚C (104 ˚F) AMBIENT COLD START MAXIMUM AVERAGE
1500
1500
1000 900 800
1000 900 800
700
700
600
600
500
500
400
400
300
300
200
200
S D N 150 O C E 100 S 90 N 80 I E M I T
150
100 90 80
70
70
60
60
50
50
40
40
30
30
20
20
15
15
10 9
10 9
8
8
7
7
6
6
5
5
4
4
3
3
2
2
1.5
1
Equipment
AC Manual Star ter
Size
FHP
Type
F
Qty. of of The Therm rma al Un Units its
1
When installed in: • Sma Smallll enclos enclosure ure (Class (Class 2510 only) only) • Hinged Hinged door and and all other other (larger (larger)) enclosures enclosures The trip current rating can be determined from the instructions given with the appropriate thermal unit selection table. The characteristics shown do not necessarily apply to equipment manufactured before the date of the referenced drawing. S D N O C E S N I
E M I T
1.5
5 . 6 . 7 . 8 . 9 . 1
5 . 1
2
3
4
5
6
7
8
9 0 1
5 1
1
0 2
MULTIPLES OF TRIP CURRENT RATING
© 2005 2005 Schneider Schneider Electric all rights ghts reserved reserved
Curve No. 2510TC0304 May 2005
MULTIPLES OF TRIP CURRENT RATING 10000 9000 8000
5 . 6 . 7 . 8 . 9 . 1
5 . 1
2
3
4
5
6
7
8
0 9 1
5 1
0 2
10000 9000 8000
7000
7000
6000
6000
5000
5000
4000
4000
3000
3000
OVERLOAD RELAY TIME-CURRENT CHARACTERISTICS REFERENCE DRAWING NO. 30068-450 Relay Design
Melting Alloy
Therm hermal al Unit Unit Type ypes
B0.44 0.44– –B32
40 °C ambient cold start trip time characteristics of: 2000
2000
40 ˚C (104 ˚F) AMBIENT COLD START MAXIMUM AVERAGE
1500
1500
Equipment
Separate Overload Relay
Size
25 A
Type
CG & CO
1000 900 800
Series
A
1000 900 800
Qty. of of The Therm rma al Un Units its
1
700
700
When installed in:
600
600
500
500
400
400
300
300
200
200
• Hinged Hinged door and and all other other (larger (larger)) enclosures enclosures
S D N 150 O C E 100 S 90 N 80 I E M I T
150
100 90 80
70
70
60
60
50
50
40
40
30
30
20
20
15
15
10 9
10 9
8
8
7
7
6
6
5
5
4
4
3
3
2
2
1.5
1
• Sma Smallll enclos enclosure ure (Class (Class 9065 only) only)
The trip current rating can be determined from the instructions given with the appropriate thermal unit selection table. The characteristics shown do not necessarily apply to equipment manufactured before S the date of the referenced drawing. D N O C E S N I
E M I T
1.5
5 . 6 . 7 . 8 . 9 . 1
5 . 1
2
3
4
5
6
7
8
9 0 1
5 1
1
0 2
MULTIPLES OF TRIP CURRENT RATING
© 2005 2005 Schneider Schneider Electric all rights ghts reserved reserved
Curve No. 9065TC0310 May 2005
MULTIPLES OF TRIP CURRENT RATING 10000 9000 8000
5 . 6 . 7 . 8 . 9 . 1
5 . 1
2
3
4
5
6
7
8
0 9 1
5 1
0 2
10000 9000 8000
7000
7000
6000
6000
5000
5000
4000
4000
3000
3000
OVERLOAD RELAY TIME-CURRENT CHARACTERISTICS REFERENCE DRAWING NO. 30068-451 Relay Design
Melting Alloy
Therm hermal al Unit Unit Type ypes
B0.44 0.44– –B56
40 °C ambient cold start trip time characteristics of: 2000
2000
40 ˚C (104 ˚F) AMBIENT COLD START MAXIMUM AVERAGE
1500
1500
Equipment
Separate Overload Relay
Size
45 A
Type
TG & TO
1000 900 800
Series
A
1000 900 800
Qty. of of The Therm rma al Un Units its
1
700
700
When installed in:
600
600
500
500
400
400
300
300
200
200
• Hinged Hinged door and and all other other (larger (larger)) enclosures enclosures
S D N 150 O C E 100 S 90 N 80 I E M I T
150
100 90 80
70
70
60
60
50
50
40
40
30
30
20
20
15
15
10 9
10 9
8
8
7
7
6
6
5
5
4
4
3
3
2
2
1.5
1
• Sma Smallll enclos enclosure ure (Class (Class 9065 only) only)
The trip current rating can be determined from the instructions given with the appropriate thermal unit selection table. The characteristics shown do not necessarily apply to equipment manufactured before S the date of the referenced drawing. D N O C E S N I
E M I T
1.5
5 . 6 . 7 . 8 . 9 . 1
5 . 1
2
3
4
5
6
7
8
9 0 1
5 1
1
0 2
MULTIPLES OF TRIP CURRENT RATING
© 2005 2005 Schneider Schneider Electric all rights ghts reserved reserved
Curve No. 9065TC0311 May 2005
MULTIPLES OF TRIP CURRENT RATING 10000 9000 8000
5 . 6 . 7 . 8 . 9 . 1
5 . 1
2
3
4
5
6
7
8
0 9 1
5 1
0 2
10000 9000 8000
7000
7000
6000
6000
5000
5000
4000
4000
3000
3000
OVERLOAD RELAY TIME-CURRENT CHARACTERISTICS REFERENCE DRAWING NO. 30068-453 Relay Design
Melting Alloy
Therm hermal al Unit Unit Type ypes
FB3.33–F 33–FB B35
40 °C ambient cold start trip time characteristics of: 2000
2000
40 ˚C (104 ˚F) AMBIENT COLD START MAXIMUM AVERAGE
1500
1500
Equipment
AC Magnetic Starter
Size
0&1
Type
SB & SC
1000 900 800
Series
A
1000 900 800
Qty Qty. of of The Therm rmal al Unit Units s
1, 2, or 3
700
700
When installed in:
600
600
500
500
400
400
300
300
200
200
S D N 150 O C E 100 S 90 N 80 I E M I T
150
100 90 80
70
70
60
60
50
50
40
40
30
30
20
20
15
15
10 9
10 9
8
8
7
7
6
6
5
5
4
4
3
3
2
2
1.5
1
• Hinged Hinged door and and all other other (larger (larger)) enclosures enclosures The trip current rating can be determined from the instructions given with the appropriate thermal unit selection table. The characteristics shown do not necessarily apply to equipment manufactured before the date of the referenced drawing. S D N O C E S N I
E M I T
1.5
5 . 6 . 7 . 8 . 9 . 1
5 . 1
2
3
4
5
6
7
8
9 0 1
5 1
1
0 2
MULTIPLES OF TRIP CURRENT RATING
© 2005 2005 Schneider Schneider Electric all rights ghts reserved reserved
Curve No. 8536TC0336 May 2005
MULTIPLES OF TRIP CURRENT RATING 10000 9000 8000
5 . 6 . 7 . 8 . 9 . 1
5 . 1
2
3
4
5
6
7
8
0 9 1
5 1
0 2
10000 9000 8000
7000
7000
6000
6000
5000
5000
4000
4000
3000
3000
OVERLOAD RELAY TIME-CURRENT CHARACTERISTICS REFERENCE DRAWING NO. 30068-454 Relay Design
Melting Alloy
Ther Therm mal Unit Unit Types ypes
FB3. FB3.33 33–F –FB3 B38. 8.3 3
40 °C ambient cold start trip time characteristics of: 2000
2000
40 ˚C (104 ˚F) AMBIENT COLD START MAXIMUM AVERAGE
1500
1500
Equipment
AC Magnetic Starter
Size
0&1
Type
SB & SC
1000 900 800
Series
A
1000 900 800
Qty Qty. of of The Therm rmal al Unit Units s
1, 2, or 3
700
700
When installed in:
600
600
500
500
400
400
300
300
200
200
S D N 150 O C E 100 S 90 N 80 I E M I T
150
100 90 80
70
70
60
60
50
50
40
40
30
30
20
20
15
15
10 9
10 9
8
8
7
7
6
6
5
5
4
4
3
3
2
2
1.5
1
• Sma Smallll enclos enclosure ure (Class (Class 8536 only) only) • Motor Motor Contro Controll Cente Centerr (Class 8998, 8999, QMB, or I-Line ® ) The trip current rating can be determined from the instructions given with the appropriate thermal unit selection table. The characteristics shown do not S necessarily apply to equipment manufactured before Dthe date of the referenced drawing. N O C E S N I
E M I T
1.5
5 . 6 . 7 . 8 . 9 . 1
5 . 1
2
3
4
5
6
7
8
9 0 1
5 1
1
0 2
MULTIPLES OF TRIP CURRENT RATING
© 2005 2005 Schneider Schneider Electric all rights ghts reserved reserved
Curve No. 8536TC0337 May 2005
MULTIPLES OF TRIP CURRENT RATING 10000 9000 8000
5 . 6 . 7 . 8 . 9 . 1
5 . 1
2
3
4
5
6
7
8
0 9 1
5 1
0 2
10000 9000 8000
7000
7000
6000
6000
5000
5000
4000
4000
3000
3000
OVERLOAD RELAY TIME-CURRENT CHARACTERISTICS REFERENCE DRAWING NO. 30068-455 Relay Design
Melting Alloy
Ther Therm mal Unit Unit Types ypes
FB4. FB4.75 75–F –FB5 B55. 5.5 5
40 °C ambient cold start trip time characteristics of: 2000
2000
40 ˚C (104 ˚F) AMBIENT COLD START MAXIMUM AVERAGE
1500
1500
Equipment
AC Magnetic Starter
Size
2
Type
SD
1000 900 800
Series
A
1000 900 800
Qty Qty. of of The Therm rmal al Unit Units s
1, 2, or 3
700
700
When installed in:
600
600
500
500
400
400
300
300
200
200
S D N 150 O C E 100 S 90 N 80 I E M I T
150
100 90 80
70
70
60
60
50
50
40
40
30
30
20
20
15
15
10 9
10 9
8
8
7
7
6
6
5
5
4
4
3
3
2
2
1.5
1
• Sma Smallll enclos enclosure ure (Class (Class 8536 only) only) • Motor Motor Contro Controll Cente Centerr (Class 8998, 8999, QMB, or I-Line ® ) The trip current rating can be determined from the instructions given with the appropriate thermal unit selection table. The characteristics shown do not S necessarily apply to equipment manufactured before Dthe date of the referenced drawing. N O C E S N I
E M I T
1.5
5 . 6 . 7 . 8 . 9 . 1
5 . 1
2
3
4
5
6
7
8
9 0 1
5 1
1
0 2
MULTIPLES OF TRIP CURRENT RATING
© 2005 2005 Schneider Schneider Electric all rights ghts reserved reserved
Curve No. 8536TC0338 May 2005
MULTIPLES OF TRIP CURRENT RATING 10000 9000 8000
5 . 6 . 7 . 8 . 9 . 1
5 . 1
2
3
4
5
6
7
8
0 9 1
5 1
0 2
10000 9000 8000
7000
7000
6000
6000
5000
5000
4000
4000
3000
3000
OVERLOAD RELAY TIME-CURRENT CHARACTERISTICS REFERENCE DRAWING NO. 30068-456 Relay Design
Melting Alloy
Therm hermal al Unit Unit Type ypes
FB3.33–F 33–FB B46
40 °C ambient cold start trip time characteristics of: 2000
2000
40 ˚C (104 ˚F) AMBIENT COLD START MAXIMUM AVERAGE
1500
1500
Equipment
AC Manual Star ter
Size
M-0, M-1 & M-1P
Type
M&T
1000 900 800
Series
A
1000 900 800
Qty Qty. of of The Therm rmal al Unit Units s
1, 2, or 3
700
700
When installed in:
600
600
500
500
400
400
300
300
200
200
S D N 150 O C E 100 S 90 N 80 I E M I T
150
100 90 80
70
70
60
60
50
50
40
40
30
30
20
20
15
15
10 9
10 9
8
8
7
7
6
6
5
5
4
4
3
3
2
2
1.5
1
• Sma Smallll enclos enclosure ure (Class (Class 2510 only) only) The trip current rating can be determined from the instructions given with the appropriate thermal unit selection table. The characteristics shown do not necessarily apply to equipment manufactured before the date of the referenced drawing. S D N O C E S N I
E M I T
1.5
5 . 6 . 7 . 8 . 9 . 1
5 . 1
2
3
4
5
6
7
8
9 0 1
5 1
1
0 2
MULTIPLES OF TRIP CURRENT RATING
© 2005 2005 Schneider Schneider Electric all rights ghts reserved reserved
Curve No. 2510TC0305 May 2005
MULTIPLES OF TRIP CURRENT RATING 10000 9000 8000
5 . 6 . 7 . 8 . 9 . 1
5 . 1
2
3
4
5
6
7
8
0 9 1
5 1
0 2
10000 9000 8000
7000
7000
6000
6000
5000
5000
4000
4000
3000
3000
OVERLOAD RELAY TIME-CURRENT CHARACTERISTICS REFERENCE DRAWING NO. 30068-457 Relay Design
Melting Alloy
Therm hermal al Unit Unit Type ypes
FB3.33–F 33–FB B44
40 °C ambient cold start trip time characteristics of: 2000
2000
40 ˚C (104 ˚F) AMBIENT COLD START MAXIMUM AVERAGE
1500
1500
Equipment
AC Manual Star ter
Size
M-0, M-1 & M-1P
Type
M&T
1000 900 800
Series
A
1000 900 800
Qty Qty. of of The Therm rmal al Unit Units s
1, 2, or 3
700
700
When installed in:
600
600
500
500
400
400
300
300
200
200
S D N 150 O C E 100 S 90 N 80 I E M I T
150
100 90 80
70
70
60
60
50
50
40
40
30
30
20
20
15
15
10 9
10 9
8
8
7
7
6
6
5
5
4
4
3
3
2
2
1.5
1
• Hinged Hinged door and and all other other (larger (larger)) enclosures enclosures The trip current rating can be determined from the instructions given with the appropriate thermal unit selection table. The characteristics shown do not necessarily apply to equipment manufactured before the date of the referenced drawing. S D N O C E S N I
E M I T
1.5
5 . 6 . 7 . 8 . 9 . 1
5 . 1
2
3
4
5
6
7
8
9 0 1
5 1
1
0 2
MULTIPLES OF TRIP CURRENT RATING
© 2005 2005 Schneider Schneider Electric all rights ghts reserved reserved
Curve No. 2510TC0306 May 2005
MULTIPLES OF TRIP CURRENT RATING 10000 9000 8000
5 . 6 . 7 . 8 . 9 . 1
5 . 1
2
3
4
5
6
7
8
0 9 1
5 1
0 2
10000 9000 8000
7000
7000
6000
6000
5000
5000
4000
4000
3000
3000
OVERLOAD RELAY TIME-CURRENT CHARACTERISTICS REFERENCE DRAWING NO. 30068-458 Relay Design
Melting alloy
Therm hermal al Unit Unit Type ypes
FB26.7 6.7–FB –FB92
40 °C ambient cold start trip time characteristics of: 2000
2000
40 ˚C (104 ˚F) AMBIENT COLD START MAXIMUM AVERAGE
1500
1500
1000 900 800
1000 900 800
700
700
600
600
500
500
400
400
300
300
200
200 150
100 90 80
70
70
60
60
50
50
40
40
30
30
20
20
15
15
10 9
10 9
8
8
7
7
6
6
5
5
4
4
3
3
2
2
1.5
1
AC Magnetic Starter
Size
3
Type
SE
Series
A
Form
Y81
Qty Qty. of of The Therm rmal al Unit Units s
2 or or 3
When installed in: • Sma Smallll enclos enclosure ure (Class (Class 8536 only) only)
S D N 150 O C E 100 S 90 N 80 I E M I T
Equipment
• Motor Motor Contro Controll Cente Centerr (Class 8998, 8999, QMB, or I-Line ® ) The trip current rating can be determined from the instructions given with the appropriate thermal unit S Dselection table. The characteristics shown do not Nnecessarily apply to equipment manufactured before Othe date of the referenced drawing. C E S N I
E M I T
1.5
5 . 6 . 7 . 8 . 9 . 1
5 . 1
2
3
4
5
6
7
8
9 0 1
5 1
1
0 2
MULTIPLES OF TRIP CURRENT RATING
© 2005 2005 Schneider Schneider Electric all rights ghts reserved reserved
Curve No. 8536TC0339 May 2005
MULTIPLES OF TRIP CURRENT RATING 10000 9000 8000
5 . 6 . 7 . 8 . 9 . 1
5 . 1
2
3
4
5
6
7
8
0 9 1
5 1
0 2
10000 9000 8000
7000
7000
6000
6000
5000
5000
4000
4000
3000
3000
OVERLOAD RELAY TIME-CURRENT CHARACTERISTICS REFERENCE DRAWING NO. 30068-459 Relay Design
Melting Alloy
Therm hermal al Unit Unit Type ypes
FB26.7 6.7–FB –FB84
40 °C ambient cold start trip time characteristics of: 2000
2000
40 C (104 F) AMBIENT COLD START MAXIMUM AVERAGE
1500
1500
1000 900 800
1000 900 800
700
700
600
600
500
500
400
400
300
300
200
200 150
100 90 80
70
70
60
60
50
50
40
40
30
30
20
20
15
15
10 9
10 9
8
8
7
7
6
6
5
5
4
4
3
3
2
2
1.5
1
AC Magnetic Starter
Size
3
Type
SE
Series
A
Form
Y81
Qty Qty. of of The Therm rmal al Unit Units s
2 or or 3
When installed in: • Hinged Hinged door and and all other other (larger (larger)) enclosures enclosures
S D N 150 O C E 100 S 90 N 80 I E M I T
Equipment
The trip current rating can be determined from the instructions given with the appropriate thermal unit selection table. The characteristics shown do not necessarily apply to equipment manufactured before S the date of the referenced drawing. D N O C E S N I
E M I T
1.5
5 . 6 . 7 . 8 . 9 . 1
5 . 1
2
3
4
5
6
7
8
9 0 1
5 1
1
0 2
MULTIPLES OF TRIP CURRENT RATING
© 2005 2005 Schneider Schneider Electric all rights ghts reserved reserved
Curve No. 8536TC0340 May 2005
MULTIPLES OF TRIP CURRENT RATING 10000 9000 8000
5 . 6 . 7 . 8 . 9 . 1
5 . 1
2
3
4
5
6
7
8
0 9 1
5 1
0 2
10000 9000 8000
7000
7000
6000
6000
5000
5000
4000
4000
3000
3000
OVERLOAD RELAY TIME-CURRENT CHARACTERISTICS REFERENCE DRAWING NO. 30068-460 Relay Design
Melting Alloy
Therm hermal al Unit Unit Type ypes
FB50.5 0.5–FB –FB115
40 °C ambient cold start trip time characteristics of: 2000
2000
40 C (104 F) AMBIENT COLD START MAXIMUM AVERAGE
1500
1500
1000 900 800
1000 900 800
700
700
600
600
500
500
400
400
300
300
200
200 150
100 90 80
70
70
60
60
50
50
40
40
30
30
20
20
15
15
10 9
10 9
8
8
7
7
6
6
5
5
4
4
3
3
2
2
1.5
1
AC Magnetic Starter
Size
4
Type
SF
Series
A
Form
Y81
Qty Qty. of of The Therm rmal al Unit Units s
2 or or 3
When installed in: • Sma Smallll enclos enclosure ure (Class (Class 8536 only) only)
S D N 150 O C E 100 S 90 N 80 I E M I T
Equipment
• Motor Motor Contro Controll Cente Centerr (Class 8998, 8999, QMB, or I-Line ® ) The trip current rating can be determined from the instructions given with the appropriate thermal unit S Dselection table. The characteristics shown do not Nnecessarily apply to equipment manufactured before Othe date of the referenced drawing. C E S N I
E M I T
1.5
5 . 6 . 7 . 8 . 9 . 1
5 . 1
2
3
4
5
6
7
8
9 0 1
5 1
1
0 2
MULTIPLES OF TRIP CURRENT RATING
© 2005 2005 Schneider Schneider Electric all rights ghts reserved reserved
Curve No. 8536TC0341 May 2005
MULTIPLES OF TRIP CURRENT RATING 10000 9000 8000
5 . 6 . 7 . 8 . 9 . 1
5 . 1
2
3
4
5
6
7
8
0 9 1
5 1
0 2
10000 9000 8000
7000
7000
6000
6000
5000
5000
4000
4000
3000
3000
OVERLOAD RELAY TIME-CURRENT CHARACTERISTICS REFERENCE DRAWING NO. 30068-461 Relay Design
Melting Alloy
Therm hermal al Unit Unit Type ypes
FB50.5 0.5–FB –FB105
40 °C ambient cold start trip time characteristics of: 2000
2000
40 ˚C (104 ˚F) AMBIENT COLD START MAXIMUM AVERAGE
1500
1500
1000 900 800
1000 900 800
700
700
600
600
500
500
400
400
300
300
200
200 150
100 90 80
70
70
60
60
50
50
40
40
30
30
20
20
15
15
10 9
10 9
8
8
7
7
6
6
5
5
4
4
3
3
2
2
1.5
1
AC Magnetic Starter
Size
4
Type
SF
Series
A
Form
Y81
Qty Qty. of of The Therm rmal al Unit Units s
2 or or 3
When installed in: • Hinged Hinged door and and all other other (larger (larger)) enclosures enclosures
S D N 150 O C E 100 S 90 N 80 I E M I T
Equipment
The trip current rating can be determined from the instructions given with the appropriate thermal unit selection table. The characteristics shown do not necessarily apply to equipment manufactured before S the date of the referenced drawing. D N O C E S N I
E M I T
1.5
5 . 6 . 7 . 8 . 9 . 1
5 . 1
2
3
4
5
6
7
8
9 0 1
5 1
1
0 2
MULTIPLES OF TRIP CURRENT RATING
© 2005 2005 Schneider Schneider Electric all rights ghts reserved reserved
Curve No. 8536TC0342 May 2005
MULTIPLES OF TRIP CURRENT RATING 10000 9000 8000
5 . 6 . 7 . 8 . 9 . 1
5 . 1
2
3
4
5
6
7
8
0 9 1
5 1
0 2
10000 9000 8000
7000
7000
6000
6000
5000
5000
4000
4000
3000
3000
OVERLOAD RELAY TIME-CURRENT CHARACTERISTICS REFERENCE DRAWING NO. 30068-463 Relay Design
Melting Alloy
Ther Therm mal Unit Unit Types ypes
FB4. FB4.75 75–F –FB5 B52. 2.5 5
40 °C ambient cold start trip time characteristics of: 2000
2000
40 ˚C (104 ˚F) AMBIENT COLD START MAXIMUM AVERAGE
1500
1500
Equipment
AC Magnetic Starter
Size
2
Type
SD
1000 900 800
Series
A
1000 900 800
Qty Qty. of of The Therm rmal al Unit Units s
1, 2, or 3
700
700
When installed in:
600
600
500
500
400
400
300
300
200
200
S D N 150 O C E 100 S 90 N 80 I E M I T
150
100 90 80
70
70
60
60
50
50
40
40
30
30
20
20
15
15
10 9
10 9
8
8
7
7
6
6
5
5
4
4
3
3
2
2
1.5
1
• Hinged Hinged door and and all other other (larger (larger)) enclosures enclosures The trip current rating can be determined from the instructions given with the appropriate thermal unit selection table. The characteristics shown do not necessarily apply to equipment manufactured before the date of the referenced drawing. S D N O C E S N I
E M I T
1.5
5 . 6 . 7 . 8 . 9 . 1
5 . 1
2
3
4
5
6
7
8
9 0 1
5 1
1
0 2
MULTIPLES OF TRIP CURRENT RATING
© 2005 2005 Schneider Schneider Electric all rights ghts reserved reserved
Curve No. 8536TC0343 May 2005
MULTIPLES OF TRIP CURRENT RATING 10000 9000 8000
5 . 6 . 7 . 8 . 9 . 1
5 . 1
2
3
4
5
6
7
8
0 9 1
5 1
0 2
10000 9000 8000
7000
7000
6000
6000
5000
5000
4000
4000
3000
3000
OVERLOAD RELAY TIME-CURRENT CHARACTERISTICS REFERENCE DRAWING NO. 30068-490 Relay Design
Melting Alloy
Thermal Unit Types
SB0.44–SB88
40 °C ambient cold start trip time characteristics of: 2000
2000
40 ˚C (104 ˚F) AMBIENT COLD START MAXIMUM AVERAGE
1500
1500
AC Magnetic Star ter
Type S
AC Manual Starter
Type M & T
Separ Sep arate ate Ove Overlo rload ad Rela Relay y
Type S, S, C & T
Qty. of Thermal Units
1, 2, or 3
1000 900 800
1000 900 800
700
700
600
600
500
500
• Motor Motor Contro Controll Cente Centerr (Class 8998, 8999, QMB, or I-Line ® )
400
400
• Hinged Hinged door and and all other other (larger (larger)) enclosures enclosures
300
300
• Open
200
200
S D N 150 O C E 100 S 90 N 80 I E M I T
150
100 90 80
70
70
60
60
50
50
40
40
30
30
20
20
15
15
10 9
10 9
8
8
7
7
6
6
5
5
4
4
3
3
2
2
1.5
1
When installed in: • Sm Smal alll encl enclos osur ure e
The trip current rating can be determined from the instructions given with the appropriate thermal unit S Dselection table. The characteristics shown do not Nnecessarily apply to equipment manufactured before Othe date of the referenced drawing. C E S N I
E M I T
1.5
5 . 6 . 7 . 8 . 9 . 1
5 . 1
2
3
4
5
6
7
8
9 0 1
5 1
1
0 2
MULTIPLES OF TRIP CURRENT RATING
© 2005 2005 Schneider Schneider Electric all rights ghts reserved reserved
Curve No. 8536TC0344 May 2005
LOAD % OF RELAY RATING 0
0 5
0 0 1
0 5 1
0 0 2
0 5 2
0 0 3
0 5 3
0 0 4
70
180
60
170
OVERLOAD RELAY TIME-CURRENT CHARACTERISTICS REFERENCE DRAWING NO. 997-J1 Relay Sizes C20–C83.
50
160
40
150
30
140
40 °C ambient cold start trip time characteristics of Separate Overload Relay when mounted on standard test blocks.
0 5 4
0 0 5
0 5 5
0 0 6
0 5 6
0 0 7
20
130
15
120
12
110
S E 10 T U N I M 9 N I E M I T
100
90
8
80
7
70
6
60
5
50
4
40
TIME TO TRIP IN SECONDS
3
S D N O C E S N I
E M I T
30
20
2
TIME TO TRIP IN MINUTES 1
10
0
0 0
0 5
0 0 1
0 5 1
0 0 2
0 5 2
0 0 3
0 5 3
0 0 4
0 5 4
0 0 5
0 5 5
0 0 6
0 5 6
0 0 7
LOAD % OF RELAY RATING
© 2005 2005 Schneider Schneider Electric all rights ghts reserved reserved
Curve No. 9065TC0313 May 2005
LOAD CURRENT % OF RELAY ULTIMATE TRIP 0
0 5
0 0 1
0 5 1
0 0 2
0 5 2
0 0 3
0 5 3
0 0 4
180
180
170
170
TYPE FB OVERLOAD RELAY TIME-CURRENT CHARACTERISTICS REFERENCE DRAWING NO. 4022-J18B
160
160
25–50 °C ambient cold start trip time characteristics characteristics of Type FB overload over load relays, for use with open Types B, C, D, X, Y, and Z starters.
150
150
140
140 0 5 4
0 0 5
0 5 5
0 0 6
0 5 6
0 0 7
130
130
120
120
110
110
S D100 N O C E 90 S N I
100
90
E M80 I T
80
70
70
60
60
50
50
40
40
30
30
20
20
10
10
0
S D N O C E S N I
E M I T
0 0
0 5
0 0 1
0 5 1
0 0 2
0 5 2
0 0 3
0 5 3
0 0 4
0 5 4
0 0 5
0 5 5
0 0 6
0 5 6
0 0 7
LOAD CURRENT % OF RELAY ULTIMATE TRIP
© 2005 2005 Schneider Schneider Electric all rights ghts reserved reserved
Curve No. 9065TC0312 May 2005
MULTIPLES OF OVERLOAD RELAY TRIP CURRENT RATING 10000 9000 8000
5 . 6 . 7 . 8 . 9 . 1
5 . 1
2
3
4
5
6
7
8
0 9 1
5 1
0 2
10000 9000 8000
7000
7000
6000
6000
5000
5000
4000
4000
3000
3000
2000
OVERLOAD RELAY TIME-CURRENT CHARACTERISTICS REFERENCE DRAWING NO. 30068-820 Relay Design
Melting Alloy
Thermal Unit Types
H
2000
Relay Design
Bimetallic
1500
Thermal Unit Types
E (Class 20)
40 ˚C (104 ˚F) AMBIENT 1500
K (Class 10) 1000 900 800
1000 900 800
700
700
600
600
500
500
400
400
300
300
200
200
S D N 150 O C E 100 S 90 N 80 I E M I T
150
100 90 80
70
70
60
60
MELTING ALLOY OVERLOAD TYPE H HEATERS AND BIMETAL OVERLOAD TYPE E HEATERS NEMA CLASS 20
50 40 30
50
15
15
10 9
10 9
7 6
8
7 6
5
5
4
4
3
3
2
2
1.5
1
E M I T
30
20
BIMETAL OVERLOAD TYPE K HEATERS NEMA CLASS 10
S D N O C E S N I
40
20
8
The trip current rating can be determined from the instructions given with the appropriate thermal unit selection table. The characteristics shown do not necessarily apply to equipment manufactured before the date of the referenced drawing.
1.5
5 . 6 . 7 . 8 . 9 . 1
5 . 1
2
3
4
5
6
7
8
9 0 1
5 1
1
0 2
MULTIPLES OF OVERLOAD RELAY TRIP CURRENT RATING
© 2005 2005 Schneider Schneider Electric all rights ghts reserved reserved
Curve No. 9065TC0315 May 2005
% ULTIMATE TRIP CURRENT 10000 9000 8000
0 0 1
0 0 2
0 0 3
0 0 4
0 0 5
OVERLOAD RELAY TIME-CURRENT CHARACTERISTICS REFERENCE DRAWING NO. 30068-810
10000 9000 8000
7000
7000
6000
6000
5000
5000
4000
4000
3000
3000
2000
2000
1500
1500
40 °C ambient cold start trip time characteristics of Type JB thermal units, 1, 2, or 3 element, on any Type S device, open or enclosed starter, or Class 9065.
0 0 6
0 0 7
1000 900 800
1000 900 800
700
700
600
600
500
500
400
400
300
300
200
200
S D N 150 O C E 100 S 90 N 80 I E M I T
150
100 90 80
70
70
60
60
50
50
40
40
30
30
20
20
15
15
10 9
10 9
8
8
7
7
6
6
5
5
4
4
3
3
2
2
1.5
1
S D N O C E S N I
E M I T
1.5
0 0 1
0 0 2
0 0 3
0 0 4
0 0 5
0 0 6
1
0 0 7
% ULTIMATE TRIP CURRENT
© 2005 2005 Schneider Schneider Electric all rights ghts reserved reserved
Curve No. 8536TC0315 May 2005
Overload Relay Trip Curves
Schnei Schneider der Electr Electric ic USA 8001 Highway 64 East Knightdale, NC 27545 1-888-SquareD (1-888-778-2733) www.us.SquareD.com
Electrical equipment should be installed, operated, serviced, and maintained only by qualified personnel. No responsibility is assumed by Schneider Electric for any consequences arising out of the use of this material. 30068 30068-IND -INDEXR2 EXR2/05 /05 © 2005 Schnei Schneider der Electric Electric All Rights Rights Reserv Reserved ed
5/2005