2016 Catalog
HVX Embedded Pole Vacuum Circuit Breaker up to 24kV Medium Voltage Distribution
schneider-electric.com/HVX
Contents
Over view
schneider-electric.com
6
HVX range
18
Functions and characteristics
26
Dimensions
42
Order for m
54
HVX embedded pole catalog | 3
High performer offers wide choice Operating up to 50 kA and 4,000 A and with voltages ranging from 12 kV to 24 kV, the HVX series of circuit breakers is a true high performer with a wide choice of configurations for easy integration. Benefit from the performance you need, with the level of safety and reliability you deserve. 7 0 6 5 0 1 M P
Note: The voltage levels 36 kV and 40.5 kV are also available. Please contact Schneider Electric.
4 | HVX embedded pole catalog
schneider-electric.com
Your needs
HVX solutions
Safety • State-of-the-art design • Manufacturing controls
Safety
• Operation with mechanical interlocks • Remote control
Reliability • Compliance with the standards • Fully type-tested equipment
Reliability
• Limited maintenance
Ease of use • Wide choice of configurations • Easy integration
Ease of use
schneider-electric.com
• Customer support
HVX embedded pole catalog | 5
Overview
6 | HVX embedded pole catalog
schneider-electric.com
schneider-electric.com
Field of application
8
Safety
9
Reliability
12
Ease of use
13
A comprehensive solution
15
Schneider Electric services
16
Environment
17
HVX embedded pole catalog | 7
Field of application
Overview
HVX offers a wide range of performance levels. It controls heavy-duty tasks in harsh conditions, low temperatures, and vibrations under normal, inductive, and capacitive loads.
The result of a sustained development effort for application in air-insulated switchgear units The HVX series of vacuum circuit breakers is the result of Schneider Electric’s long lasting experience in the medium-voltage field.
5 0 6 5 0 1 M P
The HVX series offers a proven state-of-the-art design to meet your specifications for power switching devices in air-insulated switchgear. • •
A fixed, frontal version A withdrawable, frontal version
The HVX operating mechanism gives the device an opening and closing speed that is independent of the operator whether the command is electrical or manual. It carries out reclosing cycles and is automatically recharged by a geared motor after each closing. It also ensures that the open order always takes priority over the close order. In the event of permanent opening and close orders, it has to maintain the circuit breaker in the open position as long as the open order is active. Once the open order has been canceled, the close order has to be inter rupted then reactivated to enable closing of the circuit breaker.
6 0 6 5 0 1 M P
Easy integration in modern air-insulated switchgear makes HVX the right choice for panel builders and end users. An Integration Guide is available containing instructions on how to do s o.
Applications The circuit breaker is the core component of medium voltage switchgear. The HVX offer enables panel builders to design switchgear solutions helping to protect cables, transformers, motors, or generators. It is widely used in many industries, including power distribution, power generation, nuclear power, oil and gas, mining and metals, and transport.
Energy 8 0 6 5 0 1 M P
Industry - MMM - O&G - Buildings Primar y substation (> 20 M VA)
Heavy industr y primar y substation (10-50 MVA)
0 1 6 5 0 1 M P
2 1 0 5 0 1 M D
9 0 6 5 0 1 M P
0 5 3 3 0 1 M P
8 | HVX embedded pole catalog
Large switching substation (> 4 MVA)
Large MV consumer site (10-50 MVA)
MV/LV substation (<4 MVA)
MV consumer site (1-5 MVA)
1 1 6 5 0 1 M P
2 1 6 5 0 1 M P
schneider-electric.com
Safety
Overview
Protection of people and equipment is our top priority Vacuum interrupter
State-of-the-art design 3 1 6 5 0 1 M P
Schneider Electric's VG range of vacuum interrupters have been developed using the latest computer modeling tools to achieve optimized designs. Based on advanced one-stop sealing technology, the VG of fer minimizes artificial pollution during the production process. Based on our patented design and comprehensive knowledge of vacuum interrupter technology, Schneider Electric's vacuum interrupter is a standout product in the medium voltage field with its high reliability, compact size, and long service life. The special geometry of the contacts and the choice of material used ensures limited duration of the arc and thus helps to reduce thermal and dielectric stress.
Benefits of vacuum interrupters •
Protection of contacts against oxidation and contamination in sealed vacuum
•
Low contact mass to limit the energy of the drive and to allow high mechanical endurance
4 1 6 5 0 1 M P
5 1 6 5 0 1 M P
•
Maintenance-free
•
Environmentally-friendly
Embedded-pole construction The embedded pole is another of Schneider Electric's contributions to medium voltage products, with its 10 years' plus experience in design and manufacture, and it has been tried and tested in the field for many years. Employing the embedding technology, it completely integrates the vacuum interrupter, the main circuit, and the insulated shaft in an epoxy pole to help protect the main circuit from the outside. This gives the pole optimum environmental adaptability, since the circuit breaker can function normally under harsh conditions.
Benefits of embedded poles
schneider-electric.com
•
Compact and robust design
•
Protection against vibration, dust, and humidity
•
High dielectric strength
•
Compact dimensions and possible use in high altitude
•
Sealed for life
HVX embedded pole catalog | 9
Overview
Safety Protection of people and equipment is our top priority
2 9 3 3 0 1 M D
Operating mechanism The operating mechanisms have been simplified to increase reliability and give extended life with very l ow maintenance. Instead of the traditional spring operating mechanism, the HVX series incorporates a single-shaft system and only one torsion spring, reducing the number of parts and increasing reliability. The cam output from 3 independent phases is ideal for the vacuum switch. The transmission mechanism's one-step output and the special axletree design offers optimum transmission efficiency that helps s ave energy and provides a
Drive springcharging mechanism
stable, reliable mechanism.
Operating principle Energy is stored in the spiral spring by means of the electric motor or manual crank. Opening and closing of the vacuum interrupter is controlled by the cam; upon closing, the spring automatically restores the energy for an integrated automatic on/off operating cycle. The on/off storage mechanism, with its special mechanism, can absorb the excess energy of the drive mechanism through a quick on/off operation. The operating mechanism has electric and manual charging devices. The relevant interlock prevents manipulation errors after energy storage.
6 1 6 5 0 1 M P
Robust manufacturing controls HVX is manufactured in compliance with ISO 9001 certified by Bureau Veritas. The following quality controls are implemented to ensure that each product delivered to panel builders has the same performance as the unit type tested: •
Inspection of every incoming batch of critical components with 3D device dimension checks
•
Routine tests on all products: - Dielectric tests on the main circuit - Tests on auxiliary and control circuits - Measurement of the resistance of the main circuit - Design and visual checks - Mechanical operating tests
•
Regular mechanical tests on circuit breaker samples are performed until the device breaks down
10 | HVX embedded pole catalog
schneider-electric.com
Overview
Safety Protection of people and equipment is our top priority
The IEC (1) standard stipulates: "Select equipment that minimizes the risks to personnel from improper operation (for example, fast acting ground switches on lines, motor operators to allow remote operation)". The right choice of components, such as withdrawable racking trolley, vacuum interrupter, and operating mechanism, is crucial to fulfil this IEC recommendation.
Safe operation The operating interface clearly indicates the status of the circuit breaker. Any maloperation is prohibited t hrough robust mechanical interlocks.
Interface operation OFF button 7 1 6 5 0 1
ON button
M P
(1) IEC 62271-1: Edition 2011
Nameplate
Spring status indicator Insertion point for manual charging of the operating mechanism Mechanical operations counter
8 1 6 5 0 1 M P
Circuit breaker position indicator
Racking trolley The racking trolley moves the circuit breaker from the disconnected position to the connected position and vice versa. The racking operation can be done either by rotating a lever on the front of the switchgear with the door closed, or remotely by activating an electrical command from the control room. The HVX racking trolley has a robust interlocking system with the LV plug and the circuit breaker. It can be equipped with an electric motor for remote racking from the control room. The materials used to manufacture HVX racking trolley sub-assemblies have been selected and designed to operate 1,000 cycles under the conditions defined by the IEC standard.
Remote control Remote operation is recommended as it allows convenient operation from a reasonable distance.
schneider-electric.com
HVX embedded pole catalog | 11
Overview
Reliability
Compliance with standards
9 1 6 5 0 1
M P
IEC 62271-100 defines the conditions for switching normal, inductive, and capacitive loads, as well as fault curr ents, and for withstanding, mechanical, thermal, and dielectric stresses. Proven compliance with IEC 62271-100, 2012 ed. 2 standard
HVX is fully type-tested according to the latest edition of standard IEC 62271-100, 2012 ed. 2. Certificates of conformity with other standards such as GB/China and Gost/Russia
0 2 6 5 0 1 M P
are available on request.
HVX circuit breakers have been subjected to the following type tests, as defined by standard IEC 62271-100: •
Dielectric tests
•
Measurement of the resistance of the main circuit
•
Temperature rise tests
•
Short-time withstand current and peak withstand current tests
•
Additional tests on auxiliary and control circuits
•
Mechanical operating test at ambient temperature
•
Short-circuit making and breaking tests
•
Extended mechanical endurance tests for M2 class
•
Electrical endurance tests for E2 class
•
Capacitive current switching tests: - Line-charging current breaking test - Cable-charging breaking test - Single capacitor bank inrush making tests
Normal service conditions
•
Out-of-phase making and breaking tests
•
Back-to-back capacitor breaking tests on request
HVX is designed to operate according to IEC 62271-1, in the following conditions: •
Ambient air temperature: -25 °C to +40 °C (contact Schneider Electric
•
The declaration of conformity indicates the following on the front page:
for higher or lower temperatures)
•
The apparatus type defined as fixed or withdrawable and the phase distance
Altitude:
•
The circuit breaker reference defined by the main rated characteristics: rated voltage, rated short-circuit breaking current, and rated cur rent
Less than or equal to 1,000 m ( derating coefficient to be applied for altitudes higher than 1,000 m) •
•
The list of relevant type test reports to assess HVX conformity with the IEC standard
Atmosphere: No dust, smoke, salt, corrosive, or flammable gas or vapor
•
Humidity: - Average relative humidity over 24 h ≤95% - Average relative humidity over 1 month ≤90%
Please contact us for special ser vice conditions.
Limited maintenance The state-of-the-art HVX design ensures limited maintenance up to 10,000 cycles. The vacuum interrupter has an expected service life of 30 years. HVX can even operate up to 30,000 times with a regular maintenance plan.
12 | HVX embedded pole catalog
schneider-electric.com
Overview
Ease of use
Wide choice of configurations with modular design HVX offers a wide choice of performance levels (up to 50 kA and 4,000 A) within one circuit breaker family, thus providing panel builders with a high degree of standardization in their switchgear design.
High-performance breaking devices kA 50 40
HVX 12 kV/17.5 kV
31.5
HVX 25
24 kV A 630 1,250 1,600 2,000 2,500 3,150 4,000* * Forced cooling
Easy integration,with simple and standard interfaces •
Common dimensions based on a modular design ensure easy integration into various switchgear designs
1 2 6 5 0 1 M P
Phase distance
•
The breaker offers installation flexibility
•
Panel builders can use their own trolley design to make it a withdrawable solution
HVX 12/17.5 kV
Phase distance (mm) 150
Contact distance
Contact distance (mm)
310
-
Phase distance (mm) 150
schneider-electric.com
275
205
HVX 24 kV
Contact distance (mm)
210
310
210
275
-
HVX embedded pole catalog | 13
Ease of use
Overview
Schneider Electric offers best-in-class support to customers using HVX embedded pole circuit breakers.
Technical and commercial support Schneider Electric offers extensive technical and commercial support to panel builders, including expert advice on how to customize HVX, how to integrate HVX in switchgear, how to prepare switchgear for testing in the laboratory, how to analyze the results from type tests to improve switchgear design, special commercial
5 6 3 5 0 1 M P
conditions for circuit breakers needed to verify the technical performance of HVX in assembled switchgear, as well as dedicated t raining documents and other suppor t materials. Please contact your Schneider Electric sales representative for more information.
Customer support Online document repository A QR code on the front of the HVX enables customers to easily download various online documents: 5 0 6 5 0 1 M P
2 2 6 5 0 1 M P
Product QR code "FLASH ME"
•
User guide
•
Receipt guide
•
List of spare parts
Customer Care Center Schneider Electric has set up call centers and e-mail contacts in more than 190 countries to provide a rapid response to customer inquiries. Personnel in the country using HVX are trained to provide qualified answers to customer questions.
Spare parts 7 8 3 5 0 1
M P
Under Schneider Electric's spare parts management policy, HVX parts will be available for at least 12 years after delivery of the product to the customer.
Services A service contract for the switchgear room can be offered by the local Schneider service team with packages such as predictive maintenance, preventive maintenance, 24/7 hotline, emergency on-site i ntervention, and emergency spare part delivery. The availability of the service plan of fers varies in different countries.
14 | HVX embedded pole catalog
schneider-electric.com
Overview
Schneider Electric product portfolios include a wide choice of multi-function relays to be used together with HVX to build a consistent solution for protection, control, and monitoring.
A comprehensive solution
Protection and control relays Easergy P5 Easergy P5 reliably p rotects your electrical equipment from unexpected downtime, while providing you with a powerful digital experience for greater efficiency. To best protect your electrical network, you need protection relays that: •
5 8 0 4 0 1 M P
Comply with the latest standards and regulations, including those for safety, security, and reliability
•
Are easy to order, install, use, and maintain
•
Optimize your ownership costs
Sepam Sepam series 20, series 40, series 60, and series 80 di gital protection relays take full advantage of Schneider Electric’s experience in electrical network protection.
Easergy P5
They provide the following functions: 0 0 3 0 6 E P
•
Effective fault diagnosis and p rotection planning
•
Accurate measurements and detailed diagnosis
•
Integral equipment control
•
Local or remote indication and operation
•
Easy upgrading: communication, digital I/O, analog output, or temperature acquisition systems can be added due to its modular design
Sepam range
MiCOM 8 9 8 2 0 1 M P
MiCOM protection provides the user with a choice of cost-optimized solutions for specific protection requirements within the distribution network. The MiCOM relay series offers comprehensive protective function solutions for power supply systems as well as for various functional and hardware project stages.
Power meter and circuit monitors
MiCOM range
The PowerLogic power meter replaces a whole set of basic analog meters. 2 6 3 5 0 1
3 2 1 7 5 E P
M P
This cost-effective, high-performance meter provides a wide range of accurate true-rms metering values. The PowerLogic series 3000/4000 circuit monitor is designed for critical power users and large energy consumers, to provide the information needed to confidently
PowerLogic range
1 0 5 0 9 E P
enter the evolving world of deregulation. It can be adapted to meter almost any time-of-use or real-time rate.
VAMP arc fault protection relay The VAMP arc protection unit detects an arc flash in an installation and trips the feeding breaker. The unique arc fault protection functionality enhances the safety of both people and property and has made VAMP a leading brand in arc protection VAMP 120
schneider-electric.com
relays worldwide.
HVX embedded pole catalog | 15
Schneider Electric Services
Overview
Peace of mind throughout your installation life cycle
How can you cut costs and improve performance at the same time? When it comes to your electrical distribution infrastructure, the answer is straightforward: get professional expertise.
Life cycle services
Schneider Electric helps you plan the full design and execution of your solution, looking at how to secure your process and opti mize your time: •
Technical feasibility studies: Designing a solution in your environment
•
Preliminary design: Accelerated turnaround time to reach a final solution design
Install Schneider Electric will help you to install efficient, reliable, and safe solutions based
Plan
3 4 8 8 0 4 B D
Plan
What are my options?
on your plans. •
Project management: Completing your projects on time and within budget
•
Commissioning: Ensuring your actual performance versus design, through on-site testing and commissioning, and tools and procedures
Install How do I install and commission?
Operate How do I operate and maintain?
Operate Schneider Electric helps you maximize your installation uptime and control your capital expenditure through its ser vices offer. •
Asset operation solutions: Providing the information you need to increase safety, enhance installation perfor mance, and optimize asset maintenance and investment
Optimize How do I optimize?
•
Advantage service plans: Customized service pl ans that cover preventive, predictive, and corrective maintenance
•
Renew How do I renew my solution?
On-site maintenance services: Delivering extensive knowledge and experience in electrical distribution maintenance
•
Spare parts management: Ensuring spare parts availability and optimizing your spare parts maintenance budget
0 6 3 5 0 1
•
M P
Technical training: Building the necessary skills and competencies to properly and safely operate your installations. Specific training materials with documents and videos are available. Please contact Schneider El ectric
Optimize Schneider Electric proposes recommendations for improved safety, availability, reliability, and quality. •
MP4 electrical assessment: MP4 is the Schneider Electric program for a site-wide assessment of the electrical installation in order to evaluate risks and define improvements
60,000+ Ecofit projects worldwide
110+ Ecofit customized solutions
260+ Ecofit ready solutions, tested for repeatable success for Schneider Electric and third-party legacy switchgear
Renew Schneider Electric extends the life of your system while providing upgrades. We offer to take full responsibility for the end-of-life processing of old electrical equipment. •
ECOFIT™: Keep up to date and improve the performance of your electrical installations (LV, MV, protection relays, etc.)
•
MV product end of life: Recycle and recover outdated equipment with endof-life services
16 | HVX embedded pole catalog
schneider-electric.com
Environment
Overview
3 2 6 5 0 1 M P
Environmental performance Schneider Electric is committed to a long-ter m environmental approach. The production site is certified to ISO 14001. The materials used in HVX, insulators, and conductors are identified and can easily be separated and recycled, as detailed in the "Product Environment Profile" fi le. An end-of-service-life manual details procedures for dis mantling and processing components. HVX fullfills the European regulations of RoHS (Restriction of Hazardous Substancies) and REACH (Registration, Evaluation, Authorisation and Restriction of Chemicals). 7 9 3 5 0 1
M P
4 2 6 5 0 1 M P
5 2 6 5 0 1 M P
6 2 6 5 0 1 M P
7 2 6 5 0 1 M P
RoHS Compliant
schneider-electric.com
HVX embedded pole catalog | 17
HVX range
18 | HVX embedded pole catalog
schneider-electric.com
schneider-electric.com
Overview
20
Selection guide
23
HVX 12 kV
23
HVX 17 kV
24
HVX 24 kV
25
HVX embedded pole catalog | 19
630/1,250/1,600/2,000/2,500
HVX range
Overview Introduction
HVX fixed and withdrawable types
8 2 6 5 0 1
M P
Rated voltage (kV)
12
Rated shortcircuit current (kA)
Rated current (A)
25 31.5 40
630/1,250/1,600/2,000/2,500/3,150/4,000*
50 17.5
25 31.5 40 50
24
25 31.5
630/1,250/1,600/2,000/2,500/3,150/4,000*
1,250/1,600/2,000/2,500/3,150/4,000*
630/1,250/1,600/2,000/2,500 * Forced cooling
6 0 6 5 0 1
HVX fixed type
M P
The HVX fixed version is equipped with drilled and threaded copper connection terminals at the top and bottom. The shape and dimensions of conductors are determined by the panel builder according to the dielectric withstand and temperature rise characteristics of the whole connection system. Please contact your Schneider Electric sales representative to request an HVX Integration Guide for more information.
1 2 6 5 0 1 M P
9 2 6 5 0 1 M P
Up to 1250 A rated current
20 | HVX embedded pole catalog
1600 A up to 4000 A rated current
schneider-electric.com
HVX range
Overview Introduction
5 0 6 5 0 1 M P
HVX withdrawable type The HVX withdrawable version requires a racking trolley, arms, and tulip-type contacts for connection to the switchgear power circuit, and an LV connector to connect the auxiliary circuits.
8 1 6 5 0 1 M P
Racking trolley The HVX racking trolley allows panel builder s to design switchgear solutions with enhanced safety features. It has a robust interlocking system with the switchgear door, LV plug, circuit breaker, and ground switch. It can be equipped with an electric motor for remote racking from the control room.
Racking trolley
Arms 0 3 6 5 0 1 M P
Arms The shape and size of HVX ar ms depend on the rated lightning impulse withstand voltage, the rated normal current, and the r acking trolley stroke.
Tulip-type contacts The shape of HVX contacts is tulip-type. The size depends on the rated current to provide a maximum contact surface optimizing heat dissipation and of fering good Tulip-type contacts
compensation characteristics for electrodynamic forces. The panel builder needs to provide fixed-type contacts with the cor rect shape, tolerance, and material characteristics compatible with the HVX tulip-type contacts.
1 3 6 5 0 1 M P
LV connector The HVX LV connector enables the auxiliary circuits to be connected to the switchgear control cabinet with the circuit breaker in either the disconnected or the service position.
LV connector, cubicle si de 1 3 6 5 0 1 M P
The HVX LV connector is interlocked with the circuit breaker operating mechanism to prevent any manual close commands without the LV connector latched onto the circuit breaker frame.
LV connector circuit breaker side
schneider-electric.com
HVX embedded pole catalog | 21
HVX range
Overview Main characteristics
Main electrical characteristics according to IEC 62271-100 Common characteristics Rated voltage
Ur
kV
12 (1)
17
24
38
50
Rated power frequency withstand voltage
Ud
kV
28
Rated lightening impulse withstand voltage
Up
kV
75
95
125
Rated frequency
f
Hz
50/60
50/60
50/60
Rated short circuit breaking current
Isc
kA
25-31.5-40-50
25-31.5-40-50
25-31,5
Rated short circuit making current @50 Hz
Ip
kA
2,5 Isc
2,5 Isc
2,5 Isc
Rated short circuit making current @60 Hz
Ip
kA
2,6 Isc
2,6 Isc
2,6 Isc
Rated duration of short circuit
tk
s
3
3
3
Operating sequence
• O-0.3s-CO-3 min-CO • O-180s-CO-3 min-CO • O-0.3s-CO-15s-CO (3)
Opening time
ms
40-70
40-70
40-70
Arcing time
ms
≤15
≤15
≤15
Closing time
ms
30-60
30-60
30-60
Service temperature
°C
-25 to +40
-25 to +40
-25 to +40
Mechanical endurance
M2
M2
M2
Electrical endurance
E2
E2 (2)
E2 (3)
10
10
10
C2
C2
C2
25
25
31,5
C2
C2
C2
Single capacitor bank and back-to-back capacitor bank breaking capacity
(3)
(3)
(3)
Higher number of operation cycles upon maintenance plan
30,000
30,000
30,000
Number of switching cycles vacuum interrupter at rated current
30,000 (3)
30,000 (3)
30,000 (3)
Number of full short circuit operations
100 (3)
100 (3)
100 (3)
Line charging breaking current
Cable charging breaking current
22 | HVX embedded pole catalog
A
A
(1)
Please contact Schneider Electric for 42 kV 5 min
(2)
Please contact Schneider Electric for 50 kA
(3)
Please contact Schneider Electric
schneider-electric.com
Selection guide
HVX range
HVX 12 kV Fixed and withdrawable type 6 0 6 5 0 1
-
HVX
M P
-
Rated voltage (kV)
Type
Value
Code
Designation
Code
12
12
Withdrawable
E
17.5
17
Fixed
F
24
24
Rated current (A)
5 0 6 5 0 1
Rated short-circuit current (kA)
M P
Model
Code
630
06
1,250
12 Phase distance (mm)
Value
Code
1,600
16
25
25
2,000
20
Value
Code
31.5
31
2,500
25
150
150
40
40
3,150
31
210
210
50
50
4,000
40
275
275
Rated
d e x i F
Value
e l b voltage a w (kV) a r d h t i W
Rated
Rated
Phase distance
Contact
Weight
short-
current
(mm)
distance
(kg)
circuit
(A)
(mm)
current (kA)
150
210
275
F
E
95
105
HVX 12-25-06
630
p
p
p
205
HVX 12-25-12
1,250
p
p
p
205
105
115
HVX 12-25-16
1,600
p
p
310
175
200
2,000
p
p
310
175
200
HVX 12-25-20
F
E
12
25
HVX 12-25-25
2,500
p
310
195
250
HVX 12-25-31
3,150
p
310
195
250
HVX 12-25-40
4,000 *
p
310
195
250
HVX 12-31-06
630
p
p
p
205
95
105
HVX 12-31-12
1,250
p
p
p
205
105
115
HVX 12-31-16
1,600
p
p
310
175
200
2,000
p
p
310
175
200
HVX 12-31-20
F
E
12
31
HVX 12-31-25
2,500
p
310
195
250
HVX 12-31-31
3,150
p
310
195
250
HVX 12-31-40
4,000 *
p
310
195
250
HVX 12-40-12
1,250
p
p
310
175
200
HVX 12-40-16
1,600
p
p
310
175
200
HVX 12-40-20
2,000
p
p
310
175
200
2,500
p
310
195
250
HVX 12-40-31
3,150
p
310
195
250
HVX 12-40-40
4,000 *
p
310
195
250
HVX 12-50-12
1,250
p
p
310
195
200
HVX 12-50-16
1,600
p
p
310
195
200
HVX 12-50-20
2,000
p
p
310
195
200
2,500
p
310
195
250
HVX 12-50-31
3,150
p
310
195
250
HVX 12-50-40
4,000 *
p
310
195
250
HVX 12-40-25
HVX 12-50-25
F
F
E
E
12
12
40
50
* Forced cooling
schneider-electric.com
HVX embedded pole catalog | 23
Selection guide
HVX range
HVX 17 kV Fixed and withdrawable type Model
Rated
d e x i F
e l b voltage a w (kV) a r d h t i W
Rated
Rated
Phase distance
Contact
Weight
short-
current
(mm)
distance
(kg)
circuit
(A)
(mm)
current (kA)
150
210
275
F
E
9 0/95
105
HVX 17-25-06
630
p
p
p
205
HVX 17-25-12
1,250
p
p
p
205
105
115
HVX 17-25-16
1,600
p
p
310
175
200
2,000
p
p
310
175
200
HVX 17-25-20
F
E
17
25
HVX 17-25-25
2,500
p
310
195
250
HVX 17-25-31
3,150
p
310
195
250
HVX 17-25-40
4,000 *
p
310
195
250
HVX 17-31-06
630
p
p
p
205
95
105
HVX 17-31-12
1,250
p
p
p
205
105
115
HVX 17-31-16
1,600
p
p
310
175
200
2,000
p
p
310
175
200
HVX 17-31-20
F
E
17
31
HVX 17-31-25
2,500
p
310
195
250
HVX 17-31-31
3,150
p
310
195
250
HVX 17-31-40
4,000 *
p
310
195
250
HVX 17-40-12
1,250
p
p
310
175
200
HVX 17-40-16
1,600
p
p
310
175
200
HVX 17-40-20
2,000
p
p
310
175
200
2,500
p
310
195
250
HVX 17-40-31
3,150
p
310
195
250
HVX 17-40-40
4,000 *
p
310
195
250
HVX 17-50-12
1,250
p
p
310
195
200
HVX 17-50-16
1,600
p
p
310
195
200
HVX 17-50-20
2,000
p
p
310
195
200
2,500
p
310
195
250
HVX 17-50-31
3,150
p
310
195
250
HVX 17-50-40
4,000 *
p
310
195
250
HVX 17-40-25
HVX 17-50-25
F
F
E
E
17
17
40
50
* Forced cooling
24 | HVX embedded pole catalog
schneider-electric.com
Selection guide
HVX range
HVX 24 kV Fixed and withdrawable type Model
Rated
d e x i F
Rated
Rated
Phase distance
Contact
Weight
short-
current
(mm)
distance
(kg)
circuit
(A)
(mm)
current (kA)
150
210
275
F
E
HVX 24-25-06
630
p
p
310
175
190
HVX 24-25-12
1,250
p
p
310
175
190
1,600
p
310
255
280
HVX 24-25-20
2,000
p
310
255
280
HVX 24-25-25
2,500
p
310
255
280
HVX 24-31-06
630
p
310
255
280
HVX 24-31-12
1,250
p
310
255
280
1,600
p
310
255
280
HVX 24-31-20
2,000
p
310
255
280
HVX 24-31-25
2,500
p
310
255
280
HVX 24-25-16
HVX 24-31-16
schneider-electric.com
e l b voltage a w (kV) a r d h t i W
F
F
E
E
24
24
25
31
HVX embedded pole catalog | 25
Functions and characteristics
26 | HVX embedded pole catalog
schneider-electric.com
schneider-electric.com
Opening and closing functions
28
Charging functions
30
Low voltage connection
31
Racking trolley
32
Locking functions
33
Other complementary devices
34
Secondary wiring diagrams
35
HVX embedded pole catalog | 27
Opening and closing functions
Functions and characteristics
Opening release F11/F12
Closing release F2
Undervoltage release F4
Opening release F11/F12 Anti-pumping relay K01
3 1 0 5 0 1 M D
Operating mechanism The F11/F12 release is used to open the circuit breaker. The release coil is actuated by the auxiliar y power suppl y. The coil is designed for short operation only; it is therefore routed via an auxiliary switch contact controlled by the circuit breaker shaft, and upon release it interrupts the current circuit.
Characteristics Power supply Operating range Consumption
V a.c. V d.c. V a.c. V d.c. V a.c. V d.c.
110/120*/220/230 24*/48/60/110/125/220 0.85 to 1.1 Ua 0.7 to 1.1 Ua 180 W 180 W * Please contact Schneider Electric
Closing release F2 The F2 release is used to close the circuit breaker. The release coil is actuated by the auxiliary power supply. The coil is designed for short operation only; it is therefore routed via an auxiliary switch contact controlled by the circuit breaker shaft, and upon release it interrupts the current circuit.
Overcurrent release F3
Characteristics 9 1 4 3 0 1
Power supply
M D
Operating range Opening release F11/F12
Consumption
V a.c. V d.c. V a.c. V d.c. V a.c. V d.c.
110/120*/220/230 24*/48/60/110/125/220 0.85 to 1.1 Ua 0.85 to 1.1 Ua 180 W 180 W * Please contact Schneider Electric
Overcurrent release F3 9 1 4 3 0 1
M D
Closing release F2
The F3 release is used to open the circuit breaker in the event of overcurrent or short-circuit. The power to activate the overcurrent release comes from the current transformer of the high voltage circuit, not from the auxiliary voltage supply. Thus the tripping function of this coil is independent of the auxiliary voltage supply.
Characteristics Rated supply current
A
0.5/1/5
Operating range Consumption
A W
90%-110% of rated supply current 180
0 2 4 3 0 1
M D
Overcurrent release F3
28 | HVX embedded pole catalog
schneider-electric.com
Functions and characteristics
Opening and closing functions
Undervoltage release F4 1 2 4 3 0 1 M D
The F4 release opens the circuit breaker automatically, when the auxiliary voltage drops below a certain level. Thus the undervoltage release protects the circuit breaker against a drop or loss of the auxiliary voltage supply. Undervoltage release F4
Characteristics Power supply Operating range Consumption
4 2 4 3 0 1 M D
Anti-pumping relay K01
schneider-electric.com
V a.c. V d.c. Opening V a.c. V d.c.
110/220/230 24*/48/60/110/125/220 0.35 to 0 Uop approx. 12 W approx. 12 W * Please contact Schneider Electric
Anti-pumping relay K01 The anti-pumping relay prevents continous closing and opening of the circuit breaker (anti-pumping). If both ON and OFF commands are permanently present on the circuit breaker at the same time, the circuit breaker will car ry out a CLOSE-OPEN sequence; it remains in this open position until the CLOSE command is discontinued and a new CLOSE command is i ssued again.
HVX embedded pole catalog | 29
Functions and characteristics
Auxiliary switch in switching position S11/S12
Charging functions Circuit breaker charging motor and auxiliary contacts Operating mechanism
Auxiliary switch in charging position S2
Charging motor M1 The electric motor charges the spring of the actuator automatically as soon as it is discharged. This allows the circuit breaker to switch the second close-open-cycle within the rated operating sequence.
4 1 0 5 0 1
M D
Characteristics Power supply Operating range Consumption
V a.c. V d.c. V a.c. V d.c. V a.c. V d.c.
110/220/230 24*/48/60/110/125/220 0.85 to 1.1 Ua 0.85 to 1.1 Ua approx. 100 W approx. 100 W * Please contact Schneider Electric
Operating time of motor Motor charging time
4 ~ 12 s
“Open/closed” auxiliary contacts The number of contacts available depends on the options chosen on the operating mechanism. In the basic configuration, the circuit breaker’s operating mechanism comprises a total of:
Charging motor M1
6 2 4 3 0 1 M D
•
8 normally closed (NC) contacts; some contacts are already used, free contacts as per wiring diagram
Charging motor M1
•
8 normally open (NO) contacts; some contacts are already used, free contacts as per wiring diagram
Auxiliary switch in switching position S11/S12 The auxiliary contacts in switching position indicate the ON/OFF status of the circuit breaker. They are actuated directly by the main shaft of the circuit breaker via a mechanical link. The position of the main shaft corresponds to the position of the auxiliary switches and indicates whether the breaker is in ON or OFF.
6 4 0 5 0 1
M D
Auxiliary switch in switching position S11/S12
Characteristics Rated operational voltage (Ue) V a.c./ d.c. Rated operational current (Ic) A Rated short-time withstand current (Icw) A Rated breaking capacity with inductive charge Voltage V d.c. Charging current A 3 2 4 3 0 1 M D
230 15 250 (during 3s) L/R=10 ms L/R=20 ms 48 125 125 220 10 3,8 2 1
Auxiliary switch in charging position S2 Auxiliary switch in charging position S2
30 | HVX embedded pole catalog
The auxiliary switch is used to control the charging motor and to indicate the charging status.. When contact S2 is closed, the motor is charging the spring of the driving mechanism automatically. When charging is complete, it breaks the electrical charging circuit. For technical datas of S2 please refer to the table in S11/S12.
schneider-electric.com
Low voltage connection
Functions and characteristics
Withdrawable version
2 3 6 5 0 1
M P
An optional flexible LV plug and socket system enables connection of the circuit breaker auxiliary circuits to the switchgear control cabinet. It consists of an elbowtype connector mounted on the frame of the circuit breaker and a removable connector with 58 male pins mounted on a 525 mm flexible d uct. This LV connector is to be connected to the LV cabinet of the cubicle. The counter part connector equipped with the female contacts is assembled in the low voltage cabinet of the switchgear.
1 3 6 5 0 1 M P
LV connector, cubicle side
LV connector, circuit breaker side
The LV plug collects electrical commands and status i nformation from the circuit breaker terminal blocks and from the racking trolley terminal blocks. The number of pins in the LV plug (maximum 58) may limit the number of available position contacts for the switchgear LV cabinet. For the withdrawable version, the LV plug is interlocked with the racking trolley and the operating mechanism to prevent any manual close commands without the LV plug latched onto the circuit breaker frame.
Fixed version
1 2 6 5 0 1 M P
The breaker is equipped with a set of terminal blocks or with an LV plug to connect the circuit breaker auxiliary circuit with the LV wiring from the LV box.
schneider-electric.com
HVX embedded pole catalog | 31
Racking trolley
Functions and characteristics
Withdrawable version
6 1 0 5 0 1 M D
In the withdrawable version the HVX is mounted on a racking trolley to move the circuit breaker between test position and service position . The HVX racking trolley comprises: •
A frame with 4 wheels for moving the circuit breaker
•
A drive system with a rotating shaft to move the circuit breaker inside the switchgear compartment
•
An optional motor drive for electrical operation
•
A set of auxiliary contacts to indicate the service or withdrawn position of the circuit breaker
•
A set of mechanical levers to interlock the trolley
•
A system to latch the racking trolley to the switchgear frame to withstand the mechanical forces of the short circuit
•
An interlock between the racking trolley and the door of the panel
The circuit breaker is equipped with devices to operate the s hutter mechanism.
8 1 0 5 0 1 M D
9 1 0 5 0 1 M D
Grounding The racking trolley is grounded using an additional grounding system on the bottom of the trolley. On request this can be equipped with grounding bars on the sides of the racking trolley.
Under neath g rounding
32 | HVX embedded pole catalog
Sid e ground ing
schneider-electric.com
Locking functions
Functions and characteristics
HVX withdrawable version interlocking
0 2 0 5 0 1 M D
The following table describes the interlocking functions available on the withdrawable version of HVX.
How to use the table Each box describes the possible status of parts interlocked with the circuit breaker at a given status.
Interlock
•
Removed: The circuit breaker with the racking trolley is extracted from the switchgear with the racking trolley
•
Disconnected: The circuit breaker is inside the switchgear compartment; its power connections are separated from the switchgear contacts by shutters and the LV auxiliary circuits are connected
•
Intermediate: The circuit breaker is moving from the disconnected position to the service position or vice versa
•
Service: The circuit breaker power connections are connected to the switchgear contacts, the LV auxiliary circuits are connected, and the switchgear door is closed and locked
1 2 0 5 0 1 M D
Circuit breaker status 3 2 0 5 0 1 M D
4 2 0 5 0 1 M D
5 2 0 5 0 1 M D
Racking-in
200
Racking-out
Removed
Disconnected
Intermediate
Service
Prohibited
Not possible
Operating
Mandatory
Closed
Mandatory
Mandatory
Open
Possible
Possible (1)
Closed
Possible
Preferred
Mandatory (2)
Mandatory
Unlocked
Unlocked
Locked (2)
Locked (2)
Disconnected
Mandatory
Possible (1)
Prohibited
Prohibited
Connected
Not possible
Preferred
Mandatory (3)
Mandatory (3)
Open
Possible
Preferred
Mandatory
Possible
Closed
Possible
Possible
Prohibited (4)
Possible (5)
Open
Possible
Possible
Mandatory
Mandatory
Closed
Possible
Possible (1)
Prohibited
Prohibit ed
Parts
Compartment shutters
Switchgear door
Open
Door handle LV connector
CB operating mechanism
Ground switch position
(1) Impossible to rack-in (2) Impossible to access the CB compartment (3) Impossible to access the LV plug
Not possible
Prohibited
Prohibited
(4) Impossible to activate the “close” command (5) Impossible to rack-out
Specific interlocking
2 2 0 5 0 1 M D
This is a mechanical device, which allows the panel builders to create their own interlock. Fixed type circuit breakers, which are converted into a withdrawable circuit breaker by the customer using the customer's own racking trolley, need to have an interlock between the circuit breaker and the trolley. This part is installed during the manufacturing process.
schneider-electric.com
HVX embedded pole catalog | 33
Other complementary devices
Functions and characteristics
6 2 0 5 0 1 M D
Blocking magnet on racking trolley Y1 7 2 0 5 0 1
M D
Operation counter
8 2 0 5 0 1 M D
Y1 position
Y0 position
5 2 4 3 0 1 M D
Operation counter
Operation counter The operation counter installed on the operating interface records the number of opening/closing cycles.
7 2 4 3 0 1 M D
Blocking magnet on closing Y1
Blocking magnet Blocking magnet on closing Y1 If the controlling power supply to operate this magnet is lost, the circuit breaker cannot perform the normal closing operation (including manual closing).
Blocking magnet on racking trolley Y0 8 2 4 3 0 1
M D
If the secondary controlling power supply is lost, the trolley cannot be racked in or out (either manually or by motorization). Blocking magnet on racking trolley Y0
9 2 0 5 0 1 M D
Insulating sleeves for breaker Insulating sleeves for breaker
34 | HVX embedded pole catalog
For fixed type breakers that are converted to withdrawable types, insulating sleeves can be ordered to improve the dielectric withstand at the contact point.
schneider-electric.com
Secondary wiring diagrams
Functions and characteristics
HVX withdrawable type with anti-pumping device
0 3 0 5 0 1 M D
1 0 5 2 5 0 0 0 X S A : r e b m u n g n i w a r D
e n o i c i t i v r s e o s p
1 Q -
1
1
y e l l o r t
0 Q -
schneider-electric.com
0 Q -
n o i t t i s s o e t p
. r e d r o e h t g n i c a l p n e h w d e t a t s e b d l u o h s e s e h t , d e r i u q e r e r a s m e t i l a n o i t p o f I . s m e t i l a n o i t p o e d u l c ) n 6 i t S o o n n s , e 1 o Y d o t n n ( e m m a p r i u . g a q n i e o d i t g d i r s n a o i r d p i n w a e t c e s i h v t e r n h e i T s . i n 1 t n s o e i t m y r e e f p l l i e u o r r q t , e g 1 r n Y e i k k g n a c i e r a r s o b , l t n c i o r u i t o i c r s f i t c o e p n m n g u e a m p m i x o g a d n i m n a k e e c o h t g l r b s a t w h u o c o s h h i t s d i w n s m i i a r i s r g r e a e k i d k a e t r i a u e r b c t b i r t i u c i u c r s c i i r c i h f T C I . . . 1 2 3
r e d r o e h t
o t g n i d r o c c a y e l l o r t r a e g h c t i w s e h t
) l a n o i t p o ( y e l l o h t r n c i t i r o d h w f c s t e i t t e a w n r o n s i o g t n i p a r i o s o m o t i c s p g n n o e i i c k p i s t t v c i s r l o n e e U T S B
1 8 9 0 Q S - S - Y -
n o i t i s r o e p d r d o n e e h n t i t o t o n g y n i e l d l r o o r t c r c o a r n o e i t k ) a l a r a e e r n p b o t i r o t t i e o ) t p y l u n m o a l g ( e ) a l c l s i l c o a r i n i a o o r n d t g ) r c n i t a n n m n l o t i i e h i a t p y o g s h n c o n c i b p ( t n o o e i o r k l i o t n ( e d t o c c i m i t r e p s e s o f o ( o y t d g o o l a s a a e e n m b t u a l l t i p t e t e e r r e e e a l c s s e r a h r r n o o r c f f a s e o r e g a g a t e i a e e h a l l e t g i p n h p w h r c t c m e c n a t o s i t r e r l o t e e l p i r r y w i r c g w g g o r m o n f r s s n n n g u v u w s i i i i n c r a r l i k n n i r e p o o o s i o r r t i s c e e t x c c i d t r c o e o p p l o u i i l v n n i n U M A M M B O O C O U A M 2 1 / 1 1 1 2 0 1 1 1 2 6 1 1 1 2 3 4 0 6 Q M S S S F F F F F Y - - - - - - - - - - K - S -
HVX embedded pole catalog | 35
Secondary wiring diagrams
Functions and characteristics
HVX withdrawable type without anti-pumping device
1 3 0 5 0 1 M D
2 0 5 2 5 0 0 0 X S A : r e b m u n g n i w a r D
e n o i c i t i v s r e o s p
1 Q -
1
1
y e l l o r t
0 Q -
36 | HVX embedded pole catalog
0 Q -
n o i t t i s s e o t p
. r e d r o e h t
g n i c a l p n e h w d e t a t s e b d l u o h s e s e h t , d e r i u q e r e r a s m e t i l a n o i t p o f I . s m e t i l a n o i t p o e d u l c ) n 6 i t S o o n n s , e 1 o Y d o t n n ( e m m a p r i u . g a q n i e o d i t d g r i n a s i r i d o p n w e a t c e s i h v t e r n h e i T s . 1 n t i n s o e i t m y r e e f p l l i u r o e r q t , e g 1 r n Y e i k k g n a c i e r s r a o b , l t n c i o i u t r o c i r s f i t c o e p n m n g u e a m p m i x o g a d n i m n a k e e c o h g l t b s r a t w h u o c o s h h i i s d t w n s m i i a r i s r g r e a e k i d k a t a e r i e b u r c b t i r i i t c u u c r s c i i r c h i f T C I . . . 1 2 3
r e d r o e h t o t
g n i d r o c c a y e l l o r t r a e g h c t i w s e h t n i
) l a n o i t p o ( y e l l o h t r c t r i h o d f c w e s t t t i e a w n r o n s i o t g i n s a p r i o o m o t c i s p g n n o e i i c k p i s t t v c i s r l o n e e U T S B
1 8 9 0 Q S - S - Y -
n o i t i s r o e p d r d o n e e h n t i t o t o n g y n i e l d l r o o r t c r c o a n r o e i t k ) a l a r a e e r n p b o i t t r o t i e o ) p t y l u m a l n o e ) a c l l n l ( s i c o g r i i a a o r n d t g ) o r c n i t a n n m n l o t i i e h i a p o g s y t h n c n c n o o b p ( t l o e i o r i i o c k t d n ( t t e o c r i m i e p e s o l o f o ( o d g s a y t s o a a e i e l n p m b t u a l t t e r e e e e a t s e l r c a h r r e r n s o o r e f f s a a c o g e e a r e g a e t i l e t g i h a l p n h p w h r e r e l n a t c t c m r c o s t p o t i i e e l r y w w g g g r r o i c r m w o r n f v u s n i n g u r n i i a s s i r i n c e p o l r o r o k n n i s - r o i t i s r c e t e i d e x c i c o p p l c o v n t o u i n l n i U M A M M B O O C O U A M 2 1 / 1 1 1 2 0 1 1 1 2 6 1 1 1 2 3 4 0 6 Q M S S S F F F F F Y - - - - - - - - - - K - S -
schneider-electric.com
Secondary wiring diagrams
Functions and characteristics
HVX fixed type with anti-pumping device
3 0 5 2 5 0 0 0 X S A : r e b m u n g n i w a r D
2 3 0 5 0 1 M D
1
1
y e l l o r t
0 Q -
schneider-electric.com
0 Q -
. r e d r o e h t
g n i c a l p n e h w d e t a t s e b d l u o h s e s e h t , d e r i u q e r e r a s m e t i l a n o i t p o f I . s m e t i l a n o i t p o e d u l c ) n 6 i t S o o n n s , e 1 o Y d o t n n ( e m m a p r i u . g a q n i e o d i t g d i r s n a i r i d o n p w a e t c e s i h v t e r n h e i s T . i n 1 t n s o e i t m y r e e f p l l i u o e r r q t , e g 1 r n Y e i k k g n a c i a s e r r o b , l t n c i o i u t r i o c r s f i t c o e p n m n g u e a m p m i x o g a d n i m n a k e e c o h t g l r b s a t w h u o c o s h h i t s d i w n s m i i a r s r i g r e a e k i d k a t a e r i u e r b c b i t r i t u c i c u r s c i i r c h i T C f I . . . 1 2 3
n o i t ) l a r ) a l e a n p o n i ) o l t o a i p y n t o b p ( o i o t ( e d e p e s o y t a s a ( a e u a l l t e e e e s e l r r c a s e r e g a e a t l n h e n g i l e c a p t r e e t i l r r o m w g r n g u v u s i n c r n i e p r - o r i e s e d t c o v n n i p l O C O U A M 1 1 2 1 2 3 4 0 6 F F F F - - - - K - S -
r e d r o e h t o t g n i d r o c c a r e k a e r b t i u c r i c e h t
) l a n o i t r t e p o t n m a l g ( o s i c o a i r n d t g a n n m n h i o g i s c n c n l o e i o r i k n t t o c c i i m r s o f o d g o o l e i n p m b t t t e e r r a a r o f o n s r h c f o g a e t i e h a l p p w h r e c t c m r o s t o i i r y w w g g c o r n f s s i n i n i a r i k l o o s o i r c n t e t i x r c i c l o p o u i n U M A M M B O 2 1 / 1 0 1 1 1 2 6 1 1 Q M - S - S - S - Y - F -
HVX embedded pole catalog | 37
Secondary wiring diagrams
Functions and characteristics
HVX fixed type without anti-pumping device 4 0 5 2 5 0 0 0 X S A : r e b m u n g n i w a r D
3 3 0 5 0 1 M D
1
1
y e l l o r t
0 Q -
38 | HVX embedded pole catalog
0 Q -
. r e d r o e h t g n i c a l p n e h w d e t a t s e b d l u o h s e s e h t , d e r i u q e r
e r a s m e t i l a n o i t p o f I . s m e t i l a n o i t p o e d u l c ) n 6 i t S o o n n s , e 1 o Y d o t n n ( e m m a p r i u . g a q n i e o d i t d g r i n a s o i r d p i n w e a t c e s i h v t e r n h e i T s . i n 1 t n s o e i t m y r e e p l i l f e u o r r q t , e g 1 r n Y e i k k g n a c i e r s r a o b , l t n c i o r u i t o i c r s f i t c o e p n m n g u e a m p m i x o g a d n i m n a k e e c o h t g l b s r a t w h u o c o s h h i i s d t w n s m i i a r i s r g r e a e k i d k a e t r i a u e r b c t b r t i i u c i u c r s c i i r c h i f T C I . . . 1 2 3
n o i t ) l a r ) a l n e a o p n t i ) o l o p a i y t n o b p ( o i o t d ( e e p e s o y t s a ( a a e l u a l e e r e t e r c s e l e a s r e g a e a t l n h e n g i e c a p i t r l t e e l r r g r o m w n g u v u s i n c r p o n i r e r e s e d i c o v n t p l n i O C O U A M 1 1 2 1 2 3 4 0 6 F F F F - - - - K - S -
r e d r o e h t o t g n i d r o c c a r e k a e r b t i u c r i c e h t n i
) l a n o t i r t e o t p m a l n o ( s i c o g i a r n d t g a n n m n i h i o g s c n c n o l i e i o r k c t o c r m i t s o f o d g o o l e i n p m b t t t r e e a a h r r o f o n s r f c o g a t e i e h h a l p p r w c c o s i t i t m e r o r y w w g g c o r s s n n n f i i i a r i k s i o o l r o r c n t e t i x c c o p o u i i l n U M A M M B O 2 1 / 1 0 1 1 1 2 6 1 1 Q M S S S Y - - - - - F -
schneider-electric.com
Secondary wiring diagrams
Functions and characteristics
HVX motorized trolley withdrawable type with anti-pumping device
4 3 0 5 0 1 M D
5 0 5 2 5 0 0 0 X S A : r e b m u n g n i w a r D
2 2
e n o i c i t i v s r e o s p
1 Q -
1
1
y e l l o r t
0 Q -
schneider-electric.com
0 Q -
n o i t t i s s e o t p
. r e d r o e h t
g n i c a l p n e h w d e t a t s e b d l u o h s e s e h t , d e r i u q e r e r a s m e t i l a n o i t p o f I . s m e t i l a n o i t p o e d u l c ) n 6 i t S o o n n s , e 1 o Y d o t n n ( e m m a p r m i a u . g r a g q n i a e o d i i t g d d r i n g a s i r i n i d o r n p w i a e t c e w s i h e v t h e r n t h e i s n T i . i n 1 t 2 n s o e i t o m y r t e r e f p l l i e e u o r f r q t , e r e g 1 , r n Y 0 e i Y k k g n y a c i e a s l e r l r o o , l b r t n c t i o r r u i t o o i c s f f r i t t c o e e p n n m n g g u e a a m p m m i x o g g a d n n i i m n a k k c e e c o l o h g l t r b b s a t t w h u u o c o o s h t h h i i i s d t w w n s s m i i i a r i s r g r r e e a i e k k d k a a e t r e r i a u e r b b c t b i r t i t i u u c i c u c r i r s c i i r c c i h f f T C I I . . . . 1 2 3 4
r e d r o e h t o t
g n i d r o c c a y e l l o r t r a e g h c t i w s e h t n i
) l a n o i t p o ( y e l l y o h t r l e c l t r o i r h o d c w f t e t t i s t e g a n w n r o n i s i o t g k i n s a c p r i a o o m r o t p g r c i s o n n f o e i i c k r p i s o t t v c t i s r l o o n e e U T S B M
1 8 9 0 2 Y M Q S - S - - -
n o i t i s r o e p d r d o n e e h n t i t o t o n g y n i e l d l r o o r t c r c o a n r o e i t k ) a l a r a e e r n p b o t i r o t t i e p o ) t y l u m a l n o e ) a c l g l ( s i l c r i n o i a o o r a g n d t r c n i ) t a n n m n l o t i e h i a i p o g s y t n h c n c n l o b o p ( t o e i o r i i o c t ( e d n t o k i m i t c r e p e s o l o f o o y t d g s a o s a ( a e e n m b t u a l l t i t t p r r e e e e e e a a h o o n s s e l r r c r r e f f s a a c o g e e a r e g a t e i l e t g n h h a l p p w h r c c c n a i t o s i t i t m e r e r l o e e t l p i r r r c g g y w w g o w r m o r s s n f n i n g u v n i i i r u s a r n i c p k i n n l o o e s - o o i r r c e e s r d i r t t i t c x c c o o e o u i i l p p l v n n i n U M A M M B O O C O U A M 2 1 / 1 1 1 2 0 1 1 2 6 1 1 1 1 2 3 4 0 6 Q M S S S F F F F F Y - - - - - - - - - - K - S -
HVX embedded pole catalog | 39
Secondary wiring diagrams
Functions and characteristics
5 3 0 5 0 1 M D
HVX motorized trolley withdrawable type without anti-pumping device 6 0 5 2 r . 5 e 0 d 0 r 0 o X e S h A t : g r i n e b c a l m p u n n e g h n w i w d e a t r a D t s
2 2
n e n o o i i c i t i t t i v s s r s o e e o s p t p
1 Q -
1
1
y e l l o r t
0 Q -
40 | HVX embedded pole catalog
0 Q -
e b d l u o h s e s e h t , d e r i u q e r e r a s m e t i l a n o i t p o f I . s m e t i l a n o i t p o e d u l c ) n 6 i t S o o n n s , e 1 o Y d o t n n ( e m m a p r m i a u . g r a g q n i a e o d i i t g d d r i s n g a o i r i n d p i r n w i a e t c e w s i h e v t h e r n t h e i n T s i . i n 1 t n s o 2 e i t o t m y r e r e f p l l i e e f u o r r q t , e r e 1 , r g n Y 0 e i Y k k g n y a c i e e l l r s r a o o , l b r t n c t i o r r u i t f o f o i c r s t t i c o e e p n n m n g g u e a a m p m m i x o g g a d n n i i m n a k k c e e c o l o h t g l b b r s a t t w h u u o c o o s h h i t h t i s d i w w n s s m i i i a r i s r g r r e e a i e k k d k a a e t r e r i a u e r b b c t t b i i r t i u u c i c r c u r i s c i i r c c i h f f T C I I . . . . 1 2 3 4
r e d r o e h t o t
g n i d r o c c a y e l l o r t r a e g h c t i w s e h t n i
) l a n o i t p o ( y e l l y h o r l e t c l t r o i r h o d c w f t e t t i s t e g a n w n r o n i s t i o g k i n s a c p r i a o o m r o t p g r c i s o n n f o e i i c k r p i s o t t v c t i s r l o o n e e U T S B M
1 8 9 0 2 Y M Q S - S - - -
n o i t i s r o e p d r d o n e e h n t i t o t o n g y n i e l d l r o o r t c r c o a n r o e i t k ) a l a r a e e r n p b o t i r o t t i e p o ) t y l u n m a l g ( o e ) a l c l s i l c r i n o i a o o r a g n d t r c n i ) t a n n m n l o t i e h i a i p y o g s t n h c o b n c i p ( t n o o e i o r k l i o t ( e d n t o c c i m i t r e p e s o l o f o o y t d g s a s a o ( a e e n m b t u a l l t i p t e e e r r e e e a t l a h o o n s s e r r c r r e f f s a a c o g e e a r e g a t e i l e t g i h a l p n h p w h r c c c n a t o s i t i t m e r e r l p i t o e e l r r r c y w w g g g o w r m o n f r s s n n n g u v u s i i i i n c r a r l i p k i n n o o e s - o o i r r c e e s r r t t i d i t c c c o p p l o e o x v n n i n u i i l U M A M M B O O C O U A M 2 1 / 1 1 1 2 0 1 1 2 6 1 1 1 1 2 3 4 0 6 Q M S S S F F F F F Y - - - - - - - - - - K - S -
schneider-electric.com
Notes
schneider-electric.com
HVX embedded pole catalog | 41
Dimensions
42 | HVX embedded pole catalog
schneider-electric.com
schneider-electric.com
HVX 12 kV withdrawable type
44
HVX 12/17.5 kV fixed type
46
HVX 17.5 kV withdrawable type
48
HVX 24 kV withdrawable type
50
HVX 24 kV fixed type
52
HVX embedded pole catalog | 43
HVX 12 kV withdrawable type
Dimensions
Dimensions drawing
6 3 0 5 0 1 M D
628.5 L
624.5 43
35
86
2 1
3 9 Ø
55
55 5 0 2
2 2 6 3 2 5
5 3 Ø 7 9 2
0 6 2
HVX 3 8
4 5 1
6 4 1
6 7
9 1
25
370
C
383
D .5
4
320
E
437
13.5 313
296
200
50
A P
P
8 16
5 5
HVX 12 vacuum circuit breaker
Rated current (A)
630
44 | HVX embedded pole catalog
1,250
Rated voltage (kV)
12
Rated short-circuit current (kA)
25; 31.5
Rated current (A)
630; 1,250
Rated short-circuit current (kA)
25
31.5
Installation dimensions (mm) P
A
C
D
E
L
150
502
457
492
503
494
210
650
605
640
653
638
275
850
801
836
853
844
schneider-electric.com
HVX 12 kV withdrawable type
Dimensions
Dimensions drawing
7 3 0 5 0 1 M D
L
606.5 43
602 35
86
NOTE3
M Ø 55
0 1 3
55
W Ø
H 7 0 7
7 9 2
NOTE2
NOTE1
0 8 2
HVX
5 6 1
6 7
119 25
C D 13.5
4
320 370
E
200
383
13.5
50
359 293
296
A P
P
16 16
8.5
5 5
Note 1: For rated current 2,000 A Note 2: For rated current 2,500 A Note 3: Heat sink for rated current 2,500 A
Rated current (A)
Rated short-circuit current (kA)
A
C
D
E
L
H
210
650
582
640
653
638
691.5
M 118
W 79
128
79
2,000
1,250
1,600
2,000
40
275
850
777
836
853
844
729.5
1,250
1,600
2,000
50
210
650
582
640
653
638
691.5
275
850
777
836
853
844
729.5
275
850
777
836
853
844
729.5
148
109
275
850
777
836
853
844
729.5
158
109
3,150
4,000
(1)
25 50
31.5
P
1,600
2,500
25
Installation dimensions (mm)
31.5
40
(1) The rated current 4,000 A requires forced cooling in the panel.
schneider-electric.com
HVX embedded pole catalog | 45
HVX 12/17.5 kV fixed type
Dimensions
Dimensions drawing
8 3 0 5 0 1 M D
427.5
406.5 D 112
A 55
55 5 0 2
0 8 4
5 . 8 3 4 4 1 2
4 5 2 7 1 2
30 HVX
119
48
4xM12
250
90 E 384.5 405.5
VIEW A
B P
P
II DETAIL B Ø50 M12 H25 2 2
1 1
2xM10 H15 11 22 0 3
M12
52
HVX vacuum circuit breaker Rated voltage (kV)
12; 17.5
Rated short-circuit current (kA)
25; 31.5
Rated current (A)
630; 1,250
Rated current (A)
630
46 | HVX embedded pole catalog
1,250
Rated short-circuit current (kA)
25
31.5
Installation dimensions (mm) P
D
E
150
460
400
210
576
520
275
706
650
schneider-electric.com
HVX 12/17.5 kV fixed type
Dimensions
Dimensions drawing
9 3 0 5 0 1 M D
427
427
407.5 407.5
D
112
112
A
55
9 2 6
0 1 3
0 1 3
55
4 6 6
7 7 5 5 . 8 3 4
5 . 8 3 4 4 1 2
4 5 2
7 3 2
7 3 2
HVX 119
4xM12
48
250 385.5
385.5
E
Ir ≤ 2,000 A
P
48
250
Ir ≥ 2,500 A
405
VIEW A
P
405
DETAIL B
40
Ø80
M16 H32
C
B
0 4
4xM12 H25
DETAIL C 170
F
M12
G
Ir ≥ 2,500 A
HVX vacuum circuit breaker
Rated current (A) 1,250 1,600
2,000
2,500
3,150
4,000 (1)
Rated voltage (kV)
12; 17.5
Rated short-circuit current (kA)
25; 31.5; 40; 50
Rated cur rent (Ir) (A)
1,250; 1,600; 2,000; 2,500; 3,150; 4,000 (1)
Rated short-circuit current (kA) 40
50
25
31.5
40
25
31.5
40
Installation dimensions (mm) P 210
D 576
E 520
F 30
G 0
50
275
704
650
26
137.5
50
275
704
650
26
137.5
(1) The rated current 4,000 A requires forced cooling in the panel.
schneider-electric.com
HVX embedded pole catalog | 47
HVX 17.5 kV withdrawable type
Dimensions
Dimensions drawing 0 4 0 5 0 1 M D
628.5 L
624.5 43
35
86
2 1
3 9 Ø
55
55 5 0 2
2 2 6 3 2 5
5 3 Ø
0 6 2
HVX
4 5 1 6 7
3 8 9 1
25
4
320 370
C
383 D 13.5
E
437
13.5 313
296
200
50
A P
P
8 16
5 5
HVX vacuum circuit breaker
Rated current (A)
630
48 | HVX embedded pole catalog
1,250
Rated voltage (kV)
17.5
Rated short-circuit current (kA)
25; 31.5
Rated current (A)
630; 1,250
Rated short-circuit current (kA)
25
31.5
Installation dimensions (mm) P
A
C
D
E
L
150
502
462
492
503
494
210
650
610
640
653
638
275
850
806
836
853
844
schneider-electric.com
HVX 17.5 kV withdrawable type
Dimensions
Dimensions drawing 1 4 0 5 0 1 M D
L
606.5 43
602 35
86
NOTE3
M Ø
55
HVX
0 1 3
55
W Ø
H 7 0 7
7 9 2
8
NOTE2
NOTE1
0 8 2 5 6 1
3 8
6 7
119
25
C
370
D 13.5
4
320
E
200
383
13.5
50
359 293
296
A P
P
16 16
8.5
5 5
Note 1: For rated current 2,000,A Note 2: For rated current 2,500 A Note 3: Heat sink for rated current 2,500 A
Rated current (A)
Rated short-circuit current (kA)
A
C
D
E
L
H
210
650
582
640
653
638
691.5
M 118
W 79
128
79
2,000
1,250
1,600
2,000
40
275
850
777
836
853
844
729.5
1,250
1,600
2,000
50
210
650
582
640
653
638
691.5
275
850
777
836
853
844
729.5
275
850
777
836
853
844
729.5
148
109
275
850
777
836
853
844
729.5
158
109
3,150
2,500
3,150
4,000
(1)
25 50
31.5
P
1,600
2,500
25
Installation dimensions (mm)
31.5
40
(1) The rated current 4,000 A requires forced cooling in the panel
schneider-electric.com
HVX embedded pole catalog | 49
HVX 24 kV withdrawable type
Dimensions
Dimensions drawing
2 4 0 5 0 1 M D
L 43 2 1
5 3 Ø 0 1 3
55 55 5 7 7
7 8 7
3 4 9 7 Ø Ø
119
HVX
5 . 2 8
5 . 6 9 2
5 2 3
7 6 1 6 7
8 1
25 50
C
49.5
370
441
E
±2
8 1
50
300
383 447
D
4
38 306
13.5
A P
P
8 03
5 0 1
8-10mm
HVX vacuum circuit breaker
Rated current (A)
630
50 | HVX embedded pole catalog
1,250
Rated voltage (kV)
24
Rated s hor t-circuit cur rent (k A)
25
Rated current (A)
630; 1,250
Rated short-circuit current (kA)
Installation dimensions (mm)
25
P
A
C
D
E
L
210
650
612
646
653
648
275
850
802
836
853
844
schneider-electric.com
HVX 24 kV withdrawable type
Dimensions
Dimensions drawing
3 4 0 5 0 1 M D
844 43
2 1
NOTE1
W Ø
M Ø NOTE2
0 5 1 3 1 8
148 55 55
W Ø
119
5 . 2 8
5 . 6 9 2
M Ø
5 2 3
7 6 1 6 7 25
8 1
802
7 2 8
NOTE3
370 50
836
49.5
38
383
13.5
853
4
5 . 2 2
447 A±2
850 275
306
50
300
275
8
5 0 1
8-10mm
Note 1: Heat sink for rated current 2,500 A Note 2: For rated current 3,150 A Note 3: For rated current 4,000 A
HVX vacuum circuit breaker Rated voltage (kV)
24
Rated short-circuit current (kA)
25; 31.5
Rated current (A)
1,600; 2,000; 2,500
Rated current (A) 1,600 2,000 2,500 630
schneider-electric.com
1250
Rated short-circuit current (kA) 25 31.5
31.5
Installation dimensions (mm) M
W
A
135
79
431
93
35
441
HVX embedded pole catalog | 51
HVX 24 kV fixed type
Dimensions
Dimensions drawing
457.5
4 4 0 5 0 1 M D
436.5
D 112
A
0 1 3 5 . 5 3 6
55 55
0 3 6
5 . 8 3 4 4 1 2
4 5 2
2 8 2
HVX
4xM12
57.5
119
275 89.5 414
E
435
P
VIEW A
B
P
DETAIL B
Ø45
1 2
4xM8
M12 H35 21 7 2
M12
Rated current (A)
630
1,250
52 | HVX embedded pole catalog
Rated short-circuit current (kA)
25
103
Installation dimensions (mm) P
D
E
F
G
210
600
560
27
103
275
756
700
26
137.5
schneider-electric.com
HVX 24 kV fixed type
Dimensions
Dimensions drawing
5 4 0 5 0 1 M D
457.5
457.5
436.5 756
436.5
112
112
A
0 1 3 4 7 6
0 1 3
55 55
4 4 6
2 9 6
5 . 8
5 . 8 3 4
3 4 4 1 2
4 5 2
2 8 2
2 8 2
HVX
32.5
119
(4X) M12
275 89.5
700
32.5
275 89.5
414
Ir ≤ 2,000 A
414
Ir ≥ 2,500 A
435
435
B
VIEW A DETAIL B
275
275
40
Ø80 M16 H32
0 4
4xM12 H25
6 2
M12
137.5
HVX vacuum circuit breaker
schneider-electric.com
Rated voltage Rated current (kV) (A)
Rated short-circuit current (kA)
24
1,600; 2,000; 2,500
25
630; 1,250; 1,600; 2,000; 2,500
31.5
HVX embedded pole catalog | 53
Order for form m
54 | HVX embedded pole catalog
schneider-electric.com
HVX 12 kV/17.5 kV/24 kV order for m Basic equipment
56
Options and accessories
57
Spare par ts
schneider-electric.com
56
58
HVX embedded pole catalog | 55
HVX 12 kV/17.5 kV/24 kV order form
Order form
Basic equipment •
To fill in the form, please check the boxes √ that match your choices.
•
Accessories: Each breaker requires 1 plug-in connector for cubicle and its pins.
•
Basic equipment per order: 1 trolley hand crank and 1 charging mechanism for every 5 circuit breakers. 5 is the minimum order quantity. quantity. Additional accessories should be ordered as required.
Basic equipment
Product range: HVX 12 kV Withdrawable (E)
Version type
24 kV
Quantity
Fixed (F)
IEC 62271-100
Standard
12 kV
17.5 kV
630 A
1,250 A
1,600 A
2,000 A
2,500 A
3,150 A
4000 A
25 kA
31.5 kA
40 kA
50 k A
150 mm
210 mm
275 mm
DC220V
DC125V
DC110V
AC230V
AC220V
AC110V
DC60V *
DC48V *
DC24V *
DC220V
DC125V
DC110V
AC230V
AC220V
AC110V
DC60V *
DC48V *
DC24V *
DC220V
DC125V
DC110V
AC230V
AC220V
AC110V
DC60V *
DC48V *
DC24V * Non-standard *
Drawing No
Rated voltage
24 k V
Rated current
Rated short-circuit current Phase distance (P) Opening release (F11)
Closing release (F2)
Charging motor (M1)
Wiring diagram
Standard
Type of grounding (withdrawable type only) Under neath grounding
Side grounding
58-pin plug-in connector
Low voltage plug type
Other Wiring by ter minal block in the frame English
Documentation language Type of rack-in
Manual operating mechanism
Motor operating mechanism
Motor drive for racking trolley DC220V *
DC110V *
DC48V *
Other (on request) * Limited selection of voltages for motorisation of racking trolley available
Operating sequence O-0.3 s-CO-3 min-CO Standard
56 | HVX embedded pole catalog
O-3 min-CO-3 min-CO
O-0.3 s-CO-15 s-CO (on request)
schneider-electric.com
HVX 12 kV/17.5 kV/24 kV order form
Order form
Options and accessories Optional equipment 1 Anti-pumping relay (K01) Capacitor application
With
Without
Yes
No
Optional equipment 2 Blocking magnet on closing (Y1) DC220V
DC125V
DC110V
DC60V *
DC48V *
DC24V *
AC230V
AC220V
AC110V Without
Blocking magnet on racking trolley (Y0) DC220V
DC125V
DC110V
DC60V *
DC48V *
DC24V *
AC230V
AC220V
AC110V Without
Second opening release (F12) DC220V
DC125V
DC110V
DC60V *
DC48V *
DC24V *
AC230V
AC220V
AC110V Without
Undervoltage release (F4) DC220V
DC125V
DC110V
DC60V *
DC48V *
DC24V * 0.5 A *
Overcurrent release (F3)
AC220V
AC110V Without
1A*
5A*
With
Interlock with door Delivery time
AC230V
Without Without
* Longer delivery time is possible
Special conditions (please contact Schneider Electric Application Engineer) 1
................................................................................................................................................................................................................................................................
2
................................................................................................................................................................................................................................................................
(For other requirements, please write here and attach relevant drawings or accessories)
Accessories
Drawing
Quantity
Accessories for HVX withdrawable type Crank for manual circuit breaker rackout
CHD8000092R0114
Crank for charging the operating mechanism
AGSH30498-01
58-pole connector with female pins, loose component for use in low voltage cabinet
ASXN00151-01
Accessories for HVX fixed type Crank for charging the operating mechanism
AGSH30498-01
58-pole connector with female pins, loose component for use in low voltage cabinet
ASXN00151-01
schneider-electric.com
HVX embedded pole catalog | 57
Spare parts
Order form
Opening release F11/F12 HVX voltage (kV) DC B 9 1 4 3 0 1 M D
AC
References 12
17 .5
24
p
p
p
24 V d.c.
AGSH31484-01
p
p
p
48 V d.c.
AGSH31483-01
p
p
p
60 V d.c.
AGSH31483-01
p
p
p
110 V d.c.
AGSH31482-01
p
p
p
125 V d.c.
AGSH31482-01
p
p
p
220 V d.c.
AGSH31481-01
p
p
p
110 V a.c.
AGSH31482-01
p
p
p
220/230 V a.c.
Closing release F2
References
HVX voltage (kV) DC B 9 1 4 3 0 1 M D
AC
12
17 .5
24
p
p
p
24 V d.c.
AGSH31484-01
p
p
p
48 V d.c.
AGSH31483-01
p
p
p
60 V d.c.
AGSH31483-01
p
p
p
110 V d.c.
AGSH31482-01
p
p
p
125 V d.c.
AGSH31482-01
p
p
p
220 V d.c.
AGSH31481-01
p
p
p
110 V a.c.
AGSH31483-01
p
p
p
220/230 V a.c.
Overcurrent release (F3) HVX voltage (kV) B 9 1 4 3 0 1
AGSH31481-01
Without F12
M D
With F12
58 | HVX embedded pole catalog
AGSH31482-01
References 12
17 .5
24
p
p
p
0.5 A
p
p
p
1A
AGSH31484-01
p
p
p
5A
AVXN01742-01
p
p
p
5A
AVXN01742-01
AGSH31482-01
schneider-electric.com
Spare parts
Order form
Charging motor (M1) HVX voltage (kV) DC
References 12
17 .5
24
p
p
p
24 V d.c.
AGSH33016-01
p
p
p
48 V d.c.
AGSH33017-01
p
p
p
60 V d.c.
AGSH33018-01
p
p
110 V d.c. (Isc ≤ 31.5 kA, Ir ≤ 1,250 A)
p
p
110 V d.c. (Isc ≥ 40kA or Isc ≤ 31.5 kA, Ir ≥ 1,600 A)
p
p
p
p
220 V d.c. (Isc ≤ 31.5 kA, Ir ≤ 1,250A)
p
p
220 V d.c. (Isc ≥ 40 kA or Isc ≤ 31.5 kA, Ir ≥ 1,600 A)
B 6 2 4 3 0 1
M D
AC
p
125 V d.c.
AGSH33019-01
p
110 V d.c. (Isc ≤ 25 kA, Ir ≤ 1,250 A)
p
110 V d.c. (Isc ≥ 31.5 kA or Ir ≥ 1,600 A)
p
220 V d.c. (Isc ≤ 25 kA, Ir ≤ 1,250 A)
p
220 V d.c. ( Isc ≥ 31.5 kA or Ir ≥ 1,600 A)
AGSH33020-01
p
110 V a.c. (Isc ≥ 40 kA or Isc ≤ 31.5 kA, Ir ≥ 1,600 A)
p
p
220 V a.c. (Isc ≤ 31.5 kA, Ir ≤ 1,250 A)
p
p
220 V a.c. (Isc ≥ 40kA or Isc ≤ 31.5 kA, Ir ≥ 1,600 A)
p
p
230 V a.c. (Isc ≤ 31.5 kA, Ir ≤ 1,250 A)
p
p
230 V a.c. (Isc ≥ 40 kA or Isc ≤ 31.5 kA, Ir ≥ 1,600 A)
110 V a.c.(Isc ≥ 31.5 kA or Ir ≥ 1,600 A)
p
220 V a.c. (Isc ≤ 25 kA, Ir≤ 1,250 A)
p
220 V a.c.(Isc ≥ 31.5 kA or Ir ≥ 1,600 A)
p
230 V a.c. (Isc ≤ 25 kA, Ir ≤ 1,250 A)
p
230 V a.c. (Isc ≥ 31.5 kA or Ir ≥ 1,600 A)
AVXN00401-01
p
p
AVXN00402-01 AGSH33019-01
110 V a.c. (Isc ≤ 31.5 kA, Ir≤ 1,250 A)
110 V a.c. (Isc ≤ 25 kA, Ir ≤ 1,250 A)
p
Operation counter
12
17.5
24
p
p
p
Operation counter
AVXN00402-01 AGSH33019-01
AVXN00401-01 AGSH33020-01
AVXN00402-01 AGSH33020-01
AVXN00402-01 AGSH33019-01
AVXN00401-01 AGSH33020-01
AVXN00402-01 AGSH33020-01
Auxiliary contacts
AVXN00402-01
AGSH31816-01
References
HVX voltage (kV)
schneider-electric.com
AGSH33020-01
p
p
AVXN00401-01
References
HVX voltage (kV)
5 1 0 5 0 1 M D
Operation counter
B 5 2 4 3 0 1 M D
AGSH33019-01
S11+S12
12
17 .5
24
p
p
p
8NC+8NO
AVX002294-03
HVX embedded pole catalog | 59
Spare parts
Order form
Anti-pumping relay K01 HVX voltage (kV) DC B 4 2 4 3 0 1 M D
AC
References 12
17 .5
24
p
p
p
24 V d.c.
AGSH31506-01
p
p
p
48 V d.c.
AGSH31506-02
p
p
p
60 V d.c.
AGSH31506-03
p
p
p
110 V d.c.
AGSH31506-04
p
p
p
125 V d.c.
AGSH31506-05
p
p
p
220 V d.c.
AGSH31506-06
p
p
p
110 V a.c.
AVX001154-01
p
p
p
220/230 V a.c.
LV plug assembly on withdrawable/fixed circuit breaker HVX voltage (kV) 7 4 0 5 0 1 M D
8 4 0 5 0 1 M D
12
17 .5
24
p
p
p
p
p
p
AGSH31506-08
References
58-pole connector with male pins on CB side
ASXN00152-01M
58-pole connector with female pins, loose component for use in l ow voltage cabinet
ASXN00151-01S
For the plug and socket system, pins, and special tools, please refer to the user guide
Terminal block for fixed circuit breaker HVX voltage (kV) 9 4 0 5 0 1 M D
60 | HVX embedded pole catalog
References
12
17 .5
24
p
p
p
Terminal block
AVXN01855-01M
schneider-electric.com
Spare parts
Order form
Racking trolley for manual operation HVX voltage (kV) 0 5 0 5 0 1 M D
1 5 0 5 0 1
M D
Without door interlock
With door interlock
References
12
17 .5
24
p
p
Phase distance = 150 mm
p
p
Phase distance = 210 mm, Isc ≤ 31.5 kA, Ir ≤1,250 A
CHD8000037R0171
p
p
Phase distance = 210 mm, Isc ≥ 40 kA or Ir ≥ 1,600 A
CHD8000037R0172
p
p
Phase distance = 275 mm
CHD8000037R0173
p
Phase distance = 210 mm
CHD8020028R0126
p
Phase distance = 275 mm
CHD8020028R0127
CHD8000037R0174
CHD8000037R0170
p
p
Phase distance = 150 mm
p
p
Phase distance = 210 mm, Isc ≤ 31.5 kA, Ir ≤ 1,250 A
CHD8000037R0175
p
p
Phase distance = 210 mm, Isc ≥ 40 kA or Ir ≥ 1,600 A
CHD8000037R0176
p
p
Phase distance = 275 mm
CHD8000037R0177
p
Phase distance = 210 mm
CHD8020028R0148
p
Phase distance = 275 mm
CHD8020028R0149
Motorized racking trolley HVX voltage (kV) 2 5 0 5 0 1
M D
Without door interlock
References 12
17 .5
24
p
p
Phase distance = 210 mm, Isc ≤ 31.5 kA, Ir ≤ 1,250 A CHD8000037R0127
p
p
Phase distance = 210 mm, Isc ≥ 40 kA or Ir ≥ 1,600 A CHD8000037R0183
p
p
Phase distance = 275 mm
CHD8000037R0128
Phase distance = 275mm
CHD8020028R0128
p 7 1 0 5 0 1
M D
With door interlock
p
p
Phase distance = 210 mm, Isc ≤ 31.5 kA, Ir ≤ 1,250 A CHD8000037R0185
p
p
Phase distance = 210 mm, Isc ≥ 40 kA or Ir ≥ 1,600 A CHD8000037R0186
p
p
Phase distance = 275 mm
CHD8000037R0187
Motor for motorized racking trolley HVX voltage (kV) Motor
3 5 0 5 0 1
M D
schneider-electric.com
Motor controller
References 12
17 .5
24
p
p
p
DC 110 V d.c.
AVXN00051-01
p
p
p
DC 220 V d.c.
AVXN00051-02
p
p
p
DC 48 V d.c.
AVXN00066-01
p
p
p
220 V d.c.-2 A (800/1,000 mm width cubicle)
p
p
p
110 V d.c.-2.5 A (800 mm width cubicle)
p
p
p
110 V d.c.-4.6 A (1,000 mm width cubicle)
p
p
p
48 V d.c.-4.2 A (800 mm width cubicle)
p
p
p
48 V d.c.-7.2 A (1,000 mm width cubicle)
RL-TRC-10-A1 RL-TRC-10-B1
RL-TRC-10-B2 RL-TRC-10-C1
RL-TRC-10-C2
HVX embedded pole catalog | 61
Spare parts
Order form
Micro switches inside the trolley (draw in/out position) 12
17 .5
24
S8
p
p
p
Micro switch inside the trolley
CHD8100235P0102
S9
p
p
p
Micro switch inside the trolley
CHD8100235P0102
HVX voltage (kV) 4 5 0 5 0 1
References
M D
Interlock
References
HVX voltage (kV) 5 5 0 5 0 1 M D
Racking trolley interlock
Micro switch S61
12
17 .5
p
p
24 Withdrawable type CB
AVXN00206-02M
p
Withdrawable type CB
AVXN00206-11M
p
p
p
Fixed type CB (to modify a fi xed type CB into a withdrawable CB)
AVXN00013-02M
p
p
p
Draw-out interlock micro switch
AVXN00128-01M
Pushbuttons
References
HVX voltage (kV)
12
17 .5
24
p
p
p
6 5 0 5 0 1 M D
Close
Close/open red/black pushbutton
AVXN00336-01M
Open
Front cover HVX voltage (kV) 7 5 0 5 0 1 M D
62 | HVX embedded pole catalog
References 12
17 .5
24
p
p
Phase distance 150 mm
AVXN01136-01M
p
p
Phase distance 210 mm
AVXN01136-02M
p
p
Phase distance 275 mm
AVXN01136-03M
p
Phase distance 210 mm
AVXN01137-01M
p
Phase distance 275 mm
AVXN01137-02M
schneider-electric.com
Spare parts
Order form
IP cover
References
HVX voltage (kV)
8 5 0 5 0 1
12
17 .5
p
p
p
p
p
p
p
p
p
p
24
M D
p
p
p
L x H: 498 mm x 620 mm (PD=150mm, Isc ≤ 31.5 kA, Ir ≤ 1,250 A)
AVXN00340-01M
L x H: 638 mm x 620 mm (PD = 210 mm, Isc ≤ 31.5 kA, Ir ≤ 1,250 A)
AVXN00340-02M
L x H: 844 mm x 620 mm (PD = 275 mm, Isc ≤ 31.5 kA, Ir ≤ 1,250 A)
ASXN00686-01M
L x H: 638 mm x 684 mm (PD=210mm, Isc ≥ 40 kA or Ir ≥ 1,600 A)
AVXN00340-03M
L x H: 844 mm x 684 mm (PD=275mm, Isc ≥ 40 kA or Ir ≥ 1,600 A)
AVXN00340-04M
L x H: 638 mm x 775 mm (PD=210mm, Ir ≤ 1,250 A, Isc ≤ 25 kA)
ASXN00677-01M
L x H: 844 mm x7 75 mm (PD=275mm, Ir ≤ 1,250 A, Isc ≤ 25 kA)
ASXN00677-02M
L x H: 844 mm x 815 mm (PD=275mm, Ir ≥ 1,600 A or Isc ≥ 31.5 kA)
ASXN00672-03M
Shutter lifting device
References 12
HVX voltage (kV)
9 5 0 5 0 1 M D
17 .5
24
p
Phase distance 150 mm, Contact distance 205 mm
AVXN00591-01M
p
Phase distance 210 mm, Contact distance 205 mm
AVXN00591-02M
p
Phase distance 275 mm, Contact distance 205 mm
AVXN00591-03M
p
Phase distance 210 mm, Contact distance 310 mm
AVXN00591-21M
p
Phase distance 275 mm, Contact distance 310 mm
AVXN00591-22M
p
Phase distance 150 mm, Contact distance 205 mm
AVXN00591-31M
p
Phase distance 210 mm, Contact distance 205 mm
AVXN00591-32M
p
Phase distance 275 mm, Contact distance 205 mm
AVXN00591-33M
p
Phase distance 210 mm, Contact distance 310 mm
AVXN00591-21M
p
Phase distance 275 mm, Contact distance 310 mm
AVXN00591-22M
p
Phase distance 210 mm, Contact distance 310 mm
ASXN00677-01M
p
Phase distance 275 mm, Contact distance 310 mm
ASXN00677-02M
Grounding of the racking trolley HVX voltage (kV) 8 1 0 5 0 1 M D
9 1 0 5 0 1 M D
References 12
17 .5
24
p
p
Side grounding of trolley (2 x AVXN00203-01 required)
AVXN01856-01M
p
p
Underneath grounding of trolley (PD = 275 mm)
AVXN01856-03M
p
p
Underneath grounding of trolley (PD =150 mm/210 mm) Underneath grounding of trolley (PD = 210 mm)
AVXN01856-02M
Underneath grounding of trolley (PD = 275 mm)
AVXN01856-05M
p
Underneath grounding
schneider-electric.com
Side grounding
p
AVXN01856-04M
HVX embedded pole catalog | 63
Spare parts
Order form
AC magnets are operated with a rectifier
Blocking magnets on racking trolley (Y0) HVX voltage (kV) DC
B 8 2 4 3 0 1 M D
AC
References
12
17 .5
24
p
p
p
24 V d.c.
ASX000597-01
p
p
p
48 V d.c.
ASX000597-03
p
p
p
60 V d.c.
ASX000597-08
p
p
p
110 V d.c.
ASX000597-04
p
p
p
125 V d.c.
ASX000597-05
p
p
p
220 V d.c.
ASX000597-06
p
p
p
230 V d.c.
ASX000597-07
p
p
p
110 V a.c.
ASX000597-04
p
p
p
220 V a.c.
ASX000597-06
p
p
p
230 V a.c.
ASX000597-07
AC magnets are operated with a rectifier
Blocking magnets on closing (Y1) HVX voltage (kV) DC B 7 2 4 3 0 1 M D
AC
References 12
17 .5
24
p
p
p
24 V d.c.
AVXN00186-08
p
p
p
48 V d.c.
AVXN00186-06
p
p
p
60 V d.c.
AVXN00186-05
p
p
p
110 V d.c.
AVXN00186-04
p
p
p
125 V d.c.
AVXN00186-03
p
p
p
220 V d.c.
AVXN00186-02
p
p
p
230 V d.c.
AVXN00186-01
p
p
p
110 V a.c.
AVXN00186-04
p
p
p
220 V a.c.
AVXN00186-02
p
p
p
230 V a.c.
AVXN00186-01
AC magnets are operated with a rectifier
Clusters HVX voltage (kV)
0 6 0 5 0 1
M D
References 12
17 .5
24
p
p
p
Ir = 630 A, Isc ≤ 25 kA
p
p
p
Ir = 630 A, Isc = 31.5 kA or Ir=1,250 A , Isc ≤ 31.5 kA
p
p
Ir ≤ 1,250 A, Isc ≥ 40 kA or Ir = 1,600/2,000 A, Isc ≤ 50 kA ASXN00439-03
p
p
Ir = 2,500/3,150/4,000 A, Isc ≤ 40 kA
ASXN00439-04
p
p
Ir = 2,500/3,150/4,000 A, Isc = 50 kA
ASXN00439-05
p
64 | HVX embedded pole catalog
Ir = 1,600/2,000/2,500 A, Isc ≤ 31.5 kA
ASXN00439-06
ASXN00439-07
ASXN00439-02
schneider-electric.com
Spare parts
Order form
Arms HVX voltage (kV)
References 12
17.5 2 4
p
Ir = 630 A, Isc ≤ 31.5 kA
AVXN00372-01
p
Ir = 1250 A, Isc ≤ 31.5 kA
AVXN00672-01
p
Ir = 630 A, Isc ≤ 31.5 kA
AVX8000009R0101
p
Ir = 1250 A, Isc ≤ 31.5 kA
AVX8000008R0101
p
p
Ir ≤ 1,250 A, Isc ≥ 40 kA or Ir = 1,600/2,000 A, Isc ≤ 50 kA ASXN00745-21
p
p
Ir = 2,500/3,150/4,000 A, Isc ≤ 50 kA
2 6 0 5 0 1
M D
ASXN00745-22
p
Ir = 630/1,250 A, Isc ≤ 25 kA
p
Ir = 630 A/1,250 A , Isc = 31.5 kA
p
Ir = 1,600/2,000 A/ 2,500 A, Isc ≤ 31.5 kA
ASXN00661-01
AVX8020001R0101
ASXN00661-21
Insulating sleeves HVX voltage (kV) 1 6 0 5 0 1
M D
schneider-electric.com
References 12
17.5
24
Ir ≤ 1,250 A Isc ≤ 31.5 kA
Ir ≤ 1,250 A Isc ≤ 31.5 kA
Ir ≤ 1,250 A Isc ≤ 25 kA
Ir ≤ 1,250 A Isc ≥ 40 kA or Ir ≥ 1,600 A
Ir ≤ 1,250 A Isc ≥ 40 kA or Ir ≥ 1,600 A
Ir ≤ 1,250 A Isc ≥ 31.5 kA or Ir ≥ 1,600 A
CHD8000134P0104
NVE44473
HVX embedded pole catalog | 65
TOOLS
schneider-electric.com
This international web site allows you to access all the Schneider Electric solutions and product information via: • Comprehensive descriptions • Range datasheets • A download area • Product selectors You can also access information dedicated to your business and contact your Schneider Electric country support.
7 8 6 3 0 1 M P
66 | HVX embedded pole catalog
schneider-electric.com
TOOLS Web selector This site allows you to access the Schneider Electric products in just two clicks via a comprehensive range of datasheets, with direct links to: • Complete libraries: technical documents, catalogs, FAQs, brochures • Selection guides from the e-catalog • Product discovery sites and their animations You will also find illustrated overviews, news to which you can subscribe, and a list of country contacts
Training Training allows you to acquire the expertise (installation design, work with power on, etc.) to increase efficiency and improve customer service. The training catalog includes beginner’s courses in electrical distribution, knowledge of MV and LV switchgear, operation and maintenance of installations, and design of LV installations to give a few examples.
schneider-electric.com
HVX embedded pole catalog | 67