4. Standards for for AC motors IEC 60034
Electrical tolerances Electrical tolerances cover allowable tolerances for efficiency, power factor, speed, locked-rotor torque, breakdown torque, locked-rotor current and moment of inertia
Parameter
Tolerance
Efficiency Machines P < 50 50 kW kW
-15% (1-η motor)
Machines P > 50 50 kW kW
-10% (1-η motor)
Power factor
-1/6 (cos phi)
Breakdown torque
e u q r o t d a o l l l u F %
Locked-rotor torque Full-load torque
Pull-up torque (PUT)
(Min 002; Max 007) Slip
% Synchronous speed
Machines P < 1 kW
+/- 30%
Machines P > 1 kW
+/- 20%
Lock Locked ed-r -rot otor or tor torqu quee
- 15%, 15%, +25 +25% % of gua guara rant ntee eed d torq torque ue
Locke ocked d-rot -rotor or cur current ent
+20% +20%
Speed/torque curve for an AC motor Tolerances are defined in IEC 60034-1
Not stated in connection with Grundfos motors The locked-rotor torque defines the pull-up torque Pull-up torque
The locked-rotor torque represents the minimum torque for single and three-phase MG and MMG motors during acceleration The pull-up torque for pole-changing motors (Dahlander) is smaller than the locked-rotor torque
Breakdown torque
-10% of the guaranteed torque if the break-down torque > 15 full-load torque