TECHNICAL INSTRUCTION KCM Protocol
Read this manual prior to operating or servicing the equipment. This manual contains all safety labels and warnings.
0590020612-EN
Rev. 1.0.0
Service:
If you need assistance, please call your local service center or K-Tron (Switzerland)
Industrie Lenzhard
Tel. (062) 885 71 71
CH-5702 Niederlenz,
Fax (062) 885 71 80
K-Tron (U.S.A.)
Rt. 55 and Rt. 553
Tel. (856) 589 -9083
Pitman, NJ 08071,
Fax (856) 589 - 5664
Web:
http://www.ktron.com
Before you call, gather the following information…
Do you have alarm displays? What are they exactly? Are you able able to eliminate eliminate the the cause of the alarm alarm displays? displays?
Have you modified part of the system, product or operating mode?
Have you tried to remedy the fault in accordance accord ance with the operating and service instructions?
Record the six digit project or job number located on the machine and in the project manual.
– Example: 403214 Use of the manual:
This arrow is used for identifying one-step actions or actions that have no specific order.
1. Numbers in a list identify tasks that that have sequences sequences you have to to follow.
This icon indicates a general cautionary note.
Indicates an electrical hazard. Reference to another manual section. Marks helpful information. Indicates that tools are needed for the task. Specifies where information or a situation must be checked. Indicates where power is applied or removed. Don’t place hands or other body parts into machine. Order no.: 0590020612-EN Date:2005/09/02 Original: 0290020608-EN KIT Project No: 241
“K-Tron assumes no responsibility for damages resulting from misuse of any equipment or negligence on the part of operating personnel. Further, reference is made to the purchase order, acceptance or other document that contains the express K-Tron disclaimer of warranties for a statement of the provisions limiting or disclaiming certain warranties with respect to the Company's equipment. Except as otherwise expressly provided by K-Tron in any such document, document, K-TRON MAKES NO WARRANTY OF MERCHANTABILITY OR FITNESS FOR A PARTICULAR PURPOSE, NOR ANY OTHER WARRANTY, WARRANTY, EXPRESS EXPRESS OR IMPLIED, IMPLIED, WITH RESPECT TO THE EQUIPMENT.” EQUIPMENT.” If an error or ommission is found, please contact:
[email protected].
Service:
If you need assistance, please call your local service center or K-Tron (Switzerland)
Industrie Lenzhard
Tel. (062) 885 71 71
CH-5702 Niederlenz,
Fax (062) 885 71 80
K-Tron (U.S.A.)
Rt. 55 and Rt. 553
Tel. (856) 589 -9083
Pitman, NJ 08071,
Fax (856) 589 - 5664
Web:
http://www.ktron.com
Before you call, gather the following information…
Do you have alarm displays? What are they exactly? Are you able able to eliminate eliminate the the cause of the alarm alarm displays? displays?
Have you modified part of the system, product or operating mode?
Have you tried to remedy the fault in accordance accord ance with the operating and service instructions?
Record the six digit project or job number located on the machine and in the project manual.
– Example: 403214 Use of the manual:
This arrow is used for identifying one-step actions or actions that have no specific order.
1. Numbers in a list identify tasks that that have sequences sequences you have to to follow.
This icon indicates a general cautionary note.
Indicates an electrical hazard. Reference to another manual section. Marks helpful information. Indicates that tools are needed for the task. Specifies where information or a situation must be checked. Indicates where power is applied or removed. Don’t place hands or other body parts into machine. Order no.: 0590020612-EN Date:2005/09/02 Original: 0290020608-EN KIT Project No: 241
“K-Tron assumes no responsibility for damages resulting from misuse of any equipment or negligence on the part of operating personnel. Further, reference is made to the purchase order, acceptance or other document that contains the express K-Tron disclaimer of warranties for a statement of the provisions limiting or disclaiming certain warranties with respect to the Company's equipment. Except as otherwise expressly provided by K-Tron in any such document, document, K-TRON MAKES NO WARRANTY OF MERCHANTABILITY OR FITNESS FOR A PARTICULAR PURPOSE, NOR ANY OTHER WARRANTY, WARRANTY, EXPRESS EXPRESS OR IMPLIED, IMPLIED, WITH RESPECT TO THE EQUIPMENT.” EQUIPMENT.” If an error or ommission is found, please contact:
[email protected].
Table of Contents 1
Safe Safety ty Notes Notes ..... ........ ...... ..... ..... ...... ...... ...... ...... ...... ...... ...... ...... ...... ..... ..... ...... ...... ..... ..... ...... ...... ...... ...... ...... ...... ...... ...... ...... ..... ..... ...... ...... ...... ...... ...... ...... ...... ..... ..... ..... 1
1.1 1.1.1 1.1.1
Safety Safety symbol symbol definitio definitions ns ........ ............ ........ ........ ......... ......... ........ ........ ........ ......... ......... ........ ........ ........ ......... ......... ........ ........ ........ ......... ......... ........ ....... ..... 1 Related Related safety/elec safety/electrica tricall icons icons ........ ............ ........ ........ ........ ......... ......... ........ ........ ........ ......... ......... ........ ........ ........ ......... ......... ........ ........ ........ ....... ..... .. 1
1.2
Proper Proper use ....... ........... ......... ......... ........ ........ ........ ......... ......... ........ ........ ........ ......... ......... ........ ........ ........ ......... ......... ........ ........ ........ ......... ......... ........ ........ ....... ....... ....... ... 2
1.3
Organiza Organization tional al measure measures s ........ ............ ........ ........ ........ ........ ........ ........ ........ ........ ........ ........ ......... ......... ........ ........ ........ ......... ......... ........ ........ ........ ........ ...... .. 2
1.4
Operato Operatorr respons responsibilit ibilities ies ......... ............. ........ ........ ......... ......... ........ ........ ........ ......... ......... ........ ........ ........ ......... ......... ........ ........ ........ ......... ......... ........ ........2 ....2
1.5
SafetySafety-con conscio scious us operatio operation n ....... ............ ......... ........ ........ ........ ......... ......... ........ ........ ........ ......... ......... ........ ........ ......... ......... ........ ........ ........ ......... .........3 ....3
1.6
Safety Safety devices devices ........ ............ ........ ......... ......... ........ ........ ........ ......... ......... ........ ........ ........ ......... ......... ........ ........ ........ ......... ......... ........ ........ ........ ......... ......... ........ ....... ... 3
1.7
High voltage voltage ..... ......... ......... ......... ........ ........ ........ ......... ......... ........ ........ ........ ......... ......... ........ ........ ......... ......... ........ ........ ........ ......... ......... ........ ........ ........ ....... ....... ....... ... 3
1.8
Addition Additional al equipme equipment nt ........ ............ ........ ......... ......... ........ ........ ........ ......... ......... ........ ........ ........ ......... ......... ........ ........ ........ ......... ......... ........ ........ ........ ....... ...... ... 4
1.9
Removal Removal from service service ...... .......... ........ ......... ......... ........ ........ ........ ......... ......... ........ ........ ........ ........ ........ ........ ......... ......... ........ ........ ........ ......... ......... ........ .......4 ...4
1.10
Customer Customer service service and and repairs repairs ........ ............ ........ ........ ........ ......... ......... ........ ........ ........ ........ ........ ........ ......... ......... ........ ........ ........ ......... ......... ........ ...... .. 4
1.11
Warranty Warranty ........ ............ ........ ........ ......... ......... ........ ........ ........ ......... ......... ........ ......... ......... ........ ........ ........ ......... ......... ........ ........ ........ ......... ......... ........ ........ ....... ....... .........4 .....4
1.12 1.12.1
Applied Applied safety safety signs signs and and placard placards s ......... ............. ........ ......... ......... ........ ........ ........ ......... ......... ........ ........ ........ ......... ......... ........ ........ ........ ......... ....... 4 Selected safety signs on machines ......................... ...................................... .......................... ......................... ........................ ..................... ......... 4
2
Data Data Str Struc uctu ture res, s, For Forma mats ts and and Dat Data a Type Types s for for Smar SmartC tCon onne nexx-II II .... ...... .... .... .... .... .... .... .... .... .... .... .... .... .... .... ....5 ..5
2.1
Overview Overview ......... ............. ........ ........ ......... ......... ........ ........ ........ ......... ......... ........ ......... ......... ........ ........ ........ ......... ......... ........ ........ ........ ......... ......... ........ ........ ....... ....... ........5 ....5
2.2 2.2.1 2.2.1 2.2.2 2.2.2
Data descripti descriptions ons ......... ............. ........ ........ ........ ........ ........ ......... ......... ........ ........ ........ ......... ......... ........ ........ ........ ........ ........ ........ ........ ........ ......... ......... ....... ........6 .....6 Data types types ......... ............. ......... ......... ........ ........ ........ ......... ......... ........ ........ ........ ......... ......... ........ ........ ........ ......... ......... ........ ........ ........ ......... ......... ........ ....... ....... ........ ...... .. 6 Applica Application tion types types ......... ............. ........ ........ ......... ......... ........ ........ ........ ......... ......... ........ ........ ........ ......... ......... ........ ......... ......... ........ ........ ........ ......... ........ ....... ........6 ....6
2.3 2.3.1 2.3.1 2.3.2 2.3.2 2.3.3 2.3.3 2.3.4 2.3.4 2.3.5 2.3.5 2.3.6 2.3.6 2.3.7 2.3.7 2.3.8 2.3.8 2.3.9 2.3.9 2.3.10 2.3.11 2.3.12 2.3.13 2.3.14 2.3.15 2.3.16
Data and formats formats .......... ............... ......... ........ ........ ........ ........ ........ ........ ......... ......... ........ ........ ........ ......... ......... ........ ........ ........ ........ ........ ........ ......... ......... ....... ...... ... 7 KCM global global variable variables: s: Process Process ........ ............ ........ ........ ......... ......... ........ ........ ........ ......... ......... ........ ........ ........ ......... ......... ........ ......... ......... ........ ....... ...7 7 KCM global variables: variables: Alarms ........ ............ ........ ........ ........ ......... ......... ........ ........ ........ ......... ......... ........ ........ ........ ........ ........ ........ ......... ......... ........ ...... .. 8 KCM global global variables: variables: Scale Scale parameter parameters s ........ ............ ........ ........ ........ ........ ........ ........ ........ ......... ......... ........ ........ ........ ......... ......... ........ ...... .. 9 KCM global global variables: variables: Digital Digital I-O ........ ............ ........ ........ ........ ........ ........ ........ ........ ........ ........ ........ ........ ........ ........ ........ ........ ......... ......... ........ ...... 10 KCM global global variable variables: s: Analog I-O ......... ............. ........ ......... ......... ........ ........ ........ ......... ......... ........ ......... ......... ........ ........ ........ ......... ......... ........11 ....11 KCM global global variable variables: s: Modbus Modbus I-O ........ ............ ........ ......... ......... ........ ........ ........ ......... ......... ........ ........ ........ ......... ......... ........ ........ ........ ........11 ....11 KCM global global variable variables: s: HCU Loader Loader Params Params .......... .............. ........ ........ ........ ........ ........ ......... ......... ........ ........ ......... ......... ......... .........12 ....12 HcuSelP HcuSelParam aramNum Num Definitions Definitions ........ ............ ......... ......... ........ ........ ........ ......... ......... ........ ........ ......... ......... ........ ......... ......... ........ ......... ......... ........ ...... 12 KCM global global variable variables: s: Communica Communication tions s ........ ............ ........ ........ ........ ......... ......... ........ ......... ......... ........ ........ ........ ......... ......... ........ ........14 ....14 KCM global variables: Miscellaneous Miscellaneous ....................... ................................... ......................... ......................... ......................... ................... ...... 14 KCM variables: LWF ........................ ..................................... ......................... ......................... .......................... ......................... ......................... .................. .....16 16 KCM variables: LWB ........................ ..................................... .......................... .......................... ......................... ........................ ......................... .................. .....18 18 KCM variables: PID ................................ ............................................ ........................ ........................ ......................... .......................... ...................... ............ ... 21 KCM variables: SFM ........................ ..................................... ......................... ......................... .......................... ......................... ......................... .................. .....22 22 KCM variables: VOL ...................... .................................. ......................... .......................... .......................... ......................... ........................ .................... ........24 24 KCM variables: WBF .............................. ........................................... ......................... ........................ ......................... .......................... ...................... ........... .. 24
2.4
Service Service variable variable index index ..... ......... ........ ........ ........ ........ ......... ......... ........ ........ ........ ......... ......... ........ ........ ........ ......... ......... ........ ........ ........ ......... ......... ........ ...... .. 25
3
I-O I-O Funct Functio ions ns ..... ........ ...... ..... ..... ...... ...... ...... ...... ...... ...... ...... ...... ...... ...... ...... ...... ...... ...... ...... ...... ...... ...... ...... ...... ...... ...... ...... ...... ...... ...... ...... ...... ...... ...... ...... ...... ......26 ...26
3.1 3.1.1
Global Global I-O function functions s for all applicat applications ions ........... ............... ......... ......... ........ ........ ........ ......... ......... ........ ......... ......... ........ ........ ........ ......... ....... 26 Global digital inputs ........................ ..................................... .......................... ......................... ......................... ......................... ......................... ................... ...... 26
3.1.2 3.1.3 3.1.4
Global analog setpoint input .............................................................................................26 Global digital outputs ........................................................................................................27 Global analog outputs ....................................................................................................... 27
3.2 3.2.1 3.2.2 3.2.3 3.2.4
LWF I-O ............................................................................................................................28 LWF digital inputs .............................................................................................................28 LWF analog setpoint input ................................................................................................28 LWF digital outputs ...........................................................................................................28 LWF analog outputs ..........................................................................................................29
3.3 3.3.1 3.3.2 3.3.3 3.3.4
WBF I-O ............................................................................................................................29 WBF digital inputs .............................................................................................................29 WBF analog setpoint input ................................................................................................29 WBF digital outputs ........................................................................................................... 29 WBF analog outputs ......................................................................................................... 30
3.4 3.4.1 3.4.2 3.4.3 3.4.4 3.4.5
PID I-O ..............................................................................................................................30 PID digital inputs ...............................................................................................................30 PID analog setpoint input .................................................................................................. 30 PID analog process input ..................................................................................................30 PID digital outputs .............................................................................................................30 PID analog outputs ...........................................................................................................31
3.5 3.5.1 3.5.2 3.5.3 3.5.4
VOL I-O .............................................................................................................................31 VOL digital inputs ..............................................................................................................31 VOL analog setpoint input ................................................................................................. 31 VOL digital outputs ............................................................................................................ 31 VOL analog outputs ..........................................................................................................31
3.6 3.6.1 3.6.2 3.6.3 3.6.4
SFM I-O ............................................................................................................................32 SFM digital inputs .............................................................................................................32 SFM analog setpoint input ................................................................................................32 SFM digital outputs ...........................................................................................................32 SFM analog outputs ..........................................................................................................32
3.7 3.7.1 3.7.2 3.7.3 3.7.4
LWB I-O ............................................................................................................................33 LWB digital inputs ............................................................................................................. 33 LWB analog batch setpoint input ......................................................................................33 LWB digital outputs ...........................................................................................................33 LWB analog outputs ..........................................................................................................34
4
Command Functions ...................................................................................................... 35
4.1
Overview ...........................................................................................................................35
4.2 4.2.1 4.2.2 4.2.3 4.2.4 4.2.5 4.2.6 4.2.7 4.2.8
Command tables for action functions ................................................................................35 Global command table ......................................................................................................35 HCU Loader command table ............................................................................................35 LWF command table ......................................................................................................... 36 WBF command table ........................................................................................................36 PID command table ..........................................................................................................36 VOL command table ......................................................................................................... 36 LWB command table ......................................................................................................... 37 SFM command table ......................................................................................................... 37
5 5.0.1
Condensed Process Status Variables ..........................................................................38 Introduction .......................................................................................................................38
5.1 5.1.1 5.1.2 5.1.3 5.1.4 5.1.5 5.1.6 5.1.7
Condensed process status variable table .........................................................................38 Condensed global process status variable table .............................................................. 38 Condensed LWF process status table .............................................................................. 39 Condensed WBF process status table ............................................................................. 39 Condensed PID process status table ............................................................................... 40 Condensed VOL process status table .............................................................................. 40 Condensed LWB process status table ..............................................................................40 Condensed SFM process status table .............................................................................. 41
6 6.0.1
Expanded Process Status Word - PSW ........................................................................ 42 Introduction ....................................................................................................................... 42
6.1 6.1.1 6.1.2 6.1.3 6.1.4 6.1.5 6.1.6 6.1.7
Expanded PSW tables ......................................................................................................42 PSW word mapping .......................................................................................................... 42 Global PSW Map .............................................................................................................. 42 LWF PSW Map ................................................................................................................. 44 WBF PSW Map ................................................................................................................. 44 PID and VOL PSW Map ...................................................................................................44 SFM PSW Map ................................................................................................................. 45 LWB PSW Map ................................................................................................................. 45
7 7.0.1 7.0.2
Alarm Status Variables-ASW ......................................................................................... 46 Introduction ....................................................................................................................... 46 ASW word mapping .......................................................................................................... 46
7.1 7.1.1 7.1.2 7.1.3 7.1.4 7.1.5 7.1.6 7.1.7
Alarm status word tables-ASW ......................................................................................... 47 Global ASW alarm status table ......................................................................................... 47 LWF alarm status definitions ............................................................................................ 50 VOL alarm status definitions ............................................................................................. 50 WBF alarm status definitions ............................................................................................51 LWB alarm status definitions ............................................................................................ 51 PID alarm status definitions ..............................................................................................52 SFM alarm status definitions ............................................................................................ 52
8 8.0.1
Condensed Alarm Status Words-ASR .......................................................................... 53 Introduction ....................................................................................................................... 53
8.1 8.1.1 8.1.2 8.1.3 8.1.4 8.1.5 8.1.6 8.1.7
Tables of condensed alarm status words .........................................................................53 Global ASW condensed alarm status table ...................................................................... 53 LWF condensed alarm status definitions ..........................................................................54 VOL condensed alarm status definitions ..........................................................................54 WBF condensed alarm status definitions .........................................................................54 LWB condensed alarm status definitions .......................................................................... 55 PID condensed alarm status definitions ...........................................................................55 SFM alarm status definitions ............................................................................................ 55
9 9.0.1
KSL Line Functions ........................................................................................................56 Introduction ....................................................................................................................... 56
9.1 9.1.1 9.1.2
KSL line variable listing ..................................................................................................... 56 KSL numeric parameters .................................................................................................. 56 KSL line command table ...................................................................................................57
10
KCM Built-In *.kgr Files ..................................................................................................58
10.1
Protocols supported ..........................................................................................................58
10.2
Communication settings ....................................................................................................59
10.3 10.3.1 10.3.2 10.3.3 10.3.4 10.3.5 10.3.6 10.3.7
Variable locations and mapping ........................................................................................60 Floating point reads from the KCM ...................................................................................60 Condensed process status and alarm status reads ..........................................................61 Heartbeat, single word read ..............................................................................................62 Single word writes for control ............................................................................................62 Command register ............................................................................................................62 Command functions ..........................................................................................................63 Floating point writes to the KCM .......................................................................................64
11
Index .................................................................................................................................65
Safety Notes Safety symbol definitions
1
1 1.1
Safety Notes
Installation, commissioning and programming of the specified equipment should only be undertaken by qualified personnel.
1.1
This is the safety alert symbol. It is used to alert you to the potential personal injury hazards. Obey all safety messages that follow this symbol to avoid possible injury or death.
CAUTION used without the safety alert symbol indicates a potentially hazardous situation which, if not avoided, may result in property damage.
CAUTION indicates a potentially hazardous situation which, if not avoided, may result in minor or moderate personal injury.
WARNING indicates a potentially hazardous situation which, if not avoided, may result in death or serious personal injury.
DANGER indicates an imminently hazardous situation, which if not avoided, will result in death or serious injury.
CAUTION
!
!
!
CAUTION
WARNING
DANGER
Safety symbol definitions
1.1.1
Related safety/electrical icons
This icon is used to indicate an electrical hazard. It is located on covers and doors. Only qualified personnel are allowed to remove these covers or open the doors.
This symbol shows where an electrical ground or PE is to be placed.
1 1.2
Safety Notes Proper use
1.2
Proper use
Only operate the KCM in conjunction with the feeder equipment from K-Tron.
Only operate the KCM in accordance with the specified technical data.
Do not operate where there is a risk of explosion.
Do not use the equipment in a manner not intended by the manufacturer.
1.3
Organizational measures
Observe the safety notes for the connected feeding devices.
In addition to the operating instructions, always comply with generally prescribed safety regulations governing accident prevention and environmental safety.
Always keep the metering device operating instructions within easy reach. Ensure that they are always complete and legible.
1.4
Operator responsibilities
Ensure that only qualified and trained personnel work with the KCM.
Establish personnel responsibilities for operation and maintenance.
Ensure that personnel have read and understood the operat ing instructions to all installation components, particularly these safety notes.
The operator must have damaged or missing components replaced immediately.
The operator of the KCM is responsible for compliance with the legally prescribed accident and safety regulations.
Safety Notes Safety-conscious operation
1.5
1 1.5
Safety-conscious operation
Any changes (including changes to operational behavior) which affect safety must be immediately reported to the responsible member of staff.
Perform all operations with safety in mind.
Do not make any internal adjustments to the KCM while the feeder is in operation.
1.6
Safety devices
The electrical safety devices must not be altered. This increases the danger of accidents.
Never operate the KCM with the housing open.
Replace damaged cables and connections immediately.
Only operate the feeding equipment if all safety devices are installed and fully functional.
Check that the safety devices on the KCM and on the feeding equipment operate properly daily.
Never open or remove covers or hoods while the feeding equipment is in operation.
If accessing KCM internal components, allow 10 seconds to lapse prior to opening the enclosure. This ensures safe discharge of high voltage components.
1.7
High voltage
Warning! Danger!
!
DANGER
High voltage of 230 Vac may be present on the line power cables of the KCM.
Switch off the power to the KCM for 3 minutes before:
– any disassembly, maintenance and repair work – replacing the motor. Only qualified electricians may work on the KCM.
Protect the KCM against moisture entrance.
1 1.8
Safety Notes Additional equipment
1.8
Modifications to the KCM are prohibited.
The operator is responsible for complying with all safety regulations related to operation with the feeding equipment.
1.9
!
CAUTION
Additional equipment
Removal from service
Disconnect the KCM from the power supply before removal from service.
The operator is responsible for the proper removal of the KCM from service.
1.10
Customer service and repairs
The KCM may only be repaired by
– your authorized K-Tron customer service center or – qualified personnel, trained by K-Tron. Only use original K-Tron parts for repairs.
1.11
Warranty
See project specifications and sales agreements for warranty information.
1.12
Applied safety signs and placards
1.12.1
Selected safety signs on machines
Fig. 1.1
Power applied sign
Data Structures, Formats and Data Types for SmartConnex-II Overview
2
2 2.1
Data Structures, Formats and Data Types for SmartConnex-II
This document presents the numeric and digital data that is available via the KCM Smart K-Link connectivity function. The KSL needs to be at ver. 4 software.
2.1
Overview
Two sections are presented. The first section presents a summary table of the variables that may be selected in Smart K-Link and the second shows the index settings used when binary or bit data is selec ted. Command, Alarm and Process Status functions fit this later category. Please use the following notation when using these variables. Data Type: Numeric - Float, Strings or Integer Data Types, Digital - Bit Arrays Typically used variables: Marked in Bold typeface. For PLC register assignments, use: Float, string, bit array: 2 registers Integer: 1 register Access information:’R’ means Smart K-Link output only,’R/W’ means the variable is both an input and output value. Units of time are generally in seconds unless otherwise specified. Using string data may require setting of an ASCII data block in the PLC. Then select ASCII in the Poll Record Table. It is recommended to use floating point rather than integer math. This will eliminate the need for scaling.
2 2.2
Data Structures, Formats and Data Types for SmartConnex-II Data descriptions
2.2
Data descriptions
There are different types of data that can be exchanged amount devices. This will help you to identify them. 2.2.1
Data types
Data types are broken into three major categories: ·Commands ·Status ·Variable or process data Commands are requests for an action to be taken by the controller. These mnemonics begin with the letter ’C’. Status information is a report on the operating condition of the controller. These values can be bit mapped or brought back as full 16 bit arrays for a total of 256 bits. What is left is the process data or such things as setpoint and massflow. For clarification of mnemonics, use this list. 2.2.2 Application
Application types
Function
LWF
Loss-in-Weight Feeder
WBF
Weigh Belt Feeder
PID
Proportional, Integral, Derivative Controller
LWB
Loss-in-Weight Batch Feeder
SFM
Smart Flow Meter Controller
VOL
Volumetric feeder controller
Data Structures, Formats and Data Types for SmartConnex-II Data and formats
2.3
2 2.3
Data and formats
This section provides a listing of data that is passed from various applications to the supervisory control system. You will select them using the SmartConfig PC application when defining variables and their placement in the PLC memory map. This listing shows the variables for all machines where applicable. 2.3.1
Name
ActualTemperature
KCM global variables: Process
Units
Type
R or R/W
Description
deg C
float
R
Internal temperature of the KCM.
binary
R
32 bit definition of the KCM operating status.
CondProcStat DriveCommand
percent
float
R
Value of operating drive command from the controller.
GrossWeight
weight
float
R
Weight on the scale.
GrossWeight2
weight
float
R
Weight on the secondary weighing device on a WBF or SFM.
integer
R
Integer value that increments to 9999 then rolls over and resumes the count. Indicates basic operation of the KCM.
HeartBeat
Massflow
rate
float
R
Output of the feeder in weight/time units.
MotorPower
watts
float
R
Actual power used by the motor.
MotorSpeed
rpm
float
R
Current motor speed.
NetWeight
weight
float
R
GrossWeight-TareWeight.
NetWeight2
weight
float
R
GrossWeight2-TareWeight2.
Setpoint
rate/ weight
float
R/W
Target operation of the feeder.
TareWeight
weight
float
R/W
Weight of feeder on scale.
TareWeight2
weight
float
R/W
Weight of feeder on the secondary scale.
Totalizer
weight
float
R/W
Accumulative weight delivery of the feeder.
2 2.3
Data Structures, Formats and Data Types for SmartConnex-II Data and formats
2.3.2
Name
AlarmDelay
KCM global variables: Alarms
Units
Type
R or R/W
Description
seconds
integer
R/W
Time, in seconds, for the alarm to persist before a hard alarm can occur.
integer
R/W
Alarm action:
AlarmMode
Ignore = 0, Alarm immediate = 1, Alarm timed = 2, Alarm Stop immediate = 3, Alarm Stop timed = 4 AlarmNumber
integer
R/W
Number of the actual alarm- see ASR list.
integer
R/W
Time, in seconds, upon machine start-up when the process alarms are suppressed.
AlarmStat[16]
binary
R
Alarm status, see alarm status listing.
CondAlarmStat
binary
R
Condensed alarm status, see listing.
AlarmStartupDel
seconds
DrvCmdHiLimit
percent
float
R/W
Limit for drive command for when drive command exceeds the value, an alarm occurs.
DrvCmdLoLimit
percent
float
R/W
Limit for drive command for when drive command fallls below the value, an alarm occurs.
MassflowHiLim
percent
float
R/W
Limit for massflow for when massflow exceeds the value, an alarm occurs.
MassflowLowLim
percent
float
R/W
Limit for massflow for when massflow falls below the value, an alarm occurs.
integer
R/W
When set, the stop bit clears alarms:
StpBitClrAl
0 = stop bit does not clear alarms 1 = stop bit will clear alarms
Data Structures, Formats and Data Types for SmartConnex-II Data and formats
2.3.3
Name
Units
NumSFTReq
KCM global variables: Scale parameters
Type
R or R/W
Description
integer
R/W
Number of SFTs located at the feeder.
SampleTime
seconds
float
R/W
Sample time interval of weight sampling.
ScaleGrossRange
weight
float
R/W
Weight range of scale.
ScaleSpan
float
R/W
Span correction factor.
SelectedSFT
integer
R/W
Address of the viewed SFT.
SFTAddress
integer
R/W
SFT addressed? 0 = no, 1 = yes
SFTConfig
string
R
Shows operation of connected SFTs.
SftCutOff
Hz
float
R/W
SFT low pass filter.
SFTRawWeight
weight
float
R
Weight direct from SFT.
SFTStatus
binary
R
Operational condition of SFT.
SFTType
string
R
Shows SFT weight range.
2 2.3
2 2.3
Data Structures, Formats and Data Types for SmartConnex-II Data and formats
2.3.4
Name
Units
KCM global variables: Digital I-O
Type
R or R/W
Description
DgInSelFun
integer
R/W
Selects function for the digital input.
DgInSelNum
integer
R/W
Selects the input to be used by number.
DgInSelPol
integer
R/W
Sets the polarity for the input: 0 = normal, 1 = inverse
DgInSelValue
integer
R
Shows the digital input state: 0 = off, 1 = on/active Note:
low voltage on input = active/on DgOutSelFun
integer
R/W
Selects function for the digital output.
DgOutSelMap
integer
R/W
Selects a specific output function to be mapped to a register.
DgOutSelNum
integer
R/W
Selects the output to be used by number.
DgOutSelValue
integer
R
Shows the digital output state: Output conducting = on Output not conductng = off
Data Structures, Formats and Data Types for SmartConnex-II Data and formats
2.3.5
Name
KCM global variables: Analog I-O
Units
Type
AnInSelDB
percent
float
AnInSelMax
percent
float
AnInSelMin
percent
float
Scaling for the analog minimum value.
integer
Analog input source:
AnInSelSrc
2 2.3
R or R/W
Description
Deadband setting for this analog input. R/W
Scaling for the analog maximum value.
0 = CPU(0-10kHz), 1 = CPU(Analog), 2 = External AnInSelValue
percent
float
Actual value of the analog signal.
AnOutSelDB
percent
float
Deadband setting for this analog output.
integer
Analog output function select.
AnOutSelFun AnOutSelMax
percent
float
Scaling for the analog maximum value.
AnOutSelMin
percent
float
Scaling for the analog minimum value.
integer
Selection of the desired analog output for the KCM:
AnOutSelNum
CPU = 0, EXT1 = 1, EXT2 = 2, EXT3 = 3 AnOutSelValue
percent
integer
2.3.6
Name
Units
Actual value of the analog signal.
KCM global variables: Modbus I-O
Type
R or R/W
ExtIOBinding
integer
R/W
ExtIONodeSel
integer
R/W
ExtIOTypes
integer
R
ExtIOTypeSel
integer
R/W
Description
[0 to 3]
2 2.3
Data Structures, Formats and Data Types for SmartConnex-II Data and formats
2.3.7
Name
Units
HcuActCycle
KCM global variables: HCU Loader Params
Type
R or R/W
Description
integer
R
Describes where in the loading cycle the HCU controller is. Motor Timer(1), Load Delay(2), Loading(3), Line Clear(4), Discharge Delay(5), Discharge(6).
HcuActTime
seconds
integer
R/W
Shows the active time for the specified cycle.
HcuCommand
integer
R/W
HCU command to: None(0), Run(1), Stop(2), Clear Alarms(3), or Discharge(4)
HcuSelParmNum
integer
R/W
Number of parameter loaded
HcuSelParmValue
float
R/W
Shows the parameter value for the parameter number selected
HcuStatus
integer
R
HCU status to: None(0), Alarm(1), RecFull(3), Buf Full(4), Comm Fail(5), OK(6)
2.3.8
HcuSelParamNum Definitions
Number
Description
1
Load Timer
2
Line Clear Timer
3
Discharge Timer
4
Filter Delay Timer
5
Filter Pulse Timer
6
Motor Timer
7
Load Delay Timer
8
Discharge Delay Timer
9
Receiver Proximity Sensor
10
Buffer Hopper Proximity Sensor
11
Supply Hopper Proximity Sensor
12
Remote Start Timer
13
Remote Stop Timer
Data Structures, Formats and Data Types for SmartConnex-II Data and formats
Number
Description
14
Discharge Valve Switch
15
Differential Pressure Switch
16
Discharge Request Switch
17
Digital Input Set-Up (Xor Mask)
18
Operating Mode
19
Filter Clean Mode
20
Discharge Mode
21
Not used.
22
HCU Software Version
23
Supply Hopper Low Alarm Timer
24
Differential Pressure High Alarm Timer
25
Load Cycle Alarm Counter
26
Discharge Valve Alarm Timer
27
ON/OFF Counter
28
Run Time
29
Software Version of HSU
2 2.3
2 2.3
Data Structures, Formats and Data Types for SmartConnex-II Data and formats
2.3.9
Name
Units
KCM global variables: Communications
Type
R or R/W
Description
ConfigBaud
integer
R/W
Baud rate for the KCM config port.
ConfigMode
integer
R/W
Sets the KCM config port function.
HostFile
integer
R/W
Sets whether the built-in or downloaded kgr file is used by the host function in the KCM.
HostProt
integer
R/W
Defines the host protocol to be used.
KPort1Baud
integer
R/W
Baud rate for K-Port1.
KPort1Prot
integer
R/W
Defines the protocol for K-Port1.
KPort2Baud
integer
R/W
Baud rate for K-Port2.
KPort2Prot
integer
R/W
Defines the protocol for K-Port2.
2.3.10
Name
Units
KCM global variables: Miscellaneous
Type
R or R/W
Description
AutoSpanLimit
integer
R/W
Sets the limit on auto span calculation using the auto-calibration function.
AuxBoardType
integer
R
Defines the aux board type.
CalibCorrel
percent
float
R
Variance of flow during the calibration cycle.
CalibCorrLimit
percent
float
R/W
Sets the limit for variance of flow during the calibration cycle without canceling activity.
CalibDriveCmd
percent
float
R/W
Drive command used during the auto-calibration cycle.
CalibMatFed
weight
float
R
Amount of weigh the controller states was delivered during the autocalibration cycle.
CalibTime
seconds
integer
R/W
Time for the auto-calibrate cycle.
CheckWeight
weight
float
R/W
Measured amount of product delivered during the autocalibration cycle.
ChkWEnum
integer
R
Subscroll listing showing calibration status codes.
ControlType
integer
R
Type of controller application used.
Data Structures, Formats and Data Types for SmartConnex-II Data and formats
Name
Units
DeviceID
Type
R or R/W
Description
integer
R
KCM feeder type by a numeric code
2 2.3
LWF = 60, WBF = 61, SFM = 62, PID = 63, VOL = 64, LWB = 65 DgInFun[16]
integer
R/W
Function for the digital input selected.
DgInPol[16]
integer
R/W
Polarity of the input function selected.
DgOutFun[16]
integer
R/W
Function of the digital output selected.
DgOutMap[16]
integer
R/W
PSR or ASR map value of the selected digital output.
DgOutPol[16]
integer
R/W
Polarity of the output function selected.
DrvCmdCeiling
percent
integer
R/W
Sets the limit on how high drive command can go. It is a stop limit.
EmptyDC
percent
integer
R/W
The drive command used to empty the feeder.
integer
R/W
Defines the number of pulses per revolution of the primary velocity sensor.
float
R/W
Sets the totalizer increment.
integer
R/W
Sets the mode for setpoint control:
Encoder teeth ExternTotalInc
weight
FdrCtrMode
0 = local, 1 = ratio, 2 = direct, 3 = line1, 4 = line2, 5 = line3 up to 10 = line8 FeederAddress
integer
R
Address of the KCM.
FeederName
string
R/W
Name for the KCM. [14 bytes]
float
R
Time the feeder has been running in hours.
integer
R/W
Sets the type of application used.
integer
R/W
Built-in loader control, filter clear time.
GearReduction
float
R/W
Primary gear reduction for a feeder.
IDSetpoint
integer
FeederRunTime
hours
FeederType FltClearTime
msec.
Value for remembering pictures/graphics. Used by the KSC.
KLinkTxDelay
msec.
integer
R/W
Delays host transmissions to prevent network overloads.
MassflowFiltLen
seconds
integer
R/W
Display filter time constant.
binary
R
Operational status of the drive board. See document 0490020605 for details.
MDUStatus MaximumFlow
rate
float
R/W
Sets the limit for maximum flow.
MinimumFlow
rate
float
R/W
Sets the limit for minimum flow.
2 2.3
Data Structures, Formats and Data Types for SmartConnex-II Data and formats
Name
Units
Type
R or R/W
Description
NominalPower
watts
integer
R/W
Sets the maximum motor power to be drawn.
NominalSpeed
rpm
integer
R/W
Sets the maximum, rated motor speed.
NominalVoltage
volts
integer
R/W
Sets the limit for DC voltage to the motor.
PreLoadMFeqSP
Hz
integer
R/W
SerVarSubscrl
integer
R/W
Number of the service variable selected.
SerVarValue
float
R/W
Value of the service variable selected.
float
R/W
The ratio setpoint value.
integer
R
Condition under which the KCM was last stopped.
float
R/W
Totalizer preload value. Use <0> to clear totalizer.
integer
R/W
Selects the units of operation:
SetpointRatio
percent
StoppedBy TotalizPreload
weight
Units
0 = kg/hr, 1 = kg/min, 2 = lb/hr, 3 = lb.min, 4 = metr ton/hr, 5 = en ton/hr, 6 = g/hr, 7 = g/min
2.3.11
Name
Units
KCM variables: LWF
Type
R or R/W
Description
AdaptGain
float
R/W
Learned gain value for LWF.
AdaptTuning
integer
R/W
Sets adaptive tune function: 0 = off, 1 = on
AveFeedFactor
rate
DensArray
float
R
Average feeding factor.
integer
R/W
Turns on the Refill/Density array: 0 = off, 1 = on
FeedFactAlrmLim
percent
float
R/W
Sets the bounds on good values of feedfactor.
FeedFactArray1
rate
float
R
Shows the feedfactor value in the lower portion of the Refill array.
FeedFactArray5
rate
float
R
Shows the feedfactor value in the middle portion of the Refill array.
FeedFactArray9
rate
float
R
Shows the feedfactor value in the upper portion of the Refill array.
Data Data Str Struct uctur ures es,, Form Format ats s and and Data Data Typ Types es for for Sma Smart rtCo Conn nnex ex-I -III Data an and fo formats
2 2.3
Name
Units
T y pe
R or R/W
Description
FltClearTime
msec.
integer
R/W
Built-in loader control, filter clear time.
GearReductionLo
float
R/W
Sets the higher gear reduction/lowest speed for K2 feeders with dual speed gearboxes.
GearSwitch
integer
R/W
Turns on the dual speed control: 0 = high, 1 = low, 2 = auto high, 3 = auto low
InitialFeedFact
rate
LoadEna
float
R/W
Starting feedfactor
integer
R/W
Enables the built-in loader control: 0 = off, 1 = on
LoadMaxTime
seconds
integer
R/W
Sets the maximum load time for the built-in loader control.
LoadCloseTime
seconds
integer
R/W
Sets the valve close time for the built-in loader control.
LoadDischTime
seconds
integer
R/W
Sets the time for discharge for the built-in loader control.
LoadMotorTime
seconds
integer
R/W
Sets the motor run time for the built-in loader control.
integer
R/W
Turns on modulation:
Modulation
0 = off, 1 = on MotorCtrlGain
float
R/W
Motor gain set by user.
NetWtHighLimit
weight
float
R/W
Maximum high limit on net weight.
NetWtLowLimit
weight
float
R/W
Minimum low limit on net weight.
float
R
Actual pert value.
PertValue PostRefillDelay
seconds
integer
R/W
Sets the time for post refill function.
RefArrDevlimit
percent
float
R
Maximum allowed variance in feedfactor from empty to full points on the refill array curve.
RefillDelTime
seconds
integer
R/W
Time for refill to occur before an alarm.
integer
R/W
Turns on/off the automatic refill function:
RefillEna
0 = disabled, 1 = enabled, 2 = if running RefillLevelMax
weight
float
R/W
High weight level that turns off refill.
RefillLevelMin
weight
float
R/W
Low weight level that starts the refill.
integer
R/W
Sets the refill mode:
RefillMode
0 = Manual, 1 = Auto, 2 = AutoTerm
2 2.3 2.3
Data Data Stru Structu ctures res,, Format Formats s and and Data Data Type Types s for for Smart SmartCon Connex nex-II -II Data Data and and for form mats ats
Name
Units
Type
R or R/W
Description
ScrewSpeed
rpm
float
R
Displays screw RPM when Gear Reduction is set.
VibDisplSpan
float
R/W
Sets span for vibratory drive.
VibDispVal
float
R
Current vibratory displacement output.
VibKVNumber
integer
R/W
Sets the feeder type to KV1-KV3.
float
R/W
Maximum change allowed in Setpoint before the control behavior is executed execu ted on the vibratory calibration curve.
VibY0
float
R
Correction factor for vibratory feeder nonlinearity at 8% Drive Command.
VibY1
float
R
Correction factor for vibratory feeder nonlinearity at 12% Drive Command.
VibY2
float
R
Correction factor for vibratory feeder nonlinearity at 17% Drive Command.
VibY3
float
R
Correction factor for vibratory feeder nonlinearity at 23% Drive Command.
VibY4
float
R
Correction factor for vibratory feeder nonlinearity at 33% Drive Command.
VibY5
float
R
Correction factor for vibratory feeder nonlinearity at 50% Drive Command.
VibY6
float
R
Correction factor for vibratory feeder nonlinearity at 70% Drive Command.
VibSPChgLimit
percent
2.3. 2.3.12 12
Name
Units
KCM KCM vari variab able les: s: LWB LWB
Type
R or R/W
Description
AdaptGain AdaptGain
float
R/W
Learned gain value value for LWF LWF when adaptive tuning is active.
AdaptTuning AdaptTuning
integer
R/W
Sets adaptive adaptive tune tune to on/off: on/off: 0 = off, 1 = on
AveFeedFactor AveFeedFactor
rate
float
R
Current average average feeding feeding factor. factor.
BatCompMass
weight
float
R
Current batch weight delivered.
BatCompPerc
percent
float
R
Batch weight delivered in percent of setpoint.
Data Data Str Struct uctur ures es,, Form Format ats s and and Data Data Typ Types es for for Sma Smart rtCo Conn nnex ex-I -III Data an and fo formats
Name
Units
BatCount BatchTimeGrace
seconds
BatRefMode
2 2.3
T y pe
R or R/W
Description
integer
R
Number of batches delivered but does not increment for aborted batches.
integer
R/W
If this value plus the Maximum Batch Time is exceeded during batching, a batch time exceeded alarm will occur.
integer
R/W
Sets the refill mode type: 0 = undefined, 1 = refill after batch, 2 = pause batch to refill, 3 = refill while batching
BatSize
weight
BatState
float
R/W
Batch setpoint.
integer
R
State of batcher:
BatTime
seconds
integer
R/W
Batch time in seconds.
BatTolerance
percent
float
R/W
Sets batch tolerance for out of limit final batch value.
DribDC
percent
float
R/W
Drive command in dribble mode.
DribTime
sedonds
float
R/W
Time in dribble mode.
FastDC
percent
float
R/W
Drive command in normal mode.
FeedFactAlrmLim
percent
float
R/W
Sets the bounds on acceptable values of feedfactor.
FeedFactArray1
rate
float
R
Shows the feedfactor value in the lower portion of the Refill array.
FeedFactArray5
rate
float
R
Shows the feedfactor value in the middle portion of the Refill array.
FeedFactArray9
rate
float
R
Shows the feedfactor value in the upper portion of the Refill array.
FltClearTime
msec.
integer
R/W
Built-in loader control, filter clear time.
GearReductionLo
float
R/W
Sets the higher gear reduction/lowest speed for K2 feeders with dual speed gearboxes.
GearSwitch
integer
R/W
Turns on the dual speed control: 0 = high, 1 = low, 2 = auto high, 3 = auto low
InitialFeedFact JogEna
rate
float
R/W
Starting feedfactor.
integer
R/W
Enables the jog function. 0 = off, 1 = on
LoadEna
integer
R/W
Enables the built-in loader control. 0 = off, 1 = on
2 2.3
Data Structures, Formats and Data Types for SmartConnex-II Data and formats
Name
Units
Type
R or R/W
Description
LoadMaxTime
seconds
integer
R/W
Sets the maximum load time for the built-in loader control.
LoadCloseTime
seconds
integer
R/W
Sets the valve close time for the built-in loader control.
LoadDischTime
seconds
integer
R/W
Sets the time for discharge for the built-in loader control.
LoadMotorTime
seconds
integer
R/W
Sets the motor run time for the built-in loader control.
MaxBatSize
weight
float
R/W
Maximum allowable batch size.
integer
R/W
Turns on modulation:
Modulation
0 = off, 1 = on MotorCtrlGain
float
R/W
Motor gain as set by user.
NetWtHighLimit
weight
float
R/W
Maximum high limit allowed on net weight.
NetWtLowLimit
weight
float
R/W
Minimum low limit allowed on net weight.
float
R
Actual pert value.
integer
R/W
Sets the time for post refill function.
Preact1Pulses
integer
R/W
Preact value of motor encoder pulses from fast to dribble control.
Preact2Pulses
integer
R/W
Preact value of motor encoder pulses from dribble to stop.
PertValue PostRefillDelay
seconds
RefArrDevlimit
percent
float
R
Maximum allowed variance in feedfactor from empty to full points on the refill array curve.
RefillDelTime
seconds
integer
R/W
Time for refill to occur before an alarm
integer
R/W
Turns on/off the automatic refill function:
RefillEna
0 = disabled, 1 = enabled, 2 = if running RefillLevelMax
weight
float
R/W
High weight level that turns off refill.
RefillLevelMin
weight
float
R/W
Low weight level that starts the refill.
integer
R/W
Sets the refill mode:
RefillMode
0 = Manual, 1 = Auto, 2 = AutoTerm ScrewSpeed StableWtCnt
rpm
float
R
Displays screw RPM when Gear Reduction is set.
float
R/W
Number of stable weight readings after dribble that are required for batch complete.
Data Structures, Formats and Data Types for SmartConnex-II Data and formats
Name
Type
R or R/W
Description
StopPert
float
R/W
The net weight deviation above which a PERT will be detected.
VibDisplSpan
float
R/W
Sets span for vibratory drive.
VibKVNumber
integer
R/W
Sets the feeder type to KV1-KV3.
float
R/W
Maximum change allowed in Setpoint before the control behavior is executed on the vibratory calibration curve.
VibY0
float
R
Correction factor for vibratory feeder nonlinearity at 8% Drive Command.
VibY1
float
R
Correction factor for vibratory feeder nonlinearity at 12% Drive Command.
VibY2
float
R
Correction factor for vibratory feeder nonlinearity at 17% Drive Command.
VibY3
float
R
Correction factor for vibratory feeder nonlinearity at 23% Drive Command.
VibY4
float
R
Correction factor for vibratory feeder nonlinearity at 33% Drive Command.
VibY5
float
R
Correction factor for vibratory feeder nonlinearity at 50% Drive Command.
VibY6
float
R
Correction factor for vibratory feeder nonlinearity at 70% Drive Command.
VibSPChgLimit
Units
2 2.3
percent
2.3.13
Name
KCM variables: PID
Units
Type
R or R/W
Description
AveFeedFactor
rate
float
R
Current value of feedfactor.
DerContribFreq
Hz
integer
R
Value of frequency component due to Derivative control.
DerivLimit
Hz
integer
R/W
Limit to the amount of derivative action allowed.
DerivTime
seconds
float
R/W
Derivative time interval.
FeedFactAlrmLim
percent
float
R/W
Sets the bounds on good values of feedfactor.
InitialFeedFact
rate
float
R/W
Starting feedfactor.
InputFiltLen
seconds
float
R/W
Process variable input filter.
2 2.3
Data Structures, Formats and Data Types for SmartConnex-II Data and formats
Name
Units
Type
R or R/W
Description
IntContribFreq
Hz
integer
R
Value of frequency component due to Integral control.
IntegralTime
seconds
float
R/W
Integral time interval for control.
ProcessVariable
rate
float
R
Current process value.
PropContribFreq
Hz
integer
R
Value of frequency component due to proportional control.
PropGain
float
R/W
Amount of proportional gain applied to control.
PVinMax
float
R/W
Limit on process variable input-maximum.
PVinMin
float
R/W
Limit on process variable input-minimum.
PVInSelect
integer
R/W
Selects the type of process variable input.
SelfTune
integer
R/W
Turns on/off self tuning feature: 0 = off, 1 = on
TotalInhibit
integer
R/W
Turns on/off totalizer function: 0 = off, 1 = on
2.3.14
Name
Units
AutoReZero
KCM variables: SFM
Type
R or R/W
Description
integer
R/W
Turns on/off chute auto re-tare function: 0 = manual, 1 = auto
BlowOff
integer
R/W
Turns on/off blow-off function: 0 = off, 1 = on
BypassFunct
integer
R/W
Turns on/off Auto Bypass function: .0 = off, 1 = on
BypassInterval
float
R/W
Sets bypass valve operation interval.
BypassValve
integer
R/W
Turns on/off Bypass valve function: 0 = off, 1 = on
CalDC
percent
integer
R/W
Overall calibration drive command.
CalDC1
percent
integer
R/W
Calibration drive command at flow 1.
CalDC2
percent
integer
R/W
Calibration drive command at flow 2.
CalDC3
percent
integer
R/W
Calibration drive command at flow 3.
Data Structures, Formats and Data Types for SmartConnex-II Data and formats
Name
Units
CalDev CalMassFlow
weight
CalStep
2 2.3
Type
R or R/W
Description
float
R
Deviation over the calibration range.
float
R
Amount of product delivered during calibration cycle.
integer
R/W
Cal step 1-3 taken.
ChuteAngle
degrees
float
R/W
Angle of chute to horizon.
ChuteLength
meters
float
R/W
Length of chute.
ChuteThresh
weight
float
R/W
Weight below which chute weight is considered <0>.
float
R/W
Span value for chute.
float
R/W
Derivative time for control.
float
R/W
Span value for divert.
ChuteWgtSpan DerivTime
seconds
DivertWgtSpan DivertThresh
weight
float
R/W
Weight below which divert weight is considered <0>.
IntegralTime
seconds
float
R/W
Integral time interval for control.
InternalFiltLen
seconds
float
R/W
Massflow filter value.
MaterialFact0
weight
float
R
A0 flow error correction factor.
MaterialFact1
weight
float
R
A1 flow error correction factor.
MaterialFact2
weight
float
R
A2 flow error correction factor.
MaxMFAlrmLim
rate
float
R/W
Upper limit on massflow.
MinMFAlrmLim
rate
float
R/W
Lower limit on massflow.
OverallSpan‘
float
R/W
Overall calibration factor.
PropGain
float
R/W
Amount of proportional gain applied to control.
2 2.3
Data Structures, Formats and Data Types for SmartConnex-II Data and formats
2.3.15
KCM variables: VOL
Name
Units
Type
R or R/W
Description
Density
weight/ vol
float
R/W
Density of fed product that is entered for use in calibration.
CalWt1
weight
float
R/W
Calibration weight at Cal Drive Cmd 1.
CalWt2
weight
float
R/W
Calibration weight at Cal Drive Cmd 2.
CalDC1
percent
integer
R/W
Calibration drive command at step 1.
CalDC2
percent
integer
R/W
Calibration drive command at step 2.
Feedfactor
rate
float
R
Current value of feedfactor.
integer
R/W
Actuates power-on start function:
PowerOnStart
0 = off, 1 = on 2.3.16
Name
Units
BeltIdxEna
KCM variables: WBF
Type
R or R/W
Description
integer
R/W
Enables belt index function: 0 = off, 1 = on
BeltLength
meters
float
R/W
Length of belt.
BeltLoad
weight/ length
float
R
Beltloading value.
BeltLoadSetpt
weight/ length
float
R/W
Belt loading setpoint used for volumetric control.
BeltSlipAlrmLim
percent
float
R/W
Limit on belt slip.
BeltSlipValue
percent
float
R
Actual belt slippage.
BeltSpeed
m/min or ft/min
float
R
Actual belt speed.
DeckGap
meters
float
R/W
Distance between weigh bridges.
DriveDrumDiam
meters
float
R/W
Diameter of drive roller.
HiBeltLdAlrmLim
weight/ length
float
R/W
High belt loading alarm limit.
IntegralTime
seconds
float
R/W
Integral time interval for control.
LoBeltLdAlrmLim
weight/ length
float
R/W
Low belt loading alarm limit.
integer
R/W
Location, motor or roller for velocity sensor.
PickupPos
Data Structures, Formats and Data Types for SmartConnex-II Service variable index
2 2.4
Name
Units
Type
R or R/W
Description
PreFdrDist
meters
float
R/W
Distance of prefeeder to weigh bridge.
PreFdrTune
integer
R/W
Turns on Prefeeder autotune function.
PrefeedDCSpan
float
R/W
Spans the prefeeder drive command value to set belt loading.
TotalDeadBand
weight/ length
float
R/W
Sets the lower beltload that turns off the totalizer.
TransportDist
meters
float
R/W
Distance from weigh bridge to discharge.
WeighDeckLength
meters
float
R/W
Weigh bridge length.
2.4
Service variable index
This section presents service variable index information that is available on the KSU-II or KCM/KD. Go to the Machine Menu of the KSU-II or KCM/KD and to the Service Set-Up sub-menu.
Desc
Variable
PreLoad MF=SP
Preload MF value with SP upon KCM starts or SP changes
KLink Tx Delay
Enable K-Link to delay TxD to prevent network overloads
Empty DC
Value of drive command when emptying the feeder. Default is 70%. LWB and LWF only.
Auto Span Limit
Limit in actual range of the allowed span deviation from 1.000 to allow a auto-span calculation to proceed. Default is 0.98-1.02 or an entry of 0.02.
Com1 Read
Comm board K-Port 1 reads per second; <=100
Com1 Write
Comm board K-Port 1 writes per second:<=10
Com1 Err
Comm board K-Port 1 error counter:<= 1/hour
Com2 Read
Comm board K-Port 2 reads per second:<=100
Com2 Write
Comm board K-Port 2 writes per second:<=10
Com2 Err
Comm board K-Port 2 error counter:<= 1/hour
Host Read
Host channel reads per second: <=100
Host Write
Host channel writes per second: <=10
Host Err
Host channel error counter: <= 1/hour
IntCh msgs
Internal channel (SFT/MDU) messages per second
IntCh err
Internal channel (SFT/MDU) error counter
IntCh Load
Internal channel (SFT/MDU) loading in percent: <= 50%
IntCh Node
Internal channel (SFT/MDU) last failed node
IntCh Opcode
Internal channel (SFT/MDU) last opcode
ResConfPort
Resets the config port to defaults
RefArr Dev Lim
Maximum allowed variance in Feedfactor from Empty to Full points on the Refill Array curve
Modulation%
Screw modulation-percent- amplitude, debug variable.
KCDR-K10S
When set to <1> configures K-Port 1 to function with a K-Commander or KDU using extended software. When set to <0> returns K-Port 1to normal function.
ReprogCommBd
When this variable is set to <1> and KCM power is cycled, automatic reprogramming of the comm board by the KCM will occur. This value is reset to <0> after the programming activity is complete.
3 3.1
I-O Functions Global I-O functions for all applications
3
I-O Functions
This section presents I-O mapping for KCM products with parameter code. These functions will be found in the I-O menu.
3.1
Global I-O functions for all applications
3.1.1
Global digital inputs
A true/on condition results in the desired action.
Name
Function List
None=0 Start=1 Stop=2 Interlock=3 Run Enable=4 ALS Input=5 Al. Ack=6 Al. Clr=7 Start/Stop=8 Vol Mode=9 Loc/Ext=10 Ratio/ Direct=11 External alarm=12 Totalizer Clear=13 Data Lock=14
3.1.2
Name
None=0 Setpoint=1
No function assigned. Start Machine Stop Machine Downstream interlock for temporary stop of machine. Run enable to stop and prohibit machine from starting. Alarm shutdown input Alarm Acknowledge Alarm Clear One-wire start stop. True = Start/False = Stop Force to volumetric mode if true. Local or external setpoint source. 1= Ext, 0=Local Ratio or direct mode.1=Direct, 0=Ratio Input for an external alarm. Input to clear totalizer. Input to lock data from being changed.
Global analog setpoint input
Function List
No function assigned. Feeder setpoint. = (10kHz/Max SP) x Actual SP or = (20ma/Max SP) x Actual SP
I-O Functions Global I-O functions for all applications
3.1.3
Global digital outputs
A true/on condition is the result.
Name
Function List
None=0 Feeder Run=1 Any Alarm=2 Hard Alarm Relay=3 ALS Output=4 Drive Ena=5 Mass Mode=6 PSR-Map=7 ASR-Map=8 Totalizer Pulse=9
3.1.4
Name
None=0 Setpoint=1 Massflow=2 Net Weight=3
No function assigned. Output is true if feeder is running Output is true for any alarm situation Relay output is true only for any hard alarm condition. Alarm shutdown output. Output is true when the Driver Enable line is active- drive should run. Output is true when feeder is in mass mode. Output is true when the selected PSR bit is true. See PSR mapping for LWF application.(Process Status) Output is true when the selected ASR bit is true. See ASR mapping for LWF application. (Alarm Status) Output for totalizer pulses.
Global analog outputs
Function List
No function assigned. Setpoint normalized to maximum rate. =(20ma/Max Setpoint) x Massflow Setpoint Massflow normalized to maximum rate. =(20ma/Max Setpoint) x Massflow Net Weight normalized to gross range. (This may also be NetWeight1 for a belt feeder or Chute Net Weight for the SFM.) =(20ma/Scale Range) x Netweight
3 3.1
3 3.2
I-O Functions LWF I-O
3.2
LWF I-O
This section presents I-O variables for Loss-in-Weight feeder applications. 3.2.1
LWF digital inputs
Add the following to the global digital input listing. A true/on condition results in the desired action. Name
Function List
Batch Pause=15 Empty=16 Ref Bypass=17 Ref Cmd=18 Calib=19 Loader Level=20 Loader Enable=21
3.2.2
Empty the feeder now Refill Bypass Refill Command (force refill) Starts the Auto Calibration routine. Loader is at its full level. Enables the loader function
LWF analog setpoint input
See global listing. 3.2.3
LWF digital outputs
Add the following to the global digital output listing. A true/on condition is the result. Name
Refill=10 Refill Expired=11 Loader=12 Blow-off=13 HiLoGear=14 Dribble=15 Batch Complete=16
Function List
Output is true when a refill is called for. Output is true when the refill time has expired and refill did not complete. Runs loader motor. Turns on blow off feature for loader. Selects either Hi or Lo gear function for K2 feeders. Dribble mode active Batch completed
I-O Functions WBF I-O
3.2.4
3 3.3
LWF analog outputs
Add the following to the global analog output listing. Name
Function List
Drive Cmd=4 Motor Speed=5 Feedfactor=6
3.3
Drive command. =(20ma/100%) x (%Drive Command) Motor speed normalized to maximum motor speed. = (20ma/Max motor rpm) x Actual motor speed Computed feedfactor as a function of the initial value. =(20ma/Initial Feedfactor) x Average Feedfactor
WBF I-O
This section presents I-O variables for Weigh Belt feeder applications. 3.3.1
WBF digital inputs
Add the following to the global digital input listing. A true/on condition results in the desired action.
Name
Function List
Empty=15 Empty the feeder now Belt Drift=16 Input for belt drift detection Belt Index=17 Belt index function input Dynamic A dynamic tare is to occur Tare=18
3.3.2
WBF analog setpoint input
See global listing. 3.3.3
WBF digital outputs
Add the following to the global digital output listing. A true/on condition is the result.
Name
Tare Run=10 Prefeeder Drive Enable=11
Function List
A dynamic tare is ongoing if true. Enable the prefeeder to run.
3 3.4
I-O Functions PID I-O
3.3.4
WBF analog outputs
Add the following to the global analog output listing.
Name
Function List
NW1=3 NW2=4 DriveCommand=5 Motor speed=6 Belt Load=7 Prefeeder=8
3.4
= (20mA/ScaleRange)*NetWeight 1 (Netweight on the primary weigh bridge) = (20mA/ScaleRange)*NetWeight 2 (Netweight on the secondary weigh bridge if used) = (20mA/100%) x Percent drive command = (20mA/Max Mot RPM) x Act Mot Speed Actual belt loading as a function of Belt Load SP. = (20ma/Belt Load SP) x Current belt loading Value of the prefeeder signal. For Soder feeder select Direct algorithm. = (20 ma)*(DrvCmd)*PrefeederSpan
PID I-O
This section presents I-O variables for PID applications. 3.4.1
PID digital inputs
Add the following to the global digital input listing. A true/on condition results in the desired action. Name
Function List
Calib=15
Starts the Auto Calibration routine.
3.4.2
PID analog setpoint input
See global listing. 3.4.3
PID analog process input
This entry is preset. 3.4.4
PID digital outputs
See global listing. A true/on condition is the result.
I-O Functions VOL I-O
3.4.5
3 3.5
PID analog outputs
Add the following to the global analog output listing.
Name
Function List
PVUInput=3 Drive Command=4 Motor Speed=5 Feedfactor=6
3.5
=(20mA/100%)xPVinput value percent of maximum = (20mA/100%) x Percent drive command = (20mA/Max Mot RPM) x Act Mot Speed Computed feedfactor as a function of the initial value. =(20ma/Initial Feedfactor) x Average Feedfactor
VOL I-O
This section presents I-O variables for VOL applications. 3.5.1
VOL digital inputs
Add the following to the global digital input listing A true/on condition results in the desired action.
Name
Function List
Calib=15
Starts the Auto Calibration routine.
3.5.2
VOL analog setpoint input
See global listing. 3.5.3
VOL digital outputs
See global listing. A true/on condition is the result. 3.5.4
VOL analog outputs
Add the following to the global analog output listing.
Name
Drive Command=3 Motor Speed=4
Function List
= (20mA/100%) x Percent drive command = (20mA/Max Mot RPM) x Act Mot Speed
3 3.6
I-O Functions SFM I-O
3.6
SFM I-O
This section presents I-O variables for SFM applications. 3.6.1
SFM digital inputs
Add the following to the global digital input listing. A true/on condition results in the desired action.
Name
Function List
Bypass Fb=15 Normal Fb=16
Input from the Bypass valve position contact- Bypass position Input from the Bypass valve position contact- Normal position
3.6.2
SFM analog setpoint input
See global analog setpoint input list. 3.6.3
SFM digital outputs
Add the following to the global digital output listing. A true/on condition is the result.
Name
Function List
Bypass Valve=10 BlowOff=11
3.6.4
Bypass valve is in bypass mode if true Blowoff function is active if true
SFM analog outputs
Add the following to the global analog output listing. Name
Net Chute=3 Net Divert=4 DriveCommand=5 Motor speed=6 Feedfactor=7
Function List
Net weigh on the chute = (20mA/ScaleRange)*NetWeight_Chute Net weight on the divert channel = (20mA/ScaleRange)*NetWeight_Divert = (20mA/100%) x Percent drive command = (20mA/Max Mot RPM) x Act Mot Speed Computed feedfactor as a function of the initial value. =(20ma/Initial Feedfactor) x Average Feedfactor
I-O Functions LWB I-O
3.7
3 3.7
LWB I-O
This section presents I-O variables for Loss-in-Weight batch applications. 3.7.1
LWB digital inputs
Add the following to the global digital input listing. A true/on condition results in the desired action.
Name
Function List
Ref. Bypass=11 Ref. Cmd=12 Ext. Al.=13 Pause=14 Empty15 FF Calibration=16
3.7.2
Refill Bypass Refill Command (force refill) Customer alarm from external source. If true, will force a batch pause If true, will initiate a empty function of the batch feeder If set to true, will initiate a feedfactor calibration routine.
LWB analog batch setpoint input
Name
Function List
Batch Size=1
3.7.3
Batch size setpoint. = (10kHz/Max Batch SP) x Actual Batch SP or = (20ma/Max Batch SP) x Actual Batch SP
LWB digital outputs
Add the following to the global digital output listing. A true/on condition is the result.
Name
Refill=10 Refill Expired=11 Loader Run=12 Blow-off=13 HiLoGear=14 Dribble=15 Batch Complete=16
Function List
Output is true when a refill is called for. Output is true when the refill time has expired and refill did not complete. Runs loader motor. Turns on blow off feature for loader. Selects either Hi or Lo gear function for K2 feeders. Output is true if the unit is in dribble mode Output is true if the unit has reached batch complete
3 3.7
I-O Functions LWB I-O
3.7.4
LWB analog outputs
Add the following to the global analog output listing. Name
Net Weight=1 Drive Command=2 Motor Speed=3 Feedfactor=4 Batch Size=5 Batch% Complete=6
Function List
Net Weight normalized to gross range. =(20ma/Scale Range) x Netweight = (20mA/100%) x Percent drive command = (20mA/Max Mot RPM) x Act Mot Speed Computed feedfactor as a function of the initial value. =(20ma/Initial Feedfactor) x Average Feedfactor Batch Size = (20ma/Max Batch Size) x Actual Batch Size Percentage of batch complete =(20ma/Batch Size) x Actual Amount Batched
Command Functions Overview
4
Command Functions
4.1
Overview
4 4.1
This section presents control and status functions for operation of the KCM system. Command functions are to be entered as alphanumeric values in Smart K-Link. They must be entered in upper case letters for a machine and in lower case letters for line function. For commands to be activated, a trigger will have to be provided at the PLC. This trigger can be a rising (HIT) or falling edge (LOT), a high (HI) or low (LO) level or an action on either transit ion (XOT). The (HIT) trigger is preferred for most situations.
4.2
Command tables for action functions
4.2.1
Global command table
Description
Mnemonic
Alarm acknowledge Alarm clear Stop Start Clear database invalid bit in PSR Stop and preserve alarms Clear totalizer Enable totalizer-PID only Disable totalizer-PID only
4.2.2
CALA CALC CSPC CSTC CDBI CSPA CTOC CTON CTOF
HCU Loader command table
Description
HCU Loader clear alarms HCU Loader Discharge to OFF HCU Loader Discharge to ON HCU Loader Run HCU Loader Stop
Mnemonic
CHCA CHDF CHDO CHRU CHST
4 4.2
Command Functions Command tables for action functions
4.2.3
LWF command table
Description
Mnemonic
Set MASS mode flag Set VOL. Mode flag Set tare values from gross weight Automatic feed factor calculation Empty feeder Refill start
4.2.4
CMAM CVOM CTAR CCFF CETY CCRF
WBF command table
Description
Mnemonic
Set MASS mode flag Set VOL. Mode flag Set static tare values from gross weight Dynamic belt tare Empty feeder Automatic feed factor calculation
4.2.5
CMAM CVOM CTAR CTR2 CETY CCFF
PID command table
Description
Mnemonic
Set MASS mode flag Set VOL. Mode flag Command ramp down of manual output Command ramp up of manual output
4.2.6
VOL command table
Use global commands only.
CMAM CVOM CMRD CMRU
Command Functions Command tables for action functions
4.2.7
LWB command table
Description
Mnemonic
Set MASS mode flag Set VOL. Mode flag Set tare values from gross weight Automatic feed factor calculation Clear batch count Pause batch run Empty feeder Refill start
4.2.8 Description
Set MASS mode flag Set VOL. Mode flag Tare chute & plate sft
CMAM CVOM CTAR CCFF CCBC CPAS CETY CCRF
SFM command table Mnemonic
CMAM CVOM CTAR
4 4.2
5 5.1
Condensed Process Status Variables Condensed process status variable table
5
Condensed Process Status Variables
5.0.1
Introduction
This section presents the process status variables that are presented for operational analysis. The variable that is read is a 32 bit (2 register value) with the mnemonic of
. When the condition is present, the specific bit is set high.
5.1
Condensed process status variable table
Bit code is the bit location in the CondensedProcStatus word 5.1.1
Bit Code 0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23
Condensed global process status variable table
Function
KSU-II or KCM/KD display is present Database invalid Alarm Shutdown Input active Disable Input active Line mode active Unused Auto calibration in progress CVAR – Examine changed variable Unused Machine running Drive Enabled Mass/Grav Mode Alarm relay active Alarm Shutdown output active Any hard alarm is present Any soft alarm is present - not timed out Unused Unused Unused Unused Unused Unused Unused Unused
Condensed Process Status Variables Condensed process status variable table
Condensed global status variable table, con’t Bit Code 24 25 26 27 28 29 30 31
Function
KCM initialization complete Unused Unused Feeder emptying HCU loading Waiting to run Smart K-Link Initialization complete Pert function active
5.1.2
Condensed LWF process status table
Please see the global process status table for bits not shown here. Bit
Function
Code 8 16 18 19 20 21 22 23
Refill window set true Refill Time-out set Built-in Loader function enabled Ratio setpoint mode Direct setpoint mode Refill_Enabled Refill set to Auto mode Refill timer set on (KCM = always true)
5.1.3
Condensed WBF process status table
Please see the global process status table for bits not shown here.
Bit Code 8 19 20
Function
Dynamic tare active Ratio setpoint mode Direct setpoint mode
5 5.1
5 5.1
Condensed Process Status Variables Condensed process status variable table
5.1.4
Condensed PID process status table
Please see the global process status table for bits not shown here.
Bit Code 19 20
Function
Ratio setpoint mode Direct setpoint mode
5.1.5
Condensed VOL process status table
Please see the global process status table for bits not shown here.
Bit Code 19 20
Function
Ratio setpoint mode Direct setpoint mode
5.1.6
Condensed LWB process status table
Please see the global process status table for bits not shown here.
Bit Code 8 16 18 19 20 21 22 23 26
Function
Refill window set true Refill Time-out set Built-in Loader function enabled Paused Batch complete Refill_Enabled Refill set to Auto mode Refill timer set on (KCM = always true) Dribble active
Condensed Process Status Variables Condensed process status variable table
5.1.7
Condensed SFM process status table
Please see the global process status table for bits not shown
Bit Code 18 19 20
Function
Refill Bypass enabled Ratio setpoint mode Direct setpoint mode
5 5.1
6 6.1
Expanded Process Status Word - PSW Expanded PSW tables
6
Expanded Process Status Word - PSW
6.0.1
Introduction
This list set is used for expanded PSW mapping for PSW bits 0-95. Many of these special bits can be mapped to a digital output. These bit functions are not used for Smart K-Link applications.
6.1
Expanded PSW tables
6.1.1
PSW word mapping
Here is a list that identifies the PSW word number with the Process ID code. Each PSW word is 32 bits long. The bit is set to TRUE at the condition specified.
Word Number
Bit Range
Word(0)
0-31
Word(1)
32-63
Word(2)
64-95
6.1.2
Global PSW Map
These process codes are common for all K-Tron machines. This is the bit number entered into the Smart K-Link PSW word configuration.
PSW(Process number)
Description
DB Initialized(0)
• Not used
CVAR(1)
• Not used
Run(2)
• Motor/machine running
Disa(3)
• Run disabled by Interlock input or run enable input
Ena(4)
• Drive output enabled
ALS_In(5)
• Alarm shutdown input active
ALS_Out(6)
• Alarm shutdown output active
AL_Rel(7)
• Alarm relay active
Hard_AL(8)
• Complement of AL_Rel
Soft_AL(9)
• On for any alarm present
Expanded Process Status Word - PSW Expanded PSW tables
PSW(Process number)
Description
Emptying(13)
• Machine is being emptied by Empty function
Wait(15)
• Feeder received a start command but is waiting
Start_OK(20)
• Start input will start feeder
HCU_Alarm(32)
• HCU loader alarm
HCU_Rec_Full(33)
• Loader receiver is full
HCU_Buf_Full(34)
• HCU alarm
HCU CommFail(35)
• HCU communication failure to CPU
HCU_Loading(36)
• HCU loading status
Hard_interlock(40)
• Drive (MDU) hard interlock input status
Interlock_In(41)
• Interlock input bit status
Enable_In(42)
• Run enable input bit status
Vol_Mode_In(46)
• Volumetric input bit status
Extern_In(47)
• Machine set for External SP bit input
Direct_In(48)
• Machine set for Direct SP bit input
Ext_Al_in(49)
• External alarm input bit active
Disp_Present(64)
• KCM/KD display present
CPU_Init_cpl(65)
• CPU initialization complete
Mass_mode(66)
• Unit in Grav mode
Calib(67)
• Currently running an auto calibrate routine
6 6.1
6 6.1
Expanded Process Status Word - PSW Expanded PSW tables
6.1.3
LWF PSW Map
Use these additional codes for all LWF machines.
PSW(Process number)
Description
Refill_Bypass_In(45)
• Refill bypass bit input is set for LWF
Gear_Sw_Out(51)
• Hi (Lo) gear switch output bit state
Blowoff_Out(52)
• Filter blowoff function output bit state
Pert(68)
• Unit in PERT condition
Refill(69)
• Feeder is refilling by automatic means
Ref_Timeout(70)
• Refill timer has expired
Loader_Full(75)
• Loader full input to control
Loading(76)
• Loader motor is running
Load_Ena(77)
• Loader is enabled to run
6.1.4
WBF PSW Map
Use these additional codes for all WBF machines.
PSW(Process number)
Description
Sec-Deck(14)
• Secondary weigh bridge is active
Prefeeder enabled(50)
• Prefeeder enable output bit state
BeltDrift(53)
• Belt drift has been detected
BeltIndex(54)
• Belt index function bit state
Dynamic tare ongoing(70)
• Dynamic tare is in progress
6.1.5
PID and VOL PSW Map
Use the global PSW map only.
Expanded Process Status Word - PSW Expanded PSW tables
6.1.6
SFM PSW Map
Use these additional codes for all SFM flowmeters.
PSW(Process number)
Description
BP-Open-In(43)
• Bypass valve open input bit status is true
BP-Close-In(44)
• Bypass valve close input bit status is true
Blowoff_Out(52)
• Filter blowoff function bit state.
Pert(68)
• Unit in PERT condition
Bypass(69)
• Bypass output bit state
Unstable(71)
• Weight is unstable on SFM
6.1.7
LWB PSW Map
Use these additional codes for all LWB machines.
PSW(Process number)
Description
Pause(12)
• Batcher has paused.
Gear_Sw_Out(51)
• Hi (Lo) gear switch output enabled
Blowoff_Out(52)
• Filter blowoff bit state
Pert(68)
• Unit in PERT condition
Refill(69)
• Feeder is refilling by automatic means
Ref_Timeout(70)
• Refill timer has expired
Loader_Full(75)
• Loader full input to control
Loading(76)
• Loader motor is running
Load_Ena(77)
• Loader is enabled to run
BatchComplete(78)
• Batch has completed
Dribble(79)
• Batcher is in dribble mode
6 6.1
7 6.1
Alarm Status Variables-ASW Expanded PSW tables
7
Alarm Status Variables-ASW
7.0.1
Introduction
This section presents the alarm status variables that provide feedback on all types of machine alarms. You have 95 bits of alarm reporting. If you wish to limit the register requirement you may bit map selected conditions or extract the 32 bit Condensed Alarm Status-ASR word in two registers. These are in the KCM. 7.0.2
ASW word mapping
Here is a list that identifies the ASW word number with the Alarm ID code. Each ASW word is 32 bits long
Word Number
Bit Range
Word(0)
0-31
Word(1)
32-63
Word(2)
64-95
Alarm Status Variables-ASW Alarm status word tables-ASW
7.1
Alarm status word tables-ASW
7.1.1
Global ASW alarm status table
7 7.1
These alarm codes are common for all K-Tron machines. This is the bit number entered into the Smart K-Link ASW word configuration. Note:
Some global entries will not be used for VOL and PID applications since SFTs are not employed.
ASR(Alarm number)
Description
K-Prom_Fail(1)
• Checksum error in parameter memory
K-Prom_Fail(2)
• Checksum error in kgr file area
Power_Glitch(3)
• Power dip detected. CPU did not reset
Int_Chan_Fail(5)
• Internal channel has failed to communicate between the CPU and drive pcbs
Gen_Weight_Fail(6)
• SFT(s) failed • Serial communication to the load cell interrupted • f = SFT internal failure. communication OK • t = No communication from the SFT to the controller board • ?= Not valid answer from SFT
Incorrect_Num_SFT (7)
• Number of SFTs found during polling does not match that required
Bad_SFT_Status(8)
• SFT is showing an incorrect status
No_MDU-Found(9)
• The drive pcb is not function with respect to the CPU pcb
MDU Failure(10)
• Motor drive has failed
MDU_Timeout(11)
• CPU pcb not communicating with the Drive pcb
MDU_Thermal(12)
• Drive temperature has exceeded deg C
MDU_Speed(13)
• No speed feedback signal is present when motor is asked to run
7 7.1
Alarm Status Variables-ASW Alarm status word tables-ASW
ASR(Alarm number)
Description
MDU_Current(14)
• Motor current limit is exceeded
MDU_SRelay(15)
• Safety relay disconnected while running
MDU_Motor(16)
• No current in motor leads when motor is supposed to run
MDU_Control(17)
• Drive problems
MDU_EEPROM(18)
• EEPROM checksum failed
MDU_Drive_Fail(19)
• MDU drive pcb has failed
MDU_Polarity(20)
• Coil polarity is incorrect on the vibratory drive (Vibratory feeder only)
HCU_Removed(21)
• HCU was removed
HCU_Alarm(22)
• HCU has an alarm
HCU_EEPROM(23)
• EEPROM failed
HCU_Driver(24)
• The controller's digital output driver has detected a fault
HCU_Supp_Hp(25)
• Material is below the level of the supply hopper proximity sensor • Sensor failed
HCU_Filter_DP(26)
• The differential pressure across the filter is too high indicating a clogged filter
HCU_CycCount(27)
If P20 Discharge Mode =01“Fill” mode then: • Max. numbers of load cycle exceeded, because Buffer Hopper Low input has been active (on) for more than the allowed load cycles. The Buffer Hopper Low signal going inactive clears the load cycle counter If P20 Discharge Mode =02 (LWF) mode then: • Discharge Request input has been on for more than the allowed load cycles. The Discharge Request signal going inactive clears the load cycle counter
Alarm Status Variables-ASW Alarm status word tables-ASW
ASR(Alarm number)
Description
HCU_DischVlv(28)
• Discharge valve has failed to either open or close properly. This alarm is automatically disabled in P18 Operating Modes 03 and 04
HCU_Rec_Full(29)
• Receiver is still full after discharge. • Receiver proximity switch too sensitive adjusted or failed
KLinkWrongFile(30)
• Protocol of KGR file does not match that required by the installed communication circuit card
KLink_No_File(31)
• No KGR file loaded
KLink_HPortFail(32)
• Host communication pcb error
KLink_HPortFail Init(33)
• Host communication pcb could not be initialized
KLink_HPort_IllegBd (34)
• Improper pcb installed in the host port location
KLink_KPort Fail(35)
• Check Host circuit card
KLink_KPortFail Init(36)
• Check Host circuit card
KLink_KPort_IllegBd (37)
• Host communication pcb is installed on the wrong port location-(K-Port)
KLink_BadKGR(38)
• One or more feeder parameters are not correct for the specified feeder
Ext_IO_Fail(39)
• The MODBUS I-O connection has failed
External Alarm(40)
• Digital input on KCM selected for External Alarm is active
Aux_interlock(41)
• Run Enable digital input has failed
Start_Ignored(42)
• Start conditions not fulfilled
MF-High(43)
• The current massflow is above the tolerance entered in menu parameter
MF_Low(44)
• The current massflow is below the tolerance entered in menu parameter
7 7.1
7 7.1
Alarm Status Variables-ASW Alarm status word tables-ASW
ASR(Alarm number)
Description
DC_Ceiling(45)
• Drive command has reached the limit
DC_High(46)
• The drive command has exceed the value Limit in the menu
DC_Low(47)
• The drive command has dropped below the value Limit in the menu
Check_Brush(48)
• DC motor brushes may be wearing out and ready to fail.
7.1.2
LWF alarm status definitions
Use these in addition to the global values.
ASR(Alarm number)
Description
FF_Alarm(52)
• Feedfactor is either zero or outside the Feedfactor alarm limit
Scale_Over(53)
• Scale is over its range
Scale_Under(54)
• Scale is reading under zero
Weight_High(55)
• Weight is above the High Limit
Weight_Low(56)
• Weight is below the Low Limit
Refill_Time(57)
• Refill timer has expired
Loader_Empty(58)
• Loader is empty
Low_Gain(61)
• Adaptive gain has dropped below 10, the value will be locked at 10 and a alarm will display.
7.1.3
VOL alarm status definitions
Use only the appropriate global values.
Alarm Status Variables-ASW Alarm status word tables-ASW
7.1.4
WBF alarm status definitions
Use these in addition to the global values.
ASR(Alarm number)
Description
Belt_Slip(52)
• Belt is slipping beyond the belt slip limit
Scale_Over(53)
• Scale is over its range
Scale_Under(54)
• Scale is reading under zero
Weight_High(55)
• Weight is above the High Belt Load Limit
Weight_Low(56)
• Weight is below the Low Belt Load Limit
Belt_Drift(57)
• The belt is drifting off the machine
Belt_Buildup(58)
• Belt is accumulating material beyond the limit.
7.1.5
LWB alarm status definitions
Use these in addition to the global values.
ASR(Alarm number)
Description
FF_Alarm(52)
• Feedfactor is either zero or outside the Feedfactor alarm limit
Scale_Over(53)
• Scale is over its range
Scale_Under(54)
• Scale is reading under zero
Weight_High(55)
• Weight is above the High Limit
Weight_Low(56)
• Weight is below the Low Limit
Refill_Time(57)
• Refill timer has expired
Loader_Empty(58)
• Loader is empty
BatchTolerance(59)
• Batch tolerance limit has been exceeded
BatchTime2Hi(60)
• Batch time limit has been exceeded
7 7.1
7 7.1
Alarm Status Variables-ASW Alarm status word tables-ASW
7.1.6
PID alarm status definitions
Use these in addition to the global values.
ASR(Alarm number)
Description
FF_Alarm(52)
• Feedfactor is either zero or outside the Feedfactor alarm limit
7.1.7
SFM alarm status definitions
Use these in addition to the global values.
ASR(Alarm number)
Description
Range_Div(53)
• Divert channel is over its range
Range_Chute(54)
• Chute channel is over its range
Over_Flow(55)
• Rate is above the maximum limit
NoFlow(56)
• No flow condition has been detected
Valve(57)
• Bypass valve has failed
Condensed Alarm Status Words-ASR Tables of condensed alarm status words
8 8.1
8
Condensed Alarm Status Words-ASR
8.0.1
Introduction
This section presents the various condensed alarm status words for those who only wish to import a maximum of 2 registers or alarm data. A list for each type of application will be presented here.
8.1
Tables of condensed alarm status words
8.1.1
Global ASW condensed alarm status table
These condensed alarm codes are common for all K-Tron machines. This is the bit number entered into the Smart K-Link ASW word configuration. A 32 bit word is used to describe the Condensed Alarm Status. Note:
Some global entries will not be used for VOL and PID applications since SFTs are not employed.
ASR(Alarm number)
Description
Ext_Alr(1)
• External Alarm active
DC_High, and DC_Ceiling(14)
• Either drive command has exceeded the high limit or tried to exceed the ceiling
DC_Low(15)
• Drive command has dropped below the Low DC limit
Num_SFT(19)
• Number of SFTs is incorrect
Internal_Channel_F ail(20)
• Internal channel on which the SFTs
Weight_Fail, Bad_SFT_Status (21)
• Weighing system failure
Hardware failure(22)
• All hardware and KPort or K-Link problems
MDU(23)
• Any related drive problem is identified here
Interlock(24)
• An interlock is active
Start_Ignored(25)
• A start input has been ignored
HCU problems(26)
• Any HCU problem is grouped here
8 8.1
Condensed Alarm Status Words-ASR Tables of condensed alarm status words
8.1.2
LWF condensed alarm status definitions
Use these in addition to the global values.
ASR(Alarm number)
Description
FF_Alarm(0)
• Feed factor alarm active
Loader_Empty(3)
• Loader is empty of product
Weight_High(5)
• Weight is above the high limit
Weight_Low(8)
• Weight is below the low limit
Scale_Over(9)
• Scale is over-range
Scale_Under(10)
• Scale is under-range
Refill_Time(11)
• Refill timer has expired
MF_High(12)
• Massflow is above the high limit
MF_Low(13)
• Massflow is below the low limit
8.1.3
VOL condensed alarm status definitions
Use only the appropriate global values.
8.1.4
WBF condensed alarm status definitions
Use these in addition to the global values.
ASR(Alarm number)
Description
Belt_Slip or Belt_Drift(0)
• Either belt slippage or belt drift is the problem
Belt_Buildup(2)
• Belt has buildup that exceeds the limit
Hi_Belt_Load(8)
• Belt loading exceeds the limit
Scale_Over(9)
• Scale is over-range
Scale_Under(10)
• Scale is under-range
Lo_Belt_Load(11)
• Belt loading is below the limit
Condensed Alarm Status Words-ASR Tables of condensed alarm status words
8.1.5
LWB condensed alarm status definitions
Use these in addition to the global values.
ASR(Alarm number)
Description
FF_Alarm(0)
• Feed factor alarm active
Loader_Empty(3)
• Loader is empty of product
BatchTime2High(4)
• Batch time has expired
Weight_High(5)
• Weight is above the high limit
Weight_Low(8)
• Weight is below the low limit
Scale_Over(9)
• Scale is over-range
Scale_Under(10)
• Scale is under-range
Refill_Time(11)
• Refill timer has expired
MF_High(12)
• Massflow is above the high limit
Batch_Tolerance(13)
• Batch is out of tolerance
8.1.6
PID condensed alarm status definitions
Use these in addition to the global values.
ASR(Alarm number)
Description
FF_Alarm(0)
• Feedfactor is either zero or outside the Feedfactor alarm limit
8.1.7
SFM alarm status definitions
Use these in addition to the global values.
ASR(Alarm number)
Description
Range_Div(2)
• Divert channel is over its range
Range_Chute(5)
• Chute channel is over its range
NoFlow(8)
• No flow condition has been detected
Over_Flow(9)
• Rate is above the maximum limit
Valve(10)
• Bypass valve has failed
8 8.1
9 9.1
KSL Line Functions KSL line variable listing
9
KSL Line Functions
9.0.1
Introduction
This section shows the variables for KSL Line Function. The mnemonics are indicated by lower case characters.
9.1
KSL line variable listing
Note:
Access information:’R’ means Smart K-Link output only,’R/W’ means the variable is both an input and output value. 9.1.1
KSL numeric parameters
Here is a listing of KSL line variables.
Name
Units
Type
R or R/W
Description
LineBatchSize
weight
float
R/W
Total batch size of line – for batch applications only.
LineMaxBatchSize
weight
float
R/W
Maximum total batch size of line – for batch applications only.
LineMaxRate
rate
float
R/W
Full scale line massflow rate.
LineMassflow
rate
float
R
Actual line massflow rate.
LineSetpoint
rate
float
R/W
Line target massflow setpoint.
LineBatchCompleteMass
weight
float
R
Actual weight delivered in the total batch.
LineBatchCompletePercent
percent
float
R
Actual weight delivered in the total batch in percent of the line batch setpoint.
LineTotalizer
weight
float
R/W
Summary weight information.
TempProportion
percent
float
R
Proportional percent of the Line setpoint to the total Line SP.
KSL Line Functions KSL line variable listing
9.1.2
9 9.1
KSL line command table
Use this table to construct functional commands for the KSL. Please note that the commands for Line function are lowercase.
Description Active selected recipe Batch pause for the line Recall the recipe Stop and preserve alarms for the line Stop and clear alarms for the line Start, run and clear alarms for the line Store the recipe Clear the line totalizer
Mnemonic cacr cpas crcr cspa cspc cstc cstr ctoc
10 KCM Built-In *.kgr Files 10.1 Protocols supported
10
KCM Built-In *.kgr Files
In this section, the pre-loaded kgr files for KCM data communications are shown. The user is also able to prepare and download custom kgr files specific to process needs. The KCM provides Built-In kgr files for each supported protocol. The Built-In kgr files can be used as a quick-start to test communications and as a starting point for building custom kgr files. Built-In kgr files can be extracted, customized and downloaded to the KCM as a custom kgr file using SmartConfig program. The select between the Built-In kgr files and a custom kgr file is made in the KSU Communication menu. Setting the Host File selection in that menu to selects the Built-In file as described in this section. Selecting file selects the custom downloaded kgr file that the user designs. The KSL supports only Modbus, AB-DF1 and Siemens 3694R protocols.
10.1
Protocols supported
Protocols supported for the Built-In kgr files are: • Modbus • Modbus Plus • Modbus TCP • AB Allen Bradley DF1 • Siemens 3694R • DeviceNet • ProfibusDP • EthernetIP Note:
These protocols will require a communication adapter card to be installed in the KCM.
KCM Built-In *.kgr Files 10 Communication settings 10.2
10.2
Communication settings
Below are the communications settings for each Built-In kgr file protocol. These settings appear in the header of the kgr file.
Protocol
Baud
Bits
Parity
Stop
Details
Bits
Modbus-MB
19200
8
Even
1
MS_Byte_First, Node = 0
AB-DF1
9600
8
Even
1
LS_Byte_First, Node = 0
Siemens 3694
9600
8
Even
1
MS_Byte_First, Node = 0
ProfibusDP
MS_Byte_First, In=64 bytes, Out=64 bytes, Node = 0.
Modbus TCP (Modbus over Ethernet)MBTCP
MS_Byte_First, IP address = 10.20.10.100, NetMask = 255.0.0.0, and the Gateway = 0.0.0.0
Modbus Plus MB+
MS_Byte_First, Global Database settings = (SRCID=0, NumWords=0, Offset=0), Node=0.
DeviceNet
MS_Byte_First, No I/O Blocks, Input bytes=62, Output bytes=40, Note: DeviceNet address is set by switches
EthernetIP (DeviceNet over Ethernet)
MS_Byte_First, No I/O Blocks, Input bytes=62, Output bytes=40, IP address = 10.20.10.100, Net Mask = 255.0.0.0, Gateway = 0.0.0.0
10 KCM Built-In *.kgr Files 10.3 Variable locations and mapping
10.3
Variable locations and mapping
The first group of variables are global floating point reads from the KCM. That means the registers are the same for all KCM applications. 10.3.1
Byte
MB, MB+,
Number
MBTCP register
AB-DF1, DeviceNet, ProfibusDP, Siemens, Ethernet IP register
0
40001
0
Floating point reads from the KCM
Parameter Name
KCM Application
Data Type
0
Maximum Flow
LWF, WBF, PID, SFM
Float
40001
0
MaxBatch Size
LWB, WBB, SFB
Float
4
40003
2
Setpoint
LWF, WBF, PID, SFM
Float
4
40003
2
Batch Size
LWB, WBB, SFB
Float
8
40005
4
Totalizer
All applications
Float
12
40007
6
Massflow
LWF, WBF, PID, SFM
Float
12
40007
6
Batch Complete Mass
LWB, WBB, SFB
Float
16
40009
8
Drive Command
All applications
Float
20
40011
10
Motor Speed
All applications
Float
24
40013
12
Aver Feeding Factor
LWF, LWB, PID
Float
24
40013
12
Nominal Belt Load
WBF, WBB
Float
24
40013
12
Chute Net Weight
SFM, SFB
Float
28
40015
14
Netweight
LWF, LWB
Float
28
40015
14
Belt Load
WBF, WBB
Float
28
40015
14
Divert Net Weight
SFM, SFB
Float
28
40015
14
Prop Contrib Freq
PID
Float
32
40017
16
Refill Level Max
LWF, LWB
Float
32
40017
16
Belt Speed
WBF, WBB
Float
32
40017
16
Chute Gross Weight
SFM, SFB
Float
32
40017
16
Integ Contrib Freq
PID
Float
KCM Built-In *.kgr Files 10 Variable locations and mapping 10.3
Floating point reads from the KCM, con’t
Byte
MB, MB+,
Number
MBTCP register
AB-DF1, DeviceNet, ProfibusDP, Siemens, Ethernet IP register
Parameter Name
KCM Application
Data Type
36
40019
18
Refill Level Min
LWF, LWB
Float
36
40019
18
Belt Slip Value
WBF, WBB
Float
36
40019
18
Divert Gross Weight
SFM, SFB
Float
36
40019
18
Deriv Contrib Freq
PID
Float
40
40021
20
Batch Time
LWB, WBB, SFB
Float
40
40021
20
Process Variable
PID
Float
44
40023
22
Fast Drive Command
LWB, WBB, SFB
Float
48
40025
24
Dribble mand
LWB, WBB, SFB
Float
10.3.2
Drive
Com-
Condensed process status and alarm status reads
These bits show the functional condition and alarm status of the particular KCM. See section 7.1. for more information. These parameters are two word integer reads.
Byte
MB, MB+,
Number
MBTCP register
AB-DF1, DeviceNet, ProfibusDP, Siemens, Ethernet IP register
Parameter Name
KCM Application
Data Type
52
40027
26
CondensedProcStatus
All applications
BitMapped
56
40029
28
CondensedAlarmStatus
All applications
BitMapped
10 KCM Built-In *.kgr Files 10.3 Variable locations and mapping
10.3.3
Heartbeat, single word read
Read this value to verify data communication and KCM functionality.
Byte
MB, MB+,
Number
MBTCP register
AB-DF1, DeviceNet, ProfibusDP, Siemens, Ethernet IP register
60
40031
30
Parameter Name
KCM Application
Data Type
Heartbeat
All applications
Integer
10.3.4
Single word writes for control
Use these registers to set LWF/LWB Refill and SFM/SFB Bypass valve control. Note the change in address sequence from the ‘reads’.
Byte
MB, MB+,
Number
MBTCP register
AB-DF1, DeviceNet, ProfibusDP, Siemens, Ethernet IP register
Parameter Name
KCM Application
Data Type
62
41025
1024
Refill Enable/Disable
LWF, LWB
Integer
62
41025
1024
Bypass Valve
SFM, SFB
integer
10.3.5
Command register
This table provides a single register write for KCM commands.
Byte
MB, MB+,
Number
MBTCP register
AB-DF1, DeviceNet, ProfibusDP, Siemens, Ethernet IP register
64
41026
1028
Parameter Name
KCM Application
Commands from Com- All applications mand table See next table.
Data Type
Bitmapped
KCM Built-In *.kgr Files 10 Variable locations and mapping 10.3
10.3.6
Command functions
The Built-In kgr file provides the following bit mapped commands at byte number ‘64’. . Bit Number
Mnemonic
Definition
0
CALA
Alarm acknowledge
1
CALC
Alarm clear
2
CSPA
Stop and keep alarm
3
CSPC
Stop and clear alarms
4
CSTC
Start and clear alarms
5
CTOC
Clear totalizer
6
CMAM
Set gravimetric mode
7
CVOM
Set volumetric mode
8
CTAR
Set the tare
9
CTR2
Start dynamic tare, WBF, WBB only
10
CCFF
Start FF calibration - LWF only
11
CRMD
PID Ramp Up - PID only
12
CMRU
PID Ramp down - PID only
13
CPAS
Batch pause, LWB, WBB, SFB only
14
CTON
Enable totalizer
15
CTOF
Disable totalizer
10 KCM Built-In *.kgr Files 10.3 Variable locations and mapping
10.3.7
Floating point writes to the KCM
Use this table to configure the writes (float-2 register) for the application.
Byte
MB, MB+,
Number
MBTCP register
AB-DF1, DeviceNet, ProfibusDP, Siemens, Ethernt IP register
Parameter Name
KCM Application
Data Type
0
41027
1026
Maximum Flow
LWF, WBF, PID, SFM
Float
0
41027
1026
Maximum Batch Size
LWB, SFB
Float
4
41029
1028
Setpoint
LWF, WBF, PID, SFM
Float
4
41029
1028
Batch Size
LWB, SFB
Float
8
41031
1030
Initial Feeding Factor
LWF, LWB, PID
Float
8
41031
1030
Nominal Belt Loading
WBF, WBB
Float
8
41031
1030
Bypass Interval
SFM, SFB
Float
12
41033
1032
Refill Level Maximum
LWF, LWB
Float
12
41033
1032
Prefeed DC Span
WBF, WBB
Float
12
41033
1032
Overall Span
SFM, SFB, PID
Float
16
41035
1034
Refill Level Minimum
LWF, LWB
Float
16
41035
1034
Belt Slip Alarm Limit
WBF, WBB
Float
16
41035
1034
Prop Gain
PID
Float
16
41035
1034
Chute Weight Span
SFM, SFB
Float
20
41037
1036
Scale Span
LWF,LWB, WBF, WBB
Float
20
41037
1036
Deriv Time
PID
Float
20
41037
1036
Divert Weight Span
SFM, SFB
Float
24
41039
1038
Batch Time
LWB, SFB
Float
24
41039
1038
Process Variable
PID
Float
28
41041
1040
Fast Drive Command
LWB, SFB
Float
32
41043
1042
Dribble mand
LWB, SFB
Float
Drive
Com-
Index
Index A AB CIF 58 Access information 5, 56 Al. Ack 26 Al. Clr 26 Alarm ID code 46 ALS Input 26 ALS Output=4 27 Any alarm 27 ASR-map 27 Aver Feeding Factor 60
B Batch Complete 33 Batch Complete Mass 60 Batch Complete=16 28 Batch Pause=15 28 Batch Size 60, 64 Batch Size=1 33 Batch Size=5 34 Batch Time 61, 64 Batch% Complete=6 34 Belt Drift=16 29 Belt Index=17 29 Belt Load 60 Belt Load=7 30 Belt Slip Alarm Limit 64 Belt Slip Value 61 Belt Speed 60 BlowOff=11 32 Blow-off=13 28, 33 Bypass Fb=15 32 Bypass Interval 64 Bypass Valve 62 Bypass Valve=10 32
C cacr 57 CALA 35, 63 CALC 35, 63 Calib=15 30, 31 Calib=19 28 CCBC 37 CCFF 36, 37, 63 CCRF 36, 37 CDBI 35 CETY 36, 37 CHCA 35 CHDF 35
CHDO 35 CHRU 35 CHST 35 Chute 60 Chute Gross Weight 60 Chute Weight Span 64 CMAM 36, 37, 63 CMRD 36 CMRU 36, 63 Commands 6 condensed alarm status words 53 CondensedAlarmStatus 61 CondensedProcStatus word 38 CPAS 37, 63 cpas 57 crcr 57 CRMD 63 CSPA 35, 63 cspa 57 CSPC 35, 63 cspc 57 CSTC 35, 63 cstc 57 cstr 57 CTAR 36, 37, 63 CTOC 35, 63 ctoc 57 CTOF 35, 63 CTON 35, 63 CTR2 36, 63 CVOM 36, 37, 63
D Data Lock=14 26 Data types 6 Deriv Contrib Freq 61 Deriv Time 64 DeviceNet 58 Divert Gross Weight 61 Divert Net Weight 60 Divert Weight Span 64 Dribble 33 Dribble Drive Command 61, 64 Dribble=15 28 Drive Cmd 29 Drive Command 60 Drive Command=2 34 Drive Command=3 31 Drive Command=4 31
DriveCommand=5 DriverEna 27 Dynamic Tare=18
30,
32
29
E Empty 33 Empty=15 29 Empty=16 28 EthernetIP 58 expanded PSW 42 Ext. Al. 33 External alarm=12 26
F Fast Drive Command 64 Feeder run 27 Feedfactor 29 Feedfactor=4 34 Feedfactor=6 31 Feedfactor=7 32 FF Calibration 33
61,
G global floating point reads
60
H Hard alarm 27 HiLoGear=14 28,
33
I Initial Feeding Factor 64 Integ Contrib Freq 60 Interlock 26
L LineBatchCompleteMass 56 LineBatchCompletePercent 56 LineBatchSize 56 LineMassflow 56 LineMaxBatchSize 56 LineMaxRate 56 LineSetpoint 56 LineTotalizer 56 listing of KSL line variables 56 Loader Enable=21 28 Loader Level=20 28 Loader Run=12 33 Loader=12 28 Loc/Ext 26 LWB 6 LWF 6