C e n t r o D e C o m p u t o D e U N II- F IM IM HVAC Load Analysis for
Facultad De Ingenieria Mecanica Universidad _Nacional De Ingenieria Rimac
Prepared By: IT Ecosystem SAC Refrigeracion Y Aire Acondicionado
sábado, 07 de diciembre de 2013
Chvac - Full Commercial HVAC Loads Calculation Program Elite Software Development College Station, TX 77845
Elite Software Development, Inc. Centro De Computo De UNI-FIM Page 2
General Project Data Inp Inp ut General Project Information Project file name: Project title: Project date: Weather reference city: Client name: Client address: Client city: Company name: Company representative:
CCFIM-UNI - MN374-A.CH8 Centro De Computo De UNI-FIM lunes, 02 de diciembre de 2013 LIMA, PERU Facultad De Ingenieria Mecanica Universidad _Nacional De Ingenieria Rimac Refrigeracion Y Aire Acondicionado IT Ecosystem SAC
Barometric pressure: Altitude: Latitude: Mean daily temperature range: Starting & ending time for HVAC load calculations: Number of unique rooms in this project:
29.876 42 -12 11.5 7am - 10pm 2
in.Hg. feet Degrees D egrees De
Building Default Values Calculations performed: Lighting requirements: Equipment requirements: People sensible load multiplier: People latent load multiplier: Room sensible safety factor: Room latent safety factor: Room heating safety factor: People diversity factor: Lighting profile number: Equipment profile number: People profile number: Building default ceiling height: Building default wall height:
Both heating and cooling loads 1.00 0.50 250 200 10 10 10 90 0 0 1 10.00 8.00
Wa W atts per square foot Watts per square foot Btuh per person Btuh per person % % % %
feet feet fe
Internal Operating Load Profiles (C = 100) 1 2 3 4 5 6 7 8 9 10
hr 1 5 5 5 5 C C C C C C
hr 2 5 5 5 5 C C C C C C
hr 3 5 5 5 5 C C C C C C
hr 4 5 5 5 5 C C C C C C
hr 5 5 5 5 5 C C C C C C
C:\ ...\CCFIM-UNI - MN374-A.CH8
hr 6 5 5 5 5 C C C C C C
hr 7 10 C 75 5 C C C C C C
hr 8 C C C C C C C C C C
hr 9 C C C C C C C C C C
hr 10 C C C C C C C C C C
hr 11 C C 80 C C C C C C C
hr 12 90 C 80 C C C C C C C
hr 13 90 C 80 C C C C C C C
hr 14 90 C C C C C C C C C
hr 15 C C C C C C C C C C
hr 16 C C C C C C C C C C
hr 17 C C C C C C C C C C
hr 18 70 C 80 C C C C C C C
hr 19 80 C 80 C C C C C C C
hr 20 80 C 80 C C C C C C C
hr 21 80 C 80 C C C C C C C
hr 22 80 C 30 C C C C C C C
hr 23 10 5 5 5 C C C C C C
hr 24 10 5 5 5 C C C C C C
sábado, 07 de diciembre de 2013, 07:38 a.m.
Chvac - Full Commercial HVAC Loads Calculation Program Elite Software Development College Station, TX 77845
Elite Software Development, Inc. Centro De Computo De UNI-FIM Page 3
G e n e r al Pr o j e c t D at a I n p u t (c o n t ' d ) Building-Level Design Conditions Design Month
Outdoor Dry Bulb
Outdoor Wet Bulb
Indoor Rel.Hum
Indoor Dry Bulb
Grains Diff
In/Outdoor Correction
86 84 85 58
77 74 76
75% 75% 75%
75 75 75 75
28.11 12.76 23.39
-2 -4 -3
February January March Winter
Master Roofs Roof No.
ASHRAE Roof#
Roof U-Fac
Dark Color
Susp. Ceil
1 3 0.126 Yes Yes Roof #1 Description: 8 inch lightweight concrete, 1/2 inch slag, 3/4 inch felt & membrane, dark color, suspended ceiling. 2 6 0.146 Yes Yes Roof #2 Description: 6" lightweight concrete, 25 lb./sq.ft., dark color with suspended accoustical tile ceiling.
Master Walls Wall No.
ASHRAE Group
Wall U-Fac
Wall Color
1 D 0.281 Wall #1 Description: 4 inch face brick, 1 inch air space, 4 inch tile, dark color 2 G 1.124 Wall #2 Description: Metal wall, no insulation or finish 3 G 0.070 Wall #3 Description: Self-closing double door, metal, heavy construction, light color.
D M L
Master Partitions Partition No.
Partition U-Factor
Cool T-D
Heat T-D
1 0.355 0 0 Partition #1 Description: 8 inch concrete block partition wall, adjoining shipping and receiving area
Master Glass Glass No.
Summer U-Factor
Winter U-Factor
Glass Shd.Coef.
Interior Shading
Interior Shd.Coef
1 0.900 0.910 0.700 2 0.000 Glass #1 Description: 1/4" single-pane window, low e, heat-absorbing pattern, insulated metal frame, no int shading 2 0.470 0.380 0.730 2 0.000 Glass #2 Description: 1/4 inch double pane window,1/2 inch air space, heat abs, e=0.4, 4 ft.h x 6 ft. w, no internal shade
Master Shading Devices Shade No.
Dist Horiz Overh Projects
Dist Beyond Right W.Edge
Dist Beyond Left W.Edge
Dist Overh Above Wind
Dist Right Fin Proj
Dist R-Fin Beyond W.Edge
Ht Of Right Fin
Dist Left Fin Proj
Dist L-Fin Beyond W.Edge
Ht Of Left Fin
1 6.00 2.00 2.00 2.00 0.00 0.00 0.00 0.00 0.00 0.00 Shading Device #1 Description: Aluminum store-front overhang, 6' projection with 2' extra width on both sides of window
C:\ ...\CCFIM-UNI - MN374-A.CH8
sábado, 07 de diciembre de 2013, 07:38 a.m.
Chvac - Full Commercial HVAC Loads Calculation Program Elite Software Development College Station, TX 77845
Elite Software Development, Inc. Centro De Computo De UNI-FIM Page 4
A i r H a n d l e r In p u t Air Handler Number 1 Input Data Name: Terminal type: Method for CV Supply fan type: Calculations performed: Excess supply air: Occurrences: People profile number: Lighting profile number: Equipment profile number: Exhaust may not exceed supply air: Leaving heating coil temp (deg.F): Leaving cooling coil temp (deg.F): Cooling coil CFM Misc. Btuh gain - supply side: Misc. Btuh gain - return side: Combined fan & motor efficiency: Static pressure across fan (in.wg.): Summer supply duct temp rise (deg.F): Summer return duct temp rise (deg.F): Winter supply duct temp drop (deg.F): Winter return duct temp drop (deg.F): Chilled water temp difference (deg.F): Hot water temp difference (deg.F): Cooling ventilation: Cooling infiltration: Heating ventilation: Heating infiltration: Pretreated outside air: Pretreated air Summer DB (deg.F): Pretreated air Summer WB (deg.F): Pretreated air Winter DB (deg.F):
Design Month
Tecer Piso Constant Volume Sum of Peaks Draw-thru fan Both heating and cooling loads Reserve 1 1 0 0 No 95.0 55.0 0 0 0 65 0.00 1.000 0.750 2.000 1.000 10.000 20.000 0.7 Direct 0 AC/Hr 10 CFM/Pr 0 AC/Hr none 0 0 0
Outdoor Dry Bulb
Outdoor Wet Bulb
Indoor Rel.Hum
Indoor Dry Bulb
Grains Diff
In/Outdoor Correction
86 84 85 58
77 74 76
75% 75% 75%
75 75 75 75
28.11 12.76 23.39
-2 -4 -3
February January March Winter
C:\ ...\CCFIM-UNI - MN374-A.CH8
sábado, 07 de diciembre de 2013, 07:38 a.m.
Chvac - Full Commercial HVAC Loads Calculation Program Elite Software Development College Station, TX 77845
Elite Software Development, Inc. Centro De Computo De UNI-FIM Page 5
R o o m In p u t Room 1: Aula A (391.6 sq.ft) (Zone 1) Air Handler number: 1 Room length: (feet) 22.00 Lighting Watts: 20 Number of people in room: 15 Lighting profile number: 0 Ceiling height (feet): 9.50 Sensible safety factor (%): 10 Sensible heat per person (Btuh): 250 Cooling ventilation method: Direct Cooling infiltration method: AC/Hr Heating ventilation method: CFM/Pr Heating infiltration method: AC/Hr Winter exhaust air CFM: 0 Minimum supply CFM: 0 Ceil. exposed to plenum (sq.ft): 392 Both heating and cooling loads are calculated for this room. Roof 1 Part
1 2
1 17.80 196 1 0 10 10 200 0.700 0.000 10.000 0.000 0 0 0
Type
ASHRAE#
U-Factor
Dark
Length
Width
Area
Susp.Ceil
1
3
0.126
Yes
22.00
17.80
391.6
Yes
Type
U-Factor
Cool TD
Heat TD
Height
Width
Area
1
0.355
0.000
0.000
8.00
22.00
176.0
3 Wall
Room occurrences: Room width (feet): Equipment Watts: People profile number: Equipment profile number: Heating safety factor (%): Latent safety factor (%): Latent heat per person (Btuh): Cooling ventilation value: Cooling infiltration value: Heating ventilation value: Heating infiltration value: Summer exhaust air CFM: Latent Btuh equipment load: Exposed floor slab perimeter (ft):
Type
ASHRAE#
U-Factor
Color
Height
Width
Area
Direction
1 1
D D
0.281 0.281
D D
8.00 8.00
22.00 17.80
176.0 142.4
NW SE
Room 2: Aula B (391.6 sq.ft) (Zone 1) Air Handler number: 1 Room length: (feet) 22.00 Lighting Watts: 17 Number of people in room: 15 Lighting profile number: 0 Ceiling height (feet): 9.50 Sensible safety factor (%): 10 Sensible heat per person (Btuh): 250 Cooling ventilation method: Direct Cooling infiltration method: AC/Hr Heating ventilation method: CFM/Pr Heating infiltration method: AC/Hr Winter exhaust air CFM: 0 Minimum supply CFM: 0 Ceil. exposed to plenum (sq.ft): 392 Both heating and cooling loads are calculated for this room. Roof 1 Wall 1 2 3
Room occurrences: Room width (feet): Equipment Watts: People profile number: Equipment profile number: Heating safety factor (%): Latent safety factor (%): Latent heat per person (Btuh): Cooling ventilation value: Cooling infiltration value: Heating ventilation value: Heating infiltration value: Summer exhaust air CFM: Latent Btuh equipment load: Exposed floor slab perimeter (ft):
1 17.80 196 1 0 10 10 200 0.700 0.000 10.000 0.000 0 0 0
Type
ASHRAE#
U-Factor
Dark
Length
Width
Area
Susp.Ceil
1
3
0.126
Yes
22.00
17.80
391.6
Yes
Type
ASHRAE#
U-Factor
Color
Height
Width
Area
Direction
1 1 1
D D D
0.281 0.281 0.281
D D D
8.00 8.00 8.00
22.00 17.80 22.00
176.0 142.4 176.0
NW SW SE
C:\ ...\CCFIM-UNI - MN374-A.CH8
sábado, 07 de diciembre de 2013, 07:38 a.m.
Chvac - Full Commercial HVAC Loads Calculation Program Elite Software Development College Station, TX 77845
Elite Software Development, Inc. Centro De Computo De UNI-FIM Page 6
P l en u m In p u t Plenum Number 1 Input Data Air Handler Number: Plenum active: Percent of light load to rooms: Floor u-factor (Btuh/Sq.ft-°F): Watts of equipment: Summer plenum-room temp. difference (deg.F): Winter plenum-room temp. difference (deg.F):
C:\ ...\CCFIM-UNI - MN374-A.CH8
1 No 100 0.000 0 0 0
sábado, 07 de diciembre de 2013, 07:38 a.m.
Chvac - Full Commercial HVAC Loads Calculation Program Elite Software Development College Station, TX 77845
Elite Software Development, Inc. Centro De Computo De UNI-FIM Page 7
Building Summary Loads Building peaks in February at 5pm.
Bldg Load Descriptions
Area Quan
Sen Loss
%Tot Loss
Lat Gain
Sen Gain
Net Gain
%Net Gain
783 813 0 0
1,845 4,271 0 0
14.60 33.80 0.00 0.00
0 0 0 0
6,812 5,288 0 0
6,812 5,288 0 0
20.46 15.88 0.00 0.00
6,116
48.41
0
12,100
12,100
36.34
0 0 0 0 0 0 0 0 5,500 0 0 0 0 0 0 680 340 0 0
0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 43.53 0.00 0.00 0.00 0.00 0.00 0.00 5.38 2.69 0.00 0.00
0 0 0 5,940 0 0 0 14 0 0 0 0 0 0 0 0 0 0 0
139 1,470 0 7,425 0 0 0 8 0 0 0 470 0 823 0 2,803 2,102 0 0
139 1,470 0 13,365 0 0 0 22 0 0 0 470 0 823 0 2,803 2,102 0 0
0.42 4.41 0.00 40.14 0.00 0.00 0.00 0.07 0.00 0.00 0.00 1.41 0.00 2.47 0.00 8.42 6.31 0.00 0.00
12,635
100.00
5,954
27,338
33,293
100.00
Roof Wall Glass Floor Slab Skin Loads Lighting Equipment Pool Latent People Partition Cool. Pret. Heat. Pret. Cool. Vent. Heat. Vent. Cool. Infil. Heat. Infil. Draw-Thru Fan Blow-Thru Fan Reserve Cap. Reheat Cap. Supply Duct Return Duct Misc. Supply Misc. Return
37 392 0 27 176 0 0 1 300 0 0 0 0 0 0 0 0 0 0
Building Totals
Building Summary
Sen Loss
%Tot Loss
Lat Gain
Sen Gain
Net Gain
%Net Gain
Ventilation Infiltration Pretreated Air Room Loads Plenum Loads Fan/Duct/Misc Loads
5,500 0 0 6,116 0 1,019
43.53 0.00 0.00 48.41 0.00 8.07
14 0 0 5,940 0 0
8 0 0 21,956 0 5,375
22 0 0 27,896 0 5,375
0.07 0.00 0.00 83.79 0.00 16.14
12,635
100.00
5,954
27,338
33,293
100.00
Building Totals
Check Figures Total Building Supply Air (based on a 9° TD): Total Building Vent. Air (0.03% of Supply):
2,552 CFM 1 CFM
Total Conditioned Air Space: Supply Air Per Unit Area: Area Per Cooling Capacity: Cooling Capacity Per Area: Heating Capacity Per Area:
783 3.2587 282.3 0.0035 16.13
Total Heating Required With Outside Air: Total Cooling Required With Outside Air:
12,635 Btuh 2.77 Tons
C:\ ...\CCFIM-UNI - MN374-A.CH8
Sq.ft CFM/Sq.ft Sq.ft/Ton Tons/Sq.ft Btuh/Sq.ft
sábado, 07 de diciembre de 2013, 07:38 a.m.
Chvac - Full Commercial HVAC Loads Calculation Program Elite Software Development College Station, TX 77845
Elite Software Development, Inc. Centro De Computo De UNI-FIM Page 8
B u i l d i n g S u m m a r y L o a d s ( Z) Building peaks in February at 5pm.
Bldg Load Descriptions
Area Quan
Sen Loss
%Tot Loss
Lat Gain
Sen Gain
Net Gain
%Net Gain
783 813 0 0
1,845 4,271 0 0
14.60 33.80 0.00 0.00
0 0 0 0
6,812 5,288 0 0
6,812 5,288 0 0
20.46 15.88 0.00 0.00
6,116
48.41
0
12,100
12,100
36.34
0 0 0 0 0 0 0 0 5,500 0 0 0 0 0 0 680 340 0 0
0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 43.53 0.00 0.00 0.00 0.00 0.00 0.00 5.38 2.69 0.00 0.00
0 0 0 5,940 0 0 0 14 0 0 0 0 0 0 0 0 0 0 0
139 1,470 0 7,425 0 0 0 8 0 0 0 470 0 823 0 2,803 2,102 0 0
139 1,470 0 13,365 0 0 0 22 0 0 0 470 0 823 0 2,803 2,102 0 0
0.42 4.41 0.00 40.14 0.00 0.00 0.00 0.07 0.00 0.00 0.00 1.41 0.00 2.47 0.00 8.42 6.31 0.00 0.00
12,635
100.00
5,954
27,338
33,293
100.00
Roof Wall Glass Floor Slab Skin Loads Lighting Equipment Pool Latent People Partition Cool. Pret. Heat. Pret. Cool. Vent. Heat. Vent. Cool. Infil. Heat. Infil. Draw-Thru Fan Blow-Thru Fan Reserve Cap. Reheat Cap. Supply Duct Return Duct Misc. Supply Misc. Return
37 392 0 27 176 0 0 1 300 0 0 0 0 0 0 0 0 0 0
Building Totals
Building Summary
Sen Loss
%Tot Loss
Lat Gain
Sen Gain
Net Gain
%Net Gain
Ventilation Infiltration Pretreated Air Room Loads Plenum Loads Fan/Duct/Misc Loads
5,500 0 0 6,116 0 1,019
43.53 0.00 0.00 48.41 0.00 8.07
14 0 0 5,940 0 0
8 0 0 21,956 0 5,375
22 0 0 27,896 0 5,375
0.07 0.00 0.00 83.79 0.00 16.14
12,635
100.00
5,954
27,338
33,293
100.00
Building Totals
Check Figures Total Building Supply Air (based on a 9° TD): Total Building Vent. Air (0.03% of Supply):
2,552 CFM 1 CFM
Total Conditioned Air Space: Supply Air Per Unit Area: Area Per Cooling Capacity: Cooling Capacity Per Area: Heating Capacity Per Area:
783 3.2587 282.3 0.0035 16.13
Total Heating Required With Outside Air: Total Cooling Required With Outside Air:
12,635 Btuh 2.77 Tons
C:\ ...\CCFIM-UNI - MN374-A.CH8
Sq.ft CFM/Sq.ft Sq.ft/Ton Tons/Sq.ft Btuh/Sq.ft
sábado, 07 de diciembre de 2013, 07:38 a.m.
Chvac - Full Commercial HVAC Loads Calculation Program Elite Software Development College Station, TX 77845
Elite Software Development, Inc. Centro De Computo De UNI-FIM Page 9
A i r H a n d l e r # 1 - T ec e r P i s o - S u m m a r y L o a d s Rm No
Description Room Peak Time
1
Aula A 5pm February
2
Aula B 5pm February
Area People Volume
Htg.Loss Htg.CFM CFM/Sqft
Sen.Gain Clg.CFM CFM/Sqft
Lat.Gain S.Exh W.Exh
Htg.O.A. Req.CFM Act.CFM
Clg.O.A. Req.CFM Act.CFM
392 2,596 10,499 3,300 10/P Direct 15 134 1,220 0 150 0 3,720 0.34 3.12 0 127 0 Runout duct size: 8 in. h x 4in. w, Diffusers: 10, CFM/runout: 122, Velocity: 549.2 ft/min, Pressure drop: 0.111 in.wg./100ft 392 3,521 11,459 3,300 10/P Direct 15 181 1,332 0 150 0 3,720 0.46 3.40 0 173 0 Runout duct size: 8 in. h x 4in. w, Diffusers: 11, CFM/runout: 121, Velocity: 544.9 ft/min, Pressure drop: 0.109 in.wg./100ft Room Peak Totals: 783 6,116 21,958 6,600 Total Rooms: 2 30 315 2,553 0 Unique Rooms: 2 7,440 0.40 3.26 0 Main trunk duct size: 25 in. h x 17in. w, Velocity: 864.8 ft/min, Pressure drop: 0.066 in.wg./100ft
C:\ ...\CCFIM-UNI - MN374-A.CH8
300 300
1 1
sábado, 07 de diciembre de 2013, 07:38 a.m.
Chvac - Full Commercial HVAC Loads Calculation Program Elite Software Development College Station, TX 77845
Elite Software Development, Inc. Centro De Computo De UNI-FIM Page 10
A i r H a n d l e r # 1 - Te c e r P i s o - T o t a l L o a d S u m m a r y Air Handler Description: Supply Air Fan: Fan Input: Sensible Heat Ratio:
Tecer Piso Constant Volume - Sum of Peaks Draw-Thru with program estimated horsepower of 0.19 HP 65% motor and fan efficiency with 0 in. water across the fan 0.81 --- This system occurs 1 time(s) in the building. ---
Air System Peak Time: Outdoor Conditions: Indoor Conditions:
5pm in February. Clg: 85° DB, 77° WB, 127.85 grains, Htg: 58° DB Clg: 75° DB, 75% RH, Htg: 75° DB
Summer: Ventilation controls outside air, ----- Winter: Ventilation controls outside air. Room Space sensible loss: Infiltration sensible loss: Outside Air sensible loss: Supply Duct sensible loss: Return Duct sensible loss: Return Plenum sensible loss: Total System sensible loss:
6,116 0 5,500 680 340 0
Btuh Btuh Btuh Btuh Btuh Btuh
12,635 Btuh
Heating Supply Air: 6,796 / (.998 X 1.08 X 20) = Winter Vent Outside Air (95.2% of supply) = Room space sensible gain: 21,133 Infiltration sensible gain: 0 Draw-thru fan sensible gain: 470 Supply duct sensible gain: 2,803 Reserve sensible gain: 823 Total sensible gain on supply side of coil:
315 CFM 300 CFM Btuh Btuh Btuh Btuh Btuh 25,229 Btuh
Cooling Supply Air: 25,229 / (.998 X 1.1 X 9) = Summer Vent Outside Air (0.0% of supply) = Return duct sensible gain: 2,102 Return plenum sensible gain: 0 Outside air sensible gain: 8 Blow-thru fan sensible gain: 0 Total sensible gain on return side of coil: Total sensible gain on air handling system:
0 CFM 300 CFM
2,552 CFM 1 CFM Btuh Btuh Btuh Btuh
1 CFM 2,110 Btuh 27,338 Btuh
Room space latent gain: 5,940 Btuh Infiltration latent gain: 0 Btuh Outside air latent gain: 14 Btuh Total latent gain on air handling system: Total system sensible and latent gain:
5,954 Btuh 33,293 Btuh
Check Figures Total Air Handler Supply Air (based on a 9° TD): Total Air Handler Vent. Air (0.03% of Supply):
2,552 CFM 1 CFM
Total Conditioned Air Space: Supply Air Per Unit Area: Area Per Cooling Capacity: Cooling Capacity Per Area: Heating Capacity Per Area:
783 3.2587 282.3 0.0035 16.13
Total Heating Required With Outside Air: Total Cooling Required With Outside Air:
12,635 Btuh 2.77 Tons
C:\ ...\CCFIM-UNI - MN374-A.CH8
Sq.ft CFM/Sq.ft Sq.ft/Ton Tons/Sq.ft Btuh/Sq.ft
sábado, 07 de diciembre de 2013, 07:38 a.m.
Chvac - Full Commercial HVAC Loads Calculation Program Elite Software Development College Station, TX 77845
Elite Software Development, Inc. Centro De Computo De UNI-FIM Page 11
A i r H a n d l e r # 1 - T ec e r P i s o - S u m m a r y L o a d s f o r Z o n e s (Z ) Zn No
Description Zone Peak Time
1
Zone 1 5pm February
Area People Volume
Htg.Loss Htg.CFM CFM/Sqft
Sen.Gain Clg.CFM CFM/Sqft
Lat.Gain S.Exh W.Exh
Htg.O.A. Req.CFM Act.CFM
Clg.O.A. Req.CFM Act.CFM
783 6,116 21,958 6,600 n/a n/a 30 315 2,553 0 300 1 7,440 0.40 3.26 0 300 1 Runout duct size: 8 in. h x 4in. w, Diffusers: 21, CFM/runout: 122, Velocity: 547.0 ft/min, Pressure drop: 0.110 in.wg./100ft Trunk duct feeding zone: 25 in. h x 17in. w, Velocity: 864.9 ft/min, Pressure drop: 0.067 in.wg./100ft Zone Peak Totals: Total Zones: 1
783 6,116 21,958 6,600 30 315 2,553 0 7,440 0.40 3.26 0 Main trunk duct size: 25 in. h x 17in. w, Velocity: 864.8 ft/min, Pressure drop: 0.066 in.wg./100ft
C:\ ...\CCFIM-UNI - MN374-A.CH8
300 300
1 1
sábado, 07 de diciembre de 2013, 07:38 a.m.
Chvac - Full Commercial HVAC Loads Calculation Program Elite Software Development College Station, TX 77845
Elite Software Development, Inc. Centro De Computo De UNI-FIM Page 12
A i r H a n d l e r # 1 - T ec e r P i s o - Su m m a r y L o a d s f o r R o o m s ( Z) Rm No
Description Zone Peak Time
1
Aula A 5pm February
2
Aula B 5pm February
Area People Volume
Htg.Loss Htg.CFM CFM/Sqft
Sen.Gain Clg.CFM CFM/Sqft
Lat.Gain S.Exh W.Exh
Htg.O.A. Req.CFM Act.CFM
Clg.O.A. Req.CFM Act.CFM
392 2,596 10,499 3,300 10/P Direct 15 134 1,220 0 150 0 3,720 0.34 3.12 0 127 0 Runout duct size: 8 in. h x 4in. w, Diffusers: 10, CFM/runout: 122, Velocity: 549.2 ft/min, Pressure drop: 0.111 in.wg./100ft 392 3,521 11,459 3,300 10/P Direct 15 181 1,332 0 150 0 3,720 0.46 3.40 0 173 0 Runout duct size: 8 in. h x 4in. w, Diffusers: 11, CFM/runout: 121, Velocity: 544.9 ft/min, Pressure drop: 0.109 in.wg./100ft Room Peak Totals: Total Rooms: 2
783 6,116 21,958 6,600 30 315 2,553 0 7,440 0.40 3.26 0 Main trunk duct size: 25 in. h x 17in. w, Velocity: 864.8 ft/min, Pressure drop: 0.066 in.wg./100ft
C:\ ...\CCFIM-UNI - MN374-A.CH8
300 300
1 1
sábado, 07 de diciembre de 2013, 07:38 a.m.
Chvac - Full Commercial HVAC Loads Calculation Program Elite Software Development College Station, TX 77845
Elite Software Development, Inc. Centro De Computo De UNI-FIM Page 13
A i r H a n d l e r # 1 - Te c e r P i s o - T o t a l L o a d S u m m a r y ( Z) Air Handler Description: Supply Air Fan: Fan Input: Sensible Heat Ratio:
Tecer Piso Constant Volume - Sum of Peaks Draw-Thru with program estimated horsepower of 0.19 HP 65% motor and fan efficiency with 0 in. water across the fan 0.81 --- This system occurs 1 time(s) in the building. ---
Air System Peak Time: Outdoor Conditions: Indoor Conditions:
5pm in February. Clg: 85° DB, 77° WB, 127.85 grains, Htg: 58° DB Clg: 75° DB, 75% RH, Htg: 75° DB
Summer: Ventilation controls outside air, ----- Winter: Ventilation controls outside air. Room Space sensible loss: Infiltration sensible loss: Outside Air sensible loss: Supply Duct sensible loss: Return Duct sensible loss: Return Plenum sensible loss: Total System sensible loss:
6,116 0 5,500 680 340 0
Btuh Btuh Btuh Btuh Btuh Btuh
12,635 Btuh
Heating Supply Air: 6,796 / (.998 X 1.08 X 20) = Winter Vent Outside Air (95.2% of supply) = Room space sensible gain: 21,133 Infiltration sensible gain: 0 Draw-thru fan sensible gain: 470 Supply duct sensible gain: 2,803 Reserve sensible gain: 823 Total sensible gain on supply side of coil:
315 CFM 300 CFM Btuh Btuh Btuh Btuh Btuh 25,229 Btuh
Cooling Supply Air: 25,229 / (.998 X 1.1 X 9) = Summer Vent Outside Air (0.0% of supply) = Return duct sensible gain: 2,102 Return plenum sensible gain: 0 Outside air sensible gain: 8 Blow-thru fan sensible gain: 0 Total sensible gain on return side of coil: Total sensible gain on air handling system:
0 CFM 300 CFM
2,552 CFM 1 CFM Btuh Btuh Btuh Btuh
1 CFM 2,110 Btuh 27,338 Btuh
Room space latent gain: 5,940 Btuh Infiltration latent gain: 0 Btuh Outside air latent gain: 14 Btuh Total latent gain on air handling system: Total system sensible and latent gain:
5,954 Btuh 33,293 Btuh
Check Figures Total Air Handler Supply Air (based on a 9° TD): Total Air Handler Vent. Air (0.03% of Supply):
2,552 CFM 1 CFM
Total Conditioned Air Space: Supply Air Per Unit Area: Area Per Cooling Capacity: Cooling Capacity Per Area: Heating Capacity Per Area:
783 3.2587 282.3 0.0035 16.13
Total Heating Required With Outside Air: Total Cooling Required With Outside Air:
12,635 Btuh 2.77 Tons
C:\ ...\CCFIM-UNI - MN374-A.CH8
Sq.ft CFM/Sq.ft Sq.ft/Ton Tons/Sq.ft Btuh/Sq.ft
sábado, 07 de diciembre de 2013, 07:38 a.m.
Chvac - Full Commercial HVAC Loads Calculation Program Elite Software Development College Station, TX 77845
Elite Software Development, Inc. Centro De Computo De UNI-FIM Page 14
Z o n e D e t ai l e d L o a d s ( A t Z o n e P e ak T i m e s ) Load Description
Unit Quan
-SCCFAC
CLTD SHGF
U.Fac -CLF-
Sen. Gain
Lat. Gain
Htg. Mult.
Htg. Loss
2.142 4.777 4.777 0.000
839 841 680 0
Room 1-Aula A - Air Handler 1 (Tecer Piso), Zone 1 peaks (sensible) in February at 5pm. Roof-1-3-Susp.C-D Wall-1-NW-D-D Wall-2-SE-D-D Partition-3-1 Lights-Prof=0 Equipment-Prof=0 People-Prof=1
392 176 142 176 20 196 15.0
1.00 1 1
62.8 21.3 22.8 0/0
0.126 0.281 0.281 0.355
1.000 1.000 1.000
Sub-total Safety factors: Total w/ safety factors:
3,096 1,051 910 0 69 668 3,750
0 3,000
9,545 +10% --------10,499
3,000 +10% --------3,300
2,360 +10% --------2,596
Room 2-Aula B - Air Handler 1 (Tecer Piso), Zone 1 peaks (sensible) in February at 5pm. Roof-1-3-Susp.C-D Wall-1-NW-D-D Wall-2-SW-D-D Wall-3-SE-D-D Lights-Prof=0 Equipment-Prof=0 People-Prof=1 Sub-total Safety factors: Total w/ safety factors:
C:\ ...\CCFIM-UNI - MN374-A.CH8
392 176 142 176 17 196 15.0
1.00 1 1 1 1.000 1.000 1.000
62.8 21.3 16.8 22.8
0.126 0.281 0.281 0.281
3,096 1,051 670 1,125 57 668 3,750
2.142 4.777 4.777 4.777 0 3,000
10,417 +10% --------11,459
3,000 +10% --------3,300
839 841 680 841
3,201 +10% --------3,521
sábado, 07 de diciembre de 2013, 07:38 a.m.
Chvac - Full Commercial HVAC Loads Calculation Program Elite Software Development College Station, TX 77845
Elite Software Development, Inc. Centro De Computo De UNI-FIM Page 15
R o o m D e t ai l e d L o a d s ( A t R o o m P e a k Ti m e s ) Load Description
Unit Quan
-SCCFAC
CLTD SHGF
U.Fac -CLF-
Sen. Gain
Lat. Gain
Htg. Mult.
Htg. Loss
Room 1-Aula A peaks (sensible) in February at 5pm, Air Handler 1 (Tecer Piso), Zone 1, 22.0 x 17.8, Construction Type: 8 (Medium) Roof-1-3-Susp.C-D Wall-1-NW-D-D Wall-2-SE-D-D Partition-3-1 Lights-Prof=0 Equipment-Prof=0 People-Prof=1
392 176 142 176 20 196 15.0
1.00 1 1
62.8 21.3 22.8 0/0
0.126 0.281 0.281 0.355
1.000 1.000 1.000
Sub-total Safety factors: Total w/ safety factors:
3,096 1,051 910 0 69 668 3,750
2.142 4.777 4.777 0.000 0 3,000
9,545 +10% --------10,499
3,000 +10% --------3,300
839 841 680 0
2,360 +10% --------2,596
Lighting Cooling Loads Item Name
Quantity
Fluorescent, (1) 18 in., T12 lamp, Mag-Std ballast High Pressure Sodium, (1) 200 W lamp, HID ballast
Special Quantity Allowance Type Factor
Space Fraction
Occurrences
Usage Factor
Load (Btuh)
15
watts
1.27
1
1
1
65
1
watts
1.25
1
1
1
4
Total
69
Room 2-Aula B peaks (sensible) in February at 5pm, Air Handler 1 (Tecer Piso), Zone 1, 22.0 x 17.8, Construction Type: 6 (Light) Roof-1-3-Susp.C-D Wall-1-NW-D-D Wall-2-SW-D-D Wall-3-SE-D-D Lights-Prof=0 Equipment-Prof=0 People-Prof=1
392 176 142 176 17 196 15.0
1.00 1 1 1 1.000 1.000 1.000
62.8 21.3 16.8 22.8
0.126 0.281 0.281 0.281
Sub-total Safety factors: Total w/ safety factors:
3,096 1,051 670 1,125 57 668 3,750
2.142 4.777 4.777 4.777 0 3,000
10,417 +10% --------11,459
3,000 +10% --------3,300
839 841 680 841
3,201 +10% --------3,521
Lighting Cooling Loads Item Name
Quantity
Fluorescent, (1) 18 in., T12 lamp, Mag-Std ballast High Pressure Sodium, (1) 100 W lamp, HID ballast C:\ ...\CCFIM-UNI - MN374-A.CH8
Special Quantity Allowance Type Factor
Space Fraction
Occurrences
Usage Factor
Load (Btuh)
12
watts
1.27
1
1
1
52
1
watts
1.38
1
1
1
5
sábado, 07 de diciembre de 2013, 07:38 a.m.
Chvac - Full Commercial HVAC Loads Calculation Program Elite Software Development College Station, TX 77845
Elite Software Development, Inc. Centro De Computo De UNI-FIM Page 16
R o o m D e t ai l e d L o a d s ( A t R o o m P e ak T i m e s ) (c o n t ' d ) Item Name
Quantity
Total
C:\ ...\CCFIM-UNI - MN374-A.CH8
Special Quantity Allowance Type Factor
Space Fraction
Occurrences
Usage Factor
Load (Btuh) 57
sábado, 07 de diciembre de 2013, 07:38 a.m.
Chvac - Full Commercial HVAC Loads Calculation Program Elite Software Development College Station, TX 77845
Elite Software Development, Inc. Centro De Computo De UNI-FIM Page 17
A i r S y s t e m # 1 (T ec e r P i s o ) P s y c h r o m e t r i c A n a l y s i s System Load Analysis
Latent
Leaving Coil Condition Draw-Thru Fan Misc Load on Supply Side Supply Air Duct Room Loads Sensible Reserve
Grains
Sensible
Temp
CFM
470 0 2,803 21,133 823
66.000 0.168 0.000 1.000 7.539 0.294
47 0 284 2,138 83
25,229 2,102 0 0 8 0
75.000 0.750 0.000 0.000 0.003 0.000
2,552
27,338
75.753
2,552
94.409 0
0.000
5,940
3.428
Room Condition Return Air Duct Return Air Plenum Misc Load on Return Side Vent Air 1 CFM Blow-Thru Fan
5,940
97.837
0 14
0.000 0.008
Entering Coil Condition
5,954
97.845
General Psychrometric Equations Used In Analysis: PR TSH TLH GTH
=(Barometric pressure of site / Standard ASHRAE pressure of 29.921) = PR x 1.10 x CFM x (DB entering - DB leaving) = PR x 0.68 x CFM x (Grains entering - Grains leaving) = PR x 4.50 x CFM x (Enthalpy entering - Enthalpy leaving)
TSH TLH
= =
0.998 0.998
SUM = GTH = 0.998 Total System Load
x x
x
1.10 0.68
4.50
x x
x
2,552 2,552
2,552
x ( 75.8 x ( 97.8
x ( 33.5
-
-
66.0 94.4
30.5
)= )=
)= =
27,338 5,954 ---------33,292 33,674 33,293
Btuh Btuh Btuh Btuh Btuh
Chilled and Hot Water Flow Rates and Steam Requirement Cooling GPM Heating GPM Steam Req.
= = =
33,674 / ( 12,635 / ( 12,635 /
10.00 x 20.00 x 970
Entering Cooling Coil Conditions Dry bulb temperature: Wet bulb temperature: Relative humidity: Enthalpy:
C:\ ...\CCFIM-UNI - MN374-A.CH8
) )
= = =
6.7 GPM 1.3 GPM 13.0 lb./hr
Entering Heating Coil Conditions 75.75 69.40 73.15 33.48 Btu/lbm
Leaving Cooling Coil Conditions Dry bulb temperature: Wet bulb temperature: Relative humidity: Enthalpy:
500 500
Dry bulb temperature:
58.77
Leaving Heating Coil Conditions 66.00 65.68 98.39 30.55 Btu/lbm
Dry bulb temperature:
95.00
sábado, 07 de diciembre de 2013, 07:38 a.m.
Chvac - Full Commercial HVAC Loads Calculation Program Elite Software Development College Station, TX 77845
Elite Software Development, Inc. Centro De Computo De UNI-FIM Page 18
A i r S y s t e m # 1 (T ec e r P i s o ) Ps y c h r o m e t r i c A n a l y s i s ( Z) System Load Analysis
Latent
Leaving Coil Condition Draw-Thru Fan Misc Load on Supply Side Supply Air Duct Room Loads Sensible Reserve
Grains
Sensible
Temp
CFM
470 0 2,803 21,133 823
66.000 0.168 0.000 1.000 7.539 0.294
47 0 284 2,138 83
25,229 2,102 0 0 8 0
75.000 0.750 0.000 0.000 0.003 0.000
2,552
27,338
75.753
2,552
94.409 0
0.000
5,940
3.428
Room Condition Return Air Duct Return Air Plenum Misc Load on Return Side Vent Air 1 CFM Blow-Thru Fan
5,940
97.837
0 14
0.000 0.008
Entering Coil Condition
5,954
97.845
General Psychrometric Equations Used In Analysis: PR TSH TLH GTH
=(Barometric pressure of site / Standard ASHRAE pressure of 29.921) = PR x 1.10 x CFM x (DB entering - DB leaving) = PR x 0.68 x CFM x (Grains entering - Grains leaving) = PR x 4.50 x CFM x (Enthalpy entering - Enthalpy leaving)
TSH TLH
= =
0.998 0.998
SUM = GTH = 0.998 Total System Load
x x
x
1.10 0.68
4.50
x x
x
2,552 2,552
2,552
x ( 75.8 x ( 97.8
x ( 33.5
-
-
66.0 94.4
30.5
)= )=
)= =
27,338 5,954 ---------33,292 33,674 33,293
Btuh Btuh Btuh Btuh Btuh
Chilled and Hot Water Flow Rates and Steam Requirement Cooling GPM Heating GPM Steam Req.
= = =
33,674 / ( 12,635 / ( 12,635 /
10.00 x 20.00 x 970
Entering Cooling Coil Conditions Dry bulb temperature: Wet bulb temperature: Relative humidity: Enthalpy:
C:\ ...\CCFIM-UNI - MN374-A.CH8
) )
= = =
6.7 GPM 1.3 GPM 13.0 lb./hr
Entering Heating Coil Conditions 75.75 69.40 73.15 33.48 Btu/lbm
Leaving Cooling Coil Conditions Dry bulb temperature: Wet bulb temperature: Relative humidity: Enthalpy:
500 500
Dry bulb temperature:
58.77
Leaving Heating Coil Conditions 66.00 65.68 98.39 30.55 Btu/lbm
Dry bulb temperature:
95.00
sábado, 07 de diciembre de 2013, 07:38 a.m.
Chvac - Full Commercial HVAC Loads Calculation Program Elite Software Development College Station, TX 77845
Elite Software Development, Inc. Centro De Computo De UNI-FIM Page 19
A i r S y s t e m # 1 (T ec e r P i s o ) P s y c h r o m e t r i c C h a r t RC LC SD DTF RE SM PRE MIX
Room Condition Leaving Coil Condition Supply Duct Temperature Rise Draw Through Fan Sensible Gain Reserve or Reheat Sensible Gain Supply Side Miscellaneous Sensible Gain Pretreated Air Condition Mixed Air Condition
C:\ ...\CCFIM-UNI - MN374-A.CH8
OC EC RD BTF PL MR HRV RML
Outdoor Condition Entering Coil Condition Return Duct Temperature Rise Blow Through Fan Sensible Gain Return Air Plenum Sensible Gain Return Side Miscellaneous Gain Heat Recovery Ventilator Condition Return Miscellaneous Latent Gain
sábado, 07 de diciembre de 2013, 07:38 a.m.
Chvac - Full Commercial HVAC Loads Calculation Program Elite Software Development College Station, TX 77845
Elite Software Development, Inc. Centro De Computo De UNI-FIM Page 20
A i r S y s t e m # 1 (T ec e r P i s o ) P s y c h r o m e t r i c C h a r t (Z ) RC LC SD DTF RE SM PRE MIX
Room Condition Leaving Coil Condition Supply Duct Temperature Rise Draw Through Fan Sensible Gain Reserve or Reheat Sensible Gain Supply Side Miscellaneous Sensible Gain Pretreated Air Condition Mixed Air Condition
C:\ ...\CCFIM-UNI - MN374-A.CH8
OC EC RD BTF PL MR HRV RML
Outdoor Condition Entering Coil Condition Return Duct Temperature Rise Blow Through Fan Sensible Gain Return Air Plenum Sensible Gain Return Side Miscellaneous Gain Heat Recovery Ventilator Condition Return Miscellaneous Latent Gain
sábado, 07 de diciembre de 2013, 07:38 a.m.
Chvac - Full Commercial HVAC Loads Calculation Program Elite Software Development College Station, TX 77845
Elite Software Development, Inc. Centro De Computo De UNI-FIM Page 21
R o o m # 1 - A u l a A - P i e Ch a r t s Room #1 peaks in February at 5pm
Roof - 24.68%
Room #1 Net Gain 13,799 Btuh
People - 53.81%
Wall - 15.63%
Lighting - 0.55% Equipment - 5.33%
Roof - 35.55%
Room #1 Loss 2,596 Btuh
Wall - 64.45%
C:\ ...\CCFIM-UNI - MN374-A.CH8
sábado, 07 de diciembre de 2013, 07:38 a.m.
Chvac - Full Commercial HVAC Loads Calculation Program Elite Software Development College Station, TX 77845
Elite Software Development, Inc. Centro De Computo De UNI-FIM Page 22
R o o m # 2 - A u l a B - P i e Ch a r t s Room #2 peaks in February at 5pm
Roof - 23.08%
Room #2 Net Gain 14,759 Btuh
People - 50.31%
Wall - 21.21%
Lighting - 0.42% Equipment - 4.98%
Roof - 26.21%
Room #2 Loss 3,521 Btuh
Wall - 73.79%
C:\ ...\CCFIM-UNI - MN374-A.CH8
sábado, 07 de diciembre de 2013, 07:38 a.m.