kV Series 24 kV Series TPR6 24 Expanding Range Solutions and Performances
C+
+U+
+R+
+N4
unit
unit
unit
unit
kV Series 24 kV Series TPR6 24 Expanding Range Solutions and Performances
C+
+U+
+R+
+N4
unit
unit
unit
unit
INDEX • General Presentation
5
Experience, Reliability and Continue Innovation
6
Developing
7
General Description
8
Applications
9
TPR6 Features
10
Quality
11
Internal Arc Proof
12
Outdoor Version IP54
13
Indoor Version
14
Top Busbar Busb ar Extensibility
for outdoor and indoor versions
Indoor Lateral Extensibility
16
• TPR6 Main Characteristics •
17
Main Components
18
Switch Disconnector
18
Switch Disconnector Operating Mechanism
19
Circuit Breaker
20
Circuit Breaker Operating Mechanism
21
TPR6 Standards
22
Technical Data
23
Functions
24
Outdoor Congurations
30
Indoor Congurations
31
• Components
33
Motorizations
34
Voltage Indicator
34
HVSensor Voltage Detector
34
Operating Handle
35
Key Locking and Padlock
35
Fuses and Adaptor
36
• Cable Connections
TPR6 24kV 24 kV 1801
15
39
Bushings - Cable C able Compartment - Termination Point
40
Cable Terminal
41
Testing Cables Facility
42
Operating Sequences
43
Compatibility
44
www.sel-electric.com
3
4
www.sel-electric.com
TPR6 24kV 1801
GENERAL PRESENTATION Experience, Reliability and Continue Innovation
6
Developing
7
General Description
8
Applications
9
TPR6 Features
10
Quality
11
Internal Arc Proof
12
Outdoor Version IP54
13
Indoor Version
14
Top Busbar Extensibility
15
for outdoor and indoor versions
Indoor Lateral Extensibility
TPR6 24kV 1801
16
www.sel-electric.com
5
GENERAL PRESENTATION
EXPERIENCE, RELIABILITY AND CONTINUE INNOVATION
SEL S.p.A. has over fty years of experience in the construction of medium voltage switchgears. Today SEL S.p.A. offers a comprehensive range of products for medium voltage up to 40.5kV. SEL S.p.A. offers advanced products that ensure maximum personal safety according to IEC-EN standards, providing internal arc protection as standard. The TPR6 series, thanks to the various functional units, allow a wide modularity applicable to all types of requests in MV distribution, with ease of use and compactness.
6
www.sel-electric.com
TPR6 24kV 1801
up to
up to
24kV 630A C unit up to
No Current Derating up to
55°C
IAC up to
25kA A-FLR
up to
25kA 3s
54
IP Outdoor
1250A “Experience and Innovation at Your Service” 1801
GENERAL PRESENTATION
GENERAL DESCRIPTION INTRODUCTION TPR6 is an SF6 insulated ring main unit for the secondary distribution distribution network. TPR6 uses the latest developments in switchgear technology providing an extremely compact medium voltage switchgear solution and ensuring maximum personnel safety.
CONSTRUCTION CHARACTERISTICS TPR6 is a completely “sealed for life” system with a stainless steel tank containing all live parts and switching devices. The structure can withstand the electrodynamics stresses during the operation. The operating mechanism, movable mimic and voltage signaling lamps are positioned in the front panel. Switches are operated by means of spring-operated mechanisms. Movable mimic gives the position of the switch whereas the voltage signaling lamp indicates the voltages. Fuses and cable compartment compartment are easily accessible through the front door which is interlocked with the earth switch. If present, the low voltage auxiliary compartment compartment is situated above the ring main unit.
SAFETY CHARACTERISTICS The personnel safety is obtained by using mechanical interlocks: • When the switch disconnector is closed closed the earth earth switch switch can't can't be closed simultaneous simultaneously ly and the access to MV cables is prevented. • When the earth switch is closed there is a free access to MV cables but it is impossible to close the switch. • When the access door to MV cables and fuses is opened it is impossible to close the switch. Metal screens prevent access to electrical parts during maintenance operations. It is possible to block the switch in three positions with key locks.
INTERNAL ARC CLASSIFICATION The robust design of the metal enclosure prevents deformations and ensures protection against fault. TPR6 is designed to withstand an internal arc caused by a rated short-circuit short-circuit current up to 25kA for 1s preventing every danger to the operator.
THE TPR6 RANGE CONSISTS • • • • • •
8
www.sel-electric.com
OF ALL OF THE NECESSARY MV
FUNCTIONS ENABLING:
Connection and power supply on a open open or closed ring network. Power supply and protection of transformers with circuit breaker breaker or combined fuseswitches up to 200A. Power supply and protection of lines by a 1250A circuit breaker Busbar coupling. MV metering. Earth switch for cable connection.
TPR6 24kV 24 kV 1801
GENERAL PRESENTATION
PPLICATIONS A PPLICATIONS TPR6 is a complete ring main unit range suitable for all the switching operations in 7.2kV, 12kV, 17.5kV, 24kV, secondary distribution network. Operating safely in a distribution network requires different switching points to obtain maximum service continuity in case of fault on the network. • • • • • • • • • •
TPR6 24kV 24 24kV kV 1801
Power supply companies. Power stations. Cement industry. Automotive Automotiv e industry. Iron and steel works. Windmills. Solar plant. Textile, paper and food industries. Chemical industry. Petroleum industry.
• • • • • • • • •
Pipeline installations. Offshore installations. Electrochemicall plants. Electrochemica Petrochemical plants. Seaport and shipbuilding industry. Diesel power plants. Emergency power supply installati installations. ons. Traction power supply systems. Stadium and sport center.
www.sel-electric.com www.sel-electric.com
9
GENERAL PRESENTATION
TPR6 FEATURES FLEXIBILITY • • • •
A wide range of products covering your present and future requirements. Modular cubicles adapted to future extension extensions. s. Possibility to mount auxiliary components under voltage. Options to anticipate the telecontrol.
COMPACT DIMENSIONS • •
Small dimensions and reduced weights for easier handling and installati installation. on. Reduced civil works costs.
REDUCED MAINTENANCE • • • •
TPR6 has long service life. Maintenance free live live parts which are are integrated integrated in vacuum or in a sealed tank of stainless steal. Control mechanisms are intended to function with reduced maintenanc maintenance e under normal operating conditions. High level of electrical endurance when breaking.
EASY OPERATIONS • •
Simple operations. All the control operations are carried out from the front by means of a simple devices.
EASY INSTALLATION • •
Small dimension dimensions s and reduced weights facilitate easy installation. Solutions adapted to cable connection.
SAFETY • • • •
10
www.sel-electric.com
During the testing testing cable cable operation operation itit is not needed needed to break the earthing earthing busbar busbar system of the switchgear. Interlock operated by earthing switch prevents unsafe operations. Additional interlocks to prevent incorrect operations. All active active parts parts of the TPR6 are contained contained in a sealed tank of stainless steel making making it deal for installation in difcult ambient conditions.
TPR6 24kV 1801
GENERAL PRESENTATION
QUALITY All the manufacturing process follows a quality procedure certied by TUV in accordance with ISO 9001:2008. The production conforms with the specic quality manual which is updated regularly so that it reects the most recent applicable quality control procedures.
Systematic tests Each TPR6 undergoes a thorough check before leaving the factory. The following routine tests are performed according to IEC 62271-200 standard in order to guarantee the quality, reliability and safety of the product: • Measurement of the resistance of the main circuits. • Opening and closing speed measurement on switch, earth switch and circuit-breaker. • Operating torque measurement. • Filling pressure and tightness test. • Dielectric test. • Conformity with drawings and diagrams. • Electrical function test on auxiliary circuits.
The gas enclosure is manufactured with stainless steel and fabricated using automatic “robot welding” technique to produce consistent leak-free equipment.
TPR6 24kV 1801
www.sel-electric.com
11
GENERAL PRESENTATION
INTERNAL A RC PROOF UP TO 25K A 1S All SEL’s Switchgears series are Internal Arc test proof on the four sides A-FLR including cable box, in accordance with IEC62271-200
Concerning Internal arc capability, SEL designed and tested the MV switchgears in manner to drive the exhaust gas towards the bottom because it is best solution for safety of operators.
Fault in Cables compartment
Fault in SF6 gas tank
Fault in busbar duct
SEL is able to meet customer's request for upward exhaust gas duct supplying a rear chimney that drives the gases outside. This chimney has been internal arc proof tested in C.E.S.I. Laboratory in Milan, at a fault current of 25kA 1s. During switchgear installation a suitable channel has to be arranged in order to collect the exhaust gas in a safe area.
12
www.sel-electric.com
TPR6 24kV 1801
GENERAL PRESENTATION
OUTDOOR VERSION IP54
IP
54
Outdoor
The protection against severe weather conditions, rain, humidity and dust is guaranteed by TPR6 robust deisign. The protection degree of the switchgear is IP54. The enclosure is tted with a front door and padlock. The gas piston facilitates the opening operation and maintains the door lifted in order to allow the normal operations or maintenance.
NO Current Derating up to
55°C
LTL Non Extensible 3 way RMU
Rated current of the RMU is guaranteed with no derating up to 55°C ambient temperature.
Ck-Ck-kMk-LLk composition
TPR6 24kV 1801
www.sel-electric.com
13
GENERAL PRESENTATION
INDOOR VERSION In all indoor versions is possible to install a marshalling box for auxiliary.
C+
+U+
+R+
+N4
unit
unit
unit
unit
CLT unit Customized for customer
14
www.sel-electric.com
R unit
TPR6 24kV 1801
GENERAL PRESENTATION
TOP BUSBAR EXTENSIBILITY EXTENSIBLE
FOR OUTDOOR AND INDOOR VERSIONS
VERSION TYPE “K” FOR BUSBARS.
Extensibility connection is realized with bushing interface tipe "C" on the top of RMU. Both indoor/outdoor versions of TPR6 are suitable with this connection.
CONNECTION
WITH PREMOLDED UNSHIELDED BUSBAR SYSTEM
UP TO 17,5KV
Realized with premoulded busbar system, no additional insulating belt is required.
CONNECTION
TPR6 24kV 1801
WITH PREMOLDED SHIELDED BUSBAR SYSTEM
UP TO 24KV
www.sel-electric.com
15
GENERAL PRESENTATION
INDOOR L ATERAL EXTENSIBILITY EXTENSIBLE
VERSION TYPE “+”
Bus-bar coupling system of SF 6 insulated switchgears (match-makers).
Switchgear Function Type. Extensibility Type.
Extensible version type “+” with only the prearrangement for future extension.
COUNPLING SPACE TYPE “+” In case the switchboard is prearranged for further expansions on the left, on the right or both sides, provide at least 150mm space between the switchboards and a suitable lateral space for coupling operations.
16
www.sel-electric.com
TPR6 24kV 1801
TPR6 M AIN CHARACTERISTICS Main Components
TPR6 24kV 1801
16
Switch Disconnector
16
Switch Disconnector Operating Mechanism
17
Circuit Breaker
18
Circuit Breaker Operating Mechanism
19
TPR6 Standards
20
TPR6 Technical Data
21
Functions
22
Indoor Congurations
29
Outdoor Congurations
30
www.sel-electric.com
17
TPR6 M AIN CHARACTERISTICS - M AIN COMPONENTS
SWITCH DISCONNECTOR SWITCH DISCONNECTOR The insulation level inside the TPR6 modules has been obtained by means of sulphur hexauoride (SF6). This gas has a double function: it increases dielectric rigidity in comparison with air and aids electric arc extinction. The modules with the equipment insulated in SF6, have the following advantages: • General and electrical long life. • Maintenance-free. • Secure and stable operation. • Reduced sizes. This switchgear is made of a rotating part ( movable-contacts )which opens and closes the electric circuit. Positions: The switch disconnector has three positions: A) Closed B) Opened C) Earthed
CLOSED
18
www.sel-electric.com
OPENED
EARTHED
TPR6 24kV 1801
TPR6 M AIN CHARACTERISTICS - M AIN COMPONENTS
SWITCH DISCONNECTOR OPERATING MECHANISM TPR6 switch disconnector can be provided with two kind of operating mechanisms:
LT: Dead Point over-ride, operator indipendent operating mechanism capable of making, carrying and breaking load currents.
3D: Energy Stored, operator indipendent operating mechanism capable of making, carrying and breaking load currents. Operation in two steps: • Mechanism charging by lever or motor. • Stored energy released by opening/closing knob.
A CCESSORIES
LT
3D
Padlock holder for switch
●
Padlock holder for earth switch
●
●
Switch keylock (key removable in open position)
●
●
Earth switch keylock (key removable in open position)
●
●
Earth switch keylock (key removable in closed position)
●
●
Switch auxiliary contacts
●
●
Earth switch auxiliary contacts
●
●
Shunt opening release
●
Shunt closing Release
●
Motor mechanism
●
●
Door locking when earth switch is open
●
●
Operating mechanism accessory examples
TPR6 24kV 1801
www.sel-electric.com
19
TPR6 M AIN CHARACTERISTICS - M AIN COMPONENTS
CIRCUIT BREAKER VACUUM CIRCUIT BREAKER Our circuit breaker introduces the new concept of super-compact Disconnector + Vacuum CB combined device. It comprises of three vacuum interrupters, which have a fault-make, faultbreak rating. Earthing of the outgoing cable is achieved by the use of the circuit breaker in series with the off-load disconnector/selector switch.
SCBD / CL-OP
VACUUM SF6
VACUUM SF6
CLOSED
VACUUM SF6
OPENED
EARTHED
SCB6
VACUUM
SF6
VACUUM
SF6
CLOSED
VACUUM
SF6
OPENED
EARTHED
VACUUM TECHNOLOGY Nowadays the interruption of current in vacuum is recognised as the dominant technology in medium voltage and as a consequence its use is continuously increasing. It is possible to have highly efcient vacuum circuit-breakers with electrical life which is longer than mechanical life, with total respect of environment; but in particular, vacuum circuit-breakers offer enhanced performances thanks to the reduction of arc energy, fast opening time, insulation recovery after overvoltage and reduction of mechanical energy needed for operating mechanism.
20
www.sel-electric.com
TPR6 24kV 1801
TPR6 M AIN CHARACTERISTICS - M AIN COMPONENTS
CIRCUIT BREAKER OPERATING MECHANISM The circuit breaker module operating mechanism SCB6 is composed of three different functional parts: 1. Circuit Breaker Operating Mechanism Operator independent energy stored operating mechanism with free release makes possible to carry out a complete cycle O-C-O with only one spring charging; besides it is suitable for the rapid auto-reclosing ( O-0,3s-CO– 3min-CO ). The circuit-breaker can be remote controlled by installation of some electrical accessories. 2. Operator dependent line disconnector manual operating mechanism which operates in the absence of load. 3. Operator independent earth switch operating mechanism which operates under load.
The circuit breaker module operating mechanism SCBD is composed of three different functional parts: Circuit Breaker Operating Mechanism Operator independent energy stored operating mechanism with free release makes possible to carry out a complete cycle O-C-O without spring charging; besides it is suitable for the rapid auto-reclosing ( O-0,3s-CO–3min-CO ). The circuit-breaker can be remote controlled by installation of some electrical accessories. Operator dependent line disconnector manual operating mechanism which operates in the absence of load. Operator dependent earth disconnector operating mechanism which operates in the absence of load.
The circuit breaker module operating mechanism CL-OP is composed of three different functional parts: 1. Circuit Breaker Operating Mechanism Operator independent operating mechanism with simplied closing system not intended for rapid auto-reclosing ( CO–15s-CO ). The circuitbreaker can be remote controlled by installation of some electrical accessories. 2. Operator dependent line disconnector manual operating mechanism which operates in the absence of load. 3. Operator dependent earth disconnector operating mechanism which operates in the absence of load.
SCB6 Frontal Cover
TPR6 24kV 1801
SCBD Frontal Cover
CL-OP Frontal Cover
www.sel-electric.com
21
TPR6 M AIN CHARACTERISTICS
STANDARDS IEC Standards TPR6 is manufactured and tested in conformity with the latest issues of the following IEC standards.
22
www.sel-electric.com
IEC 62271-1
High-voltage switchgear and controlgear - Part 1: Common specications for alternating current switchgear and controlgear
IEC 62271-200
High-voltage switchgear and controlgear - Part 200: AC metal-enclosed switchgear and controlgear for rated voltages above 1 kV and up to and including 52 kV
IEC 62271-100
High-voltage switchgear and controlgear - Part 100: Alternating current circuitbreakers
IEC 62271-103
High-voltage switchgear and controlgear - Part 103: Switches for rated voltages above 1 kV up to and including 52 kV
IEC 62271-102
High-voltage switchgear and controlgear - Part 102: Alternating current disconnectors and earthing switches
IEC 62271-105
High-voltage switchgear and controlgear - Part 105: Alternating current switch-fuse combinations for rated voltages above 1 kV up to and including 52 kV
IEC 62271-206
High-voltage switchgear and controlgear - Part 206: Voltage presence indicating systems for rated voltages above 1 kV and up to and including 52 kV
IEC 62271-304
High-voltage switchgear and controlgear - Part 304: Design classes for indoor enclosed switchgear and controlgear for rated voltages above 1 kV up to and includuing 52 kV to be used in severe climatic conditions
IEC 62271-307
High-voltage switchgear and controlgear - Part 307: Guidance for the extension of validity of type tests of AC metal and solid-insulation enclosed switchgear and controlgear for rated voltages above 1 kV and up to and including 52 kV
IEC 60529
Degrees of protection provided by enclosures (IP Code)
IEC 60060-1
High-voltage test techniques - Part 1: General denitions and test requirements
IEC 60376
Specication of technical grade sulfur hexauoride (SF6) for use in electrical equipment
IEC 62271-4
Handling procedures for sulphur hexauoride ( SF6 ) and its mixtures
IEC 60255
Measuring relays and protection equipment
IEC 61869-2
Instrument transformers - Part 2: Additional requirements for current transformers
IEC 61869-3
Instrument transformers - Part 3: Additional requirements for inductive voltage transformers
IEC 60044-8
Instrument transformers - Part 8: Electronic current transformers
IEC 60282-1
High-voltage fuses - Part 1: Current-limiting fuses
DIN 43625
High-voltage fuses; Rated voltage 3,6 to 36 kV; Fuse-Links
EN 50181
Plug-in type bushings above 1 kV up to 52 kV and from 250 A to 2,50 kA for equipment other than liquid lled transformer
CEI 0-16
Reference technical rules for the connection of active and passive consumers to the HV and MV electrical networks of distribution Company
TPR6 24kV 1801
TPR6 M AIN CHARACTERISTICS
TECHNICAL D ATA SWITCHGEARS M AIN CHARACTERISTICS kV
7,2
12
17,5
24
Altitude
IEC 62271-1
m
<1000 (for different value contact SEL)
Ambient air temperature
IEC 62271-1
°C
-25 ÷ 55
Relative humidity
%
95
Insulation Rated Voltage
kV
7,2
12
17,5
24
Rated Voltage
kV
7,2
12
17,5
24
Lightning impulse withstand voltage between phases and towards the ground
kV
60
95
95
125
Lightning impulse withstand voltage across the isolating distance
kV
70
110
110
145
Power frequency withstand voltage between the phases
kV
20
28
38
50
Power frequency withstand voltage across the isolating distance
kV
23
32
45
60
Rated Frequency
Hz
Rated Current
Switch disconnector
Rated Current
Vacuum Circuit Breaker
50 - 60 200 - 400 - 630 250 - 400 - 630 - 1250
Rated short time withstand current Ik
kA
Rated peak withstand current IP (making capacity )
kA
Rated duration of short circuit tk
s
1-3
Degree of protection on front face
IP
3X - 41 - 54 (outdoor version)
Degree of protection on electrical MV circuits
IP
67
kA x s
up to 25 1s
Internal Arc classifcation IAC A-F; FL; FLR; including cables box
IEC 62271-200
up to 25 50Hz 2,5 x I K -
Switchgear Classifcation
60Hz 2,6 I K
PM ( Metallic Partition )
Loss of service continuity classes
LSC2
M AIN CHARACTERISTICS (SWITCH DISCONNECTOR - DISCONNECTOR - CIRCUIT BREAKER) kV
7,2
12
17,5
24
Mechanical operation
Switch disconnector IEC 62271-103
1.000 operations / Class M1 - 5.000 operations / Class M2
Electrical operation
Switch disconnector IEC 62271-103
100 breaks at In p.f.=0,7 / Class E3
Electrical operation
Switch disconnector IEC 62271-103
making capacity 5 / Class E3
Mechanical operation
Disconnector IEC 62271-102
1.000 operations / Class M1
Mechanical operation
Earthing switch IEC 62271-102
1.000 operations / Class M0
Electrical operation
Earthing switch IEC 62271-102
making capacity 5 / Class E2
Mechanical operation
Circuit breaker IEC 62271-100 C / D unit
2000 operations / Class M1 - 10.000 operations / Class M2
Electrical operation
Circuit breaker IEC 62271-100 C / D unit
E1 / E2
Mechanical operation
Circuit breaker IEC 62271-100 T unit
2000 operations / Class M1
Electrical operation
Circuit breaker IEC 62271-100 T unit
E1
Breaking Capacity
Circuit breaker IEC 62271-100
kA
25
Making Capacity
Circuit breaker IEC 62271-100
kA
50Hz 2,5 x I K -
Break Time Vacuum Circuit Breaker
Circuit breaker IEC 62271-100
ms
Rated operating sequence
Circuit breaker IEC 62271-100
21 60Hz 2,6 I K
≤ 70 O - 0,3s - CO - 15sec - CO O - 0,3s - CO - 3min - CO CO - 15s - CO
Making & breaking on fuse-switch
IEC 62271-105 F unit
kA rms
Breaking at rated transfer current Itransfer
IEC 62271-105 F unit
A
Mainly active load breaking current
Switch disconnector IEC 62271-103
A
630
Close loop breaking current
Switch disconnector IEC 62271-103
A
630
Cable charging breaking current
Switch disconnector IEC 62271-103
A
32
Line charging breaking current
Switch disconnector IEC 62271-103
A
32
Earth fault breaking current
Switch disconnector IEC 62271-103
A
57
TPR6 24kV 1801
25 2100
20
1800
1600
www.sel-electric.com
1400
23
TPR6 M AIN CHARACTERISTICS
TPR6 UNITS FUNCTIONS L unit
F unit
G unit
24
www.sel-electric.com
Indoor
Indoor
Indoor
Outdoor
Outdoor
Outdoor
Details Unit Name
L
Unit Function
Network Switch Disconnector
Device
630A Switch Disconnector with Earthing Switch
Details Unit Name
F
Unit Function
Transformer Feeder with Fuse-Switch Disconnector
Device
200A Combined Fuse-Switch Disconnector with Earthing Switch
Details Unit Name
G
Unit Function
Network Coupling with Circuit Breaker + Disconnector
Device
630A Circuit Breaker + Disconnector with Earth Disconnector
CB TYPE
SCBD
TPR6 24kV 1801
TPR6 M AIN CHARACTERISTICS
TPR6 UNITS FUNCTIONS C unit
Indoor
T unit
Indoor
D unit
Indoor
TPR6 24kV 1801
Outdoor
Outdoor
Details Unit Name
C
Unit Function
Line Feeder with CB
Device
630A Circuit Breaker + Disconnector with Earth Disconnector
CB TYPE
SCBD OR CL-OP
Details Unit Name
T
Unit Function
Transformer Feeder with CB
Device
250A Circuit Breaker + Disconnector with Earth Disconnector
CB TYPE
CL-OP
Details Unit Name
D
Unit Function
Line Feeder with CB
Device
1250A Circuit Breaker + Disconnector with Earthing Switch-Disconnector
CB TYPE
SCB6
www.sel-electric.com
25
TPR6 M AIN CHARACTERISTICS
TPR6 UNITS FUNCTIONS S unit
U unit
I unit
Indoor
Outdoor
Indoor
Outdoor
Indoor
Details Unit Name
S
Unit Function
Network Coupling with Switch Disconnector
Device
630A Switch-Disconnector
Details Unit Name
U
Unit Function
Network Coupling with Switch Disconnector
Device
630A Switch-Disconnector with Earthing Switch
Details THE "I" UNIT IS ONLY AVAILABLE IN COMBINATION WITH ANOTHER UNIT, FOR EXAMPLE "IL" OR "IC" OR "ILLC"
Unit Name
I - I2 - I3
Unit Function
Cable Connection
Device
-
I UNIT IS DIVIDED INTO 3 TYPOLOGIES: "I" = 3 BUSHINGS "I2" = 6 BUSHINGS "I3" = 9 BUSHINGS
EXAMPLE OF "I3C" UNIT
26
www.sel-electric.com
TPR6 24kV 1801
TPR6 M AIN CHARACTERISTICS
TPR6 UNITS FUNCTIONS Q unit
Indoor
R unit
Indoor
TPR6 24kV 1801
Outdoor
Outdoor
Details Unit Name
Q
Unit Function
Circuit Breaker + Metering
Device
630A Circuit Breaker + Switch Disconnector with Earthing Switch
CB TYPE
SCBD
Details Unit Name
R
Unit Function
Metering Network Coupling with CB + Switch Disconnector
Device
630A Circuit Breaker + Switch Disconnector with Earthing Switch
CB TYPE
SCBD
www.sel-electric.com
27
TPR6 M AIN CHARACTERISTICS
TPR6 UNITS FUNCTIONS N unit Unit Name
N
Unit Function
Metering Unit + Switch Disconnector
Device
630A Switch-Disconnector with Earthing Switch
Indoor N1
N2
N3
N4
28
www.sel-electric.com
Outdoor
TPR6 24kV 1801
TPR6 M AIN CHARACTERISTICS
TPR6 UNITS FUNCTIONS M unit Unit Name
M
Unit Function
Metering Unit
Indoor M1
M2
M3
M4
M5
M6
TPR6 24kV 1801
Outdoor
www.sel-electric.com
29
TPR6 M AIN CHARACTERISTICS
OUTDOOR CONFIGURATIONS 1 FUNCTION UNIT
W
H + MARSHALLING BOX
D*
L
390
1775
720
F
390
1775
720
G
470
1775
720
C
470
1775
720
T
470
1775
720
S
470
1775
720
470
1775
720
840
1775
720
Q
840
1775
720
R
840
1775
720
840
1775
720
U M
N
1-2-3-4-5-6
1-2-3-4
2 FUNCTIONS UNITS
W
H + MARSHALLING BOX
D*
LL
740
1775
720
LT
740
1775
720
LF
740
1775
720
LC
740
1775
720
W
H + MARSHALLING BOX
D*
LLL
1090
1775
720
LCL
1090
1775
720
LTL
1090
1775
720
LLF
1090
1775
720
LTT
1090
1775
720
W
H + MARSHALLING BOX
D*
LLLL
1440
1775
720
LLTL
1440
1775
720
LLLF
1440
1775
720
LTTL
1440
1775
720
LLCL
1440
1775
720
LCCL
1440
1775
720
W
H + MARSHALLING BOX
D*
LLLLL
1790
1775
720
LLLLT
1790
1775
720
MORE CONFIGURATIONS ARE AVAILABLE ON REQUEST
3 FUNCTIONS UNITS
MORE CONFIGURATIONS ARE AVAILABLE ON REQUEST
4 FUNCTIONS UNITS
MORE CONFIGURATIONS ARE AVAILABLE ON REQUEST
5 FUNCTIONS UNITS
MORE CONFIGURATIONS ARE AVAILABLE ON REQUEST
* When a rear chimney is installed depth increases by 150 mm.
30
www.sel-electric.com
TPR6 24kV 1801
TPR6 M AIN CHARACTERISTICS
INDOOR CONFIGURATIONS 1 FUNCTION UNIT
W
H + MARSHALLING BOX
D*
L
390
1475 + 450
720
F
390
1475 + 450
720
G
470
1475 + 450
720
C
470
1475 + 450
720
T
470
1475 + 450
720
S
470
1475 + 450
720
470
1475 + 450
720
840
1475 + 450
720
840
1475 + 450
720
840
1475 + 450
720
840
1475 + 450
720
600
1475 + 450
720
W
H + MARSHALLING BOX
D*
LL
740
1475 + 450
720
LT
740
1475 + 450
720
LF
740
1475 + 450
720
LC
740
1475 + 450
720
W
H + MARSHALLING BOX
D*
LLL
1090
1475 + 450
720
LCL
1090
1475 + 450
720
LTL
1090
1475 + 450
720
LLF
1090
1475 + 450
720
LTT
1090
1475 + 450
720
U 1-2-3-4-5-6
M Q R N
1-2-3-4
D
2 FUNCTIONS UNITS
MORE CONFIGURATIONS ARE AVAILABLE ON REQUEST
3 FUNCTIONS UNITS
MORE CONFIGURATIONS ARE AVAILABLE ON REQUEST
4 FUNCTIONS UNITS
W
H + MARSHALLING BOX
D*
LLLL
1440
1475 + 450
720
LLTL
1440
1475 + 450
720
LLLF
1440
1475 + 450
720
LTTL
1440
1475 + 450
720
LLCL
1440
1475 + 450
720
LCCL
1440
1475 + 450
720
W
H + MARSHALLING BOX
D*
LLLLL
1790
1475 + 450
720
LLLLT
1790
1475 + 450
720
MORE CONFIGURATIONS ARE AVAILABLE ON REQUEST
5 FUNCTIONS UNITS
MORE CONFIGURATIONS ARE AVAILABLE ON REQUEST
6 FUNCTIONS UNITS
W
H + MARSHALLING BOX
D*
LLLLLL
2140
1475 + 450
720
LLLLLT
2140
1475 + 450
720
LLLLLC
2140
1475 + 450
720
MORE CONFIGURATIONS ARE AVAILABLE ON REQUEST
* When a rear chimney is installed depth increases by 150 mm.
TPR6 24kV 1801
www.sel-electric.com
31
32
www.sel-electric.com
TPR6 24kV 1801
COMPONENTS Motorizations
34
Voltage Indicator
TPR6 24kV 1801
34
HVSensor Voltage Detector
34
Operating Handle
35
Key Locking and Padlock
35
Fuses and Adaptor
36
www.sel-electric.com
33
COMPONENTS
MOTORIZATIONS - VOLTAGE INDICATOR - HVSENSOR MOTORIZATION All our operating mechanisms have the possibility to equip the motorizations upgrade, except the 3D operating mechanism that is built with or without the motorization.
Switch Motorization Control Board
LT Motorization Upgrade
Circuit Breaker MotorizationControl Board
CL-OP Motorization Upgrade
SCBD Motorization Upgrade
SCB6 Motorization Upgrade
VOLTAGE INDICATOR Voltage presence indicating system. Integrated 3-phase test point for phase comparison test.
HVSENSOR VOLTAGE DETECTOR Voltage detector with relay output. Use in combination with Voltage Indicator.
34
www.sel-electric.com
TPR6 24kV 1801
COMPONENTS
Operating Handle - Keylocks and Padlock Holder OPERATING HANDLE
In the TPR6 switchgear there is a single operating handle for all mechanism.
For F unit there is a special operating handle only to remove the fuses.
K EYLOCK AND PADLOCK HOLDER FRONTAL COVER SIMBOL
OPERATING MECHANISM DESCRIPTION
LT
3D
SCB6
SCBD
CL-OP
Keylock with switch open:
○
○
○
○
○
Keylock with earthing switch open:
○
○
○
○
○
Keylock with earthing switch closed:
○
○
○
-
-
Keylock with switch closed:
-
-
●
-
-
Keylock with circuit breaker open:
-
-
●
-
-
-
-
-
●
●
○
-
○
○
○
○
○
○
Keylock with earthing switch closed + Keylock with circuit breaker closed
Padlock holder on Disconnector / SwitchDisconnector
Padlock holder on Earthing Disconnector / Earthing Switch
○
- Not Expected
TPR6 24kV 1801
○
○
Optional
●
Standard
www.sel-electric.com
35
COMPONENTS
Fuses Fuse selection Some important transformer and fuse features have to be known to select the right fuse for power transformer protection: Transformer: Rated power Short circuit voltage Service rated voltage Rated current Inrush maximum current Overload current Short circuit current Maximum time withstand short circuit
Standard fuses
Pn [kVA] Ucc [%] Un [kV] Int [A] Ii [A] ( usually 12xInt) Is [A] ( usually 1,5xInt) ICCt [A] tm [s] (usually 2s for transformer up to 630kVA, 3s for bigger transformer)
Fuse Rated insulation voltage Rated current Maximum breaking current Minimum breaking current Power losses at Int
Vi [kV] In [A] I1 [kA] I3 [A] PW [W]
Time/current characteristic to get follow values: Pre-arcing current at 0,1s If (t=0,1s)[A] Pre-arcing current at tm If (t=tm )[A] Pre-arcing current at 0,05s If (t=0,05s)[A] Verify following conditions: • The rated insulation voltage of the fuse has to be higher than the service rated voltage of the transformer Vi > Un • The fuse has to be able to break the maximum short circuit current of the plant I1 > ICCt (in case of fault before the transformer) • The fuse melts in case of fault on LV wiring of the transformer I3 < ICCt • The fuse protects the transformer in case of short circuit If (tm ) < ICCt • The fuse does not melt at the transformer withstand overload In > IS • The fuse does not melt at the transformer inrush current If (0,1s) > Ii • The fuse power dissipation does not compromise the temperature inside the switchboard PW < 150W • The transfer current has to be lower then the maximum admissible value for the switchboard If (0,05s) < I transfer
Special fuses up to 12kV
Standard Striker pin fuses (1 ± 0.25 Joule) in accordance with: • IEC 60 282-1/VDE 0670-4 • IEC 60 787/VDE 0670-402 • DIN 43 625 Selection table helps to select the fuses for generic MV/LV power transformers; it is valid for ambient air temperature up to 40°C and it has to be veried with all above parameters.
FUSES SELECTION TABLE - T ABELLA SCELTA FUSIBILI
Special fuses up to 24kV
36
www.sel-electric.com
V S
V I
PN [K VA]
[K V]
[K V]
100
125
160
200
250
315
400
500
6
12
20
25
31,5
40
50
63
80
100
125
160
-
-
-
-
6,6
12
16
20
25
31,5
40
50
63
80
100
125
160
-
-
-
10
12
16
16
20
25
31,5
40
50
63
80
100
125
160
-
-
11
12
16
16
16
20
25
31,5
40
50
63
80
100
125
160
-
15
24
10
10
16
16
20
25
31,5
40
50
63
80
100
125
-
20
24
6
10
10
16
16
20
25
31,5
40
50
63
80
100
125
23
24
6
6
10
10
16
16
20
25
31,5
40
50
63
80
100
33
36
4
6
6
10
10
10
16
20
25
31,5
40
40
50
63
36
36
4
6
6
10
10
10
16
16
20
25
31,5
40
50
63
630
800
1000 1250 1600 2000
TPR6 24kV 1801
COMPONENTS
Fuses Insulation Voltage
Vi = 12 kV (Not Standard Adaptor) Vi = 24 kV (Standard Adaptor)
Frontal Fuses Extraction.
TPR6 24kV 1801
Type
e (mm)
L (mm)
12 kV
292
358
24 kV
442
508
Transfer Current ITransfer = 1800 A ITransfer = 1400 A
Order the adapter kit for fuses with "e" = 292 mm
www.sel-electric.com
37
38
www.sel-electric.com
TPR6 24kV 1801
C ABLE CONNECTIONS
TPR6 24kV 1801
Bushings - Cable Compartment - Termination Point
40
Cable Terminal
41
Testing Cable Facilities
42
Operating Sequences
43
Compatibility
44
www.sel-electric.com
39
C ABLE CONNECTIONS
BUSHINGS T YPE C 630A
BUSHINGS Epoxy resin bushings installed on TPR6 are according to DIN EN 50181.
UNITS
T YPE A 250A
Unit Function
L
F
C
T
D
Bushing Type
C
A
C
A/C
C
C
C
C
C
C
C
C
C
C
C
-
ONLY Straight Cable Conn6ector Bushing type A
-
-
-
Upper Extensibility Connection Type "K" only Outdoor Version Lateral Connection Type with "I" unit
Special Note
CALBE BUSHINGS HEIGHT INDOOR /OUTDOOR
40
www.sel-electric.com
TPR6 24kV 1801
C ABLE CONNECTIONS
C ABLE TERMINAL Premolded shielded type termination for interface “C” bushing (according with DIN EN 50181 standard) are suitable cable termination.
250A Straight Cable Connector Bushing type A
630A Disconnectable and bolted socket Connector Bushing type C
For "F" unit is possible install only this connector.
Standard air insulated heat/cold shrinkable indoor termination can be used in combination with silicon cover caps (premoulded boots) placed on the “C” bushing sealed and xed by cast resin bolts. It allows access for cable test purpose. Using our own production silicon premolded boots, this solution has been tested by C.E.S.I. Laboratory in Milan Italy.
TPR6 24kV 1801
www.sel-electric.com
41
C ABLE CONNECTIONS
TESTING C ABLES F ACILITIES TEWSTING CABLE FACILIIES The TPR6 has fully interlocked integrated ring switch and tee-off cable test facilities. To perform the testing cable remove the insulating cap from the cable connector and install the testing probe.
WITH PREMOLDED SHIELDED CABLE CONNECTOR
1
2
3
4
WITH PREMOLDED NOT SCREENED CABLE CONNECTOR
42
www.sel-electric.com
1
2
3
4
(MADE BY SEL S.P.A.)
TPR6 24kV 1801
OPERATION SEQUENCES UNITS OPERATING SEQUENCES Qr Code usage istructions: Download the right application from you device store to read QR-Code marks. Start Application. Point your device camera to the QR Code. Multimedia information will be downloaded direcly to your device.
TPR6 - LT Operating Mechanism
TPR6 - 3D Operating Mechanism
The video shows the switch operations sequences of the LT Operating Mechanism mounted on a L - S - U - N units.
The video shows the switch operations sequences of the 3D Operating Mechanism mounted on a F units.
TPR6 - SCBD Operating Mechanism
TPR6 - CLOP Operating Mechanism
The video shows the switch operations sequences of the SCBD Operating Mechanism mounted on a C - Q - R - G units.
The video shows the switch operations sequences of the CLOP Operating Mechanism mounted on a C - T units. In the video there is a LTL operating sequences
TPR6 - LT Testing Cables
TPR6 - SCBD Testing Cables
TPR6 - CLOP Testing Cables
The video shows the switch operations sequences for testing cables of the LT Operating Mechanism mounted on a L - S - U - N units.
The video shows the switch operations sequences for testing cables of the SCBD Operating Mechanism mounted on a C - Q - R - G units.
The video shows the switch operations sequences for testing cables of the CLO Operating Mechanism mounted on a C - T units.
TPR6 24kV 1801
www.sel-electric.com
43
COMPATIBILITY
ALL INDOOR VERSIONS IS FULLY COMPATIBLE WITH PREVIOUS VERSION OF TPR6 24KV
COMPATIBLE WITH PREVIOUS TPR6 24 K V COUPLING The new indoor version is compatible with the previus TPR6 line.
TPR6 24kV 25kA
Previous TPR6 24kV
Base to align the two versions of TPR6 24kV at the same height
44
www.sel-electric.com
TPR6 24kV 1801
46
www.sel-electric.com
TPR6 24kV
TPR6 24K V
INDEX • General Presentation
48
General Description
48
Internal Arc Proof
49
Extensibility Version
50
• TPR6 Main Characteristics •
52
Main Components
52
Switch Disconnector
52
Switch Disconnector Operating Mechanism
53
Circuit Breaker
54
Circuit Breaker Operating Mechanism
54
Technical Data
55
Functions
56
TPR6 Congurations
57
Dimensions
58
• Components
TPR6 24kV
59
TPR6 Detailed View
59
Key Locking and Padlock
60
Coupling Space
62
Installation Distance
62
Cables Termination Point
62
www.sel-electric.com
47
TPR6 24K V
GENERAL DESCRIPTION INTRODUCTION TPR6 is an SF6 insulated ring main unit for the secondary distribution network. TPR6 uses the latest developments in switchgear technology by providing an extremely compact medium voltage switchgear solution. All this is obtained by ensuring maximum personnel safety.
CONSTRUCTION CHARACTERISTICS TPR6 is a completely “sealed for life” system with a stainless steel tank containing all live parts and switching devices. A hermetically sealed steel tank from the outside environment ensures a high level of reliability as well as personal safety. The structure can withstand the electrodynamics stresses during the operation. The operating mechanism, movable mimic and voltage signaling lamps are positioned in the front panel. Switches are operated by means of spring-operated mechanisms. Movable mimic gives the position of the switch whereas the voltage signaling lamp indicates the voltages. Fuses and cable compartment are easily accessible through the front door which is interlocked with the earth switch. Should the low voltage auxiliary compartment be present, it is situated above the ring main unit.
SAFETY CHARACTERISTICS The personnel safety is obtained by using mechanical interlocks. These mechanical locks operate as follows: When the switch disconnector is closed the earth switch can not be closed simultaneously and the access to MV cables (T, C and F modules) is prevented. When the earth switch is closed there is a free access to MV cables (T, C and F modules) but it is impossible to close the switch. When the access door to MV cables and fuses is opened it is impossible to close the switch (T, C and F modules). Metal screens prevent access to electrical parts during maintenance operations. It is possible to block the switch in three positions with key locks.
INTERNAL ARC WITHSTAND The robust design of the metal enclosure prevents deformations and ensures protection against fault. TPR6 is designed to withstand an internal arc caused by a rated short-circuit current for 1 second preventing any danger to the operator. A safety valve against accidental overpressure caused by an internal arc is located at the bottom of the metal enclosure. The gas is released to the bottom of the TPR6 without any danger to the operator. TPR6 has been type tested and it meets all the criteria of IAC class A FL, as dened by IEC 62271-200 standard, annex A. In case the rear pressure relief duct is used in the application the internal arc classication is AFLR (arc proof on four sides).
THE TPR6 RANGE CONSISTS
OF ALL OF THE NECESSARY MV FUNCTIONS ENABLING :
Connection and power supply on a open or closed ring network. Power supply and protection of transformers with circuit breaker or combined fuse- switches up to 200A. Power supply and protection of lines by a 630A circuit breaker Busbar coupling. MV metering. Earth switch for cable connection.
48
www.sel-electric.com
TPR6 24kV
TPR6 24K V
PRESSURE RELIEF IN CASE OF INTERNAL ARC DESCRIPTION
In case of an internal fault the gases can be canalized upwards, downwards or directly outside from the substation by means of pressure relief duct (optional).
1 Internal fault 2 Gas duct 3 Opening (for ventilation)
DOWNWARDS PRESSURE RELIEF In this case the exhaust gases are directed into cable duct by using the foundation of the substation. AFL
4 Pressure relief ap (automatic)
AFLR
5 Floor opening 6 Pressure relief direction
3
3
1 5
1 5
The Switchgear must be installed with the rear against the wall.
6
6
UPWARDS PRESSURE RELIEF In this case the switchgear will be connected to a rear side pressure relief duct. Minimum height of pressure relief duct has to be 2050mm respect to the substation oor. The room has to be equipped at least with one direct opening outwards provided with an antivermin grid. AFLR
6
3
2
1
OUTWARDS PRESSURE RELIEF Also in this case the switchgear will be connected to a rear pressure relief duct. Minimum height of pressure relief duct has to be 2050mm respect to the substation oor. The room has to be equipped at least with one direct opening outwards provided with an antivermin grid or it can be provided with automatic pressure relief ap. AFLR 4 2 3 6
1
TPR6 24kV
www.sel-electric.com
49
TPR6 24K V
EXTENSIBILITY VERSIONS MODULE EXTENSIBILITY TPR6 switchboards are easily extensible on-site, without requiring the handling of gas or any special work. One or several modules may be simply added to the existing switchboard by using special connectors. VAIABLE OPTIONS A
0
Non Extensible
+
Left or right Extensible
I
Lateral incoming/outgoing cables (*)
B
Lateral incoming/outgoing cables (**)
K
Upper incoming/outgoing for busbars or cables
(*) All the modules supplied with option “I” on the left, right or on both sides will be equipped with 350mm wide metal enclosure which has the same height and depth than the module. (**) “B” version is identical to the “I” version but it is without metal enclosure. All t he singular modules and standard congurations can be extended or they can have an outgoing cable or connection to measuring module on the left, on the right or on both sides. The confguration with “0” symbols means non extensible TPR6. For example the code of LLF with the right extension is LLF+. If LLF has the right outgoing cable and the left extension the code is +LLFI Cables Incoming Unit
+LLFI Single Tank Unit
img.1
0
50
NON EXTENSIBLE .
www.sel-electric.com
I
EXTENSIBLE
Left Extensibility Type
VERSION TYPE “I” FOR LATERAL INCOMING /OUTGOING CABLES.
TPR6 24kV
TPR6 24K V
EXTENSIBILITY VERSIONS
+
EXTENSIBLE
VERSION TYPE “+”
Extensible on right side.
Extensible on right and left side.
Extensible on left side.
Extensible version type “+” with only the prearrangement for future extension.
EXTENSIBLE VERSION TYPE “K” FOR BUSBARS OR UPPER INCOMING /OUTGOING CABLES.
K
upper outgoing type K.
Upper Busbar.
TPR6 24kV
www.sel-electric.com
51
TPR6 24K V
M AIN COMPONENT - SWITCH DISCONNECTOR SF6 GAS
Molecule of SF6
The insulation level inside the TPR6 modules has been obtained by means of sulphur hexauoride (SF6). This gas has a double function; it increases dielectric rigidity in comparison with air and aids electric arc extinction. The modules with the equipment insulated in SF6, have the following advantages: • General and electrical long life. • Maintenance-free. • Secure and stable operation. • Reduced sizes.
SWITCH DISCONNECTOR (S) This switchgear is made of a rotating part (movable-contact)which opens and closes the electric circuit.
POSITIONS : A) Closed B) Opened C) Earthed
THE SWITCH DISCONNECTOR
A) CLOSED
HAS THREE POSITIONS :
B)
OPENED
C) EARTHED
VACUUM CIRCUIT BREAKER TPR6 range includes 200A and 630A circuit breakers to protect transformers and line feeders. They can be provided with self-powered protection relays with ring core CTs on cables or protection relays with power supply. Circuit breakers guarantee making and breaking capacity under fault conditions such as short-circuits (phase-to-phase and phase-to earth), over currents and earth faults. In this way they provide operating safety, continuity of service and reduced maintenance costs.
52
www.sel-electric.com
TPR6 24kV
TPR6 24K V
M AIN COMPONENT - SWITCH DISCONNECTOR OPERATING MECHANISM TPR6 SWITCH DISCONNECTOR
OPERATING MECHANISMS :
Switch disconnector Operating Mechanism:
LT operator independent operating mechanism which is capable of making, carrying and breaking currents under normal condition service
3D operator independent, energy stored operating mechanism which is capable of making, carrying and breaking currents under normal condition service.
Operating mechanism type LT
A CCESSORIES
Operating mechanism type 3D
LT
3D
Padlock holder for switch
●
Padlock holder for earth switch
●
●
Switch keylock (key removable in open position)
●
●
Earth switch keylock (key removable in open position)
●
●
Earth switch keylock (key removable in closed position)
●
●
Switch auxiliary contacts
●
●
Earth switch auxiliary contacts
●
●
Switch keylock (key removable in closed position)
Shunt opening release Shunt closing release
TPR6 24kV
●
Motor mechanism
●
●
Door locking when earth switch is open
●
●
www.sel-electric.com
53
TPR6 24K V
M AIN COMPONENTS - CIRCUIT BREAKER - OPERATING MECHANISM The circuit breaker module operating mechanism CB6 installed in the modules C and T is composed of three different functional parts: Circuit Breaker Operating Mechanism (TCB) Operator independent energy stored operating mechanism with free release makes possible to carry out a complete cycle O-C-O without spring charging; besides it is suitable for the rapid (0-0,3s-CO–3min-CO) reclosing cycle. The circuit-breaker can be remote controlled by means of some electrical accessories (spring charging motor, shunt opening release, etc.). Operator dependent switch disconnector manual operating mechanism which operates in the absence of load. Operator independent earth switch operating mechanism which operates under load.
A CCESSORIES
1
S TA ND AR D
Shunt opening release
OP TIO NA L
●
Shunt closing release
●
Undervoltage release
●
Auxiliary contacts
●
Spring charging motor
●
*
TCB Circuit breaker keylock (key removable in open position)
●
Line Switch-Disconnector keylock (key removable in Close position)
●
*
(*) The TCB key is rigged with the Line Switch-Disconnector Key to prevent wrong operation.
2
3 R ATED V OLTAGE Up to 24kV
OPERATING MECHANISM SWITCH E ARTH DISCONNECTOR SWITCH
MODULE T YPE
CIRCUIT BREAKER
L*
LT
-
F
3D
-
C-T U3 *
CB6 LT
-
* - 3D operating mechanism with shunt opening release can be mounted on this module if requested.
54
www.sel-electric.com
TPR6 24kV
TPR6 24K V
TECHNICAL D ATA M AIN CHARACTERISTICS U.M.
Mechanical and Electrical Characteristics
kV
7,2
12
17,5
24
Altitude
IEC 62271-1
m
<1000(2)
Ambient air temperature
IEC 62271-1
°C
-25 ÷55(2)
Relative humidity
%
95
Insulation Rated Voltage
kV
7,2
12
17,5
24
Rated Voltage
kV
7,2
12
17,5
24
Lightning impulse withstand voltage between phases and towards the ground
kV
60
75 - (95*)
95
125
Lightning impulse withstand voltage across the isolating distance
kV
70
85 - (110*)
110
145
Power frequency withstand voltage between the phases
kV
20
28 - (42*)
38
50
Power frequency withstand voltage across the isolating distance
kV
23
32 - (48*)
45
60
Rated Frequency
Hz
50 - 60
Rated current
A
630
Rated short time withstand current (L unit) Ik
kA
up to 25
up to 21
Rated short time withstand current (F unit) Ik
kA
up to 25
up to 21
Rated short time withstand current (C - T unit) Ik
kA
up to 25
up to 21
Rated peak withstand current IP (making capacity )
kA
Rated duration of short circuit tk
s
Degree of protection on front face
IP
3X
Degree of protection on electrical MV circuits
IP
67
2,5 x I K 3(1)
3
Mechanical operation
Switch disconnector IEC 62271-103
1.000 operations / Class M1
Electrical operation
Switch disconnector IEC 62271-103
100 breaks at In p.f.=0,7 / Class E3
Mechanical operation
Earthing switch IEC 62271-102
1.000 operations / Class M0
Electrical operation
Earthing switch IEC 62271-102
making capacity 5 / Class E2
Mechanical operation
Circuit breaker IEC 62271-100 C module
M1/2000 - M2/10,000 operations
Electrical operation
Circuit breaker IEC 62271-100 C module
E1 / E2
Mechanical operation
Circuit breaker IEC 62271-100 T module
M1 / 2000 operations
Electrical operation
Circuit breaker IEC 62271-100 T module
E1
Rated operating sequence Internal Arc withstand current AFL (AFLR on request)
Circuit breaker IEC 62271-100
O - 0,3s - CO - 3min - CO 20kA 1s
IEC 62271-200
kA x s
Making & breaking on fuse-switch
IEC 62271-105 F module
kA rms
Breaking at rated transfer current Itransfer
IEC 62271-105 F module
A
Mainly active load breaking current
Switch disconnector IEC 62271-103
A
630
Close loop breaking current
Switch disconnector IEC 62271-103
A
630
No load transformer breaking current
Switch disconnector IEC 62271-103
A
16
Cable charging breaking current
Switch disconnector IEC 62271-103
A
32
Line charging breaking current
Switch disconnector IEC 62271-103
A
32
Earth fault breaking current
Switch disconnector IEC 62271-103
A
57
ms
70
Break Time vacuum Circuit Breaker TCB 1. 2. *
25 2100
20
1800
1600
1400
For I k = 25 kA Maximum short circuit duration time 1s. For different values contact SEL. Test Value for Special Market
TPR6 24kV
www.sel-electric.com
55
TPR6 24K V
TPR6 24K V UNITS FUNCTIONS L unit
F unit Unit Function
Unit Function
Network Switch Disconnector
Transformer feeder with fuse-switch
Device
Device
630A Switch Disconnector with Earthing Switch
200A Combined Fuse-Switch Disconnector with Earthing Switch
C unit
T unit Unit Function
Unit Function
Line feeder 630A circuit breaker
Transformer feeder with 200A circuit breaker
Device
Device
630A Circuit Breaker + Disconnector with Earthing Switch
200A Circuit Breaker + Disconnector with Earthing Switch
U3 unit Unit Function Busbar coupling 630A switch + earthing Device 630A Switch Disconnector with Earthing Switch
56
www.sel-electric.com
TPR6 24kV
TPR6 24K V
TPR6 24K V CONFIGURATIONS 1 FUNCTION UNIT
W
H + MARSHALLING BOX
D + IAC P ROOF BUSBARS BOX
L
350
1200
717
F
350
1200
717
C
350
1500
717
T
350
1200
717
U3
450
1200
717
2 FUNCTIONS UNITS
W
H + MARSHALLING BOX
D + IAC P ROOF BUSBARS BOX
LL
700
1200
717
LT
700
1200
717
LF
700
1200
717
LC
700
1500
717
W
H + MARSHALLING BOX
D + IAC P ROOF BUSBARS BOX
LLL
1050
1200
717
LLF
1050
1200
717
LFF
1050
1200
717
LLT
1050
1200
717
LTT
1050
1200
717
LLC
1050
1500
717
LCC
1050
1500
717
W
H + MARSHALLING BOX
D
LLLL
1400
1200
717
LLLF
1400
1200
717
LLFF
1400
1200
717
LLLT
1400
1200
717
LLTT
1400
1200
717
LLLC
1400
1500
717
LLCC
1400
1500
717
W
H + MARSHALLING BOX
D
LLLLL
1750
1200
717
LLLLF
1750
1200
717
LLLFF
1750
1200
717
W
H + MARSHALLING BOX
D
2100
1200
717
3 FUNCTIONS UNITS
4 FUNCTIONS UNITS
5 FUNCTIONS UNITS
6 FUNCTIONS UNITS LLLLLL
CUSTOMIZED CONFIGURATIONS ON REQUEST Conguration are possible that combine up to 6 standard functions according to costumers requirements with the approval of our technical ofce.
TPR6 24kV
www.sel-electric.com
57
TPR6 24K V
DIMENSIONS L
F
T
58
www.sel-electric.com
C
C
I
U3
U3
TPR6 24kV
TPR6 24K V
TPR6 DETAILED VIEW ONE LINE DIAGRAM
Or
Frontal Panel
Fuses Status Indicator Spring Status Indicator
Manometer
Densimeter
Voltage Indicator
Movable Mimic
Mechanical Door Interlock Match Maker Lateral Extensibility "+" Line/Earth Mechanical Interlock Fuses Extraction from the front Operating Handle Upper Busbar Connetion "K"
SF6 Sealed Tank
Cables Compartment
Cables Compartment doors Operating Mechanism
Safety Valve
Bushing Interface Type "C"
TPR6 24kV
Bushing Interface Type "A"
www.sel-electric.com
59
TPR6 24K V
K EY LOCKING AND P ADLOCK S YMBOL SIMBOLO
DESCRIPTION DESCRIZIONE
OP. MECHANISM COMANDI CB6
TCB
LT
3D
Keylock with switch open: When the switch is
C
open, turn the key anticlockwise and remove it in
●
●
●
●
●
●
●
●
●
●
●
●
●
●
●
order to prevent the closing of circuit
Keylock with earthing switch open: When the
D
earthing switch is open, turn the key anticlockwise and remove it in order to prevent earthing.
Keylock with earthing switch closed: When the
E
earthing switch is closed, turn the key clockwise and remove it in order to prevent the opening of the earthing switch.
Keylock with switch closed: When the switch is
F
closed, turn the key anticlockwise and remove it
●
in order to prevent the closing of circuit
Keylock with circuit breaker open: when the
I
circuit breaker is open, turn the key clockwise ●
and remove it in order to prevent the closing of circuit breaker.
G H
Padlock holder on disconnector/ switchdisconnector Padlock holder on earthing disconnector/ earthing switch
Keylocks and padlock holders can be installed in both switch disconnectors and earthing switches as optionals.
60
www.sel-electric.com
TPR6 24kV
TPR6 24K V
K EY LOCKING AND P ADLOCK
CB6
LT
3D
CIRCUIT BREAKER MODULE
OPERATING MECHANISM
OPERATING MECHANISM
OPERATING MECHANISM
TPR6 24kV
www.sel-electric.com
61
TPR6 24K V
COUPLING SPACE - INSTALLATION DISTANCE - C ABLES TERMINATION COUPLING SPACE In case the switchboard is prearranged for further expansions on the left, on the right or both sides provide at least 150mm space between the switchboards and a suitable lateral space for coupling operations.
After Coupling
Before Coupling
DISTANCE FROM THE WALL AFL
During the installation respect the minimum distance from the wall. Leave at least 1.20 m free space in front of the switchboard for switchboard operations.
e a c p s n g i t a e r p O
CABLES TERMINATION POINT
L unit
62
www.sel-electric.com
F / T units
C unit
TPR6 24kV
TPR6 24K V
UNITS OPERATING SEQUENCES Qr Code usage istructions: Download the right application from you device store to read QR-Code marks. Start Application. Point your device camera to the QR Code. Multimedia information will be downloaded direcly to your device.
TPR6 - 3D Operating Mechanism
TPR6 - LT Operating Mechanism
The video shows the switch operations sequences of the 3D Operating Mechanism mounted on a F unit.
The video shows the switch operations sequences of the LT Operating Mechanism mounted on a L - U3 units.
TPR6 - TCB Operating Mechanism The video shows the switch operations sequences of the TCB Operating Mechanism mounted on a C - T units.
TPR6 24kV
www.sel-electric.com
63