RELAY SETTIN ING G FOR TRANSFORMER PTN. :
HANG HA NG DO DONG NG A1
REV-0 Type of Rela elay: y: MICO MIC OM P63 P632; 2; Sc hneide hneiderr
Power ower Transfor nsforme me dat data Sl.N Parame rametters 1. Powe owerr 2. HV Vo Volt lta age 3. LV Vo Volt lta age 4. C TR HV 5. C TR LV 6. NCT NC T 7. Bus PTR 8. Transforme ormerr pe perc rce ent nta age imp 9. Transf ransfo orme merr ve vec c tor group
1) PARAMETERS > CONFIG. PARAMETERS 1.1) CONFIG. PARAMETERS: COMM1 Function group C OMM 1 Line idle state prot. variant Baud rate Parity bit Dea d time monitoring Mon. time po lling Octet comm. add ress Test monitor on
With Light on / high ALSTOM D 19.2 kBaud Even Yes 25 s 1 No
Filter Fct. assignm. U 2001 Fct. assignm. U 2002 Fct. assignm. U 2003 Fct. assignm. U 2004 Oper. mode U 2001 Oper. mode U 2002 Oper. mode U 2003 Oper. mode U 2004
0 LOGIC Input 1 EXT LOGIC Input 2 EXT LOGIC Input 3 EXT LOGIC Input 4 EXT Active "high" Active "high" Active "high" Active "high"
Fct. assignm. K 2001 Fct. assignm. K 2002 Fct. assignm. K 2003 Fct. assignm. K 2004 Fct. assignm. K 2005 Fct. assignm. K 2006 Fct. assignm. K 2007 Fct. assignm. K 2008 Oper. mode K 2001 Oper. mode K 2002 Oper. mode K 2003
LOG IC Output 1 Without func tion V/ f tV/ f> elapsed DIFF Trip signa l REF_1 Trip signal DTOC 1 Trip signal tIN> DTOC 1 Trip signal tI> MAIN Prot. ext. enabled ES updating ES updating ES updating
Fct.assig. H 1 green Fct.assig. H 2 yell. Fct.assig. H 3 yell. Fct.assig. H 4 red Fct.assig. H 4 green Fct.assig. H 5 red Fct.assig. H 5 green Fct.assig. H 6 red Fct.assig. H 6 green Fct.assig. H 7 red Fct.assig. H 7 green Fct.assig. H 8 red Fct.assig. H 8 green Fct.assig. H 9 red Fct.assig. H 9 green Fct.assig. H10 red Fct.assig. H10 green
MAIN Hea lthy MAIN Bloc ked/faulty SFMO N Warning (LED) MAIN Gen. trip comma nd 1 Without func tion DIFF Trip signal Without func tion DTOC 1 Trip signal tIN> Without func tion DTOC 1 Trip signal tI> Without func tion REF_1 Trip signal Without func tion V/ f tV/ f> elap sed Without func tion Without func tion Without func tion
1. 5) C ONFIG. PARAMETERS: DIFF: Function group DIFF
With
1. 6) CONFIG. PARAMETERS: REF_1: Function group REF_1
With
1. 7) CONFIG. PARAMETERS: REF_2: Function group REF_2
Without
1. 8) CONFIG. PARAMETERS: DTOC1: Function group DTOC 1
With
1. 9) CONFIG. PARAMETERS: DTOC2: Function group DTOC 2
Without
1. 10) CONFIG. PARAMETERS: IDMT1: Function group IDMT1
Without 3 e g a P
Prepared by: M.S.Negi;
Checked by: Mr. S. Midha
Flovel Energy Pvt. Ltd. INDIA
RELAY SETTING FOR TRANSFORMER PTN. :
HANG DONG A1
1. 11) CONFIG. PARAMETERS: IDMT2: Function group IDMT2
Without
1. 12) C ONFIG. PARAMETERS: V<>: Function group V <>
Without
1. 13) CONFIG. PARAMETERS: f <>: Function group f <>
Without
1. 14) CONFIG. PARAMETERS: V/ f: Function group V/ f
With
1. 15) CONFIG. PARAMETERS: LOGIC: Function group LOGIC
With
2) PARAMETERS >> FUNCTION PARAMETERS>> GLOBAL >> MAIN 003.030 003.012 010.030 010.049 019.020 019.021 019.027 019.028 010.002 010.024 010.025 010.142 010.143 010.009 010.140 010.150 010.141 010.151
Device on-line Test mode USER Nominal frequ. fnom Phase seq uenc e Inom C .T.prim.,end a Inom C .T.prim.,end b Inom C .T.Yprim,end a Inom C .T.Yprim,end b Vnom V.T. prim. Inom device, end a Inom device, end b IY,nom devic e, end a IY,nom device, end b Vnom V.T. sec. C onn.meas.circ. IP,a C onn.meas.circ. IP,b C onn.meas.circ. IY,a C onn.meas.circ. IY,b
Yes (= on) Yes 50 Hz A - B- C 1100 A 60 A 1100 A 60 A 6.3 kV 1.0 A 1.0 A 1.0 A 1.0 A 110 V Stand ard Stand ard Standard Standard 4 e g a P
3.4) DTOC_1 PROTECTION (For HV Side): C T ratio: 60/1 Transformer rated current: =52.71A. Secondary current =52.71/60 =0.878A C urrent setting = 1.2 x 0.878 =1.05 A Time delay =3 sec. Highset to be set at 10 times IDMT set current I,e 0.878 x 10 =8.78A Timer Setting: 0.02 sec . 076.050 Enable PS1 Yes 076.067 Block tim.st. IN PS1 Without 076.066 Gen.starting mode PS1 With start. IN/Ineg 076.065 tG S PS1 0.00 s 076.063 Rush restr.enabl PS1 No 076.051 I> PS1 1.05 Inom 076.052 I>> PS1 1.10 Inom 076.053 I>>> PS1 8.78 Inom 076.151 I>dynamic PS1 1.00 Inom 076.152 I>> dyna mic PS1 1.00 Inom 076.153 I>>> dyna mic PS1 1.00 Inom 076.057 tI> PS1 3.00 s 076.058 tI>> PS1 0.50 s 076.059 tI>>> PS1 0.02 s 076.197 Ineg> PS1 0.25 Inom 3.5) V/ f PROTECTION: 081.210 081.211 081.212 081.213 081.214 081.217 081.218 081.219 081.220 081.221 081.222 081.223 081.224 081.225 081.226 081.227 081.228 081.230 081.229
Enable V/ f> (alarm) V/f(t)> V/f>> tV/f> t at V/ f=1.05 t at V/ f=1.10 t at V/ f=1.15 t at V/ f=1.20 t at V/ f=1.25 t at V/ f=1.30 t at V/ f=1.35 t at V/ f=1.40 t at V/ f=1.45 t at V/ f=1.50 t at V/ f=1.55 t at V/ f=1.60 Reset time tV/f>>
Yes 1.10 Vnom/ fnom 1.25 Vnom/fnom 1.45 1s (Alarm) Max Max Max 55 s 40 s 20 s 8s 5s 4s 3.5 s 3s 2s 2s Blocked
6 e g a P
Prepared by: M.S.Negi;
Checked by: Mr. S. Midha
Flovel Energy Pvt. Ltd. INDIA
RELAY SETTING FOR TRANSFORMER PTN. :
HANG DONG A1
3.6) BREAKER FAILURE PROTECTION: Selec t. meas. input I< t1 3p t2 Delay/ starting trig. Delay/fault beh. C B
4) Settings for E/F:
End HV SIDE 0.10 Inom 0.15 s 0.25 s 0.00 s 0.12 s
51 (MIC OM P111)
C T ratio: 60/1 Transformer rated current: = 57.70 A. Secondary current = 57.70/60 = 0.961A E/F to be set 10% of the full load current - 0.1 x 0.961 =0.096A Timer Setting: 2 sec. 5) Settings for 6.3kV Bus Earth Fault Relay:
(64BG)
MAKE
TYPE
SETTING RANG E
SETTING
PTR
AREVA
VDG14
5.4 ~ 20 A
5.4 Vo lts
6300/ 110V
6) Settings for 115kV Bus Diff. protec tion Relay:
(87B)
MAKE
TYPE
SETTING RANG E
SETTING
C TR
AREVA
C AG34
1.0 ~ 4.0 A
1.0 A
60/1A
7) Temperature Protection: Winding temperature : Alarm Winding temperature : Trip Oil temperature : Alarm Oil temperature : Trip