Outfeed and Infeed Effect Power Po wer System Power System Protection
We will discuss here the Outfeed and Infeed Effect and its implication on Distance protection. Consider the operation of distance relay R1 for a fault F close to remote bus on line BC as shown in the figure below below..
Electrical Machines DC Machine Measurement and Instrumentation AC Circuit Digital Electronics Electrical Drives Power Electronics EM Theory
Therefore fault current will be feed by Source G1, G2 and G3. Therefore, IBF= IAB + IED
Meaning of 1 Unit Electricity – Power Consumption Calculation
So Voltage seen by distance Relay R1,
Difference between Instantaneous and Definite Time Overcurrent Relay
V = (Line Impedance of AB)×I AB)×I AB+ (Line Impedance till Fault location on BC) ×IBF
Torque Equation of DC Motor AC Generator – Definition, Construction and
= Z1×I AB + XZ2IBF
Working
पीडीएफ़ डाउनलोड डाउनलोड कर कर Ad
यहाँ डाउनलोड डाउनलोड कर कर
ProPDFConverter
OPEN
Torque Equation for Synchronous Machine AC Motor – Definition and Types Transformer Protection Scheme Synchronous Motor Applications Permanent Magnet Synchronous Motor (PMSM) – Construction and Working Principle Switched Reluctance Motor – Construction and Working
= Z1I AB+XZ2(I AB+IED) = Z1I AB+XZ2I AB+XZ2IED = (Z1+ XZ2) I AB+ XZ2IED So Impedance measured by Distance Relay R1, V/I AB = (Z1+XZ2) + XZ2IED/I AB
Thus it is clear from above equation that Relay R1 do not measure the Impedance up to fault location F i.e. (Z1+XZ2) rather it overestimates the Impedance i.e. higher than the actual Impedance. If there is an equivalent generator source at bus E, then it feeds the fault current as I AB and IED are approximately in phase. This is known as infeed effect. From the above
SUBSCRIBE NOW
equation it is clear that infeed causes an equivalent increase in apparent impedance seen by the relay R1.
we respect your privacy and take protecting it seriously
From the Relay’s perspective, the fault is pushed beyond its actual location. Thus, a fault in Zone-2 may be pushed into Zone-3, thereby compromising selectivity of Zone-2. But, infeed effect does not compromise selectivity of Zone-1 as the fault current will only be I AB in that case. If there is an equivalent load at bus E, then AB I and IEB will be in phase opposition. IBF= IAB – IED So Voltage seen by distance Relay R1, V = (Line Impedance of AB)×I AB+ (Line Impedance till Fault location on BC) ×IBF = Z1×I AB + XZ2IBF = Z1I AB+XZ2(I AB-IED) = Z1I AB+XZ2I AB – XZ2IED = (Z1+ XZ2) I AB – XZ2IED So Impedance measured by Distance Relay R1, V/I AB = (Z1+XZ2) – XZ2IED/I AB Thus it is clear from above equation that Relay R1 do not measure the Impedance up to fault location F2 i.e. (Z1+XZ2) rather it underestimates the Impedance i.e. lower than the actual Impedance. This is called Outfeed Effect. In other words, the relay R1 perceives fault to be at a point closer than its actual location. If this perceived point falls well in the section AB, the relay R1 will operate instantaneously for a fault on the back up line, thereby compromising selectivity. Hence, instantaneous primary protection Zone-1of distance relay is always set below 100% line impedance. Typically, Zone-1 is set to cover 0.8 to 0.9 times the primary line length. In other words, we expect errors in measurements of fault impedance to be within 10-20% accuracy. The remaining portion of the primary line is provided with a time delayed protection known as Zone-2.
April 17, 2016 Outfeed Effect
admin
Power System Protection
No Comment
distance protection, Infeed Effect,
Your email address will not be published. Required fields are marked *
Comment
Name *
Email *
Website Notify me when new comments are a dded.
Post Comment
This site uses Akismet to reduce spam. Learn how your comment data is pr ocessed.