DR-SM150
Commissioning the Active Line Module
Comm_Infeed
page 0 01 1
SITRAIN / METAL ACADEMY © Siemens AG 2011 2011 - all rights reserved
List of Contents
I T
3.1 3.2 3.3 3.4 3.5 3.6 6 3.7 3.8 3.9 3.10 3.11 3.12 3.13 3.14 3.15 3.16 3.17 3.18 3.19 3.20 3.21 3.22 3.23 3.24
Opening the Cabi Opening Cabinet net Doors of Med Medium ium Volt Voltage age Compa Compartme rtments nts …... …....... ........ ........ ........ ........ ........ .... Grounding Make Proof Switch …........ …................. ................. ................ ................ ................. .................. ................. ................ ............ .... Insulation Test …....... …................ ........ .................. ................. ................. .................. ................. ................ ................ ................. ................. ................ ............ .... Test Modes …........ …................. ................. ................ ................ ................ ................. .................. ................. ................ ................ ................ ................. ......... Test Mode “Auxiliary Fan” …........ …............... ................ .................. ................. ................ ................ ................. ................. ................ ............ .... Test Mode “GSV, Gate Supply Voltage” …....... …................ ................. ................ ................. ................. ................ ............... ....... Test Mode “Line Breaker” (without medium voltage ! ) …...... ….............. ................. ................. ................. ........... Test Mode “Pre-charging” (without medium voltage ! ) …....... …................ ................. ................ ................ .......... Test Mode “Pre“Pre-charg charging ing and Line Brea Breaker” ker” (with (without out medi medium um volta voltage ge ! ) ….. …...... ........ ...... .. Test Mode “Pre-chargin “Pre-charging g and Line Breaker” (with medium voltage ! ) …....... …............... .......... .. Measurementt of Phase Shift Measuremen Shift …............ ….................... ................ ................. ................. ................ ................ ................ ................. ............. .... Line Side Offset Angle …........ …................. ................. ................ ................ ................ ................. ................. ................. .................. ................ ....... Basic Configuratio Configuration n of the Line Line Controller …........ …................ ................. ................. ................ ................ ................. ............ ... Actual Value Offset Compensatio Compensation n …......... ….................. .................. ................. ................. .................. ................. ................. ........... .. Actual Raw Values Values (Infeed) …........ …............... ................ ................. ................ ................ ................. ................. ................ ................ .......... .. Identification Identificatio n Routines Routines …............ …..................... ................. ................ ................ ................ ................. ................. ................ ................ .............. ...... Identification Identificatio n Routine “Identificatio “Identification n transformer phase shift” …....... …................ .................. ............... ...... Identification Identificatio n Routine “Identificatio “Identification n transformer uk” …....... …............... ................ ................ ................. .............. ..... Identification Identificatio n Routine “Identificatio “Identification n Tc Dc” …....... …............... ................. .................. ................. ................ ................ .......... .. Identification Identificatio n Routine “Reactive power steps” …....... …............... .................. .................. ................ ................ .............. ...... Identification Identificatio n Routine “DC link voltage steps” …....... …............... ................ ................ ................. ................. ................ ........ Identification Identificatio n Routine “V dc symmetry steps” …....... …............... ................. ................. ................ ................. ................ ....... Identification Identificatio n Routine “Setting, pre-control” …....... …............... ................ ................. .................. ................. ................. ........... Completing the Commissioning of the Infeed …........ …................ ................ ................ ................ ................. ................ .......
page 02
4 4 4 6 10 12 14 20 22 24 28 32 34 36 36 38 40 44 46 48 50 52 54 56
DR-SM150
Grounding Make Proof Switch / Cabinet Door Interlocking
DC-link voltage
Feedback: “Grounding make-proof switch is closed“
Release stud for electromagnet Grounding make-proof switch (DC-link grounding)
Enabling of “release doors“
Control of the “interlocking magnets mag nets”” to release the cabinet doors
Comm_Infeed
3
page 03
SITRAIN / METAL ACADEMY © Siemens AG 2011 2011 - all rights reserved
Commissioning Commissi oning the Infeed (Act (Active ive Line Module)
page 04
DR-SM150
Test Modes
Comm_Infeed
page a 05 0
SITRAIN / METAL ACADEMY © Siemens AG 2011 - all rights reserved
3.4 Test Modes The SM150 supports several “Test Modes”” for checking essential converter functions. To analyze particular properties of the system (Infeed, Motor Module) a number of “Identification modes” are available. Following of the available “Test modes” are commonly required and applied: - Auxiliary Fan - GSV (IGCT-Test) - Crowbar thyristor - Pre-charging - Pre-charging i and Line Breaker - Line Breaker (Main CB) - Cooling System - Main Fan - Redundant Main Fan Most of the Test Modes are selected by parameter p6650 of object “Infeed” (of drive device Infeed). In the fault-free state of the Infeed the preselected test mode is activated by whatever input is assigned to p6651. In standard programming, input p6651 is wired to SIMOTION DCC.
page 06
DR-SM150
Relating a BiCo-Input to a Function Block in DCC
address reference in I/O-container
any DCC-chart
Comm_Infeed
SITRAIN / METAL ACADEMY
page a 07 0
© Siemens AG 2011 - all rights reserved
Follow the steps suggested below to find out which i chart, block and input within the DCC-programming you have to use to start the “test mode” via DCC. To find the block of a chart which generates a signal fed to a BiCo-input, the I/O-variable and its assigned periphery address have to be identified first: - signal source to start the “test mode”:
A_INFMV_OM_G2 : r2095.1
- related to process data word PZD . . . . . / Bit . . . . . of object . . . . . . . . . . . . . . . . . . . . - identified by periphery address . . . . . . . . . . . . . . . . . . . . - related to I/O-variable . . . . . . . . . . . . . . . . . . . . . . . . . . . To locate chart and block to which this variable is connected, open any DCC-chart, select menu “Chart Reference Data” and a open the listing of “Cross Reference Chart Elements Address”. Search for the variable in question and double click on it; the chart page showing this variable and its wiring to a DCC-block is opened automatically. Note down which chart, which block and which input you have to use to start a “test mode” via DCC: chart / page . . . . . . . . . . . / . . . . . . . . . .
block . . . . . . . . . . . . . . . . . . . . .
page 08
input
. . . .. . .. .. .. .. .. . .. ..
DR-SM150
Test-Mode “Auxiliary Fan”
Comm_Infeed
page a 09 0
SITRAIN / METAL ACADEMY © Siemens AG 2011 - all rights reserved
3.5 Test Mode “Auxiliary Fan” Select test mode “Auxiliary Fan” and trigger the test via the assigned DCC-chart: the “Auxiliary Fan” installed in the SM150-rack is switched on and runs while the test mode is active. As an alternative to DCC the e test mode can be activated by any other input source belonging to the same drive device (Infeed) as well, i.e. by a digital input of a TMxx or via input simulation to a digital input of a TMxx. Refer to the wiring scheme of the terminal interface assigned to components =.2HC-A11 (DI/O 12) and =.2HD-A51 (DI/O 23) and assign a suitable input via the respective binector as input source: p6651_Infeed f = .... ................................... Activate test mode “auxiliary fan” by connecting the two measuring leads as substitute for a switch. Finally trigger the test mode also by simulating this digital input.
page 10
DR-SM150
Fault Messages concerning Test Mode “Gate Supply Voltage”
- DRIVE-CLiQ connections are save since the communication is monitored cyclically - any PSA-fault blocks all IGCTs via optical link - both, CU-faults and PSA-faults trip the CB
D445
CX32
IGCTs
IGCTs
PSA
PSA
fiber optic link (rip cord)
Comm_Infeed
page a 11 11
SITRAIN / METAL ACADEMY © Siemens AG 2011 - all rights reserved
3.6 Test Mode “GSV, Gate Supply Voltage” In this test the IGCTs are triggered (via optical cables) from the PSA and the feedback signals are monitored (site condition; not on the training rack). Select test mode “GSV” and trigger the test either via the assigned DCC-chart or by using the available “hardware switch” wired to component TM15/Infeed, terminal DI/O23: at the training rack the sending LEDs on the PSA light up (left LED of X11 to X14, X31 to X34, X41 to X44).
All PSAs of the converter (Infeeds and Motor Modules) are linked by a rip cord; check its function by interrupting the loop e.g. at PSA-X81.
page 12
DR-SM150
Circuit Breaker Properties / Test-Mode “Line Breaker” Circuit Breaker upstream circuit breaker
downstream circuit breaker
SM150
M
not per standard
possibly feeding other load as well
3. 1. 2. test position
Comm_Infeed
page a 13 1
SITRAIN / METAL ACADEMY © Siemens AG 2011 - all rights reserved
3.7 Test Mode “Line Breaker” (without medium voltage ! ) As this test will actuate the Line Breaker you have to make sure that NO VOLTAGE will be switched to the Infeed. Verify that the Line Breaker is withdrawn and in test-position before triggering test mode “Line Breaker”. At the training rack, switch o off the mcb to the left of contactor “TC-K41”; this condition simulates “Line Breaker in test position”. Parameters p6677 to p6680 have to be set in accordance with the Line Breaker used (commonly found Line Br eakers require a setting i as shown); parameters for the monitoring times can be set only after evaluation of switching operations (for an overview of Line Breaker configuration possibilities refer to “List Manual, page 9800”). Both, the control signals to the Line Breaker and t he feedback signals from the Line Breaker are directly wired to the CX32; verify that the wiring matches with the given reference (slide on ne xt page). The time properties of the Line Breaker will be identified by evaluating the status information of the terminals for the control and the feedback signals.
page 14
DR-SM150
Measurement of the Circuit Breaker Delay Times
2 G _ M O _ 2 3 X C _ U C
A_INFMV_OM_G2
A_INFMV_OM_G2 2 G _ M O _ 2 3 X C _ U C
L Feedback “Line Breaker Closed”
CB close
CB open
Control command “Open Line Breaker”
Control command “Close Line Breaker”
Comm_Infeed
Feedback e “Line n Breaker Open”
page a 15 1
SITRAIN / METAL ACADEMY © Siemens AG 2011 - all rights reserved
Find out which parameters and which bits you have a to trace to record the following: - “Close command” to the Line Breaker . . . . . . . . . . . . . . . . . . - “Open command” to the Line Breaker . . . . . . . . . . . . . . . . . . - Feed back signal “Line Breaker Closed”
. . . .. . . . .. . . . .. . . .
- Feed back signal “Line Breaker Open” . . . . . . . . . . . . . . . . . . Set up the tracer to record a.m. signals with following properties: - Recording time: 500 ms - Trigger on: “Close command” (1. step) respectively “Open command” (2. step) - Pretrigger: 100 ms Once more verify that the Line Breaker is in test position, select test mode “Line Breaker” and trigger the test by using the available “hardware switch” wired to component TM15/Infeed, terminal DI/O23: the Line Breaker switches on (at the training rack: contactor “TC-K1”) and the tracer r ecords the assigned signals. (NOTE: if the Line Breaker doesn’t close, check the information on the f ollowing page.) From the recording, read the delay time (“close” command to feedback “closed”): . . . . . . . ms Define the tracer to record a.m. signals when the “Open command” is given and initiate the “Open command”: the Line breaker switches off (at the training rack: contactor “TC-K1”) and the tracer records the assigned signals. From the recording, read the delay time (“open” command to feedback “open”): . . . . . . . ms (for the SM150 the “Open” delay time of the Line Breaker must be less than 80 ms). The time the circuit breaker takes to o pen is checked against the setting of the “maximum opening time (p6676)”. Set the “maximum opening time” to a value less than required (as just found out by measurement) and verify by a test that related error messages are generated. Finally set the “maximum opening time” back to a sufficiently large value, i.e. 100ms.
page 16
Blocking “Selected Bits of Control Words”
DR-SM150
i.e.: blocking “BM_PLC_EN” ( bit 10) incoming control request: 16#240A binary: outgoing control request: dto. In hex: required AND-word: (16#FBFF)
Comm_Infeed
2 0 0 1 0 0 0 1 0 2 1 1 1 1
page a 17 1
4
0
0 1 0 0 0 0 0 0 0 1 0 1 1
0 0 0 0 0 0 0 0 0 1 1 1 1
R
A 1 0 1 0 1 0 1 0 A 1 1 1 1
SITRAIN / METAL ACADEMY © Siemens AG 2011 - all rights reserved
If the Line Breaker doesn’t close, an OFF2 command might be active in the control word for the Infeed. Check this status in DCC-chart AINF1, sheet F1,, block SAI100. This DCC-program is also used to individually allow an operation of one of several Infeeds in parallel configuration by assigning an OFF2 command n to the others. For training purposes, block Infeed 1 from responding to the “Line Breaker Close command”. After this test, enable Infeed 1 again.
I T
page 18
DR-SM150
Test-Mode “Pre-Charging”
Setpoint in test-mode: “pre-charging” “pre-charging and line breaker”
L
total DC-link voltage
positive DC-link voltage
negative DC-link voltage
Comm_Infeed
page a 19 1
SITRAIN / METAL ACADEMY © Siemens AG 2011 - all rights reserved
3.8 Test Mode “Pre-charging” (without medium i voltage ! ) During this test DC-voltage up to the specified level (p6620) is generated on t he DC-link and on all components connected to it. Make sure that this test can be carried out without endangering personnel or equipment!
Define the tracer to record following DC-voltages: - r70[0] total actuall DC-link voltage - r70[1] positive actual u DC-link voltage - r70[2] negative actual DC-link voltage Since thermal losses are inevitable, the cooling system has to be switched on first. Switch on the cooling system (via Auxiliaries) e using the OP177 in “Local Mode” with key “K3/AUX ON”. Start with a small setpoint value for the DC-voltage, i.e. p6620 = 5 %, select test mode “Pre-charging” and trigger the test by using the available “hardware switch” wired to component TM15/Infeed, terminal DI/O23 : the DC-link voltage is controlled to an average value as set in p6620 by consecutive close-/ open-commands to the pre-charging contactor (at the training rack: contactor “TC-K41”). Increase the setpoint for the DC-link voltage in 5% steps to 15%; at this stage, trace the a.m. values and verify that the positive and negative DC-link voltages are symmetrical. PLEASE don’t set more than 15% at t he training rack, as this would cause a continuous ON/OFF of the Yaskawas which will overload the Yaskawa-internal pre-charging resistors.
page 20
DR-SM150
Test-Mode “Pre-Charging and Line Breaker (without MV)”
Trip with message “DC-link undervoltage” Feedback “Line Breaker Closed”
Control command “Close Line Breaker”
Comm_Infeed
page a 21 21
I R
L
SITRAIN / METAL ACADEMY © Siemens AG 2011 - all rights reserved
3.9 Test Mode “Pre-charging and Line Breaker” (without medium voltage ! ) During this test the Line Breaker will be closed. Please make sure again, that the Line Breaker is withdrawn and in test-position before triggering this test. Depending on the “pre-charging” setpoint, the DC-link will be charged up (possibly even up to 100%); so again make sure that this test can be carried out without endangering personnel or equipment!
Set up the tracer to record the “total DC-link voltage”, the “Close command” to the Line Breaker and the feed back signal “Line Breaker Closed” (refer to 3.7) with following properties: s - Recording r time: 5000 ms - Trigger on: “Close command” - Pretrigger: 3500 ms For the first test, set the “DC link pre-charging setpoint, p6621” to 95%. Select test mode “Pre-charging and Line Breaker” and trigger the test by using the available “hardware switch” wired to component TM15/Infeed, terminal DI/O23 : the DC-link voltage charges up to the value set in p6621, the Line Breaker closes and trips after expiry of the ( internally set) monitoring time with fault message “5210, pre-charging monitoring time expired”. For the second test, set the “DC link pre-charging setpoint, p6621” to 80% and trigger the test: the DC link voltage charges up to the value set in p6621, the line breaker closes and trips after a short delay with the fault message “30003, DC-link undervoltage”.
page 22
DR-SM150
Test-Mode “Pre-Charging and Line Breaker (with MV)”
Comm_Infeed
page a 23 2
SITRAIN / METAL ACADEMY © Siemens AG 2011 - all rights reserved
3.10 Test Mode “Pre-charging and Line e Breaker” (with medium voltage ! ) As before, during this test the Line Breaker r will again be closed. This time, however, the Line Breaker will be inserted. The DC-link will be charged up to 100% with the full line power available; so once more make sure that this test can be carried out without endangering personnel or equipment!
At this stage some very essential settings have not yet been verified; therefore it is not yet permissible to change over to “active mode” of the Infeed. Only its operation as Basic Line Module (via the free-wheeling diodes) can be accepted. You have to make sure that the “pulse enable” input of the Infeed (p0852) is reliably on “L”: - possible approach (not recommended): set p0852 = 0 - preferred approach: block the “pulse enable” signal from being handed on (if “Simotion” should generate it by wrong control on behalf of the o perator’s side). Find out which value has to be set on “chart AINF1, sheet F1, block SAI102 at Input 2” or on “block SAI100 at Input 1” to satisfy above requirement: ........ ......... ........ ..
page 24
DR-SM150
Infeed Operation as “Basic Line Module”
Feedback “Line Breaker Closed”
Control command “Close Line Breaker”
Comm_Infeed
page a 25 2
Changeover from “precharge” to operation as Basic Line Module
I
SITRAIN / METAL ACADEMY © Siemens AG 2011 - all rights reserved
Keep the tracer settings (as in 3.8) to record r the “total DC-link voltage”, the “Close command” to the Line Breaker and the Feed back signal “Line Breaker Closed” (referr to 3.6) with the same properties as before. Now rack in the Line Breaker (at the training t rack, switch on the mcb to the left of contactor “TC-K41”; this condition simulates “Line Breaker in operating position”), select test mode “Pre-charging and Line Breaker” and trigger the test by using the available “hardware switch” wired to component TM15/Infeed, terminal DI/O23: the DC-link voltage charges up to the value set in p6621, the Line Breaker closes and remains closed. If the line breakerr should o trip r after a short delay, analyze the fault message and adjust the responsible setting by a change of 5%: ........ ......... ........ .... Repeatt the above test. Now the Line Breaker remains closed, the DC-link voltage reads: “sqr 2 * u.line.ph-ph”.
page 26
Measurement of “Phase shift”
DR-SM150 R E V R E S B O
L2
L1
L1L2
L1L3
L2L3
L3
L2L1
L3L1
L3L2
R E V R E S B O
L1
reference measurement:
L2L1
L2L1 leads L3L2 by 1200 L3N L2L1
test measurement 1:
L1L3
L
L3L2 leads L1L2 by 600
L3L2
test measurement 2: L2
L3L2
L1L3 lags L3N by 1500
L3 L1L2
Comm_Infeed
page a 27 2
L1L3
SITRAIN / METAL ACADEMY © Siemens AG 2011 - all rights reserved
3.11 Measurement of Phase Shift The “power voltage” at the ALM inputt will typically be phase shifted versus the voltage measured by the VSM. Value and polarity of the phase displacement (leading, lagging) have to be identified without doubt. On the basis of a known voltage system (phases L1 to L3 on the VSM) you should first make a “reference measurement” crosschecking the indication on your scope versus “theory” followed by the second step of identifying the phase shift between “power voltage at ALM input” and “reference voltage at VSM”. To gain experience use the “transformer box” and carry out the measurements as suggested. Follow the procedure listed below to make the FIRST MEASUREMENT, then the SECOND MEASUREMENT and finally do the lab work. -
select the same V/div for both channels, invert channel B, align the two tracks to the zero line with input = GND use an appropriate voltage divider to measure voltages outside the range of the scope connect the voltages you want to measure to channels A (L1) and B (L3) of the scope (via voltage divider if large) set both channels to DC-measurement and ADD the two channels; you then measure L1 + (-L3) = UL1L3 follow the same steps to measure the second phase-to-phase voltage (channels A2, B2) if you have to adapt the V/div for any of the measurements, always select the same setting for channels A and B and verify the zero line alignment
FIRST MEASUREMENT make the “reference measurement” to find out how your scope displays voltage U L2L1 versus UL3L2
SECOND MEASUREMENT make one “test measurement” to verify your scope reading versus the “theoretical expectation”; i.e. U L1L3 versus UL3N
UL2L1
UL1L3
UL3L2
UL3N
reference measurement: u.L2L1 leads u.L3L2 by 120 0 page 28
DR-SM150
Measurement of “Phase Shift” phase L1
10MOhm
phase L2
10MOhm channel 1 direct
100kOhm
channel 2 inverted 100kOhm
operating mode: channel 1 + channel 2
voltage divider used at the training center
N
L2 L1
L3
L1
L2
L2
L3
L1L2
L3 400V
I R E T A L3L2
“transformer box” for lab work N
24V
Comm_Infeed
L L2L1
L1
L1L3
SITRAIN / METAL ACADEMY
page a 29 2
© Siemens AG 2011 - all rights reserved
Find out the phase shifts of the voltages suggested t in the table below both by “theoretical expectation” and by actual measurement.
N I A R
leads
lags
by
UL3L2
UL1L2
UL1L3
uL2N
UL1L3
uL1N
UL1L3
uL3N
degrees
UL3L2
UL1L3
UL1L3
UL1L3
UL1L2
uL2N
uL1N
uL3N
If you should only have a 2-channel scope available, the voltage U L2L1 has to be measured using channels “A – B” with e.g. “line trigger”, followed by the measurement of voltage U L3L2 using the same channels “A – B” with identical trigger criteria. These two measurements then have to be “mentally” superposed to read the phase displacement. UL2L1
UL3L2
page 30
Measurement of the “Line Side Offset Angle”
DR-SM150
Yy0
Yy0d5
100 V
power voltage 3.3 kV
VSM
VSM
UL1L3 CH 1 – 2
M CH 3 – 4
UL1L3 1500
reference voltage
power voltage lags reference c voltage by 1500
CH 1 – 2 / CH 1: UL1, CH 2: UL3
CH 3 – 4 / CH 3: UL1, CH 4: UL3 either or
negative angle (-1500)
one measurement with a 4-channel scope two consecutive measurements with a 2-channel scope with common trigger (i.e. line trigger)
Comm_Infeed
page a 31 31
SITRAIN / METAL ACADEMY © Siemens AG 2011 - all rights reserved
3.12 Line Side Offset Angle For the operation as “Active Line Module” (pulses enabled) the Infeed has to be programmed with the phase angle displacement between the “power voltage” l and the “reference voltage”; typical values will read 30 0, 150, 200 or 7.50 (an appropriate phase shift between the different Infeeds helps to reduce the line side harmonics). The definition of the offset angle has to be made “in rough” u by manual setting; fine-tuning (+/-10) is carried out by means of an “identification mode”. ” Using the equipment available, measure the phase angle displacement in test mode “Pre-Charging and Line Breaker” (with medium voltage, v , inverter pulses blocked). At the training rack sockets to pick up all re quired voltages are located on the upper left side of the rack. Phase angle displacement:
p6420 = . . . . . . . . . . . . .
Likewise the voltage fed to the VSM has to be programmed “in rough”. Measure the voltage. VSM supply voltage:
p3663 = . . . . . . . . . . . . .
page 32
DR-SM150
Definition of Transformer Data
i.e. 10 MVA transformer : 20 s + pre-charging time
+ 2s
A Comm_Infeed
page a 33 3
SITRAIN / METAL ACADEMY © Siemens AG 2011 - all rights reserved
3.13 Basic Configuration of the Line Controller l At the training rack, the steps listed below will be omitted since the data are already programmed correctly. At site, however, they have to be carried out..
page 34
DR-SM150
Actual Raw Values / Actual Value Offset Compensation
X70 U.DC.pos X71 U.DC.neg X72 I.L1 X73 I.L3
via PSA-stamping
Comm_Infeed
SITRAIN / METAL ACADEMY
page a 35 3
© Siemens AG 2011 - all rights reserved
3.14 Actual Value Offset Compensation Verify that the “Actual Value Offset Compensation” is enabled (in an operating mode where voltage and current are definitely zero, the feedback values are measured and then automatically set as offset values). 3.15 Actual Raw Values (Infeed) Physical quantities of the Infeed available via parameters (r….) have been evaluated already. The “Raw Values” as read in on the PSA (from the AVT-Cs) are displayed in r6760 – r6763. With parameter p6770 a number of assignments of these values can be viewed (i.e. the a.m. offset value). Raw values are helpful to check an individual actual channel if in doubt about the correct indication of the value. While still in test mode “pre-charging and line breaker”, use the tracer to record the values of the positive and negative DC-link k voltage as “processed values” available on parameters r70[1], r70[2] and as “raw values” of the PSA. assignment of “raw values” via: p . . . . . . . . . . . = . . . . . . “raw values” U.DC.pos:
r...........
“raw values” U.DC.neg: r . . . . . . . . . . .
A comprehensive list of other important variables regarding the Infeed can be found at the end of this chapter. Discontinue the test mode currently active by selecting “p6650 = Test mode inactive”.
page 36
DR-SM150
User Defined Parameter List (for Identification Modes)
L Comm_Infeed
page a 37 3
SITRAIN / METAL ACADEMY © Siemens AG 2011 - all rights reserved
3.16 Identification Routines Similar to the “Test Modes” used in the previous v steps the SM150 also offers a number of “Identification Routines”. They help to identify and set data such as the fine-tuning values of the “displacement angle” and the “input voltage of the VSM”, the “Line Transformer u.k” or the “DC-link capacity”. Identification Routines are selected with p3410; the currently active Identification Routine is indicated in r6442. The commands “Infeed ON” and “Pulse Enable” ( start the identification) are activated via chart AINF1, sheet F1. After having sswitched c on the Infeed and after having selected the intended Identification Routine the pulses for the Infeed have to be enabled; the selected Identification Routine will then be activated and indicated in r6442. A small number of additional parameters may prove to be helpful (refer to the list above). Edit a “user defined parameter list” similar to the one above to have quick access to the parameters that might be needed in carrying out the Identification Routines.
page 38
DR-SM150
Identification “Transformer Phase Shift”
1) select mode
result of 3): change to 3) change to 16# 0001
2) initially set 16#FFF7 4) change to 16#FFFF
1
16#FFF7
16#FFF7
result of 3): change to 16#240B 16#FFF7 1
Comm_Infeed
page a 39 3
SITRAIN / METAL ACADEMY © Siemens AG 2011 - all rights reserved
3.17 Identification Routine “Identification transformer phase shift” Please remember that this identification i is a “fine-tuning” only and that the settings of parameters p6420, p3663 and p210 have to be correct in the first place. a Now execute the routine “Identification transformer phase shift” as follows: - select routine “Identification transformer phase shift” - disable the pulses for Infeed 1 (chart AINF1, sheet F1, block SAI102, value 16#FFF7 at I2)
- switch on the heat exchanger unit (Auxiliaries = on via OP177) - activate tthe Infeed (ON-command) via chart AINF1, sheet F1, block SAI100, value 16#0001 at the OR-input - enable l the pulses after expiry of the inrush time and the pre-charging delay via chart AINF1, sheet F1, block SAI102, value 16#FFFF at I2
page 40
DR-SM150
Programming the Identified Values
result of 2)
L result of second identification result of first identification t initial values
Comm_Infeed
SITRAIN / METAL ACADEMY
page a 41 41
© Siemens AG 2011 - all rights reserved
- note down the values identified for r6440 and r6441 r6440 = . . . . . . . . . . . . . .
r6441 = . . . . . . . . . . . . . . ; these values MUST NOT significantly differ from 00 respectively from 100%. - change back to state “ready”” (16#FFFF 16#FFF7) - assign these correction values as follows: p6420_new = p6420_old - r6440; p6420_new = . . . . . . . . . . . . p6421_new = p6421_old * r6441 (100% * 100% = 100%);
p6421_new = . . . . . . . . . . . .
- again enable l the pulses via chart AINF1, sheet F1, block SAI102, value 16#FFFF at I2 - now the values for r6440 and r6441 both have to read very close to 00 respectively 100% - change back to state “ready” (16#FFFF 16#FFF7), keep the Infeed in ON-state
page 42
DR-SM150
Identification “Transformer uk”
1) select “type of Identification”
result of 3): change to 3) change to 16# 0001
2) initially set 16#FFF7 4) change to 16#FFFF
1
16#FFF7
16#FFF7
result of 3): change to 16#240B 16#FFF7 1
Comm_Infeed
page a 43 4
SITRAIN / METAL ACADEMY © Siemens AG 2011 - all rights reserved
3.18 Identification Routine “Identification transformer uk” This identification “fine-tunes” the transformer’s relative short circuit voltage uk as set in p6520 by injecting a reactive current. Keep the setpoint value of the reactive current (p3415) as set, unless Warning A06815 is issued; in this case reduce p3415 until the “Identification” is carried out successfully. Now start the routine “Identification transformer uk” as follows: - select routine “Identification transformer uk” - enable the pulses s via chart AINF1, sheet F1, block SAI102, value 16#FFFF at I2 - note d down the values identified in r3411 for five identification runs (they are carried out in sequence automatically) and calculate the average value: . . . . . . . . . . / . . . . . . . . . . / . . . . . . . . . . / . . . . . . . . . . / . . . . . . . . . . r3411 = . . . . . . . . . - change a back to state “ready” (16#FFFF 16#FFF7) - assign the correction value as follows: p6411_new = p6411_old * r3411 (100% * 100% = 100%); p6411_new = . . . . . . . . . . . . - again enable the pulses via chart AINF1, sheet F1, block SAI102, value 16#FFFF at I2 - now the average value for r3411 has to read very close to 100% - change back to state “ready” (16#FFFF 16#FFF7), keep the Infeed in ON-state
page 44
DR-SM150
Identification “Tc Dc” / DC-link capacity
I R E T A Comm_Infeed
page a 45 4
L
SITRAIN / METAL ACADEMY © Siemens AG 2011 - all rights reserved
3.19 Identification Routine “Identification Tc Dc” This identification “fine-tunes” the value of the DC-link capacitance as set in p3422 by generating small variations of the DC-link voltage. Keep the values for the amplitude (p3416) and for the frequency (p6488[1]) of the voltage variations as set. Now start the routine “Identification Tc Dc” as follows: - select routine “Identification Tc Dc” - enable the pulses s via chart AINF1, sheet F1, block SAI102, value 16#FFFF at I2 - note down the values identified in r3412 for five identification runs (they are carried out in sequence automatically) and calculate the average value: -
. . . . . . . . . . / . . . . . . . . . . / . . . . . . . . . . / . . . . . . . . . . / . . . . . . . . . . r3412 = . . . . . . . . . change back to state “ready” (16#FFFF 16#FFF7) assign the correction value as follows: p6412_new = p6412_old * r3412 (100% * 100% = 100%); p6412_new = . . . . . . . . . . . . again enable the pulses via chart AINF1, sheet F1, block SAI102, value 16#FFFF at I2 now the average value for r3412 has to read very close to 100% change back to state “ready” (16#FFFF 16#FFF7), keep the Infeed in ON-state
page 46
DR-SM150
Identification “Reactive Power Steps” / DC-link Current Controller
depending on the current “Identification method” the physical quantities assigned to indices [0] to [4] will be different
reactive current
p6485 = 100%
Comm_Infeed
p6485 = 70%
page a 47 4
p6485 = 60%
SITRAIN / METAL ACADEMY © Siemens AG 2011 - all rights reserved
3.20 Identification Routine “Reactive power steps” This identification “fine-tunes” the controller properties of the Infeed current controller. The repetition sequence of the steps of setpoint and the step value can be modified by parameters p6448[0] and p6446 (not normally necessary). The Identification Routine only o provides the test signals, the optimization of the Infeed current controller has to be made manually. Find out in which way to use r6444[0…3] as a signal source in the tracer to record the “reactive current actual value” and program the tracer accordingly (recording time: 1s). Now optimize the Infeed current controller as suggested: - start the mode “Reactive power steps” and enable the pulses ( 16#FFFF at I2) - analyze the step response of the reactive current - in ssmall variations adapt the damping factor (p6485) to get a response which steps up fast but doesn’t perceptibly overshoot; optimum setting: p6485 = . . . . . . . . . . . . . . . . . - change back to state “ready” (16#FFFF 16#FFF7), keep the Infeed in ON-state
page 48
DR-SM150
Identification “DC Link Voltage Steps” / DC Link Voltage Controller
DC-link voltage
L p6484 = 150%
Comm_Infeed
p6484 = 65%
page a 49 4
p6484 = 60%
SITRAIN / METAL ACADEMY © Siemens AG 2011 - all rights reserved
3.21 Identification Routine “DC link voltage l steps” This identification “fine-tunes” the controller properties of the DC-link voltage controller. The repetition sequence of the steps of setpoint and the step value can be modified by parameters p6448[0] and p6446 (not normally necessary). Assign the “DC-link voltage actual value” to be recorded by the tracer (recording time: 1s). Now optimize the DC-link voltage controller as suggested: - start the routine “DC link voltage steps” and enable the pulses ( 16#FFFF at I2) - analyze the step t rresponse of the DC-link voltage - in small variations i adapt the damping factor (p6484) to get a response as per “symmetrical optimum”(overshoot about 43%), but don’t set p6484 to less than 25%; optimum setting: p6484 = . . . . . . . . . . . . . . . . . - change back to state “ready” (16#FFFF 16#FFF7), keep the Infeed in ON-state
page 50
DR-SM150
Identification “DC Link Voltage Steps” / Decoupling
reactive current
p6488 = 100% p6488 = 140%
Comm_Infeed
page a 51 51
A
p6488 8 = 70%
SITRAIN / METAL ACADEMY © Siemens AG 2011 - all rights reserved
Current control of the line current components is handled on the basis of controlling the α- and β-components; the control of these components has to be functionally l decoupled. The decoupling has to be optimized via v p6488 to g et the least possible influence of the step change of the DC-link voltage setpoint on the reactive current actual value. - record the reactive current actual value and optimize p6488 to get the result stated above; p6488 = . . . . . . . . . . . . - change back to state a “ready”” (16#FFFF 16#FFF7), keep the Infeed in ON-state
3.22 Identification Routine “V dc symmetry steps” This identification “fine-tunes” the controller properties of the DC-link common potential controller. As for the other Identification i Routines, this one also provides the test signals only and the optimization has to be made manually. For this control loop (essentially p6475) it is recommended to keep t he factory settings.
page 52
You're Reading a Preview Unlock full access with a free trial.
Download With Free Trial
DR-SM150
Saving Data / Operation of the Infeed
Load to target
Open project
HD
RAM
Save project
PG / PC
Copy RAM to ROM Save parameters
D445 CFC
RAM
Load to PG not for SIM_D445
Reboot Parameter reset
SIMOTION_CX32 // SINAMICS-Integrated
I R E Comm_Infeed
page a 55 5
SITRAIN / METAL ACADEMY © Siemens AG 2011 - all rights reserved
3.24 Completing the Commissioning off the IInfeed With the (inevitable) exception of adapting the “pre-control” r the Infeed is commissioned and ready for operation. Don’t forget following steps: - reassign the “original setting” for any changes you have made on DCC-charts while commissioning the Infeed (chart AINF1, sheet F1) - upload the online changes you have made on the Infeed (…CX32) - save the uploaded data in your project (Save project) - save the changes on the CFC (Copy RAM to ROM) On the OP177, select “Local Mode” (K9/Local). The OP177 has to indicate following status: Line CB and Exciter CB = not r eady to switch on, other units = Off / ready to switch on Now verify that the Infeed can be switched on via the OP177: - with a delay of 10s the Auxiliaries switch on (state = ready) and “K3/AUX ON” - the state of the Motor changes to “not ready to switch on” “K4/Power ON” - after pre-charging the Line Breaker closes, - the Infeed changes to operation (state = ready) and - the state of the Motor changes to “ready to switch on” Change the DC-link voltage setpoint to 600V and check the “negative”, “positive” and “total” DC-link voltage. Check the feedback signals (status information) to “Automation” on chart AINF1, sheet E1, block SBA90, output VM_ZSW1_AI1.
page 56
DR-SM150
Important Values for the Infeed
Actual Value
Meaning
Sheet Comment
U&I r6910 [0-4] r0069[0-4] r0078 r0076 r0082
I_act_sys_with harmonic oscillations (raw values) I_act_corrected (without pulsing) Iq_act Id_act P_act
8944 Calculated current actual values (U und W measured, V calculated) 8944 Filtered current actual values (r6910) -> more in sine form 8944 Current actual value active component 8944 Current actual value reactive component 8944 Active power actual value
U Syn r3661 r3662 r6426[0] r6426[1] r6427[0-1] r6428[0-1]
Vsyn: U12 raw signal Vsyn: U23 raw signal Vsyn Alpha component Vsyn Beta component Vsyn_q/d unsmoothed Vsyn_q/d unsmoothed
9880 9880 9880 9880 8962 8962
Line-to-line synchronization voltage U12 (VSM) Line-to-line synchronization voltage U23 (VSM) Rotated synchronization voltage α -> alpha to beta = 90° Rotated synchronization voltage β -> alpha to beta = 90° Unsmoothed active and reactive components of the synch. voltage Smoothed active and reactive components of the synch. voltage
DC link Voltage r6435[0] V ZK total r6435[1] V_ZK center potential r6435[2] V_ZK pos r6435[3] V_ZK neg
8944 8944 8944 8944
V_ZK overall % Center potential % V_ZK positive half % V_ZK negative half % (absolute value)
PSA Raw Values r6760[0…n] PSA raw value loaded to X70 r6761[0…n] PSA raw value loaded to X71 r6762[0…n] PSA raw value loaded to X72 r6763[0…n] PSA raw value loaded to X73
9971 9971 9971 9971
Raw actual value at X70 -> U_ZK_P Raw actual value at X71 -> U_ZK_N Raw actual value at X72 -> I_U Raw actual value at X73 -> I_W
Parameters p6960 p6972 [0-7] p6974 [0-37] p6920
Select the pulse pattern table (OPM) V/F Table type V/F Table guide Current limit software
Comm_Infeed
(1 = Standard; 0 = OPM P for 11./13. 1 and transformer shift 30°)
for commissioning purposes rp / protection
page a 57 5
U O C N I A R I T
DEF = 100%
SITRAIN / METAL ACADEMY © Siemens AG 2011 - all rights reserved