The primary objective of this report is to provide a convenient, consistent and accurate method of calculating heating and cooling loads and to enable the designer to select systems that meet the requirement for efficient utilization and are also res
Load Calculations a] Dead Load Load due to M.S screen (jally) Jally spacing b/n 1st and 2nd Column Jally spacing b/n 2nd and 3rd Column Jally spacing b/n 3rd and 4th Column Height of jally Load on jally First column Load on jally 2nd column Load on jally 3rd column Load on jally 4th column Dead Load due to shutter Width of Staircase Height of shutter Shutter Width Shutter load create point Load on column Shutter load create Moment on column Total DL on the roof Bay Length1 Bay Length2 Bay Length3 Bay Length4 Bay Length5 Bay Length6 Bay Length7 Bay Length8
b] Live Load Live load (as per IS 875 pt.3) (For Curved Roof with slope greater than 10 deg.)
Load on Rafter:
DOCUMENT NO. HM-LE-METMET-MO201DOC-DC-STC-08-023
kN/m kN/m kN/m kN/m kN/m kN/m kN/m kN/m
CHECKED BY SHEET
BVR
LARSEN & TOUBRO LIMITED ECC Division - B & FIC c] Wind Load (Considered Curved Profile) As per IS 875 Part III Basic Wind Speed Design Wind Speed where,
Design Wind Pressure Ht of Building
k2
for 15m ht.
1.02
Assuming % of openings more than 20 % Internal Pressure Coff. ( Cpi ) H = L = H/L =
C value = C2 value = = = =
Vb
=
Vz
=
k1
=
1.07
k2
=
1.02
k3
=
1.00
Pz
=
Bay Length1 Bay Length2 Bay Length3 Bay Length4 Bay Length5 Bay Length6 Bay Length7 Bay Length8
On C2 Area -
k1 x
0.6
-1.00 -0.3 -0.4 -0.7 -0.5
Bay Length1 Bay Length2 Bay Length3 Bay Length4 Bay Length5
= = = = = = = =
= = = = =
x
x
k3 x
Vb
As per clause 5.3 of IS 875 Part III
As per clause 5.3.1 of IS 875 Part III As per clause 5.3.2.2 for 15m ht. Category 2 of table 2 of IS 875 Part III Class B Structure. As per clause 5.3.3.1 of IS 875 Part III Vz x Vz
As per clause 5.4 of IS 875 Part III Design Wind Pressure 2 kN/m 1.380
Refer cl 6.2.2.5 of table 5 of IS 875 (III) Note: When the wind is blowing Normal to the gable end, Cpe may be taken as equal to -0.7 for the full width of the roof over a length of L/2 from the gable ends and -0.5 for the remaining portion.
For -ve coefficient Wind Load on Front side Column Wind Load on Back side Column
1.5
= =
Full Load 0.273 kN/m 0.018 kN/m
d] SEISMIC LOAD CALCULATION (Based on IS:1893-2002 provisions) Zone of the building location = II (hyderabad Area) Building System = Steel Frame With Concentric Braces. The framing consideration = Steel Frame Building Soil type = Rocky/ Hard soil site width of the building in X-direction = 3 m width of the building in Z-direction = 30 m Height of the building = 15 m