PEMEX REFINACION HVAC Load Analysis for
REFINERIA ING. ANTONIO M. AMOR SUBESTACION ELECTRICA SE-EC-04
Prepared By:
CORPORACION IPSA S.A DE C.V J.A.A. G.N.L.O. Agosto 2015
Chvac - Full Commercial HVAC Loads Calculation Program Pimaarc Cuajimalpa de Morelos, DF 05410
Elite Software Development, Inc. PEMEX REFINACION Page 2
General Project Data Input General Project Information Project file name: Project title: Project date: Weather reference city: Client name: Client address: Company name: Company address: Company city: Company e-mail address: Company website:
CC SALAMANCA EC-04 AGO 2015 2.CH8 PEMEX REFINACION Agosto 2015 SALAMANCA, GUANAJUATO, MEXICO REFINERIA ING. ANTONIO M. AMOR SUBESTACION ELECTRICA SE-EC-04 CORPORACION IPSA S.A DE C.V J.A.A. G.N.L.O.
[email protected] http://www.corporacionipsa.mx/
Barometric pressure: Altitude: Latitude: Mean daily temperature range: Starting & ending time for HVAC load calculations: Number of unique rooms in this project:
24.303 5643 21 19 1am - 12am 1
in.Hg. feet Degrees Degrees
Building Default Values Calculations performed: Lighting requirements: Equipment requirements: People sensible load multiplier: People latent load multiplier: Room sensible safety factor: Room latent safety factor: Room heating safety factor: People diversity factor: Lighting profile number: Equipment profile number: People profile number: Building default ceiling height: Building default wall height:
Cooling loads only 2.00 0.00 250 200 10 10 0 100 10 10 2 14.14 14.14
Watts per square foot Watts per square foot Btuh per person Btuh per person % % % %
feet feet
Internal Operating Load Profiles (C = 100) 1 2 3 4 5 6 7 8 9 10
hr 1 C C C C C C C C C C
hr 2 C C C C C C C C C C
hr 3 C C C C C C C C C C
hr 4 C C C C C C C C C C
hr 5 C C C C C C C C C C
hr 6 C C C C C C C C C C
hr 7 C C C C C C C C C C
hr 8 C C C C C C C C C C
hr 9 C C C C C C C C C C
hr 10 C C C C C C C C C C
hr 11 C C C C C C C C C C
hr 12 C C C C C C C C C C
hr 13 C C C C C C C C C C
hr 14 C C C C C C C C C C
hr 15 C C C C C C C C C C
hr 16 C C C C C C C C C C
hr 17 C C C C C C C C C C
hr 18 C C C C C C C C C C
hr 19 C C C C C C C C C C
hr 20 C C C C C C C C C C
hr 21 C C C C C C C C C C
hr 22 C C C C C C C C C C
hr 23 C C C C C C C C C C
hr 24 C C C C C C C C C C
Chvac - Full Commercial HVAC Loads Calculation Program Pimaarc Cuajimalpa de Morelos, DF 05410
Elite Software Development, Inc. PEMEX REFINACION Page 3
General Project Data Input (cont'd) Building-Level Design Conditions Design Month
Outdoor Dry Bulb
August Winter
93 10
Outdoor Wet Bulb 70
Indoor Rel.Hum
Indoor Dry Bulb
Grains Diff
In/Outdoor Correction
50%
75 75
17.67
2
Master Roofs Roof No. 1
ASHRAE Roof#
Roof U-Fac
Dark Color
Susp. Ceil
6
0.641
No
No
ASHRAE Group
Wall U-Fac
Wall Color
E
0.543
M
Master Walls Wall No. 1
Chvac - Full Commercial HVAC Loads Calculation Program Pimaarc Cuajimalpa de Morelos, DF 05410
Elite Software Development, Inc. PEMEX REFINACION Page 4
Air Handler Input Air Handler Number 1 Input Data Name: Terminal type: Method for CV Supply fan type: Calculations performed: Excess supply air: Occurrences: People profile number: Lighting profile number: Equipment profile number: Exhaust may not exceed supply air: Leaving heating coil CFM: Leaving cooling coil temp (deg.F): Cooling coil CFM Misc. Btuh gain - supply side: Misc. Btuh gain - return side: Combined fan & motor efficiency: Static pressure across fan (in.wg.): Summer supply duct temp rise (deg.F): Summer return duct temp rise (deg.F): Winter supply duct temp drop (deg.F): Winter return duct temp drop (deg.F): Chilled water temp difference (deg.F): Hot water temp difference (deg.F): Cooling ventilation: Cooling infiltration: Heating ventilation: Heating infiltration: Pretreated outside air: Pretreated air Summer DB (deg.F): Pretreated air Summer WB (deg.F): Pretreated air Winter DB (deg.F):
Design Month
Outdoor Dry Bulb
August Winter
93 10
Uma 101/101r Constant Volume Sum of Peaks Draw-thru fan Cooling loads only Reheat 1 0 0 0 No 0.0 55.0 0 0 0 85 2.00 1.000 0.750 2.000 1.000 0.000 0.000 551 Direct 0 Direct 0 AC/Hr 0 AC/Hr none 0 0 0
Outdoor Wet Bulb 70
Indoor Rel.Hum
Indoor Dry Bulb
Grains Diff
In/Outdoor Correction
50%
75 75
17.67
2
Chvac - Full Commercial HVAC Loads Calculation Program Pimaarc Cuajimalpa de Morelos, DF 05410
Elite Software Development, Inc. PEMEX REFINACION Page 5
Room Input Room 1: Cuarto De Tableros Electricos (1170.534 sq.ft) (Zone 1) Air Handler number: Room length: (feet) Lighting Watts: Number of people in room: Lighting profile number: Ceiling height (feet): Sensible safety factor (%): Sensible heat per person (Btuh): Cooling ventilation method: Cooling infiltration method: Heating ventilation method: Heating infiltration method: Winter exhaust air CFM: Minimum supply CFM: Ceil. exposed to plenum (sq.ft): Cooling loads only are calculated for this room. Roof 1 Wall 1 2 3 4
1 45.44 1,152 2 10 14.14 10 250 Direct Direct AC/Hr Direct 0 0 1
Room occurrences: Room width (feet): Equipment Watts: People profile number: Equipment profile number: Heating safety factor (%): Latent safety factor (%): Latent heat per person (Btuh): Cooling ventilation value: Cooling infiltration value: Heating ventilation value: Heating infiltration value: Summer exhaust air CFM: Latent Btuh equipment load: Exposed floor slab perimeter (ft):
1 25.76 16,764 2 10 0 10 475 551.000 35.000 0.000 35.000 0 667 0
Type
ASHRAE#
U-Factor
Dark
Length
Width
Area
Susp.Ceil
1
6
0.641
No
1.00
1,177.10
1,177.1
No
Type
ASHRAE#
U-Factor
Color
Height
Width
Area
Direction
1 1 1 1
E E E E
0.543 0.543 0.543 0.543
M M M M
13.18 13.18 14.14 14.14
45.44 45.44 25.76 25.76
598.9 598.9 364.2 364.2
N S E W
Chvac - Full Commercial HVAC Loads Calculation Program Pimaarc Cuajimalpa de Morelos, DF 05410
Elite Software Development, Inc. PEMEX REFINACION Page 6
Building Envelope Report Envelope Report Using Summer U-Factors Material Types
Gross Area
Glass Area
Net Area
-UFactor
Area x U-Factor
Average U-Factor
Roof Tot.Roof
1
1,177.1 1,177.1
0.0 0.0
1,177.1 1,177.1
0.641 N/A
754.521 754.521
0.641 0.641
Wall Tot.Wall
1
1,926.3 1,926.3
0.0 0.0
1,926.3 1,926.3
0.543 N/A
1,045.976 1,045.976
0.543 0.543
1,800.497
0.580
Totals
3,103.4
Wall Direction
Wall Area
Glass Area
Wall Net Area
Wall Avg U-Factor
Glass Avg U-Factor
N NE E SE S SW W NW
598.9 0.0 364.2 0.0 598.9 0.0 364.2 0.0
0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0
598.9 0.0 364.2 0.0 598.9 0.0 364.2 0.0
0.543 0.000 0.543 0.000 0.543 0.000 0.543 0.000
0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000
0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000
1,926.3
0.0
1,926.3
0.543
0.000
0.000
Totals
Glass Avg Shd.Coef
Chvac - Full Commercial HVAC Loads Calculation Program Pimaarc Cuajimalpa de Morelos, DF 05410
Elite Software Development, Inc. PEMEX REFINACION Page 7
Building Summary Loads Building peaks in August at 5pm.
Bldg Load Descriptions Roof Wall Glass Floor Slab
Area Quan
Sen Loss
%Tot Loss
Lat Gain
Sen Gain
Net Gain
%Net Gain
1,177 1,926 0 0
0 0 0 0
0.00 0.00 0.00 0.00
0 0 0 0
27,140 28,084 0 0
27,140 28,084 0 0
10.84 11.22 0.00 0.00
0
0.00
0
55,224
55,224
22.06
0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0
0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
0 1,467 0 1,045 0 0 0 6,851 0 441 0 0 0 0 0 0 0 0 0
4,324 142,882 0 550 0 0 0 7,877 0 561 0 9,667 0 0 0 11,318 8,120 0 0
4,324 144,349 0 1,595 0 0 0 14,728 0 1,002 0 9,667 0 0 0 11,318 8,120 0 0
1.73 57.66 0.00 0.64 0.00 0.00 0.00 5.88 0.00 0.40 0.00 3.86 0.00 0.00 0.00 4.52 3.24 0.00 0.00
0
0.00
9,804
240,522
250,326
100.00
Skin Loads Lighting Equipment Pool Latent People Partition Cool. Pret. Heat. Pret. Cool. Vent. Heat. Vent. Cool. Infil. Heat. Infil. Draw-Thru Fan Blow-Thru Fan Reserve Cap. Reheat Cap. Supply Duct Return Duct Misc. Supply Misc. Return
1,152 16,764 0 2 0 0 0 551 0 35 0 0 0 0 0 0 0 0 0
Building Totals
Building Summary
Sen Loss
%Tot Loss
Lat Gain
Sen Gain
Net Gain
%Net Gain
Ventilation Infiltration Pretreated Air Room Loads Plenum Loads Fan/Duct/Misc Loads
0 0 0 0 0 0
0.00 0.00 0.00 0.00 0.00 0.00
6,851 441 0 2,512 0 0
7,877 561 0 202,979 0 29,105
14,728 1,002 0 205,492 0 29,105
5.88 0.40 0.00 82.09 0.00 11.63
Building Totals
0
0.00
9,804
240,522
250,326
100.00
Check Figures Total Building Supply Air (based on a 20° TD): Total Building Vent. Air (4.35% of Supply): Total Conditioned Air Space: Supply Air Per Unit Area: Area Per Cooling Capacity: Cooling Capacity Per Area: Heating Capacity Per Area: Total Heating Required With Outside Air: Total Cooling Required With Outside Air:
12,668 CFM 551 CFM 1,171 10.8223 56.1 0.0178 0.00
Sq.ft CFM/Sq.ft Sq.ft/Ton Tons/Sq.ft Btuh/Sq.ft
0 Btuh 20.86 Tons
Chvac - Full Commercial HVAC Loads Calculation Program Pimaarc Cuajimalpa de Morelos, DF 05410
Elite Software Development, Inc. PEMEX REFINACION Page 8
Air Handler #1 - Uma 101/101r - Summary Loads Rm No
Description Room Peak Time
1
Cuarto De Tableros Electricos 6pm August Room Peak Totals: Total Rooms: 1 Unique Rooms: 1
Area People Volume
Htg.Loss Htg.CFM CFM/Sqft
Sen.Gain Clg.CFM CFM/Sqft
Lat.Gain S.Exh W.Exh
Htg.O.A. Req.CFM Act.CFM
Clg.O.A. Req.CFM Act.CFM
1,171 2 16,551
0 0 0.00
205,382 12,668 10.82
2,899 0 0
None 0 0
Direct 551 551
1,171 2 16,551
0 0 0.00
205,382 12,668 10.82
2,899 0 0
0 0
551 551
Chvac - Full Commercial HVAC Loads Calculation Program Pimaarc Cuajimalpa de Morelos, DF 05410
Elite Software Development, Inc. PEMEX REFINACION Page 9
Air Handler #1 - Uma 101/101r - Total Load Summary Air Handler Description: Supply Air Fan: Fan Input: Sensible Heat Ratio:
Uma 101/101r Constant Volume - Sum of Peaks Draw-Thru with program estim ated horsepower of 4.69 HP 85% motor and fan efficiency with 2 in. water across the fan 0.99 --- This system occurs 1 time(s) in the building. ---
Air System Peak Time: Outdoor Conditions: Indoor Conditions:
5pm in August. Clg: 91° DB, 70° WB, 100.61 grains Clg: 75° DB, 50% RH
Summer: Ventilation controls outside air, ----- Winter: Exhaust controls outside air. Room Space sensible loss: Infiltration sensible loss: Outside Air sensible loss: Supply Duct sensible loss: Return Duct sensible loss: Return Plenum sensible loss: Total System sensible loss:
0 0 0 0 0 0
Btuh Btuh Btuh Btuh Btuh Btuh
0 CFM 0 CFM
0 Btuh
Heating Supply Air: 0 / (.812 X 1.08 X 0) = Winter Vent Outside Air (0.0% of supply) =
0 CFM 0 CFM
Room space sensible gain: 202,979 Infiltration sensible gain: 561 Draw-thru fan sensible gain: 9,667 Supply duct sensible gain: 11,318 Reheat sensible gain: 0 Total sensible gain on supply side of coil:
Btuh Btuh Btuh Btuh Btuh
Cooling Supply Air: 226,367 / (.812 X 1.1 X 20) = Summer Vent Outside Air (4.3% of supply) = Return duct sensible gain: 8,120 Btuh Return plenum sensible gain: 0 Btuh Outside air sensible gain: 7,877 Btuh Blow-thru fan sensible gain: 0 Btuh Total sensible gain on return side of coil: Total sensible gain on air handling system: Room space latent gain: Infiltration latent gain: Outside air latent gain: Total latent gain on air handling system: Total system sensible and latent gain:
224,526 Btuh 12,668 CFM 551 CFM
551 CFM 15,996 Btuh 240,522 Btuh
2,512 Btuh 441 Btuh 6,851 Btuh 9,804 Btuh 250,326 Btuh
Check Figures Total Air Handler Supply Air (based on a 20° TD): Total Air Handler Vent. Air (4.35% of Supply): Total Conditioned Air Space: Supply Air Per Unit Area: Area Per Cooling Capacity: Cooling Capacity Per Area: Heating Capacity Per Area: Total Heating Required With Outside Air: Total Cooling Required With Outside Air:
12,668 CFM 551 CFM 1,171 10.8223 56.1 0.0178 0.00
Sq.ft CFM/Sq.ft Sq.ft/Ton Tons/Sq.ft Btuh/Sq.ft
0 Btuh 20.86 Tons
Chvac - Full Commercial HVAC Loads Calculation Program Pimaarc Cuajimalpa de Morelos, DF 05410
Elite Software Development, Inc. PEMEX REFINACION Page 10
Zone Detailed Loads (At Zone Peak Times) Load Description
Unit Quan
-SCCFAC
CLTD SHGF
U.Fac -CLF-
Sen. Gain
Lat. Gain
Htg. Mult.
Htg. Loss
Room 1-Cuarto De Tableros Electricos - Air Handler 1 (Uma 101/101r), Zone 1 peaks (sensible) in August at 6pm. Roof-1-6-No.Clg-L Wall-1-N-E-M Wall-2-S-E-M Wall-3-E-E-M Wall-4-W-E-M Lights-Prof=10 Equipment-Prof=10 People-Prof=2 Cool. Infil.Direct CFM Heat. Infil.Direct CFM Sub-total Safety factors: Total w/ safety factors:
1,177 599 599 364 364 1,152 16,764 2.0 35 0
0.50 0.83 0.83 0.83 0.83 1.000 1.000 1.000
33.7 17.0 25.7 27.4 36.6
0.641 0.543 0.543 0.543 0.543
25,427 5,513 8,347 5,425 7,231 3,931 129,893 500 444 186,711 +10% --------205,382
41.665 35.295 35.295 35.295 35.295
49,044 21,138 21,138 12,856 12,856
0.000
0
1,334 950 351 2,635 +10% --------2,899
0 +0% --------0
Chvac - Full Commercial HVAC Loads Calculation Program Pimaarc Cuajimalpa de Morelos, DF 05410
Elite Software Development, Inc. PEMEX REFINACION Page 11
Room Detailed Loads (At Room Peak Times) Load Description
Unit Quan
-SCCFAC
CLTD SHGF
U.Fac -CLF-
Sen. Gain
Lat. Gain
Htg. Mult.
Htg. Loss
Room 1-Cuarto De Tableros Electricos peaks (sensible) in August at 6pm, Air Handler 1 (Uma 101/101r), Zone 1, 45.4 x 25.8, Construction Type: 24 (Heavy) Roof-1-6-No.Clg-L Wall-1-N-E-M Wall-2-S-E-M Wall-3-E-E-M Wall-4-W-E-M Lights-Prof=10 Equipment-Prof=10 People-Prof=2 Cool. Infil.Direct CFM Heat. Infil.Direct CFM
1,177 599 599 364 364 1,152 16,764 2.0 35 0
0.50 0.83 0.83 0.83 0.83 1.000 1.000 1.000
33.7 17.0 25.7 27.4 36.6
0.641 0.543 0.543 0.543 0.543
Sub-total Safety factors:
25,427 5,513 8,347 5,425 7,231 3,931 129,893 500 444
49,044 21,138 21,138 12,856 12,856
0.000
0
1,334 950 351
186,711 +10% --------205,382
Total w/ safety factors:
41.665 35.295 35.295 35.295 35.295
2,635 +10% --------2,899
0 +0% --------0
Equipment Cooling Loads Item Name
Nominal Output Sensible
Quantity Type Sensible
Nominal Output Latent
Quantity Type Latent
Sensible Load (Btuh)
Latent Load (Btuh)
18 16,764
watts/sq.ft. watts
667 195
Btuh watts
72,691 57,201
667 667
129,893
1,334
EQUPO INTERIOR TABLEROS Miscellaneous Equipment Total
Lighting Cooling Loads Item Name Compact Fluorescent, Twin, (2) 40 W lamp, Mag-Std ballast Total
Quantity
Quantity Type
Special Allowance Factor
Space Fraction
Occurrences
12
watts
8
1
12
Usage Factor 1
Load (Btuh) 3,931
3,931
Chvac - Full Commercial HVAC Loads Calculation Program Pimaarc Cuajimalpa de Morelos, DF 05410
Elite Software Development, Inc. PEMEX REFINACION Page 12
Air System #1 (Uma 101/101r) Psychrometric Analysis System Load Analysis
Latent
Leaving Coil Condition Draw-Thru Fan Misc Load on Supply Side Supply Air Duct Room Loads Reheat
Grains
Sensible
Temp
CFM
9,667 0 11,318 205,382 0
55.000 0.854 0.000 1.000 18.146 0.000
541 0 633 11,494 0
226,367 8,120 0 0 7,877 0
75.000 0.750 0.000 0.000 0.663 0.000
12,668
242,363
76.413
12,668
79.391 0
0.000
2,953
0.422
Room Condition Return Air Duct Return Air Plenum Misc Load on Return Side Vent Air 551 CFM Blow-Thru Fan
2,953
79.813
0 6,851
0.000 0.981
Entering Coil Condition
9,804
80.794
General Psychrometric Equations Used In Analysis: PR TSH TLH GTH TSH TLH
=(Barometric pressure of site / Standard ASHRAE pressure of 29.921) = PR x 1.10 x CFM x (DB entering - DB leaving) = PR x 0.68 x CFM x (Grains entering - Grains leaving) = PR x 4.50 x CFM x (Enthalpy entering - Enthalpy leaving) = =
0.812 0.812
x x
1.10 0.68
x x
12,668 12,668
x( x(
76.4 80.8
-
55.0 79.4
)= )=
SUM = GTH = 0.812 Total System Load
x
4.50
x
12,668
x(
31.0
-
25.5
)= =
242,363 Btuh 9,818 Btuh ---------252,180 Btuh 253,113 Btuh 250,326 Btuh
= = =
0.0 GPM 0.0 GPM 0.0 lb./hr
Chilled and Hot Water Flow Rates and Steam Requirement Cooling GPM Heating GPM Steam Req.
= = =
253,113 / ( 0 /( 0 /
0.00 0.00 0
x x
500 500
Entering Cooling Coil Conditions Dry bulb temperature: Wet bulb temperature: Relative humidity: Enthalpy:
Entering Heating Coil Conditions 76.41 62.26 48.25 30.98 Btu/lbm
Leaving Cooling Coil Conditions Dry bulb temperature: Wet bulb temperature: Relative humidity: Enthalpy:
) )
Dry bulb temperature:
75.00
Leaving Heating Coil Conditions 55.00 54.98 99.87 25.51 Btu/lbm
Dry bulb temperature:
75.00
Chvac - Full Commercial HVAC Loads Calculation Program Pimaarc Cuajimalpa de Morelos, DF 05410
Elite Software Development, Inc. PEMEX REFINACION Page 13
Air System #1 (Uma 101/101r) Psychrometric Chart RC LC SD DTF RE SM PRE MIX
Room Condition Leaving Coil Condition Supply Duct Temperature Rise Draw Through Fan Sensible Gain Reserve or Reheat Sensible Gain Supply Side Miscellaneous Sensible Gain Pretreated Air Condition Mixed Air Condition
OC EC RD BTF PL MR HRV RML
Outdoor Condition Entering Coil Condition Return Duct Temperature Rise Blow Through Fan Sensible Gain Return Air Plenum Sensible Gain Return Side Miscellaneous Gain Heat Recovery Ventilator Condition Return Miscellaneous Latent Gain
Chvac - Full Commercial HVAC Loads Calculation Program Pimaarc Cuajimalpa de Morelos, DF 05410
Elite Software Development, Inc. PEMEX REFINACION Page 14
Building Pie Charts Building peaks in August at 5pm.
Roof - 10.84%
Return Duct - 3.24% Supply Duct - 4.52% Draw-Thru Fan - 3.86% Cool. Infil. - 0.40% Cool. Vent. - 5.88%
Wall - 11.22%
People - 0.64%
Building Net Gain 250,326 Btuh
Lighting - 1.73%
Equipment - 57.66%
Chvac - Full Commercial HVAC Loads Calculation Program Pimaarc Cuajimalpa de Morelos, DF 05410
Elite Software Development, Inc. PEMEX REFINACION Page 15
Room #1 - Cuarto De Tableros Electricos - Pie Charts Room #1 peaks in August at 6pm
Cool. Infil. - 0.42% People - 0.77% Roof - 13.43%
Wall - 14.00% Room #1 Net Gain 208,280 Btuh
Lighting - 2.08%
Equipment - 69.31%