MATERI TRAINING KWH METER EDMI
By PT EDMI Indonesia
TYPE KWH METER EDMI YANG DIPASARKAN DI INDONESIA 1.
ATLAS SERIES MK10 CLASS 1
2. GENIUS SERIES MK6 CLASS 1
3. GENIUS SERIES Plus MK6E CLASS 0.2
4. GENIUS SERIES MK6N CLASS 0.5
ATLAS SERIES MK10A
Active Energy (kWh) class: 1 ( IEC62052-11, IEC62053-21) Reactive Energy (kVARh) class: 2 ( IEC62053-23) Nominal voltage: 230/400V Operating Range : 140 / 290 Frequency: 45 - 65 Hz CT range: 1/6A, 5/20A , 5/100A Measurement modes: 3 phase 4 wire Measured energy: 4 quadrant (full quadrant) Pulsing output voltage: 240Vac/dc (current 0.1A maximum) Pulsing input passive voltage: 5V,12V,48V,110V,240V ac/dc Pulsing input active Voltage: 5V,up to 6 I/O Total (Up to 2 inputs, 6 outputs ) Communication: ANSI type 2 optical, IEC 61107, RS 232, for Modems connection (GSM/PSTN/CDMA/GPRS etc),RS 485 multi drop (2 or 4 wire, RJ 45 or screw terminal) MV90, UDP, IP,PPP/GPRS capable Temperature range: operating (-40 to 70C), storage (-40 to 85C) Time Of Use: 8 rates plus unified rates, up to 32 separate import and export register up to 200 programmable special days13 previous periods, block or rolling maximum demand Load Survey: Up to 32 channels (interval programmable from 1-60 min), over 1800 days (5 years) storage ( 1 channel, 30 minute interval), 2 independent survey, Energy, instantaneous reading, pulsing input as channel sources, ability to store average/minimum/maximum values for internal duration. Backup Type : Lithium Battery LCD display: 7 Segment LCD Sag/Swell record Equipment Failure Alarms (EFAs)
GENIUS SERIES MK6
Active Energy (kWh) Accuracy class: 1 (IEC62053-22) Reactive Energy (kVARh) Accuracy class: 2s (IEC62053-23) Nominal voltage: 57-240V (phase to neutral) Frequency: 45-65 Hz CT range: 5/20A Auxiliary supply: 240V, 110V (others available on special order) Measurement modes: 3 phase 3 wire or 3 phase 4 wire Measured energy: 4 quadrant (full quadrant) Pulsing output voltage: 5-220Vdc, 12-240Vac (current 0.1A maximum) Pulsing input voltage: 5, 12, 48, 110, 240V ac/dc Communication: ANSI type 2 optical, IEC 61107, RS-232, RS485(2 or 4 wire multidrop), SCADA, Modems (GSM/PSTN/CDMA/GPRS etc), MV90, MODBUS, PPP/GPRS, DNP3, Master/slave communications accessed through one master gateway meter Temperature range: operating (-10 to 60C), storage (-40 to 85C) Time Of Use: 8 rates plus unified rates, 13 previous periods, block or rolling maximum demand Load Survey: Up to 50 channels (interval programmable from 1 second to 1 month) LCD display: 16 character by 2 line alphanumeric display Waveform capture (Harmonic analysis to the 50 harmonics) Equipment Failure Alarms (EFAs): Self checks, tamper and wiring checks (turn on an LED, LCD indicator, relay output, or trigger to send SMS)
GENIUS SERIES MK6N
Active Energy (kWh) Accuracy class: 0.5 (IEC62053-22) Reactive Energy (kVARh) Accuracy class: 2 (IEC62053-23) Nominal voltage: 57-240V (phase to neutral) Frequency: 45-65 Hz CT range: 5/20A Auxiliary supply: 240V, 110V (others available on special order) Measurement modes: 3 phase 3 wire or 3 phase 4 wire Measured energy: 4 quadrant (full quadrant) Pulsing output voltage: 5-220Vdc, 12-240Vac (current 0.1A maximum) Pulsing input voltage: 5, 12, 48, 110, 240V ac/dc Communication: ANSI type 2 optical, IEC 61107, RS-232, RS485(2 or 4 wire multidrop), SCADA, Modems (GSM/PSTN/CDMA/GPRS etc), MV90, MODBUS, PPP/GPRS, DNP3, Master/slave communications accessed through one master gateway meter Temperature range: operating (-10 to 60C), storage (-40 to 85C) Time Of Use: 8 rates plus unified rates, 13 previous periods, block or rolling maximum demand Load Survey: Up to 50 channels (interval programmable from 1 second to 1 month) LCD display: 16 character by 2 line alphanumeric display Waveform capture (Harmonic analysis to the 50 harmonics) Equipment Failure Alarms (EFAs): Self checks, tamper and wiring checks (turn on an LED, LCD indicator, relay output, or trigger to send SMS)
GENIUS SERIES MK6E Class 0.2
Active Energy (kWh) Accuracy class: 0,2 (IEC62053-22, 62052-11) Reactive Energy (kVARh) Accuracy class: 2s (IEC62053-23) Nominal voltage: 57-240V (phase to neutral) Frequency: 45-65 Hz CT range: 1/4A & 5/20A Auxiliary supply: 240V, 110V (others available on special order) Measurement modes: 3 phase 3 wire ( 2 element ) or 3 phase 4 wire ( 3 element ) Measured energy: 4 quadrant (full quadrant) Pulsing output voltage: 5-220Vdc, 12-240Vac (current 0.1A maximum) Pulsing input voltage: 110 / 240V ac/dc, up to 16 input or output via optical external Card. Communication: ANSI type 2 optical, IEC 61107, RS-232, RS485(2 or 4 wire multidrop), SCADA, Modems (GSM/PSTN/CDMA/GPRS etc), MV90, MODBUS, UDP/IP, PPP/GPRS, DNP3 level 2, Master/slave communications accessed through one master gateway meter Temperature range: operating (-25 to +60C), storage (-25 to 80C) Time Of Use: 8 rates plus unified rates, 13 or more previous periods, block or rolling maximum demand Load Survey: Up to 50 channels (interval programmable from 1 second to 1 month) LCD display: 16 character by 2 line alphanumeric display Waveform capture (Harmonic analysis to the 50 harmonics) Equipment Failure Alarms (EFAs): Self checks, tamper and wiring checks (turn on an LED, LCD indicator, relay output, or trigger to send SMS)
PERBANDINGAN DARI MASING-MASING TYPE METER NO
ITEM to COMPARE
TYPE METER MK-10
MK6
MK-6N
MK6E
1
Class
1s
1s
0.5s
0.2s
2
IEC
IEC 62052-11 IEC 62053-21 IEC 62053-23
IEC 62052-11 IEC 62053-21 IEC 62053-23
IEC 62052-11 IEC 62053-22 IEC 62053-23
IEC 62052-11 (GR) IEC 62053-22 (kwh) IEC 62053-23 (kvarh)
3
Memory
Up To 2.1 MByte
2.1 MByte
2.1 MByte
Up To 900 kbyte
4
LCD Display
Seven Segment
Dot Matrik
Dot Matrik
Dot Matrik
5
Harmonic Analisys
Not Support
Support
Support
Support
6
Metode Pengukuran
Total
Total & Fundamental
Total & Fundamental
Total & Fundamenal
7
SCADA MODBUS RTU
Not Support
Support
Support
Support
8
Script Tambahan
Not Support
Support
Support
Support
9
Measurement
Direct / CT
CT/VT
CT/VT
CT/VT
EDMI METERS PIRAMIDA
MK6E
MK6E / MK6N
MK6N/ MK6 / MK10
MK10
ATLAS METER Tombol Billing Reset
Led untuk Testing Accuracy Wh Varh
Tombol Select
LCD 7 Segment
Optical Port + IEC Flag
Modem Port
Digital I/O Battery
Terminal Tegangan R S T N Terminal Arus R S T
GENIUS METER Led untuk Testing Accuracy Wh Varh Tombol Billing Reset
LCD Dot Matrix
Tombol Select Optical Port
Digital I/O
Modem Port
Battery
Terminal Tegangan R S T N Terminal Arus R S T
TAMPILAN LCD ATLAS SERIES MK10A
7 Segment LCD GENIUS SERIES MK6, MK6N, MK6E
DOT Matrics LCD
METER INSTALLATION
Sistem Pengukuran 2 Element – 3 Phasa 3 Kawat (Tegangan yang bekerja adalah tegangan antar phasa)
Sistem Pengukuran 3 Element – 3 Phasa 4 Kawat (Tegangan yang bekerja adalah tegangan phasa)
MK10 Direct
MK10 CT
3 or 4 wire in one model
BASIC METERING CALCULATION
WHAT IS EZIVIEW ???..... EZIVIEW ADALAH SOFTWARE BERBASIS WINDOW YANG DIGUNAKAN UNTUK MEMBACA, MENGAMBIL DATA DAN MENGKOFIGURASI ENERGI METER MERK EDMI, EZIVIEW JUGA BISA DI GUNAKAN SEBAGAI SYSTEM AMR KARENA MEMILIKI FASILITAS SCHEDULER
DIAGRAM SYSTEM AMR GSM Network
KWh Meter + Modem
PC SERVER Modem
Modem