DIgSILENT Pacific User Conference 2007
DETAILED MODELLING OF HV SINGLE CORE CABLE SYSTEMS USING POWERFACTORY determine armour armour and screen screen …..to determine current magnitudes under varying conditions of installation Peter Willis, DIgSILENT Pacific
Perth Office DIgSILENT Pacific PowerFactory Training
1
SYSTEM MODELLING
Cable Systems Systems – Frequency domain model model • Tr Trad aditi ition onal ally ly rep repre rese sent nted ed by by equi equiva vale lent nt PI PI representation for Z1 and Z0 impedances. • Im Impe peda danc nce e dat data a is is typ typic ical ally ly ta take ken n fro from m manufactur manu facturers’ ers’ cata catalogu logues es
DIgSILENT Pacific PowerFactory Training
2
1
CABLE SYSTEM MODELLING – Multi-Core Cables
For multi-core cables, manufacturer data is used. Here we see a non-SWA OLEX cable.
DIgSILENT Pacific PowerFactory Training
3
CABLE SYSTEM MODELLING – Multi-Core Cables
..and here we see the same OLEX cable with SWA.
DIgSILENT Pacific PowerFactory Training
4
2
CABLE SYSTEM MODELLING – Single-Core Cables For single core cables systems, the overall impedance is based on assumptions on the installation and connection of screens.
DIgSILENT Pacific PowerFactory Training
5
CABLE SYSTEM MODELLING – Single-Core Cables
For single core cables systems, the overall impedance must be calculated from the geometric arrangement of the conductors, as is the requirement for overhead lines. These complexity of these calculations are also compounded by the multiple insulation and conducting layers of single core cable profiles, however the new PowerFactory cable system tools encapsulates this.
DIgSILENT Pacific PowerFactory Training
6
3
CABLE SYSTEM MODELLING – Single-Core Cables
Unlike multi-core cables, the individual phase screens are not in electrical contact along the cable length, so there can be substantial induced currents flowing when screens are bonded together and earthed at the cable terminations. If the screens are not bonded at both ends, induced currents do not flow however screen voltages become elevated. All this requires engineering assessment, hence new tools were developed (first supported in Version 13.1) to model single phase cable systems.
DIgSILENT Pacific PowerFactory Training
7
CABLE SYSTEM MODELLING – New PowerFactory Objects
There are three new PowerFactory objects in the model: TypCab Single Phase cable profile TypCabsys Geometric arrangement of cables making up the circuits in a cable system ElmCabsys The link between cable system type and the line elements in the active network Overhead line equivalents: Arial Conductor Type TypCon Tower geometry Type TypTow Tower Element ElmTow
DIgSILENT Pacific PowerFactory Training
8
4
CABLE SYSTEM MODELLING – TypCab
DIgSILENT Pacific PowerFactory Training
9
CABLE SYSTEM MODELLING – TypCabsys
DIgSILENT Pacific PowerFactory Training
10
5
CABLE SYSTEM MODELLING – ElmCabsys
DIgSILENT Pacific PowerFactory Training
11
CABLE SYSTEM MODELLING – ElmCabsys (EMT Tab)
DIgSILENT Pacific PowerFactory Training
12
6
GRAPHICS
DIgSILENT Pacific PowerFactory Training
13
GRAPHICS
DIgSILENT Pacific PowerFactory Training
14
7
WHY DO IT ???
Why do we need this tool? • Customers asked for this • Screen and armour currents need to be quantified so connections & equipment can be correctly dimensioned. • Where screens or armours are lifted, the standing voltage can be determined under load and fault conditions. • Screen-cross bonding distances can be examined • Effect of cascading failures can be examined DIgSILENT Pacific PowerFactory Training
15
CASE STUDY – Real Failure
Example of how the ‘Cabsys’ model was used to quantify screen currents following screen joint failure in 6.6kV generator incomer and how the geometric orientation of cable grouping in the field affects current imbalance across all conducting layers.
DIgSILENT Pacific PowerFactory Training
16
8
CASE STUDY
Oil & Gas Installation - VESDA System detected fault but damage was already done - Generator outage - Very significant $AUD in production losses
DIgSILENT Pacific PowerFactory Training
17
SINGLE CORE CABLE SYSTEMS
3 Main Areas of Concern - Orientation & configuration multiple cable runs, rotating phases within trefoil groups..
- Circulating currents armour and screen bonding and earthing, termination kits..
SCREEN CURRENTS – Cable Damage due to Hot Joints (cont)
DIgSILENT Pacific PowerFactory Training
20
10
Cable Profile
DIgSILENT Pacific PowerFactory Training
21
Joint Instructions
DIgSILENT Pacific PowerFactory Training
22
11
Constant Force Springs
DIgSILENT Pacific PowerFactory Training
23
Final outer layer of joint
DIgSILENT Pacific PowerFactory Training
24
12
What should have been done
DIgSILENT Pacific PowerFactory Training
25
Thermography – Effect of screen connection
Screens Connected
DIgSILENT Pacific PowerFactory Training
Screens Lifted on end
26
13
Thermography – Effect of screen connection
PowerFactory Study cases: • Effect of parallel circuits
• •
Lack of transposition Phase positions in trefoil groups • Effect of high resistance joints leading to cascading failure • Lifting screens and isolating armour-clamping glands
Screens Connected
DIgSILENT Pacific PowerFactory Training
27
Repaired Joints
DIgSILENT Pacific PowerFactory Training
28
14
SUMMARY
Modelling Cable Systems• A tool that has a time and a place
• Can also be used to offline to valid Z1/Z0 in conventional models. • Has associated line objects for each conducting path (sheath, armour, conductor) of each circuit. Going forward…..
• Easier to visualise with composite branch line graphic (V14 feature) • Has some application for EPR calculation, whereby ground impedance is modelled from external tool (CDEGS). Feedback welcome…always