COMPRESSORS
Collection of Datasheets
Compressors for R134a 115V 60Hz
REFRIGERATION AND AIR CONDITIONING
Standard Compressors
Energy-optimized Compressors
Tropical Compressors
P-Series
T-Series
T-Series
PL30F PL50F (LST) PL50F
Page 12 Page 14 Page 16
T T E3 F K TTE4F
Page 60 Page 62
TFS4.5FT (LBP) Pag agee 90 TFS4.5FT (LBP/MBP) Pag agee 92
Page 64 Page 66 Page 68
S-Series
N-Series
NLE5.5F NLE6F NLE7F
T-Series
TL2.5F TL3F TL4F TLS4.5F TF3F TF3.5F T F S4 F TT2.5F
Page 18 Page 20 Page 22 Page 24 Page 26 Page 28 Page 30 Page 32
High Energy-optimized Compressors
SC12FTX SC15FTX
Page 94 Page 96
Universal Compressors
T-Series T-Series N-Series
NF6FK NF7FK NF9FK NF9.5FK NF5.5FX NF7FX NF9FX NF10FX NF11FX NF6.1FX.2 NF7.3FX.2 NF8.4FX.2
Page 34 Page 36 Page 38 Page 40 Page 42 Page 44 Page 46 Page 48 Page 50 Page 52 52 Page 54 54 Page 56 56
TTY5F TTY6F
Page 70 Page 72
T L 2 .5 G TL4G (50/60Hz)
Page 98 Page 100
F-Series N-Series
NTY5.5FK NTY6FK NTY7FK NTY9FK NTY10FK NTX5.2FK NTX5.7FK NTX7.3FK
Page 74 74 Page 76 Page 78 Page 80 Page 82 Page 84 84 Page 86 86 Page 88 88
FF6GK FF7.5GK FF8.5GX FF10GX
Page 102 Page 104 Page 106 Page 108
S-Series
SC12G SC15G SC18G
Page 110 Page 112 Page 114
F-Series
FF8.5FK
2
Page 58
CK.40.A5.22
J u l y 2 00 3
Standard Compressors
Energy-optimized Compressors
Tropical Compressors
P-Series
T-Series
T-Series
PL30F PL50F (LST) PL50F
Page 12 Page 14 Page 16
T T E3 F K TTE4F
Page 60 Page 62
TFS4.5FT (LBP) Pag agee 90 TFS4.5FT (LBP/MBP) Pag agee 92
Page 64 Page 66 Page 68
S-Series
N-Series
NLE5.5F NLE6F NLE7F
T-Series
TL2.5F TL3F TL4F TLS4.5F TF3F TF3.5F T F S4 F TT2.5F
Page 18 Page 20 Page 22 Page 24 Page 26 Page 28 Page 30 Page 32
High Energy-optimized Compressors
SC12FTX SC15FTX
Page 94 Page 96
Universal Compressors
T-Series T-Series N-Series
NF6FK NF7FK NF9FK NF9.5FK NF5.5FX NF7FX NF9FX NF10FX NF11FX NF6.1FX.2 NF7.3FX.2 NF8.4FX.2
Page 34 Page 36 Page 38 Page 40 Page 42 Page 44 Page 46 Page 48 Page 50 Page 52 52 Page 54 54 Page 56 56
TTY5F TTY6F
Page 70 Page 72
T L 2 .5 G TL4G (50/60Hz)
Page 98 Page 100
F-Series N-Series
NTY5.5FK NTY6FK NTY7FK NTY9FK NTY10FK NTX5.2FK NTX5.7FK NTX7.3FK
Page 74 74 Page 76 Page 78 Page 80 Page 82 Page 84 84 Page 86 86 Page 88 88
FF6GK FF7.5GK FF8.5GX FF10GX
Page 102 Page 104 Page 106 Page 108
S-Series
SC12G SC15G SC18G
Page 110 Page 112 Page 114
F-Series
FF8.5FK
2
Page 58
CK.40.A5.22
J u l y 2 00 3
1. General
This collection of datasheets contains information on Danfoss hermetic refrigeration compressors for 115V especially designed for refrigeration systems using refrigerant R134a (CF3-CH2F). The programme consists of the basic types PL, TF, TL, TT, NF, NL, NT, FF and SC.
8238-11
8238-2
PL
8238-6
FF
SC
8238-3
8238-13
TF/TT
TL
8238-12
8238-4
NF/NT 1.1 Compressor designations
NL
The compressor designations are built up according to the following system: Compressor design
Optimization level
Compressor size
Application range
Generation
F Blank R134a LBP/(MBP) Blank First FT Standard energy leve levell generation R134a LBP/(MBP) tropical TF,, TL, T TF TT T Nominal FK S displacement in 2 R134a LBP/(MBP) LST Semi-direct intake cm3 Second FX NF, NL, NT generation R134a LBP/(MBP) HST E Exception: G Energy-optimized For PL 3 R134a LBP/MBP/HBP LBP/MBP/HB P FF (optimized motor) compressors the Third GK Y, X capacity at generation R134a LBP/MBP/HBP LST High Energy-optimized rating point is GX SC (high optimization level) stated etc. R134a LBP/MBP/HBP HST PL
Example
J ul y 2 00 3
TF
S
4.5
FT
NL
E
7
F
FF
8.5
GX
NF
6.1
FX
C K . 40 . A 5 . 22
2 3
1.2 Design
Compressors with the denominations PL, TFS, TLS, TTE, NLE, NF are designs wi th semidirect intake. Compressors with the denominations TTY and NTY are designs with direct intake. Please note that the suction and process connectors on all TFS, TLS, TTE and TTY compressors have been interchanged as compared with the normal TL compressors. Using the wrong connector as suction connector on PL, TFS, TLS, TTE, NF, NL and NLE compressors will lead to reduced capacity and efficiency. Using the wrong connector as suction connector on TTY and NTY is not allowed since the compressor will not function. All compressors have a green label with the type designation. This label has a blue stripe and the text ’R134a’.
1.3 Type label 105G
NLE5.5F Application
115V~60Hz LBP LST
Blue stripe Barcode on white background
R134a
5605
DANFOSS COMPRESSORS
3 5 1 3 8
Green background
1.4 Data stamping
Danfoss compressors have a manufacturing date code stamping on the housing. The form mainly used recently is stamping into the top cover of the housing. On some compressor production lines the stamping has been changed to needle printing into the side of the housing. This is going to be introduced on all products. For a certain period 2 different codes, in needle printing and cover stamping, will be used in parallel. The coding is designed not to be mixed up with the previous version. Example (recent date code):
L--4F-4400 F-203E1157
The first line states the model designation and the code no. L= last letter (or last two letters) of the compressor type -4F- = nominal displacement and application 4400 = 4 last digits in the code no. (= position mark) The second line states the date of manufacture and internal Danfoss codes. F = manufacturing place (F = Germany, AL = Slovenia, AM = Mexico) 20 = week 20 3 = 2003 E = Friday (A = Monday etc.) 115 = nominal voltage 7 = internal Danfoss code The country of origin (manufacturing place) is also stamped on the compressor cover. Example (new date code):
(6 characters) (7 characters) Composition of line 1 H4947: Compressor type information (102H4947 = H4947) 7: internal Danfoss code Composition of line 2 Production week 11: Production year 3: Production day A: A = Monday, B = Tuesday, C = Wednesday, etc. Production hour 00 to 23 or shift code -1, -2, -3 01: B: Danfoss Compressors internal production location code A to G Germany K to N Slovenia R, S Mexico H49477 113A01B
4
CK.40.A5.22
July 2003
1.5 Compressor dimensions
2. Application range
The build-in conditions (total height, weight, tube dimensions etc.) are specified in the individual datasheets including dimensional sketches for the compressors.
F Compressors with denominations ending with F are primarily designed for low evaporating temperatures (LBP Low Back Pressure/MBP Medium Back Pressure on small displacements) for use in refrigerators, freezers and similar applications in regions with stable supply voltage. FT Compressors with denominations ending with FT are F-types designed for low evaporation temperatures (LBP Low Back Pressure) for use in refrigerators, freezers and similar applications operating in regions with unstable supply voltage. FK Compressors with denominations ending with FK are F-types designed for low evaporation temperatures with LST starting characteristics (capillary tube). FX Compressors with denominations ending with FX are F-types designed for low evaporation temperatures with HST starting characteristics (expansion valve). G Compressors with denominations ending with G are primarily designed for high evaporation temperatures (HBP High Back Pressure) for use in liquid coolers, dehumidifiers, refrigerated display counters, vending machines and similar applications. The compressors can also be used for ’Heavy Duty’ purposes at low evaporating temperatures for use in refrigerators, freezers and similar applications operating in regions with unstable supply voltage. GK Compressors with denominations ending with GK are G-types designed for high evaporating temperatures with LST starting characteristics (capillary tube). GX Compressors with denominations ending with GX are G-types designed for high evaporating temperatures with HST starting characteristics (expansion valve). The table on page 6 shows the normally recommended applications as regards voltage/frequency, ambient temperature, evaporating temperature and necessary compressor cooling. The recommandations must be regarded as a guideline only as they presuppose a proper dimensioning of the refrigeration system.
In order to secure a satisfying lifetime of the compressor, and to protect the compressor against overload, some design criteria for the appliances must be fulfilled. Both the condensing temperature and the compressor temperature should be kept as low as possible. This can be done by using well-dimensioned condenser surfaces and by ensuring good ventilation around the compressor under all operating conditions. In order to protect the compressor against overload, the compressor has to start and work properly through pressure peaks obtained in the highest ambient temperature and lowest obliging voltage. At peak load the condensing temperature must not exceed 158°F (70°C). The winding Condensing temperature temperature must not exceed 275°F (135°C). Winding temperature At stable operation conditions the condensing temperature must not exceed 140°F (60°C). The winding temperature must not exceed 257 °F (125°C). These limitations secure protection of valves, gaskets, oil, and motor insulation
2.1 Design limits
July 2003
CK.40.A5.22
5
Compressor
FT
MBP
HBP
90 - 127 / 50
S
S
S
90 - 127 / 60
S
S
S
PL50F
103 - 127 / 60
S
S
TL2.5 - 3 - 4F
103 - 127 / 60
S
S
TLS4.5F
103 - 127 / 60
S
TF3 - 3.5F
95 - 135 / 60
S
TFS4F
95 - 135 / 60
S
TT2.5F
103 - 127 / 60
TTE3FK
103 - 127 / 60
S
TTE4F
103 - 127 / 60
S*
TTY5 - 6F
103 - 127 / 60
S*
NLE5.5 - 6 -7F
103 - 127 / 60
S*
TFS4.5FT (LBP)
95 - 135 / 60
S
TFS4.5FT (LBP / MBP)
95 - 135 / 60
F1
F1
SC12FTX
95 - 135 / 60
F2* *
F2* *
95 - 135 / 60
F2
F2
90 -110 / 50
F2
F2
90 -110 / 60
F2
F2
NF6 - 7FK
95 - 135 / 60
F1 (38°C: S)
F1 (38°C: S)
NF9 - 9.5FK
95 - 135 / 60
F2
F2
NTY5.5 - 6FK
103 - 127 / 60
S*
NTY7 - 9 - 10FK
103 - 127 / 60
F1*
NTX5.2 - 5.7 - 7.3FK
103 - 127 / 60
S*
FF8.5FK
103 - 127 / 60
F2
F2
NF5.5 - 7FX
95 - 135 / 60
O / F1
O / F1
NF9FX
95 - 135 / 60
F2
O / F1
NF10FX
95 - 135 / 60
F2
F1
NF11FX
95 - 127 / 60
NF6.1 - 7.3FX.2
95 - 135 / 60
O / F1
O / F1
NF8.4FX.2
95 - 135 / 60
F2
O / F1
103 - 127 / 60
S
S
S
90 - 127 / 50
S
S
S
90 - 127 / 60
S
S
S
103 - 127 / 60
O / F1
O / F1
O / F1
95 - 135 / 60
F2
F2
SC15FTX
FK
FX
TL2.5G TL4G
G
SC12 -15G SC18G
S O F1 F2 * **
= = = = = = =
Ambient temperature 110°F (43°C) LBP
PL30F
F
Power Supply [V / Hz]
S
F2
103 - 127 / 60
F2
GK
FF6 - 7.5GK
103 - 127 / 60
O / F1
O / F1
O / F1
GX
FF8.5 - 10GX
103 - 127 / 60
F1
F1
F1
Static cooling normally sufficient Oil cooling Fan cooling 1.5 m/s (compressor compartment temperature equal to ambient temp.) Fan cooling 3.0 m/s necessary Outside application range, not recommended Run capacitor compulsory Not applicable below -20°F evaporating temperature in 110 °F ambient temperature above 127V
The application limits regarding evaporating temperatures and motor systems are specified in the individual compressor datasheets. 6
CK.40.A5.22
July 2003
3. Electrical equipment
3.1 LST (RSIR)
The compressors are equipped with a single-phase AC motor. The electrical equipment is classified as ’normal tight’ (IP20) Earth connections are located on the bracket around the current lead-in of the compressor. No attempt must be made to start the compressor without a complete starting device. The compressors can be supplied with the following motor systems: Compressors with the motor type Resistant Start Induction Run (RSIR) have a starting device for Low Starting Torque (LST). This starting device requires a pressure-equalized system before each start. This starting device is normally used in well-designed refrigerating systems with capillary tube as throttling device. The design of the electrical equipment depends on the actual compressor design. As shown in the drawings the following designs of starting devices exist: a) PTC + cord relief + cover, the motor protector is built into the motor (winding protector) b) PTC + motor protector + cover c) relay housing incl. motor protector + terminal board with cord relief + cover d) relay housing incl. motor protector + cord relief + cover Starting devices with PTC need a compressor standstill period of
5 minutes to cool down the
PTC before each start.
2 7 8 0 8
3 7 0 8
a) PL, TL, TLE, TLS
b) TT, NTE
2 4 7 0 8
4 7 0 8
c) FF-GK (alternative)
July 2003
CK.40.A5.22
d) TF, TFS, FF, NF
7
3.2 LST (RSCR)
Compressors with the motor type Resistant Start Capacitor Run (RSCR) have a starting device for Low Starting Torque (LST). This starting device requires a pressure-equalized system before each start. This starting device is normally used in well-designed refrigerating systems with capillary tube as throttling device. The design of the electrical equipment depends on the actual compressor design. As shown in the drawings the following designs of starting devices exist: a) PTC + run capacitor + cord relief + cover, the motor protector is built into the motor (winding protector) b) PTC + run capacitor + motor protector + cover Starting devices with PTC need a compressor standstill period of 5 minutes to cool down the PTC before each start. This starting device is mandatory for some compressor designs and it is an option for others (specified in the invidual data sheets).
5 7 0 8
b) NTE, NTY, TT
a) NLE
3.3 HST (CSIR)
7 8 0 8
Compressors with the motor type Capacitor Start Induction Run (CSIR) have a starting device for High Starting Torque (HST). This starting device requires no pressure-equalization before each start and is normally used in refrigerating systems with expansion valve as throttling device or in capillary tube systems where pressure equalizing is not obtained during the standstill periods. The starting capacitor is designed for short time cut-in. ’1.7% ED’ , which is stamped on the starting capacitor, means for instance max. 10 cut-ins per hour each with a duration of 6 seconds. The design of the electrical equipment depends on the actual compressor design. As shown in the drawings the following designs of starting devices exist: a) Relay + starting capacitor + cord relief + cover, the motor protector is built into the motor (winding protector) b) Relay housing incl. motor protector + starting capacitor with bracket + cord relief (2x) + cover c) Relay housing incl. motor protector + starting capacitor + cord relief (2x) + cover d) Relay + starting capacitor + cord relief + cover (SC) e) Relay + starting capacitor (with bracket) + cover/ protector/protector holder (parts of compressor), used for compressors with the denomination SC which have an external protector. 6 7 0 8
a) TL, TLS
This starting device is mandatory for some compressor designs and it is an option for others (specified in the invidual data sheets). 8
CK.40.A5.22
July 2003
2 7 7 0 8
7 7 0 8
b) FF-X
c) NF-X, TFS
7 6 4 8 8 8 0 8
d) SC
3.4 Connections
e) SC (external protector)
The electrical components are equipped with connectors depending on the ordered code number, 1 Starting relays: / 4 in. (6.3 mm) spade connectors only 1 PTCs: / 4 or 3 / 16 in. (6.3 or 4.8 mm) spade connectors The power supply must be connected as shown in the wiring diagrams for the chosen electrical equipment given in the actual datasheets.
3.5 Approvals
Most compressors have been approved in respect of safety by testing authorities UL and CSA. Actual standards to which the compressors have been approved are specified in the individual datasheets. Approval markings appear on a separate approval mark label.
R
NLE5.5F 115V-60Hz 1PH THERMALLY PROTECTED
2 5 1 3 8
Approval mark
July 2003
CK.40.A5.22
9
4. Moisture and Impurities
The compressors are dried to a maximum moisture content of 60 to 75 mg depending on the compressor size. The maximum impurity content is 40 to 50 mg depending on the compressor size.
5. Max. refrigerant charge
The refrigerant charge must never be too large to be contained on the condenser side of the refrigeration system. Only the refrigerant amount which is necessary for the system to function must be charged. The refrigerant amount may be critical as regards oil foaming and liquid hammer after long standstill periods. Because of this, limitations of refrigerant charges have been introduced. The maximum refrigerant charge is specified in the individual datasheets. If these limitations cannot be complied with, the risk may be reduced if a crankcase heater is properly used or if a pump down system is established.
6. Oil charge
The compressors are supplied charged with dried and degassed oil, which is normally sufficient for the lifetime of the compressor. The refrigeration systems and the system components must be dimensioned in such a way that the oil can be lead back continuously to the compressor housing without accumulating in the system, e.g. without oil pockets and with sufficient gas velocity. The compressors use polyolester oils and are approved only for these oils and R134a. The oil charge is specified in the individual datasheets.
7. Mounting
Soldering problems caused by oil in the connectors can be avoided by placing the compressor on its baseplate some time before soldering it into the system. The compressor must never be placed upside down when mounting the rubber grommets in the baseplate. Instead place the compressor on its side with the connectors upwards.
Washer
Nut M6
Washer Compressor base
Grommet sleeve
Clip Steel pin
Compressor base
9
9
3327-2
7382-2
Cabinet base Cabinet base
Screw M6 x 25
Rubber grommet
Bolt joint (metric sytem)
7.1 Mounting accessories
Rubber grommet
Snap-on joint
The mounting accessories for the compressors are available in two versions, with bolt joint or snap-on joint. The code numbers for the mounting accessories are specified in the individual compressor datasheets. These rubber grommets are designed for the 5 / 8 in. (16 mm) holes of the baseplate: Bolt joint for one compressor in a bag 118 - 1917 (with screw M6 x 25 mm) 118 - 1946 (with screws 1 / 4 inch) Bolt joint in quantities 118 - 1918 (with screws M6 x 25 mm) Snap-on in quantities 118 - 1919 Snap-on for one compressor in a bag 118 - 1947 These rubber grommets are designed for the 3 / 4 in. (19 mm) holes of the baseplate: Bolt joint in quantities 118 - 1949 (with screws 1 / 4 inch)
10
CK.40.A5.22
July 2003
8. Condition at delivery
The compressors are delivered without mounted starting devices on pallets with the dimensions 1144 x 800 mm. Quantities per pallets are specified in the individual datasheets. Electrical components are packed in separate boxes. The most important performance controls carried out during manufacturing are, A high potential insulation test with 1650V for 1 second Pumping capacity Tightness of discharge side and discharge valve Tightness of compressor housing Check of the right oil charge Noise test The compressors are supplied with sealed connectors and the sealing should not be removed before the system assembly takes place (max 15 minutes with open connectors). • • • • •
9. Conversion from R12 to R134a
Normally, the capillary tube shall be adjusted at low evaporating temperatures. Compared to an optimized R12 system with the same evaporator capacity, the R134a system must have an increased resistance defined as approx. 10% less N2 flow at 10 bar inlet pressure. The same size of capillary tube as used for R12 can be used at high evaporating temperatures. A drier with 3Å desiccant of Molecular Sieves must always be used. Rules for dryness and cleanliness of system components (e.g. DIN 8964) are transferred to R134a systems. The system components must not contain mineral oil or greasy substances. The compressors must be soldered into the system no later than 15 minutes after the connector seals have been removed. The same evacuation procedure as for R12 systems must be used. Max. 1% non-condensable gases. The system must not contain any chlorine. The charging equipment must only be used for R134a. If the same vacuum pump is to be used for R12 and R134a systems, a special Ester oi l must be used in agreement with the pump supplier.
10. Warnings
July 2003
No high potential test nor start tests must be carried out while the compressor is under vacuum. No attempt must be made to start the compressor without a complete starting device. Allow the compressor to assume a temperature above 50 °F (10°C) before starting the first time in order to avoid starting problems. Anti-freeze agents must not be used in the compressors as such agents are damaging to several of the materials used. In particular, the ethyl or methyl alcohol contents of such antifreeze agents have a destructive effect on the synthetic motor insulation.
CK.40.A5.22
11
PL30F Standard Compressor R134a 100-115V 50/60Hz Data Sheet (Replaces CD.41.J4.22) General
PL30F
PL30F
Compressor (CU-plated steel connectors) Code number
101G
Application
101G9100
R134a
Blue stripe
9100
Application Application
Barcode on white background Green background
LBP/HBP
Evaporating temperature range
°F (°C)
Voltage range
-13 to 59 (-25 to 15)
V/Hz
DANFOSS COMPRESSORS
90 - 127 /50,60
Motor type
3 8 0 3 8
R
RSIR/CSIR
Max. ambient temperature
V/°F (°C)
115 / 110 (43)
at Voltage
V/°F (°C)
100 / 100 (38)
Comp. cooling at max. ambient temperature
110°F (43°C)
S
100°F (38°C)
S
S O F1 F2
= Static cooling normally sufficient = Oil cooling = Fan cooling 1.5 m/s (compressor compartment temp. equal to ambient temperature) = Fan cooling 3.0 m/s necessary
PL30F 115V-60Hz 1PH THERMALLY PROTECTED
4 8 0 3 8
Approval mark
Design cu.in. (cm 3)
Displacement
0.09 (1.41)
3
Oil quantity
fl.oz. (cm )
5.1 (150)
oz. (g)
10.5 (300)
fl.oz. (cm3)
28.9 (850)
Maximum refrigerant charge Free gas vol. in compressor housing Weight without electr ical equipment
lbs. (kg)
9.5 (4.3)
Motor Motor size
watt
LRA (rated after 4 sec.UL984) LST/HST Cut-in current LST/HST
50
A
9.5/6.1
A
) 0 5 (
) 5 . 0 6 (
) 6 4 (
" 8 " 3 . 7 9 2 . 1
5.00"(127)
7.6/13.6
Approvals
C
D
Suction connector
in. (mm) A
5.28 (134)
B
5.20 (132)
B1
4.88 (124)
B2
2.87 (73)
location/I.D. in. (mm) C
0.252-0.259 (6.5±0.09)
Process connector
location/I.D. in. (mm) D
0.252-0.259 (6.5±0.09)
Discharge connector
location/I.D. in. (mm) E 0.202-0.205 (5.0+0.12/0.20)
Compressors on a pallet
pcs.
B1 B A B2 8.11"(206) 8.03"(204) 6.70"(170)
) 0
150
12
CD.41.J5.22
CK.40.A5.22
8240
) 0 0
7 " ( 1 ( 8 ) 5 " 3 3 6 " . ( 4 7 9 1 .
2
ø0.63"(16)
April 2003
E
UL984/CSA-C22.2
Dimensions Height
5
2
9.5/6.1
Resistance, main and start winding (77°F) Ω
)
" 9 5 1 ( 8 " . 1 2 3 .
) 0 3 1 (
" 2 1 .
. 3
ø0.35"(9)
1
July 2003
Capacity at LBP conditions (ASHRAE) Comp \ . °F Comp \ . °C PL30F
-13 -25 89.1
-10 -23.3 103
0 -17.8 156
10 -12.2 221
Btu/h
20 -6.7 302
30 -1.1 399
40 4.4 517
45 7.2 584
50 10 657
20 -6.7 268
30 -1.1 354
40 4.4 458
45 7.2 517
50 10 581
-6.7 20 71.2
-1.1 30 94.2
4.4 40 122
7.2 45 137
10 50 154
59 15 804
Capacity at HBP conditions (ASHRAE) Comp \ . °F Comp \ . °C PL30F
-13 -25 79.2
-10 -23.3 91.6
0 -17.8 139
10 -12.2 197
Btu/h 59 15 711
Capacity (EN 12900/CECOMAF) Comp \ . °C Comp \ . °F PL30F
-25 -13 21.0
-23.3 -10 24.3
-17.8 0 36.8
-12.2 10 52.3
-13 -25 49.7
-10 -23.3 50.8
-13 -25 1.07
-10 -23.3 1.07
-13 -25 1.79
-10 -23.3 2.03
0 -17.8 55.2
10 -12.2 60.5
20 -6.7 66.3
30 -1.1 72.4
40 4.4 78.5
45 7.2 81.4
50 10 84.2
59 15 88.9
0 -17.8 1.09
10 -12.2 1.11
20 -6.7 1.13
30 -1.1 1.16
40 4.4 1.19
45 7.2 1.20
50 10 1.22
59 15 1.25
-13 -25 1.59
-10 -23.3 1.80
20 -6.7 4.55
30 -1.1 5.51
40 4.4 6.58
45 7.2 7.17
50 10 7.79
0 -17.8 2.82
10 -12.2 3.66
-25 -13 0.42
-23.3 -10 0.48
Main winding a1 Start winding N
0 -17.8 2.51 -17.8 0 0.67
N
C
L
Btu/Wh 59 15 9.04 Winding protector
Btu/Wh
10 -12.2 3.25
20 -6.7 4.04
30 -1.1 4.89
40 4.4 5.83
45 7.2 6.35
50 10 6.90
-12.2 10 0.86
-6.7 20 1.07
-1.1 30 1.30
4.4 40 1.55
7.2 45 1.69
10 50 1.83
COP (EN 12900/CECOMAF) Comp \ . °C Comp \ . °F PL30F
d
A
EER at HBP conditions (ASHRAE) Comp \ . °F Comp \ . °C PL30F
a1
watt
EER at LBP conditions (ASHRAE) Comp \ . °F Comp \ . °C PL30F
8224 8224-2
15 59 189
Current consumption Comp \ . °F Comp \ . °C PL30F
b
watt
Power consumption Comp \ . °F Comp \ . °C PL30F
LST
59 15 7.99
W/W
Test conditions ASHRAE (LBP) ASHRAE (HBP) EN12900/CECOMAF Condensing temperatur e 130 °F (54.4°C) 130°F (54.4°C) 55°C (131°F) Ambient and suction gas temp. 90 °F (32°C) 95°F (35°C) 32°C (90°F) Liquid temperature 90°F (32°C) 115°F (46°C) 55°C (131°F) Static cooling, 115V 60Hz, PTC consumption incl.
15 59 2.12
HST c
b 8225
Accessories
a2
Devices
Fig.
PL30F d
PTC star ting device 1
/ 4 in. (6.3 mm) spades / 16 in. (4.8 mm) spades
a1
103N0003 103N0023
Star ting relay
a2
117U6000
Star ting capacitor 80 µF
c
117U5015
Cover
b
103N0492
Cord relief
d
103N1010
3
Mounting accessories Bolt joint for one compressor Bolt joint in quantities Snap-on in quantities
2
July 2003
Ø in. (mm) 5 / 8 (16) 5 / 8 (16) 5 / 8 (16)
118-1917 118-1918 118-1919
CD.41.J5.22
CK.40.A5.22
c 11
10
12
13 14
Main winding Winding protector
Start winding
April 2003
13
PL50F Standard Compressor - LST Starting Characteristics R134a 115V 60Hz Data Sheet (Replaces CD.41.A6.22) General
PL50F
PL50F
Compressor (CU-plated steel connectors) Codenumber
101G
Application
101G9200
R134a
Blue stripe
9200
Application Application Evaporating temperature range
°F (°C)
Voltage range
V/Hz
LBP/MBP
Barcode on white background
-13 to 32 (-25 to 0)
Green background
DANFOSS COMPRESSORS
103 - 127 /60
Motor type
8 0 3 8
R
RSIR
Max. ambient temperature
°F (°C)
110 (43)
Comp. cooling at max. ambient temperature
110°F (43°C)
S
S O F1 F2
= Static cooling normally sufficient = Oil cooling = Fan cooling 1.5 m/s (compressor compartment temp. equal to ambient temperature) = Fan cooling 3.0 m/s necessary
PL50F 115V-60Hz 1PH THERMALLY PROTECTED
2 8 0 3 8
Approval mark
Design cu.in. (cm 3)
Displacement
0.12 (2.00)
3
Oil quantity Maximum refrigerant charge Free gas vol. in compressor housing Weight without electr ical equipment
fl.oz. (cm )
5.1 (150)
oz. (g)
10.5 (300)
3
fl.oz. (cm )
28.9 (850)
lbs. (kg)
9.5 (4.3)
Motor Motor size
watt
50
LRA (rated after 4 sec.UL984) LST
A
4.9
Cut-in current LST
A
14.0
Resistance, main and start winding (77 °F)
) 0 5 (
) 5 . 0 6 (
) 6 4 (
" 8 " 3 . 7 9 2 . 1
Approvals
5
2
8.8/5.5
Ω
)
" 9 5 1 ( 8 " . 1 2 3 .
) 0 3 1 (
" 2 1 .
5.00"(127)
UL984/CSA-C22.2
C
D
E Dimensions Height
in. (mm) A
5.28 (134)
B
5.20 (132)
B1
4.88 (124)
B2
2.87 (73)
Suction connector
location/I.D. in. (mm) C
0.252-0.259 (6.5±0.09)
Process connector
location/I.D. in. (mm) D
0.252-0.259 (6.5±0.09)
Discharge connector
location/I.D. in. (mm) E 0.202-0.205 (5.0+0.12/0.20)
Compressors on a pallet
pcs.
B1 B A B2 8.11"(206) 8240
8.03"(204) 6.70"(170) ) 0
150
2
ø0.63"(16)
February 2003
14
CD.41.A7.22
CK.40.A5.22
) 0 0
7 " ( 1 ( 8 ) 5 " 3 3 6 " . ( 4 7 9 1 .
. 3
ø0.35"(9)
1
July 2003
Capacity at LBP conditions (ASHRAE) Comp \ . °F Comp \ . °C PL50F
-13 -25 155
-10 -23.3 175
0 -17.8 249
Btu/h
10 -12.2 335
20 -6.7 437
30 -1.1 557
20 -6.7 388
30 -1.1 494
32 0 584
Capacity at MBP conditions (ASHRAE) Comp \ . °F Comp \ . °C PL50F
-13 -25 138
-10 -23.3 156
0 -17.8 221
10 -12.2 297
Btu/h 32 0 518
Capacity (EN 12900/CECOMAF) Comp \ . °C Comp \ . °F PL50F
-25 -13 36.8
-23.3 -10 41.5
-17.8 0 58.9
-13 -25 62.3
-10 -23.3 65.0
-12.2 10 79.3
-6.7 20 103
-1.1 30 132
0 32 138
-13 -25 1.12
-10 -23.3 1.13
0 -17.8 73.2
10 -12.2 80.9
20 -6.7 88.5
30 -1.1 96.2
-13 -25 2.49
-10 -23.3 2.70
0 -17.8 1.18
10 -12.2 1.22
20 -6.7 1.27
32 0 97.8
30 -1.1 1.33
-13 -25 2.21
-10 -23.3 2.40
-25 -13 0.59
-23.3 -10 0.64
N
0 -17.8 3.39
10 -12.2 4.14
0 -17.8 3.02
32 0 1.34
20 -6.7 4.94
30 -1.1 5.79
N
10 -12.2 3.67
20 -6.7 4.38
30 -1.1 5.14
-12.2 10 0.98
-6.7 20 1.17
-1.1 30 1.37
C
L
32 0 5.97
Btu/Wh
COP (EN 12900/CECOMAF) Comp \ . °C Comp \ . °F PL50F
Main winding a1 Start winding
Btu/Wh
EER at MBP conditions (ASHRAE) Comp \ . °F Comp \ . °C PL50F
d
A
EER at LBP conditions (ASHRAE) Comp \ . °F Comp \ . °C PL50F
a1
watt
Current consumption Comp \ . °F Comp \ . °C PL50F
8224 8224-2
watt
Power consumption Comp \ . °F Comp \ . °C PL50F
b
Winding protector
32 0 5.29
W/W
-17.8 0 0.80
Test conditions ASHRAE (LBP) ASHRAE (MBP) Condensing temperatur e 130 °F (54.4°C) 130°F (54.4°C) Ambient and suction gas temp. 90 °F (32°C) 95°F (35°C) Liquid temperature 90°F (32°C) 115°F (46°C) Static cooling, 115V 60Hz, PTC consumption incl.
0 32 1.41
EN12900/CECOMAF 55°C (131°F) 32°C (90°F) 55°C (131°F)
Accessories Devices
Fig.
PL50F
a1
103N0003 103N0023
Cover
b
103N0492
Cord relief
d
103N1010
PTC star ting device 1 / 4 in. (6.3 mm) spades 3 / 16 in. (4.8 mm) spades
Mounting accessories Bolt joint for one compressor Bolt joint in quantities Snap-on in quantities
2
July 2003
Ø in. (mm) 5 / 8 (16) 5 / 8 (16) 5 / 8 (16)
118-1917 118-1918 118-1919
CD.41.A7.22
CK.40.A5.22
February 2003
15
PL50F Standard Compressor R134a 115V 60Hz Data Sheet (Replaces CD.41.I3.22) General
PL50F
PL50F
Compressor (CU-plated steel connectors) Codenumber
101G
Application
101G9202
R134a
Blue stripe
9202
Application Application Evaporating temperature range
°F (°C)
Voltage range
V/Hz
LBP/MBP
Barcode on white background
-13 to 32 (-25 to 0)
Green background
DANFOSS COMPRESSORS
103 - 127 /60
Motor type
5 8 0 3 8
R
RSIR/CSIR
Max. ambient temperature
°F (°C)
110 (43)
Comp. cooling at max. ambient temperature
110°F (43°C)
S
S O F1 F2
= Static cooling normally sufficient = Oil cooling = Fan cooling 1.5 m/s (compressor compartment temp. equal to ambient temperature) = Fan cooling 3.0 m/s necessary
PL50F 115V-60Hz 1PH THERMALLY PROTECTED
2 8 0 3 8
Approval mark
Design cu.in. (cm 3)
Displacement
0.12 (2.00)
3
Oil quantity
fl.oz. (cm )
5.1 (150)
oz. (g)
10.5 (300)
Maximum refrigerant charge Free gas vol. in compressor housing Weight without electr ical equipment
3
fl.oz. (cm )
28.9 (850)
lbs. (kg)
9.5 (4.3)
Motor Motor size
watt
50
LRA (rated after 4 sec.UL984) LST/HST
A
9.5/6.1
Cut-in current LST/HST
A
9.5/6.1
Resistance, main and start winding (77 °F) Ω
) 0 5 (
) 5 . 0 6 (
) 6 4 (
" 8 " 3 . 7 9 2 . 1
5
2
7.6/13.6
Approvals
)
" 9 5 1 ( 8 " . 1 2 3 .
) 0 3 1 (
" 2 1 .
5.00"(127)
UL984/CSA-C22.2
C
D
E Dimensions Height
in. (mm) A
5.28 (134)
B
5.20 (132)
B1
4.88 (124)
B2
2.87 (73)
Suction connector
location/I.D. in. (mm) C
0.252-0.259 (6.5±0.09)
Process connector
location/I.D. in. (mm) D
0.252-0.259 (6.5±0.09)
Discharge connector
location/I.D. in. (mm) E 0.202-0.205 (5.0+0.12/0.20)
Compressors on a pallet
pcs.
B1 B A B2 8.11"(206) 8240
8.03"(204) 6.70"(170) ) 0
150
2
ø0.63"(16)
February 2003
16
CD.41.I4.22
CK.40.A5.22
) 0 0
7 " ( 1 ( 8 ) 5 " 3 3 6 " . ( 4 7 9 1 .
. 3
ø0.35"(9)
1
July 2003
Capacity at LBP conditions (ASHRAE) Comp \ . °F Comp \ . °C PL50F
-13 -25 155
-10 -23.3 175
0 -17.8 249
Btu/h
10 -12.2 335
20 -6.7 437
30 -1.1 557
20 -6.7 388
30 -1.1 494
32 0 584
Capacity at MBP conditions (ASHRAE) Comp \ . °F Comp \ . °C PL50F
-13 -25 138
-10 -23.3 156
0 -17.8 221
10 -12.2 297
Btu/h 32 0 518
Capacity (EN 12900/CECOMAF) Comp \ . °C Comp \ . °F PL50F
-25 -13 36.8
-23.3 -10 41.5
-17.8 0 58.9
-13 -25 62.3
-10 -23.3 65.0
-12.2 10 79.3
-6.7 20 103
-1.1 30 132
-13 -25 1.12
-10 -23.3 1.13
-13 -25 2.49
-10 -23.3 2.70
0 -17.8 73.2
10 -12.2 80.9
20 -6.7 88.5
30 -1.1 96.2
-13 -25 2.21
-10 -23.3 2.40
32 0 97.8
0 -17.8 1.18
10 -12.2 1.22
20 -6.7 1.27
30 -1.1 1.33
-25 -13 0.59
-23.3 -10 0.64
Main winding a1 Start winding N
0 -17.8 3.39
10 -12.2 4.14
0 -17.8 3.02
32 0 1.34
-17.8 0 0.80
N
C
Btu/Wh 20 -6.7 4.94
30 -1.1 5.79
10 -12.2 3.67
20 -6.7 4.38
30 -1.1 5.14
-12.2 10 0.98
-6.7 20 1.17
-1.1 30 1.37
Btu/Wh
Winding protector
32 0 5.29
W/W
Test conditions ASHRAE (LBP) ASHRAE (MBP) Condensing temperatur e 130 °F (54.4°C) 130°F (54.4°C) Ambient and suction gas temp. 90 °F (32°C) 95°F (35°C) Liquid temperature 90°F (32°C) 115°F (46°C) Static cooling, 115V 60Hz, PTC consumption incl.
0 32 1.41
HST c
EN12900/CECOMAF 55°C (131°F) 32°C (90°F) 55°C (131°F)
b 8225
a2
Accessories Devices PTC star ting device 1 / 4 in. (6.3 mm) spades 3 / 16 in. (4.8 mm) spades
PL50F
a1
103N0003 103N0023
d
a2
117U6000
Star ting capacitor 80 µF
c
117U5015
Cover
b
103N0492
Cord relief
d
103N1010
2
July 2003
Fig.
Star ting relay
Mounting accessories Bolt joint for one compressor Bolt joint in quantities Snap-on in quantities
L
32 0 5.97
COP (EN 12900/CECOMAF) Comp \ . °C Comp \ . °F PL50F
d
A
EER at MBP conditions (ASHRAE) Comp \ . °F Comp \ . °C PL50F
a1
watt
EER at LBP conditions (ASHRAE) Comp \ . °F Comp \ . °C PL50F
8224 8224-2
0 32 138
Current consumption Comp \ . °F Comp \ . °C PL50F
b
watt
Power consumption Comp \ . °F Comp \ . °C PL50F
LST
Ø in. (mm) 5 / 8 (16) 5 / 8 (16) 5 / 8 (16)
c 11
10
12
13 14
118-1917 118-1918 118-1919
Main winding Winding protector
CD.41.I4.22
CK.40.A5.22
Start winding
February 2003
17
TL2.5F Standard Compressor R134a 115V 60Hz Data Sheet (Replaces CD.42.B5.22) General Compressor Connector-material
Sealing
Code number
Copper-plated steel
Aluminium caps
102G3206
Copper-plated steel
Rubber plugs
Copper
Rubber plugs
102G
TL2.5F
TL2.5F Application
R134a
Blue stripe
3206
Barcode on white background
DANFOSS COMPRESSORS
Green background
Application
0 1 3 8
R
Application
LBP/MBP
Evaporating temperature range
°F (°C)
Voltage range
V/Hz
103 - 127 /60
Motor type
RSIR
Max. ambient temperature
°F (°C)
110 (43)
Comp. cooling at
S O F1 F2
max. ambient temperature
TL2.5F 115V-60Hz 1PH
-13 to 23 (-25 to -5)
110°F (43°C)
= Static cooling normally sufficient = Oil cooling = Fan cooling 1.5 m/s (compressor compartment temp. equal to ambient temperature) = Fan cooling 3.0 m/s necessary
2 0 1 3 8
THERMALLY PROTECTED
Approval mark
S
Design cu.in. (cm 3)
Displacement
0.16 (2.61)
3
Oil quantity Maximum refrigerant charge Free gas vol. in compressor housing Weight without electr ical equipment
fl.oz. (cm )
6.1 (180)
oz. (g)
14.0 (400)
fl.oz. (cm3)
54.2 (1600)
lbs. (kg)
) 7 5 1 (
" 8 1 . 6
) 5 . 0 6 (
" 8 3 . 2
14.7 ( 6.7)
°
) 6 6 (
" 0 6 . 2
0 2
4 5
°
°
1 5
4.02"(102)
Motor Motor size
watt
75
LRA (rated after 4 sec.UL984) LST
A
5.3
Cut-in current LST
A
14.5
Resistance, main and start winding (77 °F) Ω
UL984/CSA-C22.2
in. (mm) A
6.42 (163)
B
6.26 (159)
Suction connector
location/I.D. in. (mm) C
0.252-0.259 (6.5±0.09)
Process connector
location/I.D. in. (mm) D
0.252-0.259 (6.5±0.09)
Discharge connector
location/I.D. in. (mm) E 0.202-0.205 (5.0+0.12/0.20)
Compressors on a pallet
pcs.
125
7 (
" 0 8 . 2
8261
3.78"(96) 4.61"(117)
or
8.74"(222) 6.93"(176)
D C
3 2 1 8 . 5
°
0 3
A B
° °
) 5 0 1 (
) 5 0 1 (
" 3 1 . 4
Dimensions
(
1
E
7.3/4.8
Approvals
Height
C or D
" ) 4 ) 9 1 . 2 1
" 3 1 . 4
ø0.75"(19)
6.50"(165)
) 7 0 1 (
" 1 2 . 4
ø0.63"(16)
) 0 7 (
" 6 7 . 2
) 6 . 1 0 1 (
" 0 0 . 4
) 6 3 1 (
" 5 3 . 5
ø0.14"(3.6) 6.70"(170) 7.01"(178) 8.03"(204)
June 2003
18
CD.42.B6.22
CK.40.A5.22
1
July 2003
Capacity at LBP conditions (ASHRAE) Comp \ . °F Comp \ . °C TL2.5F
-13 -25 181
-10 -23.3 202
0 -17.8 287
10 -12.2 396
Btu/h 20 -6.7 524
Capacity at MBP conditions (ASHRAE) Comp \ . °F Comp \ . °C TL2.5F
-13 -25 162
-10 -23.3 180
0 -17.8 255
10 -12.2 354
20 -6.7 466
23 -5 568
Btu/h b
23 -5 506
8217-2
a1
Capacity (EN 12900/CECOMAF) Comp \ . °C Comp \ . °F TL2.5F
-25 -13 43
-23.3 -10 48
-17.8 0 68
-12.2 10 93
watt -6.7 20 124
d
-5 23 134
Main winding a1 Start winding N
Power consumption Comp \ . °F Comp \ . °C TL2.5F
-13 -25 61
-10 -23.3 65
watt 0 -17.8 77
10 -12.2 90
20 -6.7 104
23 -5 109
Current consumption Comp \ . °F Comp \ . °C TL2.5F
-13 -25 0.91
-10 -23.3 0.94
-13 -25 2.96
-10 -23.3 3.11
10 -12.2 1.08
20 -6.7 1.22
0 -17.8 3.73
10 -12.2 4.42
-13 -25 2.63
-10 -23.3 2.77
0 -17.8 3.32
10 -12.2 3.93
-25 -13 0.70
-23.3 -10 0.74
-17.8 0 0.88
-12.2 10 1.04
23 -5 1.29
Winding protector
23 -5 5.22
Btu/Wh 20 -6.7 4.49
COP (EN 12900/CECOMAF) Comp \ . °C Comp \ . °F TL2.5F
-6.7 20 1.19
23 -5 4.65
W/W
Accessories
-5 23 1.23
Devices
Test conditions ASHRAE (LBP) ASHRAE (MBP) Condensing temperatur e 130 °F (54.4°C) 130°F (54.4°C) Ambient and suction gas temp. 90 °F (32°C) 95°F (35°C) Liquid temperature 90°F (32°C) 115°F (46°C) Static cooling, 115V 60Hz, PTC consumption incl.
EN12900/CECOMAF 55°C (131°F) 32°C (90°F) 55°C (131°F)
Fig.
TL2.5F
PTC star ting device 1 / 4 in. (6.3 mm) spades 3 / 16 in. (4.8 mm) spades
a1
103N0003 103N0023
Cover
b
103N2011
Cord relief
d
103N1010
Mounting accessories Bolt joint for one compressor Bolt joint in quantities Snap-on in quantities
2
July 2003
L
Btu/Wh 20 -6.7 5.05
EER at MBP conditions (ASHRAE) Comp \ . °F Comp \ . °C TL2.5F
C
A 0 -17.8 1.00
EER at LBP conditions (ASHRAE) Comp \ . °F Comp \ . °C TL2.5F
N
CD.42.B6.22
CK.40.A5.22
Ø in. (mm) 5 / 8 (16) 5 / 8 (16) 5 / 8 (16)
118-1917 118-1918 118-1919
June 2003
19
TL3F Standard Compressor R134a 115V 60Hz Data Sheet (Replaces CG.42.O1.22) General Compressor Connector-material
Sealing
Code number
Copper-plated steel
Aluminium caps
102G3300
Copper-plated steel
Rubber plugs
102G3307
Copper
Rubber plugs
102G
TL3F
TL3F Application
R134a
Blue stripe
3300
Barcode on white background
DANFOSS COMPRESSORS
Green background
Application
3 0 1 3 8
R
Application
LBP/MBP
Evaporating temperature range
°F (°C)
Voltage range
103 - 127 /60
Motor type
RSIR
Max. ambient temperature
°F (°C)
110 (43)
Comp. cooling at max. ambient temperature
TL3F 115V-60Hz 1PH
-13 to 23 (-25 to -5)
V/Hz
110°F (43°C)
S
S O F1 F2
= Static cooling normally sufficient = Oil cooling = Fan cooling 1.5 m/s (compressor compartment temp. equal to ambient temperature) = Fan cooling 3.0 m/s necessary
4 0 1 3 8
THERMALLY PROTECTED
Approval mark
Design cu.in. (cm 3)
Displacement
0.19 (3.13)
3
Oil quantity Maximum refrigerant charge Free gas vol. in compressor housing Weight without electr ical equipment
fl.oz. (cm )
6.1 (180)
oz. (g)
14.0 (400)
fl.oz. (cm3)
54.2 (1600)
lbs. (kg)
14.7 ( 6.7)
Motor size
watt
90
LRA (rated after 4 sec.UL984) LST
A
6.0
Cut-in current LST
A
15.0
Resistance, main and start winding (77 °F)
Ω
6.3/4.8
Approvals
UL984/CSA-C22.2
°
) 6 6 (
" 0 6 . 2
0 2
4 5
°
°
1 5
C or D
in. (mm) A
6.42 (163)
B
6.26 (159)
Suction connector
location/I.D. in. (mm) C
0.252-0.259 (6.5±0.09)
Process connector
location/I.D. in. (mm) D
0.252-0.259 (6.5±0.09)
Discharge connector
location/I.D. in. (mm) E 0.202-0.205 (5.0+0.12/0.20) pcs.
125
" ) 4 ) 9 1 . 2 1 (
1
7 (
" 0 8 . 2
8261
3.78"(96) 4.61"(117)
or
8.74"(222) 6.93"(176)
D C E
3 2 1 8 . 5
°
0 3
A B
° °
) 5 0 1 (
) 5 0 1 (
" 3 1 . 4
Dimensions
Compressors on a pallet
) 5 . 0 6 (
" 8 3 . 2
4.02"(102)
Motor
Height
) 7 5 1 (
" 8 1 . 6
" 3 1 . 4
ø0.75"(19)
6.50"(165)
) 7 0 1 (
" 1 2 . 4
ø0.63"(16)
) 0 7 (
" 6 7 . 2
) 6 . 1 0 1 (
" 0 0 . 4
) 6 3 1 (
" 5 3 . 5
ø0.14"(3.6) 6.70"(170) 7.01"(178) 8.03"(204)
July 2003
20
CG.42.O2.22
CK.40.A5.22
1
July 2003
Capacity at LBP conditions (ASHRAE) Comp \ . °F Comp \ . °C TL3F
-13 -25 228
-10 -23.3 253
0 -17.8 351
10 -12.2 478
Btu/h 20 -6.7 636
Capacity at MBP conditions (ASHRAE) Comp \ . °F Comp \ . °C TL3F
-13 -25 203
-10 -23.3 225
0 -17.8 312
10 -12.2 425
20 -6.7 566
23 -5 692
Btu/h b
23 -5 616
8217-2
a1
Capacity (EN 12900/CECOMAF) Comp \ . °C Comp \ . °F TL3F
-25 -13 54
-23.3 -10 60
-17.8 0 83
-12.2 10 113
watt -6.7 20 150
d
-5 23 163
Main winding a1 Start winding N
Power consumption Comp \ . °F Comp \ . °C TL3F
-13 -25 72
-10 -23.3 77
watt 0 -17.8 92
10 -12.2 108
20 -6.7 125
23 -5 130
Current consumption Comp \ . °F Comp \ . °C TL3F
-13 -25 1.09
-10 -23.3 1.12
-13 -25 3.15
-10 -23.3 3.29
10 -12.2 1.32
20 -6.7 1.47
0 -17.8 3.80
10 -12.2 4.42
-13 -25 2.80
-10 -23.3 2.93
0 -17.8 3.38
10 -12.2 3.93
-25 -13 0.75
-23.3 -10 0.78
-17.8 0 0.90
23 -5 1.52
23 -5 5.34
July 2003
Accessories
23 -5 4.75
Devices
W/W -12.2 10 1.04
-6.7 20 1.20
-5 23 1.26
Test conditions ASHRAE (LBP) ASHRAE (MBP) Condensing temperatur e 130 °F (54.4°C) 130°F (54.4°C) Ambient and suction gas temp. 90 °F (32°C) 95°F (35°C) Liquid temperature 90°F (32°C) 115°F (46°C) Static cooling, 115V 60Hz, PTC consumption incl.
2
Winding protector
Btu/Wh 20 -6.7 4.55
COP (EN 12900/CECOMAF) Comp \ . °C Comp \ . °F TL3F
L
Btu/Wh 20 -6.7 5.11
EER at MBP conditions (ASHRAE) Comp \ . °F Comp \ . °C TL3F
C
A 0 -17.8 1.21
EER at LBP conditions (ASHRAE) Comp \ . °F Comp \ . °C TL3F
N
EN12900/CECOMAF 55°C (131°F) 32°C (90°F) 55°C (131°F)
Fig.
TL3F
PTC star ting device 1 / 4 in. (6.3 mm) spades 3 / 1 6 in. (4.8 mm) spades
a1
103N0003 103N0023
Cover
b
103N2011
Cord relief
d
103N1010
Mounting accessories (102G3307) Bolt joint for one compressor Bolt joint for one compressor Snap-on for one compressor
Ø in. (mm)
Mounting accessories (102G3300) Bolt joint for one compressor Bolt joint in quantities Snap-on in quantities
Ø in. (mm)
CG.42.O2.22
CK.40.A5.22
5
/ 8 (16) / 4 (19) 5 / 8 (16) 3
5
/ 8 (16) / 8 (16) 5 / 8 (16) 5
118-1946 118-1949 118-1947 118-1917 118-1918 118-1919
July 2003
21
TL4F Standard Compressor R134a 115V 60Hz Data Sheet (Replaces CG.42.P1.22) General Compressor Connector-material
Sealing
Code number
Copper-plated steel
Aluminium caps
102G3400
Copper-plated steel
Rubber plugs
102G3402
Copper
Rubber plugs
102G
TL4F
TL4F Application
R134a
Blue stripe
3400
Barcode on white background
DANFOSS COMPRESSORS
Green background
Application
5 0 1 3 8
R
Application
LBP/MBP
Evaporating temperature range
°F (°C)
Voltage range
103 - 127 /60
Motor type
RSIR
Max. ambient temperature
°F (°C)
110 (43)
Comp. cooling at
S O F1 F2
max. ambient temperature
TL4F 115V-60Hz 1PH
-31 to 20 (-35 to -6.7)
V/Hz
110°F (43°C)
= Static cooling normally sufficient = Oil cooling = Fan cooling 1.5 m/s (compressor compartment temp. equal to ambient temperature) = Fan cooling 3.0 m/s necessary
6 0 1 3 8
THERMALLY PROTECTED
Approval mark
S
Design cu.in. (cm 3)
Displacement
0.23 (3.86)
3
Oil quantity Maximum refrigerant charge Free gas vol. in compressor housing Weight without electr ical equipment
fl.oz. (cm )
6.1 (180)
oz. (g)
14.0 (400)
fl.oz. (cm3)
54.2 (1600)
lbs. (kg)
14.7 ( 6.7)
Motor size
watt
105
LRA (rated after 4 sec.UL984) LST
A
7.0
Cut-in current LST
A
16.0
Resistance, main and start winding (77 °F) Ω
°
) 6 6 (
" 0 6 . 2
C or D
0 2
4 5
°
°
1 5
UL984/CSA-C22.2
in. (mm) A
6.42 (163)
B
6.26 (159)
Suction connector
location/I.D. in. (mm) C
0.252-0.259 (6.5±0.09)
Process connector
location/I.D. in. (mm) D
0.252-0.259 (6.5±0.09)
Discharge connector
location/I.D. in. (mm) E 0.202-0.205 (5.0+0.12/0.20) pcs.
125
(
1
7 (
" 0 8 . 2
8261
3.78"(96) 4.61"(117)
or
8.74"(222) 6.93"(176)
D C
3 2 1 8 . 5
°
0 3
A B
° °
) 5 0 1 (
) 5 0 1 (
" 3 1 . 4
Dimensions
" ) 4 ) 9 1 . 2 1
E
5.3/4.9
Approvals
Compressors on a pallet
) 5 . 0 6 (
" 8 3 . 2
4.02"(102)
Motor
Height
) 7 5 1 (
" 8 1 . 6
" 3 1 . 4
ø0.75"(19)
6.50"(165)
) 7 0 1 (
" 1 2 . 4
ø0.63"(16)
) 0 7 (
" 6 7 . 2
) 6 . 1 0 1 (
" 0 0 . 4
) 6 3 1 (
" 5 3 . 5
ø0.14"(3.6) 6.70"(170) 7.01"(178) 8.03"(204)
July 2003
22
CG.42.P2.22
CK.40.A5.22
1
July 2003
Capacity at LBP conditions (ASHRAE) Comp \ . °F Comp \ . °C TL4F
-30 -34.4 181
-20 -28.9 228
-13 -25 281
-10 -23.3 310
0 -17.8 430
Btu/h 10 -12.2 594
Capacity at MBP conditions (ASHRAE) Comp \ . °F Comp \ . °C TL4F
-30 -34.4 161
-20 -28.9 203
-13 -25 250
-10 -23.3 276
0 -17.8 383
20 -6.7 802
Btu/h 10 -12.2 529
b
20 -6.7 714
8217-2
a1
Capacity (EN 12900/CECOMAF) Comp \ . °C Comp \ . °F TL4F
-34.4 -30 43
-28.9 -20 54
-25 -13 66
-23.3 -10 73
watt -17.8 0 102
-12.2 10 141
d
-6.7 20 190
Main winding a1 Start winding N
Power consumption Comp \ . °F Comp \ . °C TL4F
-30 -34.4 64
-20 -28.9 77
watt -13 -25 87
-10 -23.3 91
0 -17.8 107
10 -12.2 124
Current consumption Comp \ . °F Comp \ . °C TL4F
-30 -34.4 1.36
-20 -28.9 1.43
-30 -34.4 2.81
-20 -28.9 2.97
-10 -23.3 1.52
0 -17.8 1.61
10 -12.2 1.72
-13 -25 3.25
-10 -23.3 3.41
0 -17.8 4.03
10 -12.2 4.79
-30 -34.4 2.50
-20 -28.9 2.64
-13 -25 2.89
-10 -23.3 3.03
0 -17.8 3.59
10 -12.2 4.26
-34.4 -30 0.66
-28.9 -20 0.70
-25 -13 0.77
July 2003
L
Winding protector
20 -6.7 5.64
Accessories
20 -6.7 5.02
Devices
W/W -23.3 -10 0.80
-17.8 0 0.95
-12.2 10 1.13
Test conditions ASHRAE (LBP) ASHRAE (MBP) Condensing temperatur e 130 °F (54.4°C) 130°F (54.4°C) Ambient and suction gas temp. 90 °F (32°C) 95°F (35°C) Liquid temperature 90°F (32°C) 115°F (46°C) Static cooling, 115V 60Hz, PTC consumption incl.
2
20 -6.7 1.84
Btu/Wh
COP (EN 12900/CECOMAF) Comp \ . °C Comp \ . °F TL4F
C
Btu/Wh
EER at MBP conditions (ASHRAE) Comp \ . °F Comp \ . °C TL4F
N
A -13 -25 1.49
EER at LBP conditions (ASHRAE) Comp \ . °F Comp \ . °C TL4F
20 -6.7 142
-6.7 20 1.33
EN12900/CECOMAF 55°C (131°F) 32°C (90°F) 55°C (131°F)
Fig.
TL4F
PTC star ting device 1 / 4 in. (6.3 mm) spades 3 / 1 6 in. (4.8 mm) spades
a1
103N0003 103N0023
Cover
b
103N2011
Cord relief
d
103N1010
Mounting accessories (102G3402) Bolt joint for one compressor Bolt joint for one compressor Snap-on for one compressor
Ø in. (mm) 5 / 8 (16) 3 / 4 (19) 5 / 8 (16)
118-1946 118-1949 118-1947
Mounting accessories (102G3400) Bolt joint for one compressor Bolt joint in quantities Snap-on in quantities
Ø in. (mm) 5 / 8 (16) 5 / 8 (16) 5 / 8 (16)
118-1917 118-1918 118-1919
CG.42.P2.22
CK.40.A5.22
July 2003
23
TLS4.5F Standard Compressor R134a 115V 60Hz Data Sheet (Replaces CD.42.D4.22) General TLS4.5F
Compressor (CU-plated steel connectors) Codenumber (small baseplate)
102G3420
Codenumber (large baseplate)
102G3421
Application
Application °F (°C)
Voltage range
3420
Barcode on white background
LBP
Evaporating temperature range
R134a SUCTION CONNECTOR
Blue stripe
Application
102G
TLS4.5F
DANFOSS COMPRESSORS
Green background
-31 to 23 (-35 to -5)
V/Hz
R
103 - 127 /60
Motor type
TLS4.5F 115V-60Hz 1PH
RSIR/CSIR
Max. ambient temperature
°F (°C)
110 (43)
S O F1
Comp. cooling at max. ambient temperature
1 1 3 8
110°F (43°C)
S
F2
= Static cooling normally sufficient = Oil cooling = Fan cooling 1.5 m/s (compressor compartment temp. equal to ambient temperature) = Fan cooling 3.0 m/s necessary
THERMALLY PROTECTED
2 1 1 3 8
Approval mark
Design cu.in. (cm 3)
Displacement
0.29 (4.63)
3
Oil quantity
fl.oz. (cm )
Maximum refrigerant charge Free gas vol. in compressor housing Weight without electr ical equipment
6.1 (180)
oz. (g)
14.0 (400)
fl.oz. (cm3)
60.7 (1790)
lbs. (kg)
) 7 5 1 (
14.7 ( 6.7)
" 8 1 . 6
Motor Motor size
watt
) 5 . 0 6 (
" 8 ) 3 6 . 6 ( 2 " 0 6 . 2
170
LRA (rated after 4 sec.UL984) LST/HST
A
12.2/14.2
Cut-in current LST/HST
A
22.6/14.2
Resistance, main and start winding (77 °F)
Ω
3.2/3.4
Approvals
°
0 2
4 5
1 5
4.02"(102)
C
" ) 4 ) 9 1 2 1 . ( 7 ( 1 "
°
°
0 8 . 2
8403
3.78"(96) 4.61"(117)
D
8.74"(222) 6.93"(176)
E
UL984/CSA-C22.2
3 2 1 8 . 5
°
0 3
A B
Dimensions Height
in. (mm) A
6.42 (163)
B
6.26 (159)
Suction connector
location/I.D. in. (mm) C 0.252-0.259 (6.5±0.09)
Process connector
location/I.D. in. (mm) D 0.252-0.259 (6.5±0.09)
Discharge connector
location/I.D. in. (mm) E 0.202-0.205 (5.0+0.12/0.20)
Compressors on a pallet
pcs.
125
° °
) 5 0 1 (
) 5 0 1 (
" 3 1 . 4
" 3 1 . 4
ø0.75"(19)
6.50"(165)
) 7 0 1 (
" 1 2 . 4
ø 0.63"(16)
ø 0.35"(9) ) 0 7 (
" 6 7 . 2
) 0 7 (
" 8 ) 5 3 3 . ( 1
" 6 7 . 2
) 6 . 1 0 1 (
" 0 0 . 4
) 6 3 1 (
" 5 3 . 5
) 0 0 1 (
" 4 9 . 3
ø0.14"(3.6) 6.70"(170) 7.01"(178) 8.03"(204)
June 2003
24
CD.42.D5.22
CK.40.A5.22
1
July 2003
Capacity at LBP conditions (ASHRAE) Comp \ . °F Comp \ . °C TLS4.5F
-30 -34.4 245
-20 -28.9 340
-13 -25 431
-10 -23.3 477
Btu/h
0 -17.8 654
10 -12.2 875
20 -6.7 1135
-17.8 0 155
-12.2 10 208
-6.7 20 269
23 -5 1225
Capacity (EN 12900/CECOMAF) Comp \ . °C Comp \ . °F TLS4.5F
-34.4 -30 58
-28.9 -20 80
-25 -13 102
LST
watt
-23.3 -10 113
-5 23 290
b 8217-2
a1
Power consumption Comp \ . °F Comp \ . °C TLS4.5F
-30 -34.4 92
watt
-20 -28.9 110
-13 -25 123
-10 -23.3 129
0 -17.8 150
10 -12.2 174
20 -6.7 199
d
23 -5 207
Main winding a1 Start winding N
Current consumption Comp \ . °F Comp \ . °C TLS4.5F
-30 -34.4 1.87
-20 -28.9 1.93
A -13 -25 1.99
-10 -23.3 2.02
0 -17.8 2.13
10 -12.2 2.27
20 -6.7 2.41
EER at LBP conditions (ASHRAE) Comp \ . °F Comp \ . °C TLS4.5F
-30 -34.4 2.66
-20 -28.9 3.10
-13 -25 3.50
23 -5 2.46
-34.4 -30 0.63
-28.9 -20 0.73
-25 -13 0.83
C
L
Btu/Wh
-10 -23.3 3.69
0 -17.8 4.34
10 -12.2 5.03
20 -6.7 5.71
-23.3 -10 0.87
-17.8 0 1.03
-12.2 10 1.19
-6.7 20 1.35
23 -5 5.91
COP (EN 12900/CECOMAF) Comp \ . °C Comp \ . °F TLS4.5F
N
Winding protector
W/W
Test conditions ASHRAE Condensing temperature 130 °F (54,4°C) Ambient and suction gas temp. 90°F (32°C) Liquid temperature 90°F (32°C) Static cooling, 115V 60Hz, PTC consumption incl.
-5 23 1.40
HST c
EN 12900/CECOMAF 55°C (131°F) 32°C (90°F) 55°C (131°F)
b 8219
a2
Accessories Devices
Fig.
TLS4.5F d
PTC star ting device 1 / 4 in. (6.3 mm) spades 3 / 16 in. (4.8 mm) spades
103N0003 103N0023
Star ting relay
a2
117U6003
Star ting capacitor 240 µF
c
117U5023
Cover
b
103N2011
Cord relief
d
103N1010
Mounting accessories Bolt joint for one compressor Bolt joint in quantities Snap-on in quantities
2
July 2003
a1
Ø in. (mm) 5 / 8 (16) 5 / 8 (16) 5 / 8 (16)
118-1917 118-1918 118-1919
c 10
12
CK.40.A5.22
13 14
Main winding
CD.42.D5.22
11
Winding protector Start winding
June 2003
25
TF3F Standard Compressor R134a 115-127V 60Hz Data Sheet (Replaces CD.42.C4.22) General Compressor
TF3F Application
Rubber plugs
102G3303
Blue stripe
Rubber plugs
102G3301
Barcode on white background
Sealing
Copper-plated steel
Aluminium caps
Copper-plated steel Copper
102G
TF3F
Code number
Connector-material
R134a
3303
3 7 2 3 8
DANFOSS COMPRESSORS
Green background
Application Application
LBP
Evaporating temperature range
°F (°C)
Voltage range
-31 to 14 (-35 to -10)
V/Hz
95 - 135 /60
Motor type
S O F1
RSIR
Max. ambient temperature
°F (°C)
110 (43)
Comp. cooling at max. ambient temperature
110°F (43°C)
F2
S
= Static cooling normally sufficient = Oil cooling = Fan cooling 1.5 m/s (compressor compartment temperature equal to ambient temperature) = Fan cooling 3.0 m/s necessary
Design 3
Displacement
cu.in. (cm )
0.19 (3.13)
3
Oil quantity Maximum refrigerant charge Free gas vol. in compressor housing Weight without electr ical equipment
fl.oz. (cm )
6.1 (180)
oz. (g)
14.0 (400)
3
fl.oz. (cm )
) 5 . 9 5 (
) 7 5 1 (
" 8 1 . 6
" ) 4 6 3 6 . ( 2 " 0 6 . 2
°
°
1 5
4.02"(102)
54.2 (1600)
lbs. (kg)
°
0 2
4 5
C or D
14.7 ( 6.7)
" ) 4 ) 9 1 2 1 . ( 7 ( 1
" 0 8 . 2
8370
3.78"(96) 4.61"(117)
or
8.90"(226) 6.93"(176)
E
Motor Motor size
watt
100
LRA (rated after 4 sec.UL984) LST
A
15.7
Cut-in current LST
A
A B
) 5 0 1 (
" 3 1 . 4
) 7 0 1 (
" 1 2 . 4
ø0.75"(19)
Dimensions
102G3303
Height
102G3301
in. (mm) A
6.42 (163)
B
6.26 (159)
locat io n/ I. D. in. (mm) C
0 .2 52 -0 .2 59 (6.5±0.09)
0.252-0.259 (6.5±0.09)
Pro ce ss co nn ecto r
locat io n/ I. D. in . (mm) D
0 .2 52 -0 .2 59 (6.5±0.09)
0.252-0.259 (6.5±0.09)
Discharge connector
location/I.D. in. (mm) E 0.202-0.205 (5.0+0.12/0.20) 0.189-0.193 (4.9+0.10/-0) pcs.
125
CD.42.C5.22
CK.40.A5.22
6.50"(165)
ø0.63"(16)
ø0.14"(3.6)
Suction co nn ecto r
Compressors on a pallet
26
° °
) 5 0 1 (
" 3 1 . 4
5.1/10.0
Approvals
3 2 1 8 . 5
°
0 3
15.7
Resistance, main and start winding (77 °F) Ω
July 2003
D C
) 0 7 (
" 6 7 . 2
) 6 . 1 0 1 (
" 0 0 . 4
) 6 3 1 (
" 5 3 . 5
6.70"(170) 7.01"(178) 8.03"(204)
1
July 2003
Capacity (ASHRAE) Comp \ . °F Comp \ . °C TF3F
-30 -34.4 69.9
Btu/h
-20 -28.9 148
-13 -25 210
-10 -23.3 239
0 -17.8 348
10 -12.2 478
14 -10 538 a2
Capacity (EN 12900/CECOMAF) Comp \ . °C Comp \ . °F TF3F
-34.4 -30 16.1
-28.9 -20 34.7
watt
-25 -13 49.5
-23.3 -10 56.4
-17.8 0 82.2
-12.2 10 113
-13 -25 71.0
-10 -23.3 76.5
0 -17.8 93.6
10 -12.2 109
-10 14 127
Power consumption Comp \ . °F Comp \ . °C TF3F
-30 -34.4 37.0
-20 -28.9 57.7
-30 -34.4 1.10
8230
watt
d
14 -10 116
Current consumption Comp \ . °F Comp \ . °C TF3F
b
a2
A
-20 -28.9 1.20
-13 -25 1.28
-10 -23.3 1.31
0 -17.8 1.43
10 -12.2 1.54
14 -10 1.59
10 12
Main winding
EER (ASHRAE) Comp \ . °F Comp \ . °C TF3F
-30 -34.4 1.89
-34.4 -30 0.44
Start winding Thermostat
14
Btu/Wh -20 -28.9 2.56
-13 -25 2.96
-10 -23.3 3.13
0 -17.8 3.72
10 -12.2 4.37
14 -10 4.65
-23.3 -10 0.74
-17.8 0 0.88
-12.2 10 1.03
-10 14 1.10
COP (EN 12900/CECOMAF) Comp \ . °C Comp \ . °F TF3.F
11 13
-28.9 -20 0.61
Motor protector
W/W
-25 -13 0.70
Test conditions Condensing temperature Ambient and suction gas temp. Liquid temperature Static cooling, 115V 60Hz
M
ASHRAE 130 °F (54,4°C) 90°F (32°C) 90°F (32°C)
EN 12900/CECOMAF 55°C (131°F) 32°C (90°F) 55°C (131°F)
Accessories Devices
Fig.
Star ting relay (protector incl.) Protector 3 / 4"
Texas Instr.
MRP61GL-6
Cover
b
117U1021
Cord relief
d
117U0349
Ø in. (mm) 5 / 8 (16) 3 / 4 (19) 5 / 8 (16)
118-1946 118-1949 118-1947
Mounting accessories Bolt joint for one compressor Bolt joint for one compressor Snap-on for one compressor
2
July 2003
a2
TF3F 117U4100
CD.42.C5.22
CK.40.A5.22
July 2003
27
TF3.5F Standard Compressor R134a 115-127V 60Hz Data Sheet (Replaces CG.42.Q1.22) General Compressor Connector-material
Sealing
Copper-plated steel
Aluminium caps
Copper-plated steel
Rubber plugs
102G3304
Copper
Rubber plugs
102G3302
102G
TF3.5F
TF3.5F Application
Code number
R134a
Blue stripe
3304
Barcode on white background
7 2 3 8
DANFOSS COMPRESSORS
Green background
Application
R
Application
LBP
Evaporating temperature range
°F (°C)
Voltage range
-31 to 14 (-35 to -10)
V/Hz
95 - 135 /60
Motor type
S O F1
RSIR
Max. ambient temperature
°F (°C)
110 (43)
Comp. cooling at max. ambient temperature
110°F (43°C)
F2
S
= Static cooling normally sufficient = Oil cooling = Fan cooling 1.5 m/s (compressor compartment temp. equal to ambient temperature) = Fan cooling 3.0 m/s necessary
Displacement
cu.in. (cm 3)
0.22 (3.59)
Oil quantity
fl.oz. (cm 3)
6.1 (180)
oz. (g)
14.0 (400)
Maximum refrigerant charge Free gas vol. in compressor housing Weight without electr ical equipment
3
fl.oz. (cm )
" 8 1 . 6
C or D
16.5 ( 7.5)
Approval mark
°
0 2
4 5
°
°
1 5
4.02"(102)
60.6 (1790)
lbs. (kg)
" ) 4 6 3 6 . ( 2 " 0 6 . 2
2 7 2 3 8
THERMALLY PROTECTED
) 5 . 9 5 (
) 7 5 1 (
Design
TF3.5F 115V-60Hz 1PH
" ) ) 4 9 1 2 1 . ( 7 ( 1
" 0 8 . 2
8370
3.78"(96) 4.61"(117)
or
8.90"(226) 6.93"(176)
D C E
Motor
3 2 1 8 . 5
°
Motor size
watt
0 3
135
LRA (rated after 4 sec.UL984) LST
A
18.9
Cut-in current LST
A
18.9
Resistance, main and start winding (77 °F) Ω
A B
° °
) 5 0 1 (
) 5 0 1 (
" 3 1 . 4
" 3 1 . 4
) 7 0 1 (
" 1 2 . 4
3.8/7.8
Approvals
UL984/CSA-C22.2
ø0.75"(19)
6.50"(165)
ø0.63"(16)
ø0.14"(3.6)
Dimensions
102G3304
Height
in. (mm) A
6.81 (173)
B
6.65 (169)
Suction co nn ecto r
locat io n/ I. D. in. (mm) C
0 .2 52 -0 .2 59 (6.5±0.09)
0.252-0.259 (6.5±0.09)
Pro ce ss co nn ecto r
locat io n/ I. D. in . (mm) D
0 .2 52 -0 .2 59 (6.5±0.09)
0.252-0.259 (6.5±0.09)
Discharge connector
location/I.D. in. (mm) E 0.202-0.205 (5.0+0.12/0.20) 0.189-0.193 (4.9+0.10/-0)
Compressors on a pallet
July 2003
28
102G3302
pcs.
) 0 7 (
" 6 7 . 2
) 6 . 1 0 1 (
" 0 0 . 4
) 6 3 1 (
" 5 3 . 5
6.70"(170) 7.01"(178) 8.03"(204)
125
CG.42.Q2.22
CK.40.A5.22
1
July 2003
Capacity (ASHRAE) Comp \ . °F Comp \ . °C TF3.5F
-30 -34.4 133
Btu/h
-20 -28.9 205
-13 -25 270
-10 -23.3 303
0 -17.8 426
10 -12.2 581
14 -10 651 a2
Capacity (EN 12900/CECOMAF) Comp \ . °C Comp \ . °F TF3.5F
-34.4 -30 32
-28.9 -20 49
watt
-25 -13 64
-23.3 -10 72
-17.8 0 101
-12.2 10 138
-13 -25 89
-10 -23.3 93
0 -17.8 108
10 -12.2 123
-10 14 155
Power consumption Comp \ . °F Comp \ . °C TF3.5F
-30 -34.4 66
-30 -34.4 1.55
-20 -28.9 1.60
8230
watt
-20 -28.9 79
d
14 -10 129
Current consumption Comp \ . °F Comp \ . °C TF3.5F
b
a2
A -13 -25 1.64
-10 -23.3 1.66
0 -17.8 1.73
10 -12.2 1.82
14 -10 1.86
10 12
Main winding
EER (ASHRAE) Comp \ . °F Comp \ . °C TF3.5F
-30 -34.4 2.03
-34.4 -30 0.48
Start winding Thermostat
14
Btu/Wh -20 -28.9 2.59
-13 -25 3.04
-10 -23.3 3.25
0 -17.8 3.96
10 -12.2 4.73
14 -10 5.03
-23.3 -10 0.77
-17.8 0 0.94
-12.2 10 1.12
-10 14 1.20
COP (EN 12900/CECOMAF) Comp \ . °C Comp \ . °F TF3.5F
11 13
-28.9 -20 0.62
Motor protector
W/W
-25 -13 0.72
Test conditions Condensing temperature Ambient and suction gas temp. Liquid temperature Static cooling, 115V 60Hz
M
ASHRAE 130 °F (54,4°C) 90°F (32°C) 90°F (32°C)
EN 12900/CECOMAF 55°C (131°F) 32°C (90°F) 55°C (131°F)
Accessories Devices
Fig.
Star ting relay (protector incl.) Protector 3 / 4"
Texas Instr.
Protector 3 / 4"
Electrica
a2
MRP57JK-6 T 0727 / 06
Cover
b
117U1021
Cord relief
d
117U0349
Ø in. (mm) 5 / 8 (16) 3 / 4 (19) 5 / 8 (16)
118-1946 118-1949 118-1947
Mounting accessories Bolt joint for one compressor Bolt joint for one compressor Snap-on for one compressor
2
July 2003
TF3.5F 117U4122
CG.42.Q2.22
CK.40.A5.22
July 2003
29