OIL AND NATURAL GAS CORPORATION LIMITED
Client:
L&T, E&C DIVISION
ADDITIONAL PROCESS UNITS
Contractor : Larsen & Toubro Limited,
Doc. No. : 5015-LT-00-EL-04-CA-0003 Rev. : 00
E&C DIVISION, Mumbai
CAPACITOR SIZING CALCULATION OWNER
: OIL AND NATURAL GAS CORPORATION LIMITED, URAN
UNIT
: ADDITIONAL PROCESS UNITS
L&T JOB NO.
: 5015
A
DOC. CATEGORY: DOCUMENT STATUS
□
FINAL FOR CODE – 1
1st
2nd
□
R
I
REVIEW CODE 1
REVIEWED, NO COMMENTS.WORK TO PROCEED.
2
REVIEWED AS COMMENTED. WORK SHALL PROCEED WITH FABRICATION / MANUFACTURING TAKING CARE AND INCORPORATING OWNER /PMC COMMENTS.
3
MAJOR NON CONFORMANCE AND DEVIATIONS TO CONTRACT SPECIFICATIONS. RESUBMIT FOR REVIEW AFTER INCORPORATING COMMENTS.
1. SCOPE The scope of this document covers capacitor sizing calculation to be installed in APU Substation for Uran APU project.
2. REFERENCE DOCUMENTS
Engineering Design Basis Electrical
: V002-00-50-50-DB-001, Rev 1
Design Philosophy for Electrical Facilities
: 6-51-0099 Rev 04
Job Specification Electrical
: V002-00-50-50-SP-02-0
Overall Electrical Load Analysis
: 5015-LT-00-EL-03-CA-0001 Rev 0
Overall key single line Diagram
: 5015-LT-00-EL-00-SL-0002 Rev 0
3. CAPACITOR SIZING CALCULATION The kW and kVA loading on the HV switchboards HT-201 under normal running load as per overall electrical load analysis are as follows
KW 21244.6
NORMAL RUNNING LOAD/ MAXIMUM DEMAND LOAD KVAR KVA P.F. 11378.7 24100 0.881
The present power factor of 6.6kV bus is calculated as cos Ø1 = (kW/kVA) = 21244.6/24100=0.881 The required Power Factor as per ITB is 0.9. Hence cos Ø 2 = 0.9 Total MW considering 15% future load growth = 21.2446* 1.15 = 24.43 MW