BFK BF K 620A Controlle ntroller Oper Operation M anua nual T he contents are inte intended for for qu quick ick guidan idance and supplem lement to the the user wh who is using ing BFK 620A co controlle troller. Pleaseread the standar standard manual manual for mor mor e detai detaills.
Comm. Address Startup mode Press Unit Temperature Unit Send SMS count
1
1.18 1.19 1.20 1.21
Engine ECU type Display contrast Auto scroll time Firmware update
Preset
NO.
I tems
Preset
90% not used 115% not used 48.0Hz not used 55.0Hz 57.0Hz not used 100%
2.11 2.12 2.13 2.14 2.15 2.16 2.17 2.18 2.19
Alarm delay Overcurrent level Overcurrent delay Overcurrent action Loading Voltage Loading Frequency GEN. ON delay GCB closing time Test mode
5s 100% 1s
Preset
NO.
I tems
0ÿ MANÿ 0(Bar) 0(! ) not used
Preset
00000000000 00000000000 00000000000
Initial password is 2213. not used 5 not used
2. GENERATOR NO.
I tems
2.1 2.2 2.3 2.4 2.5 2.6 2.7 2.8 2.9 2.10
GEN-V under preALM GEN- V under Alarm GEN-V over preALM GEN-V over Alarm GEN-Hz under preALM GEN-Hz under Alarm GEN-Hz over preALM GEN-Hz over Alarm KW Overload preALM KW Overload Alarm
0(warning) 95% 48.0Hz 5s 5s 1ÿ with loadÿ
NGINE 3.E NO.
I tems
3.1 Rated speed 1500 RPM 3.20 Pre-heat mode 3.2 MPU input 0 (NO) 3.21 Pre-heat time 3.3 Fly wheel teeth 120 3.22 Safety-on delay 3.4 Set pickup now 3.23 Cool down mode 3.5 Pair of Poles 2 3.24 Cool down time 3.6 Fuel mode 0(N.C. type) 3.25 Stop delay 3.7 T-sensor type 3 3.26 Under SP preALM 3.8 P-sensor type 4 3.27 Under SP Alarm 3.9 Start delay 10s 3.28 Over SP preALM Wuxi Baifa Power Ltd,China http;//www.baifapower.com.com Tel:+086510-85345555
Preset
1 3s 10s 0(full speed) 300s 20s 1440 RPM not used 1600 RPM Fax:+086510-85343333
3.10 3.11 3.12 3.13 3.14 3.15 3.16 3.17 3.18 3.19
Crank attempt Crank time Crank time add Crank rest Crank cutout RPM Crank cutout volt Crank cutout ALT-V Crank cutout Oil-P Cutout P-delay Idle time
3 times 5s not used 10s 300 RPM 85% not used 1.0 Bar not used not used
A-sen 1 under level A-sen 1 under act. A-sen 1 over level A-sen 1 over act. A-sensor 2 use A-sensor 2 type Pre-heat ON Pre-heat OFF A-sen2 under level A-sen2 under act. A-sen2 over level A-sen2 over act. User relay 1 User relay 2 User relay 3 User relay 4 User relay 5
1710 RPM 1.4 Bar 1.1 Bar 92! 100! 8.0V 28.0V 8.0V 0(NO)
not used 0 not used 0 1 3 20! 70! not used 0 not used 0 20 11 2 3 5
6. SPEED CONTROL NO.
I tems
Preset
NO.
I tems
Preset
6.1 6.2 6.3 6.4
Proportional gain Integral gain Derivative ratio Deadband
10.0 1.0s 1.0s 0.2Hz
6.5 6.6 6.7
Time pulse minimum Raise rate Lower rate
0.2s 5% / s 5% / s
M anu notes: %ÏVOLTAGE TYPE Code
voltage input type
Code
1 4
3 phases 4 wires star Single phase 3 wires
2 5
voltage input type
3 phrases 4 wires angle Single phase 2 wires
Code
3
voltageinput type
3 phases 3 wires
%ÏTYPES OF SENSORS Code T-sensor Type
1 2 3 4 5 6 7
close for high temperature (D-input) open for high temperature (D-input) VDO 120! VDO 150! Datcon Murphy Pt100
P-sensor Type
close for low oil pressure (D-input) open for low oil pressure (D-input) VDO 5 bar VDO 10 bar Datcon 7 bar Murphy 7 bar Note: 7~13 are defined by user. More details are in Operation
Wuxi Baifa Power Ltd,China http;//www.baifapower.com.com Tel:+086510-85345555 Fax:+086510-85343333
Note: 8~14 are defined by user. More details are in Operation Manual.
Under frequency pre-alarm Over frequency pre-alarm
GEN. under voltage pre-alarm GEN. over voltage pre-alarm
49 50
GEN. under voltage alarm GEN. over voltage alarm
Output mode defined
P-Sensor open alarm Config. D-input1 active Config. D-input2 active Config. D-input3 active Config. D-input4 active Config. D-input5 active Config. D-input6 active Config. D-input7 active Buzzer sounds alarm Air flap control Reserved Test without load mode Test with load mode Emergency stop
65
Reserved
66
Cooling down
KW overload alarm
Wuxi Baifa Power Ltd,China http;//www.baifapower.com.com Tel:+086510-85345555 Fax:+086510-85343333
!c . TY PICAL WIRI NG DIA GRAM Note:
Terminal #40 of controller must be electrically connected with system’s FGND very well; in addition the cross section 2
area of the connected wire should not be less than 2.5mm . Otherwise it will impact the correctness of electrical measuring, even damage the controller. If you want more technical support, please call Service Hotline: 0510-85345555-178 Wuxi Baifa Power Ltd,China http;//www.baifapower.com.com Tel:+086510-85345555 Fax:+086510-85343333