Find this product online at www.eland.co.uk | Electrical Cable | Aluminium Conductors
A A AC Conductor Conductor Eland Product Group
A4A
Application AAAC is used as a bare overhead conductor for power transmission and distribution lines, on aerial circuits that require a larger mechanical resistance than AAC, and a better corrosion resistance than ACSR. The sag characteristics and the strength-to-weight ratio of AAAC is better than AAC / ACSR.
Standards ASTM - B 399 Metric Units, ASTM - B 231, TS IEC 1089, DIN 48201, BS 215, UNE 21.018
Technical Data Conductor
All Aluminium Alloy
Dimensions ASTM Sizes Code
Size KCM
Stranding
Diameter
Cross Sectional Area
inches
Weight 1000ft Lbs
Rated Strength Lbs
Resistance Ohms/1000ft
Current Rating Amps
Size
Sq In Individual Wires
Total
D C at 20ºC
AC at 75º C
ACSR with Equiv.Diam. Stranding
AL/Stl
AKRON
30.58
7
0 .0661
0.198
0.024
28 .7
1.110
0.6590
0.7850
107
6
6\1
ALTON
48.69
7
0.0 834
0. 250
0.0382
45.7
1.760
0.4140
0.4930
143
4
6\1
AMES
77.47
7
0.1052
0. 316
0.0 608
72.7
2. 8 00
0. 260 0
0. 310 0
191
2
6\1
AZUSA
123.3
7
0.1327
0.3 98
0.0 968
115 .7
4 .4 6 0
0.1630
0 .1950
256
1/ 0
6\1
ANAHEIM 155.4
7
0.1490
0.447
0.1221
145 .9
5 . 390
0.1300
0 .1540
296
2/ 0
6\1
AMHERST 195.7
7
0.1672
0. 502
0.1537
183 .7
6 .790
0.1030
0.1230
342
3/ 0
6\1
ALLIANCE 246.9
BUTTE
CANTON
7
0 .1878
0.56 3
0.1939
231.8
8 .560
0.0 816
0.0 973
395
4/0
6\1
312.8
19
0.1283
0.642
0.2456
293.6
11.0 00
0 .0644
0 .0769
460
266 . 8
26\7
394.5
19
0.1441
0.721
0. 3098
370. 3
13 . 30 0
0.0511
0.0 610
532
336 .4
26\7
59 0
3 97.5
26\7
CAIRO
465.4
19
0 .1565
0.783
0. 3655
436 . 9
15.6 00
0 .0433
0 .0518
DARIEN
559.5
19
0.1716
0. 858
0.4394
525. 2
18. 800
0.0360
0.0431
663
477. 0
2617
ELGIN
652.4
19
0.1853
0. 927
0. 5124
612.4
21. 900
0.0309
0.0371
729
556 . 5
2617
FLINT
740.8
37
0.1415
0. 991
0. 5818
695. 5
24.400
0. 0272
0.0327
790
636 .0
26\7
927.2
37
0.1583
1.108
0.7282
870.4
30. 500
0. 0217
0.0263
908
795. 0
26\7
GREELY
1. Resistance is calculated using ASTM standard increments of stranding, and metal conductivity of 52.5% IACS. AC resistance at 60 Hz. 2. Current ratings are based on 75ºC conductor temperature, 250ºC ambient, 2 ft/s wind, 96/watts/sq.foot sun, 0.5 coefficients of emissivity and absorption.
0 1 0 1 . 1 0 E U S S I
[email protected] www.eland.co.uk www.eland.co.uk tel tel +44 (0)20 7241 8787 fax +44 (0)20 (0 )20 724 7241 1 8700
PAGE 1 OF 5
Find this product online at www.eland.co.uk | Electrical Cable | Aluminium Conductors ASTM Sizes Conductor Size
Area
c mil
mm2
Number and Diameter of Wires
inch
Overal Diameter of Conductor
mm
inch
Linear Weight
Rate Strengyh
lb
mm
kg/km
Maximum Resistance DC at 20ºC km
daN
Ohms/Km
66360
33.62
7 x 0.0974
7 x 2.47
0.291
7.41
93
1068
2400
0.9942
105600
53.50
7 x 0.1228
7 x 3.12
0.368
9.36
148
1697
3815
0.6256
133100
67.44
7 x 0.1379
7 x 3.50
0.413
10.50
187
2052
4612
0.4959
167800
85.02
7 x 0.1548
7 x 3.93
0.464
11.80
235
2586
5810
0.3936
211600
107.21
7 x 0.1739
7 x 4.42
0.522
13.26
296
3263
7332
0.3119
400000
202.68
19 x 0.1451
19 x 3.68
0.724
18.40
560
5974
13426
0.1650
450000
228.00
19 x 0.1539
19 x 3.91
0.769
19.55
630
6719
15100
0.1487
500000
253.35
19 x 0.1622
19 x 4.12
0.811
20.60
700
4764
16774
0.1321
550000
278.68
37 x 0.1219
37 x 3.10
0.854
21.70
769
8380
18835
0.1202
600000
304.00
37 x 0.1273
37 x 3.23
0.890
22.60
839
9138
20535
0.1102
650000
329.35
37 x 0.1325
37 x 3.36
0.926
23.52
910
9494
21336
0.1016
700000
354.70
37 x 0.1375
37 x 3.49
0.962
24.43
978
10220
22967
0.0944
750000
380.00
37 x 0.1424
37 x 3.61
0.995
25.27
1050
10940
24630
0.0880
800000
405.36
37 x 0.1470
37 x 3.73
1.020
26.10
1118
11680
26248
0.0826
900000
456.00
37 x 0.1560
37 x 3.96
1.090
27.72
1260
13150
29551
0.0733
1000000
506.70
37 x 0.1644
37 x 4.17
1.150
29.20
1400
14610
32832
0.0660
ASTM Sizes Metric Units Code
Sizes KCM
Nominal Size
Stranding
Weight 1
Diameter
mm2
inches
Rated Strength2
Resistance3
Ohms/km
Current Rating4 Amps
Size
mm2
kg Individual Wires
Total
DC at 20ºC
AC at 75ºC
ACSR with Equiv. Diam. Stranding
Al/Stl
AKRON
30.58
15.50
7
1.679
5.04
42.7
503
2.1600
2.5700
107
13.30
6/1
ALTON
48.69
24.67
7
2.118
6.36
68.0
798
1.3600
1.6200
143
21.15
6/1
AMES
77.47
39.25
7
2.672
8.02
108.2
1270
0.8530
1.0200
191
33.63
6/1
AZUSA
123.3
62.48
7
3.371
10.11
172.2
2023
0.5360
0.6390
256
53.31
6/1
ANAH EI M
155.4
78.74
7
3.785
11.35
217.1
2445
0.4250
0.5090
296
67.44
6/1
AM HE RST
195.7
99.16
7
4.247
12.74
273.3
3080
0.3380
0.4030
342
85.03
6/1
246.9
125.10
7
4.770
14.31
344.9
3883
0.2680
0.3190
395
107.22
6/1
BUTTE
312.8
158.50
19
3.259
16.29
436.9
4989
0.2110
0.2520
460
135.19
26/7
CANTON
394.5
199.90
19
3.660
18.30
551.1
6033
0.1680
0.2000
532
170.46
26/7
CAIRO
465.4
235.80
19
3.975
19.88
650.0
7076
0.1420
0.1700
590
201.42
26/7
DARIEN
559.5
283.50
19
4.359
21.79
781.5
8527
0.1180
0.1420
663
241.70
26/7
ELGIN
652.4
330.60
19
4.707
23.53
911.3
9934
0.1010
0.1220
729
281.98
26/7
FLINT
740.8
375.40
37
3.594
25.16
1035.0
11068
0.0892
0.1070
790
322.27
26/7
GR EELY
927.2
469.80
37
4.021
28.15
1295.0
13834
0.0713
0.0863
908
402.83
26/7
ALLIANCE
1. Weights are calculated using ASTM standard increments of stranding, 2. Rated strengths are calculated by ASTM methods and converted to metric units after rounding. 3. Resistance is calculated using ASTM sta ndard increments of stranding, and metal conductivity of 52.5% IACS, AC resistance at 60 Hz. 4. Current ratings are based on 751 C conductor temperature, 250C ambient, 0.61 m/s wind, 1033 watts/sq. meter sun, 0.5 coefficients of emissivily and absorption.
[email protected] www.eland.co.uk tel +44 (0)20 7241 8787 fax +44 (0)20 7241 8700
PAGE 2 OF 5
Find this product online at www.eland.co.uk | Electrical Cable | Aluminium Conductors
ASTM Sizes Metric Units Conductor Size mm2
Number of Wires
Diameter of Wire mm
Overall Diameter of Conductor
Linear Weight
Rated Strength daN
Maximum Resistance DC at 20ºC Km
kg/km
mm
Ohms/km
40
7
2.70
8.10
110
1270
0.8370
50
7
3.02
9.06
138
1590
0.6700
63
7
3.39
10.17
173
1910
0.5320
80
7
3.81
11.43
220
2410
0.4180
100
7
4.26
12.78
275
3020
0.3350
112
7
4.51
13.53
308
3380
0.3000
125
19
2.89
14.45
343
3830
0.2680
140
19
3.06
15.30
385
4290
0.2400
160
19
3.27
16.35
440
4670
0.2100
180
19
3.47
17.35
494
5260
0.1860
200
19
3.66
18.30
550
5860
0.1670
224
19
3.87
19.35
615
6550
0.1500
250
19
4.09
20.45
686
7310
0.1340
280
37
3.10
21.70
770
8390
0.1200
315
37
3.29
23.03
865
9020
0.1060
355
37
3.50
24.50
975
10200
0.0943
400
37
3.71
25.97
1098
11500
0.0837
450
37
3.94
27.58
1235
12900
0.0744
500
37
4.15
29.05
1372
14300
0.0470
560
37
4.39
30.73
1537
16100
0.0598
630
37
4.66
32.62
1730
18100
0.0531
British Sizes Code
N
Rated Strength1
lbf
kg
Ohm / km
-
3714
379
835
BOX
5960
608
ACACIA
7606
776
ALMOND
Maximum Resistance DC at 20º C2
Ohm / 1000ft
Current Rating3 Temperate
Tropical
Amp
Amp
73
2.8700
0.8730
90
1340
1.7900
0.5440
121
98
1710
1.4000
0.4260
140
114
9563
975
2150
1.1100
0.3390
162
131
CEDA
11253
1148
2530
0.9440
0.2880
180
145
-
13433
1370
3020
0.7940
0.2420
200
162
FIR
15168
1547
3410
0.7000
0.2130
217
175
HAZEL
18993
1937
4270
0.5590
0.1700
250
201
PINE
21840
2227
4910
0.4670
0.1420
279
224
-
25576
2608
5750
0.3980
0.1210
309
247
WILLOW
27355
2790
6150
0.3730
0.1140
322
258
-
29401
2998
6610
0.3470
0.1060
337
270
-
33093
3375
7440
0.3080
0.0938
343
290
OAK
36207
3692
8140
0.2820
0.0859
384
307
-
36563
3729
8220
0.2820
0.0860
385
307
MULBERRY
46704
4763
10500
0.2220
0.0676
448
356
ASH
53376
5443
12000
0.1850
0.0565
501
398
ELM
62272
6350
14000
0.1590
0.0480
553
438
POPLAR
72058
7348
16200
0.1400
0.0427
598
473
-
81398
8301
18300
0.1240
0.0337
647
511
SYCAMORE
91184
9299
20500
0.1110
0.0377
694
547
UPAS
104528
10659
23500
0.0925
0.0282
776
610
-
121875
12428
27400
0.0794
0.0242
854
669
YEW
138333
14107
31100
0.0698
0.0213
925
723
1. Rated strengths are calculated by ASTM methods and converted to metric units after rounding. 2. Resistance is calculated using ASTM standard increments of stranding, and metal conductivity of 52.5% IACS. 3. Current ratings are based on 50 Hz AC, 75ºC conductor temperature, and 0.61 m/s (2 ft/s) wind, 0.5 coefficients of emissivity and absorption, Temperate rating - 250ºC ambient, 1000 watts/sq. meter sun, Tropical rating - 400ºC ambient, 1200 watts/sq. meter sun.
[email protected] www.eland.co.uk tel +44 (0)20 7241 8787 fax +44 (0)20 7241 8700
PAGE 3 OF 5
Find this product online at www.eland.co.uk | Electrical Cable | Aluminium Conductors British Sizes Code
Nominal Al Area
mm2
Equivalent Cu Area
mm2
Stranding and Wire
Approximate Overall Diameter
inch 2
mm
0.010
7/1.47
7/0.0574
4.41
inch
-
-
6.45
BOX
-
9.68
0.015
7/1.85
7/0.0727
ACACIA
-
12.9
0.020
7/2.08
7/0.0822
mm
Weight 1
Total Area
mm2
inch
inch 2
Kg/Km
32.2
lb/M ft
0.174
11.7
0.01812
21.7
5.55
0.219
18.8
0.02908
51.7
34.7
6.24
0.246
21.9
0.03711
66.1
44.4
ALMOND
25
16.1
0.025
7/2.34
7/0.0921
7.02
0.276
30.1
0.04666
82.9
55.7
CEDA
30
19.4
0.030
7/2.54
7/1000
7.62
0.300
35.5
0.05498
97.8
65.7
-
40
22.6
0.035
7/2.77
7/1091
8.31
0.327
42.2
0.06543
116.4
78.2
FIR HAZEL
50
25.8
0.040
7/2.95
70161
8.85
0.348
47.8
0.07415
131.8
88.6
100
32.3
0.050
7/3.30
7/0.1299
9.90
0.390
59.9
0.09280
165.0
110.9
PINE
-
38.7
0.060
7/3.61
70422
10.83
0.426
71.7
0.11110
197.7
132.9
-
-
45.2
0.070
7/3.91
7/1539
11.73
0.462
84.1
0.13030
231.6
155.6
WILLOW
150
48.4
0.075
7/4.04
7/1591
12.12
0.477
89.8
0.13920
247.5
166.3
-
175
51.6
0.080
7/4.19
7/1650
12.57
0.495
96.5
0.14960
266.2
178.9
-
300
58.1
0.090
7/4.45
7/0.1751
13.35
0.526
108.8
0.16860
299.8
201.5
OAK
-
64.5
0.100
7/4.65
70831
13.95
0.549
118.9
0.18430
327.8
220.3
-
-
80.6
0.100
19/2.82
190111
14.10
0.555
118.8
0.18410
327.6
220.2
MULBERRY
-
96.8
0.125
19/3.18
19/1253
15.90
0.626
151.1
0.23420
416.7
280.0
ASH
-
113.0
0.150
19/3.48
19/1370
17.40
0.685
180.7
0.28010
498.1
334.8
ELM
-
129.0
0.175
19/3.76
19/1481
18.80
0.740
211.0
0.32710
582.1
391.2
POPLAR
-
145.0
0.200
37/2.87
37/1129
20.09
0.791
239.0
0.37050
658.8
442.7
-
-
161.0
0.225
37/3.05
37/1202
21.35
0.841
270.8
0.41970
746.7
501.8
SYCAMORE
-
194.0
0.250
37/3.23
37/0.1271
22.61
0.890
303.0
0.46970
834.9
561.1
UPAS
-
226.0
0.300
37/3.53
37/1390
24.71
0.973
362.1
0.56130
998.6
671.1
-
-
258.0
0.350
37/3.81
370500
26.47
1.050
421.8
0.65380
1163.0
781.5
YEW
-
-
0.400
37/4.06
370600
28.42
1.119
479.9
0.74390
1323.0
889.2
1. Weights are calculated using ASTM standard increments of stranding.
French Sizes Code
Area mm2
Number of Wires
Diameter of Wires
Overall Diameter Tensile Strength of Conductor mm of Wire
mm
Rated Strength of Conductor
hbar
daN
Maximum Resistance DC at 20ºC km
Linear Weight
kg/km
Elasticity ModuCoefficient of lus * hbar Linear Expansion
* /oc
ASTER 22
21.99
7
2.00
6.00
32.4
710
1.5000
60.2
6200
23.10-6
ASTER 34.4
34.36
7
2.50
7.50
32.4
1105
0.9580
94.1
6200
23.10-6
ASTER 54.6
54.55
7
3.15
9.45
32.4
1755
0.6030
149.0
6200
23.10-6
ASTER 75.5
75.54
19
2.25
11.25
32.4
2430
0.4380
208.0
6000
23.10-6
ASTER 117
116.98
19
2.80
14.00
32.4
3765
0.2830
322.0
6000
23.10-6
ASTER 148
168.01
19
3.15
15.75
32.4
4765
0.2240
407.0
6000
23.10-6
ASTER 181.6
181.62
37
2.50
17.50
32.4
5845
0.1830
500.0
5700
23.10-6
ASTER 228
227.83
37
2.80
19.60
32.4
7340
0.1460
627.0
5700
23.10-6
ASTER 288
288.34
37
3.15
22.05
32.4
9280
0.1150
794.0
5700
23.10-6
ASTER 366
366.22
37
3.55
24.85
32.4
11785
0.0905
1009.0
5700
23.10-6
ASTER 570
570.22
61
3.45
31.05
32.4
18360
0.0583
1574.0
5400
23.10-6
ASTER 851
850.66
91
3.45
37.95
32.4
27390
0.0391
2354.0
5250
23.10-6
ASTER 1144
1143.51
91
4.00
44.00
31.9
36260
0.0292
3164.0
5250
23.10-6
ASTER 1600
1595.93
127
4.00
52.00
31.9
50640
0.0206
4425.0
5050
23.10-6
* These values are given for information only
[email protected] www.eland.co.uk tel +44 (0)20 7241 8787 fax +44 (0)20 7241 8700
PAGE 4 OF 5
Find this product online at www.eland.co.uk | Electrical Cable | Aluminium Conductors German Sizes Conductor Size
Alloy Area
mm2
mm2
Number of Wires
Diameter
mm
Overall Diameter of Conductor
Linear Weight kg/km
Rated Strength
daN
mm
Maximum Resistance DC at 20ºC km
Ohms/Km
16
15.89
7
1.70
5.1
43
444
2.09100
25
24.26
7
2.10
6.3
66
677
1.37030
35
34.36
7
2.50
7.5
94
690
0.96690
50
49.48
7
3.00
9.0
135
1382
0.67140
50
48.35
19
1.80
9.0
133
1350
0.69050
70
65.81
19
2.10
10.5
181
1838
0.50730
95
93.27
19
2.50
12.5
256
2605
0.35790
120
116.99
19
2.80
14.0
322
3268
0.28540
150
147.11
37
2.25
15.8
406
4109
0.22740
185
181.62
37
2.50
17.5
500
5073
0.18420
240
242.54
61
2.25
20.3
670
6774
0.13830
300
299.43
61
2.50
22.5
827
8363
0.11200
400
400.14
61
2.89
26.0
1104
11176
0.08380
500
499.83
61
3.23
29.1
1379
13960
0.06709
625
626.20
91
2.96
32.6
1732
17490
0.05400
800
802.09
91
3.35
36.9
2218
22402
0.04180
1000
999.71
91
3.74
41.1
2767
27922
0.03350
1. Weights are calculated using ASTM standard increments of stranding.
The information contained within this datasheet is for guidance only. When selecting accessories such as cleats, glands, etc please note that actual cable dimensions may vary due to manufacturing tolerances.
[email protected] www.eland.co.uk tel +44 (0)20 7241 8787 fax +44 (0)20 7241 8700
PAGE 5 OF 5