How the control function is designed in SIPROTEC 5 To understand the basic principles for user defined functions Where the differences are compared to SIPROTEC 4 How to use DIGSI 5 for these purposes How the SIPROTEC 5 devices work in a Substation Automation Environment
Signal Types (1/2) What do I have to do if I need a…. SIPROTEC 4 Information Catalog
SIPROTEC 5 Library
Information type SPS (Single Point Status) Protocol text or „transient indication“ (Wischermeldung) is a setting No differentiation external / internal signal
Not necessary any longer Circuit breaker or disconnect switch „status only“
SPS (if source = BI or CFC), SPC (if source = Communication) Binary Counter Reading BCR Not necessary any longer
Grouping of signals in „User Defined Function Group“ (2/2)
Routing of command output to relays Same options for both types! Off: Set relay when command is „off“ On: Set relay when command is „on“ Cc: Common contact; set relay when command is „off“ or „on“ BF: Busy Flag; set relay when command is „off“ or „on“, starting with „select“ and ending with end of feedback monitoring time
Select Single Line Template Create circuit breaker and disconnect switch objects in the device Connect switches and CTs / VTs in Single Line to device objects Engineering of breaker and disconnect switch:
Connect to BI / BO Create interlocking logic in CFC Route position information to event log
Create Display Page from Single Line Editor picture
Use GOOSE messages for interlocking Show complete settings and properties of switches (for example chatter blocking, filter times) Create new single point / double point indications