UPS Sizing Calculations
Home
UPS Sizing Calculations
power plantFull description...
Author:
knx175
2 downloads
351 Views
49KB Size
Report
DOWNLOAD .PDF
Recommend Documents
UPS Sizing Calculation_Emerson
UPS Sizing calculation for Design Electrical EngineersFull description
Arar Ups Sizing
UPS sizing calculationFull description
UPS & Battery Sizing
sdk
CT Sizing Calculations
xfgSFFull description
Valve Sizing Calculations
PSV Sizing Calculations
RELIEF VALVE SIZING CALCULATIONS
Steam Line Sizing Calculations
Pipe Sizing and Calculations
pipingFull description
Filter Press Sizing Calculations.
Filter Press Sizing Calculations.Full description
UPS and Battery Sizing Calculation
UPS,Battery,InverterFull description
AC UPS Sizing - Open Electrical
a
Cable Sizing Calculations front sheet
Full description
Sizing Calculations of Thrust Blocks
Sizing Calculations of Thrust Blocks
Deskripsi lengkap
Sizing Calculations of Thrust Blocks
Full description
IEEE 1115 NiCd Battery Sizing Calculations 1
hoFull description
CT Sizing Calculations 3-5-2013
CT Sizing CalculationsFull description
IEEE 1115 NiCd Battery Sizing Calculations 1
hoDescripción completa
Ups
UPS
Aramco std
Ups
UPSFull description
Ups
Descripción completa
Ups
Ups
HINDUSTAN ZINC LTD 1 X 80MW, ZAWAR CPP ZAWAR MINES, RAJASTHAN ABB LIMITED
SIZING CALCULATION FOR UPS
Doc Ref.No. 3VYN591602
Sheet 1 of 3
SIZING CALCULATION FOR UPS
OWNER:
MAIN CONTRACTOR
e-BOP CONTRACTOR:
HINDUSTAN ZINC LIMITED. ZAWAR MINES, RAJASTHAN.
TATA PROJECTS LTD. HYDERABAD.
ABB LIMITED. FARIDABAD.
We reserve all rights in this document and in the information therein. Reproduction, use or disclosure to third parties without express authority is strictly forbidden. © ABB eBoP.
HINDUSTAN ZINC LTD 1 X 80MW, ZAWAR CPP ZAWAR MINES, RAJASTHAN ABB LIMITED
Doc Ref.No. 3VYN591602
SIZING CALCULATION FOR UPS
Sheet 2 of 3
REVISION STATUS SHEET
REV. NO.
R0
DATE
DESCRIPTION
10.07.2007
FOR REFERENCE ONLY
Rev. No.
Date
KK
AB
For Reference
R0
10.07.2007
Prepared by
Reviewed by
Remarks
We reserve all rights in this document and in the information therein. Reproduction, use or disclosure to third parties without express authority is strictly forbidden. © ABB eBoP.
HINDUSTAN ZINC LTD 1 X 80MW, ZAWAR CPP ZAWAR MINES, RAJASTHAN ABB LIMITED
3VYN591602
SIZING CALCULATION FOR UPS
Sheet 3 of 3
LOAD IN REMARKS kVA
FEEDER/LOAD DESCRIPITION
S.No.
Doc Ref.No.
A 1
BTG LOADS SG/TG DCS
12
2
BOP DCS
6.5
3
HMI & MAXNET FOR UNIT # 1
10
4
6.5
5
MAX DNA – BMS PANELS (SOLENOIDS)
4.0
6
LEVEL SWITCH
1.0
7
VMS
0.75
8
EWLI
1.20
9
COAL FLOW DETECTOR
0.60
10
ESP IOS
2.0
11
LIGHT OIL FLOW METER PD TYPE
0.2
12
SPARE FEEDERS
1.5
13
0.55
14
CONTROL PANEL (FOR TRANSDUCERS & RECORDERS) TSI MONITORING SYSTEM
15
VMS SYSTEM WORK STN & PRINTER
1.5
B
BOP LOADS
1
SWAS & GAS ANALYSERS
2.00
C
TOTAL KVA
50.55
LOADING FACTOR OF 25% AS PER CONTRACT UPS RATING (STANDARD RATING)
63.18
Reference has been taken from UPS sizing calculation of HZL, Phase-I, Unit-1. Vide Doc. No: TCE.4221A-EL-CAL-580-01, R1, Dated 08-09-2004
Feeder Description not enlisted in the TPL document. However, load has been retained.
0.25
65 KVA
As per the standard rating.
CONCLUSION Selected UPS Rating Voltage Rating No. of UPS per Unit in line with HZL, phase-1 & 2.
: : :
65 kVA 110V AC 1 No., parallel redundant type
We reserve all rights in this document and in the information therein. Reproduction, use or disclosure to third parties without express authority is strictly forbidden. © ABB eBoP.
×
Report "UPS Sizing Calculations"
Your name
Email
Reason
-Select Reason-
Pornographic
Defamatory
Illegal/Unlawful
Spam
Other Terms Of Service Violation
File a copyright complaint
Description
×
Sign In
Email
Password
Remember me
Forgot password?
Sign In
Our partners will collect data and use cookies for ad personalization and measurement.
Learn how we and our ad partner Google, collect and use data
.
Agree & close