Transformer Volt Drop Start Up Regulation
Home
Transformer Volt Drop Start Up Regulation
Transformer Volt Drop Start Up RegulationFull description...
Author:
Pramod B.Wankhade
3 downloads
182 Views
103KB Size
Report
DOWNLOAD .PDF
Recommend Documents
Transformer Voltage Drop
voltage drop.Full description
Voltage Drop Calculation-Transformer
This Document is Used to Verify the Sizing of Transformer for a Motor Starting.Full description
Commissioning Start Up
Trombone Start Up
eorfkfodFull description
Plant Start Up
Descripción: Plant Start Up
GT START UP SOP
Preparation for Start Up
Preparation for Start UpDescription complète
Start me up
The Rolling Stones - Start me up
Start Up Routine OVF10
Descripción: OVF10
Start Up Routine OVF10
OVF10Full description
Entity Start-Up Checklist
Full description
Instant Start Up
Descripción: startup
Tests Start Up
gfd
Start Me Up Complete
.
Start Up, Shut Down
Start Up Sales Guide
how to get start up ideas and following up on them.
Airline Start-Up Information
Airline Start-Up InformationFull description
Pengertian Start Up
perusahaan
Start-up Handbook
Descripción: UIUC Start-up Handbook
Start Me Up Play_banda
Up to 35kV Transformer
Harvard University START-UP GUIDE
Business Start-Up GuideDescrição completa
Harvard University START-UP GUIDE
Business Start-Up GuideFull description
Oil Separator Start Up Procedure
Descripción: procedure for starting up an oil seperator
CALCULATION FOR TRANSFORMER VOLTAGE DROP DUE TO MOTOR STARTING DUTY
EQUIVALENT CIRCUIT
TRFR. REACTANCE
VD
VD sin
VD
U
VECTOR DIAGRAM
M
V
I V U
V TRANSFORMER NO LOAD VOLTAGE
= U
TRANSFORMER LOAD VOLTAGE
= V
TRANSFORMER VOLT DROP
VD cos
= VD
DRIVE DESCRIPTION MOTOR TAG. MOTOR SERIAL No. MOTOR MANUFACTURER
INPUT DATA TRANSFORMER SECONDARY NO LOAD VOLTAGE (U)
6600
MOTOR STARTING POWER FACTOR
0.75
PRIMARY VOLTAGE
33000
MOTOR FULL LOAD POWER FACTOR
0.85
PRIMARY FLC (AMPS)
140.0
MOTOR EFFICIENCY
0.95
% IMPEDANCE VOLTAGE
8.5
TRANSFORMER kVA
8000
VECTOR GROUP
Dyn11
TRANSFORMER BASE LOAD (kVA)
7800
RATING (kVA)
8000
8.5
SECONDARY NO-LOAD
MOTOR kW
1340
SECONDARY FLC (AMPS)
700
MOTOR RATED VOLTAGE
6600 BASE LOAD (kVA)
7800
CALCULATED DATA
OUTPUT POWER (kW)
1340
MOTOR
FULL LOAD CURRENT (AMPS)
145
RATED VOLTAGE
6600
START POWER FACTOR
0.75
RUN POWER FACTOR
0.85
EFFICIENCY
0.95
TRANSFORMER % IMPEDANCE
MOTOR LOCKED ROTOR CURRENT RATIO
1.5
145
FULL LOAD CURRENT
218
STARTING CURRENT
TRANSFORMER TRANSFORMER FULL LOAD CURRENT
700
VOLTAGE
6600
M
VOLT DROP AT TRANSFORMER SECONDARY BUSHINGS TRANSFORMER VOLT DROP (VD) TRANSFORMER LOAD VOLTAGE (V) PERCENTAGE VOLT DROP
6427.3 257
96.11
REMARKS:
Prepared by: Checked by:
PROJECT:
PRAMOD WANKHADE
Date:
6600
×
Report "Transformer Volt Drop Start Up Regulation"
Your name
Email
Reason
-Select Reason-
Pornographic
Defamatory
Illegal/Unlawful
Spam
Other Terms Of Service Violation
File a copyright complaint
Description
×
Sign In
Email
Password
Remember me
Forgot password?
Sign In
Our partners will collect data and use cookies for ad personalization and measurement.
Learn how we and our ad partner Google, collect and use data
.
Agree & close