CLIENT CONSULTANT CONTRACTOR PROJECT: PACKAGEII : DOCUMENT NAME : REV
DOCUMENT NO.
‐
2
SUMMARY SHEET The total plant is divided into the following major areas and the soil resistivity considered for calculation (based on soil report) are as follows 1
SS1 SUBSTATION
‐
70.53
Ωm 14 TRANSFER HOUSE (TH2A)
‐
151.39
Ωm
2
SS2 SUBSTATION
‐
25.050
Ωm 15 PARKING STATION (PS1)
‐
151.39
Ωm
3
SS3 SUBSTATION
‐
25.050
Ωm 16 PARKING STATION (PS2)
‐
35.100
Ωm Ωm
4
TRANSFER HOUSE (TH1)
‐
72.640
Ωm 17 TRANSFER HOUSE (TH3)
‐
35.100
5
SILO BUILDING
‐
151.390
Ωm 18 TRANSFER HOUSE (TH4)
‐
44.840
Ωm
6
TAIL DRIVE HOUSE
‐
151.390
Ωm 19 TRANSFER HOUSE (TH5)
‐
41.940
Ωm
7
TRANSFER HOUSE (TH2)
‐
151.390
Ωm 20 TRANSFER HOUSE (TH6)
‐
128.940
Ωm
8
PUMP HOUSE1
‐
205.510
Ωm 21 PUMP HOUSE2
‐
228.680
Ωm
9
AT HTP1
‐
128.380
Ωm 22 AT HTP2
‐
70.150
Ωm
10
AT HTP3
‐
25.050
Ωm 23 AT HTP4
‐
26.040
Ωm
11
AT HTP5
2 ‐
49.870
Ωm 24 AT HTP6
‐
37.530
Ωm
12
AT HTP7
‐
51.150
Ωm 25 AT HTP8
‐
35.100
Ωm
13
AT SECONDARY CRUSHER
‐
441.550
Ωm 26 AT TRANDFER STATION
‐
49.890
Ωm
The earth grid values of each areas is calculated seperately and all these areas are interconnected through earth flat.The combined earth resistance for the total layout as per project specifications shall be less than 1 Ω Calculation of overall Earth resistance of the total plant 10 1.0
2
Earth Resistance around Electrical Substation Building SS1 R1
=
0.81
10.0 Refer AnnexureI
Earth Resistance around Electrical Substation Building SS2 R10
=
0.29
Refer AnnexureX
2.0 Earth Resistance around Electrical Substation Building SS3 & Earth 11.0 Resistance around Pump house Building 2 Refer AnnexureII R2 = 0.82
Earth Resistance around Transfer House TH1
3.0 Earth Resistance around silo building
Earth Resistance around Travel drive house
R3
=
12.0 9.61
Refer AnnexureIII
4.0 Earth Resistance around Transfer House TH2 R4
=
9.61
13.0 Refer AnnexureIV
5.0 Earth Resistance around parking station PS1 R5
=
9.61
14.0 . Refer AnnexureV
6.0 Earth Resistance around Transfer House TH3 R6
=
2.23
15.0 Refer AnnexureVI
7.0 Earth Resistance around Transfer House TH5 R7
=
2.66
16.0 Refer AnnexureVII
8.0 Earth Resistance around Pump house1 R8 9.0
=
17.0 10.44
Refer AnnexureVIII
R11
R12
=
=
4.61
9.61
Refer AnnexureXI
Refer AnnexureXII
Earth Resistance around Transfer House TH2A R13
=
9.61
Refer AnnexureXIII
Earth Resistance around parking station PS2 R14
=
4.46
Refer AnnexureXIV
Earth Resistance around Transfer House TH4 R15
=
2.85
Refer AnnexureXV
Earth Resistance around Transfer House TH6 R16
=
8.19
Refer AnnexureXVI
Earth Resistance Near Transfer Station R17
=
6.33
Refer AnnexureXVII
Earth Resistance of down hill conveyor DHC723 at Near HTP2 (TR64) R9A
=
0.80
2
Refer AnnexureIX
10.0 Earth Resistance of down hill conveyor DHC723 at Near HTP6 (TR107) R9B
2
DOC.NO.-EL00007,REV-02
=
0.75
Refer AnnexureIXA
1 OF 42
SUMMARY
Note:The Overall Plant Earth Grid resistance value will be reduced when all Tail End TH's & SS grid will be interconnected. 1 R
=
1 R1
1 R
=
1 0.81
1 R 1 R 1 R
=
1 R3
+
1 R4
+
1 R5
+
1 R8
+
1 R11
+
1 R12
+
1 R13
+
1 9.61
+
1 9.61
+
1 9.61
+
1 10.44
+
1 4.61
+
1 9.61
+
1 9.61
0.81 + 0.81 x
9.61 9.61
9.61 9.61
+ x
9.61 9.61
10.44 10.44
+ x
4.61 4.61
+
9.61 9.61
+ x
9.61 9.61
+
+
+
=
10.43 7.83
+
19.22 92.38
+
15.05 48.14
+
19.22 92.38
+
0.21
+
0.31
+
0.21
=
1.33
1 R
=
2.06
R
=
1 2.06
R
=
0.485
Note: Refer the Earthing Pit & Strip Scheme for overall plant.
Finally we calculate as
RT
2
Ohms Earth Resistance of overall plant Tail end side
0.49
=
Note: The Overall Plant Earth Grid resistance value will be reduced when all Head End TH's & SS grid will be interconnected. 1 R
=
1 R2
1 R6
+
1 R7
+
1 R10
+
1 R14
+
1 R15
+
1 R16
+
1 R17
1 R
=
1 0.82
+
1 2.23
+
1 2.66
+
1 0.29
+
1 4.46
+
1 2.85
+
1 8.19
+
1 6.33
0.82 + 0.82 x
2.23 2.23
2.66 2.66
+ x
0.29 0.29
4.46 4.46
+ x
2.85 2.85
+
8.19 8.19
+ x
6.33 6.33
+
1 R
=
1 R
=
3.05 1.83
+
2.95 0.77
+
7.30 12.69
+
14.52 51.86
+
3.83
+
0.58
+
0.28
1 R
=
1.67
1 R
=
6.36
R
=
1 6.36
R
=
0.157
Finally we calculate as
2
+
+
Note: Refer the Earthing Pit & Strip Scheme for overall plant.
RT
=
0.16
Ohms Earth Resistance of overall plant Head end side
NOTE: 1 The calculated earth pit qty.are minimum to be provided at site.However as per site condition,the overall resistance is not achived less than 1 Ω with above earth pit qty than additional pits shall be provided to meet the overall grid resistance less than 1 Ω. 2 Earth flat running through cable tray will be consider as interconnection between two grids wherever ground profile is not hilly area.
DOC.NO.-EL00007,REV-02
2 OF 42
SUMMARY
CALCULATION OF MAIN GRID CONDUCTOR & EARTHING STRIP
REFERENCE IEC:60364-5-54 IS:3043
=
ENTER THE VALUE IN YELLOW COLOR BOXES ONLY
STEP-1 : BASIC DESIGN DATA 1.00 SYSTEM DATA
Vs
1.01 System nominal voltage MV Voltage
=
11
kV
25
kA
1
sec
=
1
sec
=
0.415
kV
50
kA
1
sec
=
The value (r.m.s) in A of prospective fault current for a fault of negligible impedance, which can 1.02 flow through the protective device for HV System (see IEC 60909-0);
If
1.03 The operating time of the protective device for automatic disconnection in s;
ts
=
1.04 Fault clearing time
tsc
1.05 System nominal voltage LV Voltage
Vs
1.06
The value (r.m.s) in A of prospective fault current for a fault of negligible impedance, which can flow through the protective device for LV System (see IEC 60909-0);
=
If
1.07 Fault clearing time
tsc
=
Pipe
=
Steel
QC
=
3.8 x 10-3
β
=
202
2.00 Earthing Conductor Data 2.01 Earth Electrode Material (Rod or Pipe) 2.02 Volumetric heat capacity of conductor material
J/0C mm3
(J/oC mm3) at 20 oC 2.03 Reciprocal Of temp.Cofficient of resistivity at O 0C
°C
for the conductor (2020C as IEC 60364-5-54)
ρ20
=
138x10-6
2.05 Initial temperature of conductor (40 0C)
θi
=
45
2.06 Final temperature of conductor (200 0C)
θf
=
500
2.04 Electrical resistivity of conductor material at 200C
Ω-mm
°C
3.00 CALCULATION FOR SIZING OF EARTH CONDUCTOR BASED ON 11KV SYSTEM
Minimum Cross sectional area required = A As per IEEE - 80 ,the minimum cross sectional area of the earthing conductor to withstand the Short circuit current is given by A If
= Is the cross-sectional area, in mm2; =
is the value (r.m.s) in A of prospective fault current for a fault of negligible impedance, which can flow through the protective device (see IEC 60909-0);
t = is the operating time of the protective device for automatic disconnection in s; k
= is the factor dependent on the material of the protective conductor, the insulation and is the factor dependent on the material of the protective conductor, the insulation and
A
(If √ t) k
=
The factor of K is determine from the formula (Annex A - IEC - 60364-5-54) 0
k
Qc( + 20 C)
=
ln
ρ20
1+
θf - θi
+ θi
Qc(β + 20°C)
=
ρ20
The value of
k
80
=
k
=
k
=
80
for steel as per ,Table A.54.1 of IEC 60364-5-54
x
ln
1+
500 202
+
45 45
=
80
x
1.045
81.76
Therefore ,the area of conductor for the maximum fault level of 40A and consider the fault clearing time is < 0.5 sec.the conductor area is
25000 A
=
A
=
X
1
81.76 Considering 15% corrosion allowance of the strip will be
306
A
Sq.mm
Hence the calculated minimum diameter of the GI rod
A
=
D
=
D
=
D
=
=
351.63
Sq.mm
Hence the calculated minimum width & Thickness of the Earthing strip
∏D²/4
Earthing Conductor(strip) width
=
Earthing Conductor(strip) Thickness
=
40 X 10
mm mm
Ax4 П 306 x 3.142 20
4
2
However as per TS 75x10mm strip shall be used for main earthing grid.
mm
Considering 15% corrosion allowance the diameter of the MS rod will be 32mm will be sufficient However we will select a standard size of 100mm MS rod for the main earth mat below ground as per contract specifications.
D =
DOC.NO.-EL00007,REV-02
100Ø mm
6 OF 42
MAIN CONDUCTOR SIZING
TRANSFER STATION GROUNDING CALCULATION
ANNEXURE-XVII REFERENCE IEC:60364-5-54 IS:3043
=
ENTER THE VALUE IN YELLOW COLOR BOXES ONLY
STEP-1 : BASIC DESIGN DATA 1.00
SYSTEM DATA Vs
1.01 System nominal voltage
= =
The value (r.m.s) in A of prospective fault current for a fault of negligible impedance, which 1.02 can flow through the protective device (see IEC 60909-0);
If
1.03 The operating time of the protective device for automatic disconnection in s;
ts
=
415
V
50
kA
1
sec
tsc
=
LxB
=
1.06 Area of earth grid around Substation
A
=
41.25
1.07 Resistivity of the soil
ρ
=
49.89
1.09 Design Ambient temperature
Ta
=
45
°C
2.01 Length of burial of Earthing Strip
L
=
2600.0
cm
2 02 Depth 2.02 D th off b burial i l off conductor d t (St (Strip) i )
ω
=
80
cm
t
=
7.50
cm
1.04 0 Fault clearing time 1.05 Length and breadth of the earth grid around Substation
2.00
sec x
5.5 m
m
2
Ω-m
Buried earth conductor (strip)
2.03 Width (Incase of strip) of the conductor (Strip) 2.04
1 7.5
2
Earth conductor (Rod or Pipe) Pipe
=
G.I.Pipe
2.06 Length of earth electrode rod/pipe
l
=
3
Mtr.
2.07 Diameter of earth electrode rod/pipe
d
=
100
mm
2.05 Earth Electrode Material (Rod or Pipe)
2
Resistance of Buried earth conductor (Strip) Th resistance The i t off earth th grid id can be b calculated l l t d by b using i the th formula f l As per IS:3043 clause no.9.2.3
L = Length of the Strip (in Cm) ω = Depth of burial of the Earthing strip cm t = Width(incase of Strip) or twice the diameter(fir Conductors) in cm. ρ = Resistivity of the soil in Ω m Rg = Resistance of the earth conductor
Rg =
( 100 x ρ ) ( 2 x ∏ x L)
Rg =
(100 x 49.89) (2 x 3.142 x 2600)
Rg =
0.305354
Rg =
3.06
ln
X
(2xL L² ) (ωx t) ln
(2 x 6760000) (80 x 7.5)
10.023
The resistance of the earth Conductor (Strip)
Rg =
DOC.NO.-EL00007,REV-02
3.06
ohms
41 OF 42
TRANSFER STATION
Resistance of earth Electrode (Steel Rod Or Pipe) As per IS:3043 clause no.9.2.2 l
= Length of rod or Pipe (in Cm)
d = Diameter of rod or pipe in cm
ρ = Resistivity of the soil in Ω m Re = Resistance of the earth Electrode The resistance of earth electrode is given by
Re =
( 100 x ρ ) ( 2 x ∏ x l)
Re =
(100 x 49.89) (2 x 3.142 x 300)
Re =
2.646404
Re =
12.67
ln
X
4x
l d
ln
4
1 Rn-1
+
300 10
X
4.787
The resistance of the earth electrode
Re =
12.67
ohms
The overall earth resistance of Electrodes:-
1 = R 1 = R
1 R1
+ 1
12.67
1 -----R2
1 12.67
+
1 Rn 1
+
---------------------
12.67
1 Rn
Finally we calculate as Add no. of pits
2
n
the Combined value of
n pits
R18 =
R1- Total Resistance of Earth Electrodes(pits)
(Re)
6.33
Ω
R2 - Total Earth Resistance of the buried Conductor
(Rg)
3.06
Ω
6.33
Ohms
Refer Annexure-VI 1 R 1 R
=
1 R1
+
1 6.33
=
2
1 R2 +
1 3.06
Hence the combined resistance of grid + Earth pits R
DOC.NO.-EL00007,REV-02
=
R
=
R18A
=
R1
x
R2
R1
+
R2
=
6.33 6.33
x +
3.06 3.06
19.39 9.40
2.06
Ohms
42 OF 42
TRANSFER STATION
4.00 CALCULATION FOR SIZING OF EARTH CONDUCTOR BASED ON LV SYSTEM
Minimum Cross sectional area required = A As per IEEE - 80 ,the minimum cross sectional area of the earthing conductor to withstand the Short circuit current is given by A If
= Is the cross-sectional area, in mm2; =
is the value (r.m.s) in A of prospective fault current for a fault of negligible impedance, which can flow through the protective device (see IEC 60909-0);
t = is the operating time of the protective device for automatic disconnection in s; k
= is the factor dependent on the material of the protective conductor, the insulation and is the factor dependent on the material of the protective conductor, the insulation and
A
(If √ t) k
=
The factor of K is determine from the formula (Annex A - IEC - 60364-5-54)
k
Qc( + 200C) ρ20
=
ln
1+
θf - θi
+ θi
Qc(β + 20°C)
=
ρ20
The value of
k
80
=
k
=
k
=
80
for steel as per ,Table A.54.1 of IEC 60364-5-54
x
ln
1+
500 202
+
45 45
=
80
x
1.045
81.76
Therefore ,the area of conductor for the maximum fault level of 40A and consider the fault clearing time is < 0.5 sec.the conductor area is
50000 A
=
A
=
X
1
81.76 Considering 15% corrosion allowance of the strip will be
612
Sq.mm
Hence the calculated minimum diameter of the MS Rod
A
=
D
=
D
=
D
=
A
=
703.26
Sq.mm
Hence the calculated minimum width & Thickness of the Earthing strip
∏D²/4
Earthing Conductor(strip) width
=
Earthing Conductor(strip) Thickness
=
70 X 10
mm mm
Ax4 П 612 x 3.142 28
4
Hence ,1R x 75 x10Sqmm GI.strip shall be used for main earthing grid as per NIT
mm
Considering 15% corrosion allowance the diameter of the GI pipe will be 32mm. However we will select a standard size of 100mm GI pipe for the main earth mat below ground as per contract specifications
D =
100Ø mm
Conculation:5.00
from the above calculations,we concluded that the required size of main earthing conductor for LV system is higher than that of HV(11kv system) Hence the size of earth conductor of main grid is selected based on LV system earthing calculation
6.00
The conductor selected for main earth is 1 Run of 75 x 10mm GI flat as per NIT. The earthing Electrode selected for earth pit is 100mm dia & 3mtr.as per NIT
DOC.NO.-EL00007,REV-02
7 OF 42
MAIN CONDUCTOR SIZING
SS-1-ELECTRICAL SUBSTATION GROUNDING CALCULATION
ANNEXURE-I REFERENCE IEC:60364-5-54 IS:3043
=
ENTER THE VALUE IN YELLOW COLOR BOXES ONLY
STEP-1 : BASIC DESIGN DATA 1.00 SYSTEM DATA
Vs
1.01 System nominal voltage The value (r.m.s) in A of prospective fault current for a fault of negligible impedance, which 1.02 can flow through the protective device (see IEC 60909-0);
If
= =
415
V
50
kA
1.03 The operating time of the protective device for automatic disconnection in s;
ts
=
1
1.04 Fault clearing time
tsc
=
1
LxB
=
1.06 Area of earth grid around Substation
A
=
551.8
1.07 Resistivity of the soil
ρ
=
70.53
1.08 Design Ambient temperature
Ta
=
45
°C
1.05 Length and breadth of the earth grid around Substation
15.5
sec sec x
35.6 m
m
2
Ω-m
2
2.00 Buried earth conductor (strip) 2.01 Length of burial of Earthing Strip
L
=
10220.0
cm
2.02 Depth of burial of conductor (Strip)
ω
=
80
cm
2.03 Width (Incase of strip) of the conductor (Strip)
t
=
7.50
cm
G.I.Pipe
3.00 Earth conductor (Rod or Pipe)
Pipe
=
3.02 Length of earth electrode rod/pipe
l
=
3
Mtr
3.03 Diameter of earth electrode rod/pipe
d
=
100
mm
3.01 Earth Electrode Material (Rod or Pipe)
2
Resistance of Buried earth conductor (Strip) The resistance of earth grid can be calculated by using the formula As per IS:3043 clause no.9.2.3
L = Length of the Strip (in Cm) ω = Depth of burial of the Earthing strip cm t = Width(incase of Strip) or twice the diameter(fir Conductors) in cm. ρ = Resistivity of the soil in Ω m Rg = Resistance of the earth conductor
Rg =
( 100 x ρ ) ( 2 x ∏ x L)
Rg =
(100 x 70.53) (2 x 3.142 x 10220)
Rg =
0.109821
Rg =
1.40
ln
X
( 2 x L² ) (ωx t) ln
(2 x 104448400) (80 x 7.5)
12.760
The resistance of the earth Conductor (Strip)
Rg =
DOC.NO.-EL00007,REV-02
1.40
ohms
2
8 OF 42
SS-1
Resistance of earth Electrode (Steel Rod Or Pipe) As per IS:3043 clause no.9.2.2 l
= Length of rod or Pipe (in Cm)
d = Diameter of rod or pipe in cm
ρ = Resistivity of the soil in Ω m Re = Resistance of the earth Electrode The resistance of earth electrode is given by
Re =
( 100 x ρ ) ( 2 x ∏ x l)
Re =
(100 x 70.53) (2 x 3.142 x 300)
Re =
3.741248
Re =
17.91
ln
X
4x
l d
ln
4
1 Rn-1
+
300 10
X
4.787
The resistance of the earth electrode
2
Re =
17.91
ohms
The overall earth resistance of Electrodes:-
1 = R 1 = R
1 R1
+ 1
17.91
1 -----R2
1 17.91
+
1 Rn 1
+
---------------------
17.91
1 Rn
Finally we calculate as
22
Add no. of pits n
the Combined value of n pits
R1
=
0.81
Ohms
2
add all transformer body&neutral earth pit
R1- Total Resistance of Earth Electrodes(pits)
(Re)
0.81
Ω
R2 - Total Earth Resistance of the buried Conductor
(Rg)
1.40
Ω
Refer Annexure-I 1 R 1 R
=
1 R1
+
1 0.81
=
1 R2 +
1 1.40
Hence the combined resistance of grid + Earth pits R
R
=
=
R1A =
DOC.NO.-EL00007,REV-02
R1
x
R2
R1
+
R2
=
0.81 0.81
x +
1.40 1.40
1.14 2.22
0.51
Ohms
2
9 OF 42
SS-1
SS-2-ELECTRICAL SUBSTATION GROUNDING CALCULATION
ANNEXURE-X REFERENCE IEC:60364-5-54 IS:3043
=
ENTER THE VALUE IN YELLOW COLOR BOXES ONLY
STEP-1 : BASIC DESIGN DATA 1.00
SYSTEM DATA Vs
1.01 System nominal voltage 1.02
The value (r.m.s) in A of prospective fault current for a fault of negligible impedance, which can flow through the protective device (see IEC 60909-0);
1.03 The operating time of the protective device for automatic disconnection in s;
If
= =
ts
=
415
V
50
kA
1
sec
tsc
=
LxB
=
A
=
551.8
1.07 Resistivity of the soil
ρ
=
25.05
1.09 Design Ambient temperature
Ta
=
45
°C
2.01 Length of burial of Earthing Strip
L
=
10220.0
cm
2.02 Depth of burial of conductor (Strip)
ω
=
80
cm
2.03 Width (Incase of strip) of the conductor (Strip)
t
=
7.50
cm
G.I.Pipe
1.04 Fault clearing time 1.05 Length and breadth of the earth grid around Substation 1.06 Area of earth grid around Substation
2.00
2.04
1 15.5
sec x
35.6
m
m2
Ω-m
Buried earth conductor (strip)
2
Earth conductor (Rod or Pipe) Pipe
=
2.06 Length of earth electrode rod/pipe
l
=
3
Mtr.
2.07 Diameter of earth electrode rod/pipe
d
=
100
mm
2.05 Earth Electrode Material (Rod or Pipe)
Resistance of Buried earth conductor (Strip) The resistance of earth grid can be calculated by using the formula As p per IS:3043 clause no.9.2.3
L = Length of the Strip (in Cm) ω = Depth of burial of the Earthing strip cm t = Width(incase of Strip) or twice the diameter(fir Conductors) in cm. ρ = Resistivity of the soil in Ω m Rg = Resistance of the earth conductor
Rg =
( 100 x ρ ) ( 2 x ∏ x L)
Rg =
(100 x 25.05) (2 x 3.142 x 10220)
Rg =
0.039005
Rg =
0.50
ln
X
( 2 x L² ) (ωx t) ln
(2 x 104448400) (80 x 7.5)
12.760
The resistance of the earth Conductor (Strip)
Rg =
DOC.NO.-EL00007,REV-02
0.50
ohms
10 OF 42
SS-2
Resistance of earth Electrode (Steel Rod Or Pipe) As per IS:3043 clause no.9.2.2 l
= Length of rod or Pipe (in Cm)
d = Diameter of rod or pipe in cm
ρ = Resistivity of the soil in Ω m Re = Resistance of the earth Electrode The resistance of earth electrode is given by
Re =
( 100 x ρ ) ( 2 x ∏ x l)
Re =
(100 x 25.05) (2 x 3.142 x 300)
Re =
1.328771
Re =
6.36
ln
X
4x
l d
ln
4
1 Rn-1
+
300 10
X
4.787
The resistance of the earth electrode
Re =
6.36
ohms
The overall earth resistance of Electrodes:-
1 = R
1 R1
+ 1
1 = R
6.36
1 -----R2
1 6.36
+
1 Rn 1
+
---------------------
6.36
Finally we calculate as Add no. of pits
1 Rn
2
22
n
the Combined value of
n pits
R10 =
0.29
Ohms
add all transformer body&neutral earth pit R1- Total Resistance of Earth Electrodes(pits)
(Re)
0.29
Ω
R2 - Total Earth Resistance of the buried Conductor
(Rg)
0.50
Ω
Refer Annexure-X 1 R 1 R
=
1 R1
+
1 0.29
=
2
1 R2 +
1 0.50
Hence the combined resistance of grid + Earth pits R
R
=
=
R10A =
DOC.NO.-EL00007,REV-02
R1
x
R2
R1
+
R2
=
0.29 0.29
x +
0.50 0.50
0.14 0.79
0.18
Ohms
2
11 OF 42
SS-2
SS-3-ELECTRICAL SUBSTATION GROUNDING CALCULATION
ANNEXURE-II REFERENCE IEC:60364-5-54 IS:3043
=
ENTER THE VALUE IN YELLOW COLOR BOXES ONLY
STEP-1 : BASIC DESIGN DATA 1.00
SYSTEM DATA Vs
1.01 System nominal voltage
= =
The value (r.m.s) in A of prospective fault current for a fault of negligible impedance, which 1.02 can flow through the protective device (see IEC 60909-0);
If
1.03 The operating time of the protective device for automatic disconnection in s;
ts
=
415
V
50
kA
1
sec
tsc
=
LxB
=
A
=
102.8625
1.07 Resistivity of the soil
ρ
=
25.05
1.09 Design Ambient temperature
Ta
=
45
°C
2.01 Length of burial of Earthing Strip
L
=
4465.0
cm
2.02 Depth of burial of conductor (Strip)
ω
=
80
cm
2.03 Width (Incase of strip) of the conductor (Strip)
t
=
7.50
cm
1.04 Fault clearing time 1.05 Length and breadth of the earth grid around Substation 1.06 Area of earth grid around Substation
2.00
2.04
1 6.5
sec x
15.83 m m2
Ω-m
Buried earth conductor (strip)
Earth conductor (Rod or Pipe) Pipe
=
G.I.Pipe
2.06 Length of earth electrode rod/pipe
l
=
3
Mtr
2.07 Diameter of earth electrode rod/pipe
d
=
100
mm
2.05 Earth Electrode Material (Rod or Pipe)
2
Resistance of Buried earth conductor (Strip) The resistance of earth grid can be calculated by using the formula As per IS:3043 clause no.9.2.3
L = Length of the Strip (in Cm) ω = Depth of burial of the Earthing strip cm t = Width(incase of Strip) or twice the diameter(fir Conductors) in cm. ρ = Resistivity of the soil in Ω m Rg = Resistance of the earth conductor
Rg =
( 100 x ρ ) ( 2 x ∏ x L)
Rg =
(100 x 25.05) (2 x 3.142 x 4465)
Rg =
0.089279
Rg =
0.99
ln
X
( 2 x L² ) (ωx t) ln
(2 x 19936225) (80 x 7.5)
11.104
The resistance of the earth Conductor (Strip)
Rg =
DOC.NO.-EL00007,REV-02
0.99
ohms
12 OF 42
SS-3
Resistance of earth Electrode (Steel Rod Or Pipe)
As per IS:3043 clause no.9.2.2 l
= Length of rod or Pipe (in Cm)
d = Diameter of rod or pipe in cm
ρ = Resistivity of the soil in Ω m Re = Resistance of the earth Electrode The resistance of earth electrode is given by
Re =
( 100 x ρ ) ( 2 x ∏ x l)
Re =
(100 x 25.05) (2 x 3.142 x 300)
Re =
1.328771
Re =
6.36
ln
X
4x
l d
ln
4
1 Rn-1
+
X
300 10
4.787
The resistance of the earth electrode
Re =
6.36
ohms
The overall earth resistance of Electrodes:-
1 = R
1 R1
+ 1
1 = R
1 -----R2
1 6.36
+
6.36
1 Rn 1
+
---------------------
6.36
1 Rn
Finally we calculate as Add no. of pits
7
n
the Combined value of
n pits - (RA)
=
0.91
Ohms
Add Pump House-2 earth pit
RA- Total Resistance of Earth Electrodes(pits) of SS-3
(Re)
0.91
Ω
RB- Total Resistance of Earth Electrodes(pits) of Pump House-2
(Re)
8 30 8.30
Ω
1 R
=
1 R
=
1 R1
+
1 0.91
Refer Annexure-II
2
1 R2 +
1 8.30
Hence the combined resistance of grid + Earth pits R
R
=
=
R2 =
DOC.NO.-EL00007,REV-02
R1
x
R2
R1
+
R2
=
0.91 0.91
x +
8.30 8.30
7.54 9.21
0.82
Ohms
2
13 OF 42
SS-3
TRANSFER HOUSE (TH-1) GROUNDING CALCULATION
ANNEXURE-XI REFERENCE IEC:60364-5-54 IS:3043
=
ENTER THE VALUE IN YELLOW COLOR BOXES ONLY
STEP-1 : BASIC DESIGN DATA 1.00 SYSTEM DATA
Vs
1.01 System nominal voltage 1.02
The value (r.m.s) in A of prospective fault current for a fault of negligible impedance, which can flow through the protective device (see IEC 60909-0);
1.03 The operating time of the protective device for automatic disconnection in s; 1.04 Fault clearing time 1.05 Length and breadth of the earth grid around Substation
If
= =
ts
=
tsc
=
LxB
=
415
V
50
kA
1
sec
1 11
sec x
8
1.06 Area of earth grid around Substation
A
=
88
1.07 Resistivity of the soil
ρ
=
72.64
1.09 Design Ambient temperature
Ta
=
45
°C
2.01 Length of burial of Earthing Strip
L
=
3800.0
cm
2.02 Depth of burial of conductor (Strip)
ω
=
80
cm
2.03 Width (Incase of strip) of the conductor (Strip)
t
=
7.50
cm
Pipe
=
G.I.Pipe
2.06 Length of earth electrode rod/pipe
l
=
3
Mtr.
2.07 Diameter of earth electrode rod/pipe
d
=
100
mm
m
m
2
Ω-m
2.00 Buried earth conductor (strip)
2
2.04 Earth conductor (Rod or Pipe) 2.05 Earth Electrode Material (Rod or Pipe)
2
Resistance of Buried earth conductor (Strip) The resistance of earth grid can be calculated by using the formula As per IS:3043 clause no.9.2.3
L = Length of the Strip (in Cm) ω = Depth of burial of the Earthing strip cm t = Width(incase of Strip) or twice the diameter(fir Conductors) in cm. ρ = Resistivity of the soil in Ω m Rg = Resistance of the earth conductor
Rg
=
( 100 x ρ ) ( 2 x ∏ x L)
ln
Rg =
(100 x 72.64) (2 x 3.142 x 3800)
Rg =
0.304198
Rg =
3.28
X
( 2 x L² ) (ωx t) ln
(2 x 14440000) (80 x 7.5)
10.782
The resistance of the earth Conductor (Strip)
2
DOC.NO.-EL00007,REV-02
Rg =
3.28
ohms
14 OF 42
TH-1
Resistance of earth Electrode (Steel Rod Or Pipe) As per IS:3043 clause no.9.2.2 l
= Length of rod or Pipe (in Cm)
d = Diameter of rod or pipe in cm
ρ = Resistivity of the soil in Ω m Re = Resistance of the earth Electrode The resistance of earth electrode is given by
Re
=
( 100 x ρ ) ( 2 x ∏ x l)
Re
=
(100 x 72.64) (2 x 3.142 x 300)
Re
=
3.853172
Re
=
18.45
ln
X
4x
l d
ln
4
1 Rn-1
+
X
300 10
4.787
The resistance of the earth electrode
Re =
18.45
ohms
The Earth resistance with numbers of Electrodes:-
1 = R 1 = R
1 R1
+ 1
18.45
1 -----R2
1 18.45
+
1 Rn 1
+
---------------------
18.45
1 Rn
Finally we calculate as
4
Add no. of pits n
the Combined value of n pits
R11 =
R1- Total Resistance of Earth Electrodes(pits)
(Re)
4.61
Ω
R2 - Total Earth Resistance of the buried Conductor
(Rg)
3.28
Ω
4.61
Ohms
Refer Annexure-XI 1 R 1 R
=
1 R1
+
1 4.61
=
2
1 R2 +
1 3.28
Hence the combined resistance of grid + Earth pits R
R
2
DOC.NO.-EL00007,REV-02
=
=
R11A =
R1
x
R2
R1
+
R2
=
4.61 4.61
x +
3.28 3.28
15.13 7.89
4.61
Ohms
15 OF 42
TH-1
TRANSFER HOUSE (TH-2) GROUNDING CALCULATION
ANNEXURE-IV REFERENCE IEC:60364-5-54 IS:3043
=
ENTER THE VALUE IN YELLOW COLOR BOXES ONLY
STEP-1 : BASIC DESIGN DATA 1.00 SYSTEM DATA
Vs
1.01 System nominal voltage 1.02
The value (r.m.s) in A of prospective fault current for a fault of negligible impedance, which can flow through the protective device (see IEC 60909-0);
1.03 The operating time of the protective device for automatic disconnection in s;
If
= =
ts
=
415
V
50
kA
1
sec
tsc
=
LxB
=
13.7
A
=
147.275
1.07 Resistivity of the soil
ρ
=
151.39
1.09 Design Ambient temperature
Ta
=
45
°C
2.01 Length of burial of Earthing Strip
L
=
4890.0
cm
2.02 Depth of burial of conductor (Strip)
ω
=
80
cm
2.03 Width (Incase of strip) of the conductor (Strip)
t
=
7.50
cm
Pipe
=
G.I.Pipe
2.06 Length of earth electrode rod/pipe
l
=
3
Mtr.
2.07 Diameter of earth electrode rod/pipe
d
=
100
mm
1.04 Fault clearing time 1.05 Length and breadth of the earth grid around Substation 1.06 Area of earth grid around Substation
1
sec x
10.75 m m2
Ω-m
2.00 Buried earth conductor (strip)
2
2.04 Earth conductor (Rod or Pipe) 2.05 Earth Electrode Material (Rod or Pipe)
2
Resistance of Buried earth conductor (Strip) The resistance of earth grid can be calculated by using the formula As per IS:3043 clause no.9.2.3
L = Length of the Strip (in Cm) ω = Depth of burial of the Earthing strip cm t = Width(incase of Strip) or twice the diameter(fir Conductors) in cm. ρ = Resistivity of the soil in Ω m Rg = Resistance of the earth conductor
Rg =
( 100 x ρ ) ( 2 x ∏ x L)
Rg =
(100 x 151.39) (2 x 3.142 x 4890)
Rg =
0.492666
Rg =
5.56
ln
X
( 2 x L² ) (ωx t) ln
(2 x 23912100) (80 x 7.5)
11.286
The resistance of the earth Conductor (Strip)
2
DOC.NO.-EL00007,REV-02
Rg =
5.56
ohms
16 OF 42
TH-2
Resistance of earth Electrode (Steel Rod Or Pipe) As per IS:3043 clause no.9.2.2 l
= Length of rod or Pipe (in Cm)
d = Diameter of rod or pipe in cm
ρ = Resistivity of the soil in Ω m Re = Resistance of the earth Electrode The resistance of earth electrode is given by
Re =
( 100 x ρ ) ( 2 x ∏ x l)
Re =
(100 x 151.39) (2 x 3.142 x 300)
Re =
8.030448
Re =
38.45
ln
X
4x
l d
ln
4
1 Rn-1
+
300 10
X
4.787
The resistance of the earth electrode
Re =
38.45
ohms
The Earth resistance with numbers of Electrodes:-
1 = R 1 = R
1 R1
+ 1
38.45
1 -----R2
1 38.45
+
1 Rn 1
+
---------------------
38.45
1 Rn
Finally we calculate as
4
Add no. of pits n
the Combined value of n pits
R4
R1- Total Resistance of Earth Electrodes(pits)
(Re)
9.61
Ω
R2 - Total Earth Resistance of the buried Conductor
(Rg)
5.56
Ω
=
9.61
Ohms
Refer Annexure-IV 1 R 1 R
=
1 R1
+
1 9.61
=
2
1 R2 +
1 5.56
Hence the combined resistance of grid + Earth pits R
R
2
DOC.NO.-EL00007,REV-02
=
=
R4A =
R1
x
R2
R1
+
R2
=
9.61 9.61
x +
5.56 5.56
53.44 15.17
3.52
Ohms
17 OF 42
TH-2
TRANSFER HOUSE (TH-2A) GROUNDING CALCULATION
ANNEXURE-XIII REFERENCE IEC:60364-5-54 IS:3043
=
ENTER THE VALUE IN YELLOW COLOR BOXES ONLY
STEP-1 : BASIC DESIGN DATA 1.00 SYSTEM DATA
Vs
1.01 System nominal voltage 1.02
The value (r.m.s) in A of prospective fault current for a fault of negligible impedance, which can flow through the protective device (see IEC 60909-0);
1.03 The operating time of the protective device for automatic disconnection in s; 1.04 Fault clearing time 1.05 Length and breadth of the earth grid around Substation
If
=
415
V
50
kA
1
sec
=
ts
=
tsc
=
LxB
=
1 9
sec x
7.5
1.06 Area of earth grid around Substation
A
=
67.5
1.07 Resistivity of the soil
ρ
=
151.39
1.09 Design Ambient temperature
Ta
=
45
°C
m
m
2
Ω-m
2.00 Buried earth conductor (strip) 2.01 Length of burial of Earthing Strip
L
=
3300.0
cm
2.02 Depth of burial of conductor (Strip)
ω
=
80
cm
2.03 Width (Incase of strip) of the conductor (Strip)
t
=
7.50
cm
Pipe
=
G.I.Pipe
2.06 Length of earth electrode rod/pipe
l
=
3
Mtr.
2.07 Diameter of earth electrode rod/pipe
d
=
100
mm
2
2.04 Earth conductor (Rod or Pipe) 2.05 Earth Electrode Material (Rod or Pipe)
2
Resistance of Buried earth conductor (Strip) The resistance of earth grid can be calculated by using the formula As per IS:3043 clause no.9.2.3
L = Length of the Strip (in Cm) ω = Depth of burial of the Earthing strip cm t = Width(incase of Strip) or twice the diameter(fir Conductors) in cm. ρ = Resistivity of the soil in Ω m Rg = Resistance of the earth conductor
Rg =
( 100 x ρ ) ( 2 x ∏ x L)
Rg =
(100 x 151.39) (2 x 3.142 x 3300)
Rg =
0.730041
Rg =
7.67
ln
X
( 2 x L² ) (ωx t) ln
(2 x 10890000) (80 x 7.5)
10.500
The resistance of the earth Conductor (Strip)
2
DOC.NO.-EL00007,REV-02
Rg =
7.67
ohms
18 OF 42
TH-2A
Resistance of earth Electrode (Steel Rod Or Pipe) As per IS:3043 clause no.9.2.2 l
= Length of rod or Pipe (in Cm)
d = Diameter of rod or pipe in cm
ρ = Resistivity of the soil in Ω m Re = Resistance of the earth Electrode The resistance of earth electrode is given by
Re =
( 100 x ρ ) ( 2 x ∏ x l)
Re =
(100 x 151.39) (2 x 3.142 x 300)
Re =
8.030448
Re =
38.45
ln
X
4x
l d
ln
4
1 Rn-1
+
X
300 10
4.787
The resistance of the earth electrode
Re =
38.45
ohms
The Earth resistance with numbers of Electrodes:-
1 = R 1 = R
1 R1
+ 1
38.45
1 -----R2
1 38.45
+
1 Rn 1
+
---------------------
38.45
1 Rn
Finally we calculate as
4
Add no. of pits n
the Combined value of n pits
R13 =
R1- Total Resistance of Earth Electrodes(pits)
(Re)
9.61
Ω
R2 - Total Earth Resistance of the buried Conductor
(Rg)
7.67
Ω
9.61
Ohms
2
Refer Annexure-XIII 1 R 1 R
=
1 R1
+
1 9.61
=
2
1 R2 +
1 7.67
Hence the combined resistance of grid + Earth pits R
R
2
DOC.NO.-EL00007,REV-02
=
=
R13A =
R1
x
R2
R1
+
R2
=
9.61 9.61
x +
7.67 7.67
73.67 17.28
4.26
Ohms
19 OF 42
TH-2A
SILO BUILDING GROUNDING CALCULATION
ANNEXURE-III REFERENCE IEC:60364-5-54 IS:3043
=
ENTER THE VALUE IN YELLOW COLOR BOXES ONLY
STEP-1 : BASIC DESIGN DATA 1.00 SYSTEM DATA
Vs
1.01 System nominal voltage 1.02
The value (r.m.s) in A of prospective fault current for a fault of negligible impedance, which can flow through the protective device (see IEC 60909-0);
1.03 The operating time of the protective device for automatic disconnection in s; 1.04 Fault clearing time 1.05 Length and breadth of the earth grid around Substation
If
= =
ts
=
tsc
=
LxB
=
415
V
50
kA
1
sec
1 11
sec x
9.6
1.06 Area of earth grid around Substation
A
=
105.6
1.07 Resistivity of the soil
ρ
=
151.39
1.09 Design Ambient temperature
Ta
=
45
°C
m
m
2
Ω-m
2.00 Buried earth conductor (strip) 2.01 Length of burial of Earthing Strip
L
=
4120.0
cm
2.02 Depth of burial of conductor (Strip)
ω
=
80
cm
2.03 Width (Incase of strip) of the conductor (Strip)
t
=
7.50
cm
Pipe
=
G.I.Pipe
2.06 Length of earth electrode rod/pipe
l
=
3
Mtr.
2.07 Diameter of earth electrode rod/pipe
d
=
100
mm
2
2.04 Earth conductor (Rod or Pipe) 2.05 Earth Electrode Material (Rod or Pipe)
2
Resistance of Buried earth conductor (Strip) The resistance of earth grid can be calculated by using the formula As per IS:3043 clause no.9.2.3
L = Length of the Strip (in Cm) ω = Depth of burial of the Earthing strip cm t = Width(incase of Strip) or twice the diameter(fir Conductors) in cm. ρ = Resistivity of the soil in Ω m Rg = Resistance of the earth conductor
Rg
=
( 100 x ρ ) ( 2 x ∏ x L)
Rg
=
(100 x 151.39) (2 x 3.142 x 4120)
Rg
=
0.584741
Rg
=
6.40
ln
X
( 2 x L² ) (ωx t) ln
(2 x 16974400) (80 x 7.5)
10.943
The resistance of the earth Conductor (Strip)
2
DOC.NO.-EL00007,REV-02
Rg
=
6.40
ohms
20 OF 42
SILO BUILDING
Resistance of earth Electrode (Steel Rod Or Pipe) As per IS:3043 clause no.9.2.2 l
= Length of rod or Pipe (in Cm)
d = Diameter of rod or pipe in cm
ρ = Resistivity of the soil in Ω m Re = Resistance of the earth Electrode The resistance of earth electrode is given by
Re
=
( 100 x ρ ) ( 2 x ∏ x l)
Re
=
(100 x 151.39) (2 x 3.142 x 300)
Re
=
8.030448
Re
=
38.45
ln
X
4x
l d
ln
4
300 10
X
4.787
The resistance of the earth electrode
Re
=
38.45
ohms
2
The Earth resistance with numbers of Electrodes:-
1 R
=
1 R
=
1 R1
+ 1
38.45
1 -----R2
1 Rn-1
1 38.45
+
1 Rn
+
1
+
---------------------
38.45
1 Rn
Finally we calculate as
4
Add no. of electrode per pits
the Combined value of n pits
R3
R1- Total Resistance of Earth Electrodes(pits)
(Re)
9.6
Ω
R2 - Total Earth Resistance of the buried Conductor
(Rg)
6.40
Ω
=
9.61
Ohms
Refer Annexure-III 1 R
= 1
R
1 R1
+
1 9.61
=
2
1 R2 +
1 6.40
Hence the combined resistance of grid + Earth pits R
R
2
DOC.NO.-EL00007,REV-02
=
=
R3A =
R1
x
R2
R1
+
R2
=
9.61 9.61
x +
6.40 6.40
61.50 16.01
3.84
Ohms
21 OF 42
SILO BUILDING
TAIL DRIVE HOUSE GROUNDING CALCULATION
ANNEXURE-XII REFERENCE IEC:60364-5-54 IS:3043
=
ENTER THE VALUE IN YELLOW COLOR BOXES ONLY
STEP-1 : BASIC DESIGN DATA 1.00 SYSTEM DATA
Vs
1.01 System nominal voltage 1.02
The value (r.m.s) in A of prospective fault current for a fault of negligible impedance, which can flow through the protective device (see IEC 60909-0);
1.03 The operating time of the protective device for automatic disconnection in s; 1.04 Fault clearing time 1.05 Length and breadth of the earth grid around Substation
If
= =
ts
=
tsc
=
LxB
=
415
V
50
kA
1
sec
1 20.5
sec x
16.5
1.06 Area of earth grid around Substation
A
=
338.25
1.07 Resistivity of the soil
ρ
=
151.39
1.09 Design Ambient temperature
Ta
=
45
°C
2.01 Length of burial of Earthing Strip
L
=
7400.0
cm
2.02 Depth of burial of conductor (Strip)
ω
=
80
cm
2.03 Width (Incase of strip) of the conductor (Strip)
t
=
7.5
cm
Pipe
=
G.I.Pipe
2.06 Length of earth electrode rod/pipe
l
=
3
Mtr.
2.07 Diameter of earth electrode rod/pipe
d
=
100
mm
m
m
2
Ω-m
2.00 Buried earth conductor (strip)
2.04 Earth conductor (Rod or Pipe) 2.05 Earth Electrode Material (Rod or Pipe)
2
Resistance of Buried earth conductor (Strip) The resistance of earth grid can be calculated by using the formula As per IS:3043 clause no.9.2.3
L = Length of the Strip (in Cm) ω = Depth of burial of the Earthing strip cm t = Width(incase of Strip) or twice the diameter(fir Conductors) in cm. ρ = Resistivity of the soil in Ω m Rg = Resistance of the earth conductor
Rg
=
( 100 x ρ ) ( 2 x ∏ x L)
ln
Rg =
(100 x 151.39) (2 x 3.142 x 7400)
Rg =
0.325559
Rg =
3.94
X
( 2 x L² ) (ωx t) ln
(2 x 54760000) (80 x 7.5)
12.115
The resistance of the earth Conductor (Strip)
Rg =
DOC.NO.-EL00007,REV-02
3.94
ohms
22 OF 42
TRAVEL DRIVE HOUSE
Resistance of earth Electrode (Steel Rod Or Pipe) As per IS:3043 clause no.9.2.2 l
= Length of rod or Pipe (in Cm)
d = Diameter of rod or pipe in cm
ρ = Resistivity of the soil in Ω m Re = Resistance of the earth Electrode The resistance of earth electrode is given by
Re
=
( 100 x ρ ) ( 2 x ∏ x l)
Re
=
(100 x 151.39) (2 x 3.142 x 300)
Re
=
8.030448
Re
=
38.45
ln
X
4x
l d
ln
4
X
300 10
4.787
The resistance of the earth electrode
Re =
38.45
ohms
2
The overall earth resistance of Electrodes:-
1 = R 1 = R
1 R1
+ 1
38.45
1 -----R2
1 Rn-1
1 38.45
+
1 Rn
+
1
+
---------------------
38.45
1 Rn
Finally we calculate as
4
Add no. of pits n
the Combined value of n pits
R12 =
R1- Total Resistance of Earth Electrodes(pits)
(Re)
9.61
Ω
R2 - Total Earth Resistance of the buried Conductor
(Rg)
3.94
Ω
9.61
Ohms
Refer Annexure-XII 1 R 1 R
=
1 R1
+
1 9.61
=
2
1 R2 +
1 3.94
Hence the combined resistance of grid + Earth pits R
R
=
=
R12A =
DOC.NO.-EL00007,REV-02
R1
x
R2
R1
+
R2
=
9.61 9.61
x +
3.94 3.94
37.91 13.56
2.80
Ohms
23 OF 42
TRAVEL DRIVE HOUSE
PARKING STATION-1 GROUNDING CALCULATION
ANNEXURE-V REFERENCE IEC:60364-5-54 IS:3043
=
ENTER THE VALUE IN YELLOW COLOR BOXES ONLY
STEP-1 : BASIC DESIGN DATA 1.00 SYSTEM DATA
Vs
1.01 System nominal voltage 1.02
The value (r.m.s) in A of prospective fault current for a fault of negligible impedance, which can flow through the protective device (see IEC 60909-0);
1.03 The operating time of the protective device for automatic disconnection in s; 1.04 Fault clearing time 1.05 Length and breadth of the earth grid around Substation
If
= =
ts
=
tsc
=
LxB
=
415
V
50
kA
1
sec
1 10
sec x
12
1.06 Area of earth grid around Substation
A
=
120
1.07 Resistivity of the soil
ρ
=
151.39
1.09 Design Ambient temperature
Ta
=
45
°C
m
m
2
Ω-m
2.00 Buried earth conductor (strip) 2.01 Length of burial of Earthing Strip
L
=
4400.0
cm
2.02 Depth of burial of conductor (Strip)
ω
=
80
cm
2.03 Width (Incase of strip) of the conductor (Strip)
t
=
7.50
cm
Pipe
=
G.I.Pipe
2.06 Length of earth electrode rod/pipe
l
=
3
Mtr.
2.07 Diameter of earth electrode rod/pipe
d
=
100
mm
2
2.04 Earth conductor (Rod or Pipe) 2.05 Earth Electrode Material (Rod or Pipe)
2
Resistance of Buried earth conductor (Strip) The resistance of earth grid can be calculated by using the formula As per IS:3043 clause no.9.2.3
L = Length of the Strip (in Cm) ω = Depth of burial of the Earthing strip cm t = Width(incase of Strip) or twice the diameter(fir Conductors) in cm. ρ = Resistivity of the soil in Ω m Rg = Resistance of the earth conductor
Rg
=
( 100 x ρ ) ( 2 x ∏ x L)
Rg
=
(100 x 151.39) (2 x 3.142 x 4400)
Rg
=
0.547531
Rg
=
6.06
ln
X
( 2 x L² ) (ωx t) ln
(2 x 19360000) (80 x 7.5)
11.075
The resistance of the earth Conductor (Strip)
2
DOC.NO.-EL00007,REV-02
Rg =
6.06
ohms
24 OF 42
PARKING STATION-1
Resistance of earth Electrode (Steel Rod Or Pipe) As per IS:3043 clause no.9.2.2 l
= Length of rod or Pipe (in Cm)
d = Diameter of rod or pipe in cm
ρ = Resistivity of the soil in Ω m Re = Resistance of the earth Electrode The resistance of earth electrode is given by
Re
=
( 100 x ρ ) ( 2 x ∏ x l)
Re
=
(100 x 151.39) (2 x 3.142 x 300)
Re
=
8.030448
Re
=
38.45
ln
X
4x
l d
ln
4
1 Rn-1
+
X
300 10
4.787
The resistance of the earth electrode
Re
=
38.45
ohms
The overall earth resistance of Electrodes:-
1 = R 1 = R
1 R1
+ 1
38.45
1 -----R2
1 38.45
+
1 Rn 1
+
---------------------
38.45
1 Rn
Finally we calculate as
4
Add no. of pits n
the Combined value of n pits
R5
R1- Total Resistance of Earth Electrodes(pits)
(Re)
9.61
Ω
R2 - Total Earth Resistance of the buried Conductor
(Rg)
6.06
Ω
=
9.61
Ohms
Refer Annexure-V 1 R
= 1
R
1 R1
+
1 9.61
=
2
2
1 R2 +
1 6.06
Hence the combined resistance of grid + Earth pits R
R
2
DOC.NO.-EL00007,REV-02
=
=
R5A =
R1
x
R2
R1
+
R2
=
9.61 9.61
x +
6.06 6.06
58.28 15.68
3.72
Ohms
25 OF 42
PARKING STATION-1
PARKING STATION-2 GROUNDING CALCULATION
ANNEXURE-XIV REFERENCE IEC:60364-5-54 IS:3043
=
ENTER THE VALUE IN YELLOW COLOR BOXES ONLY
STEP-1 : BASIC DESIGN DATA 1.00 SYSTEM DATA
Vs
1.01 System nominal voltage 1.02
The value (r.m.s) in A of prospective fault current for a fault of negligible impedance, which can flow through the protective device (see IEC 60909-0);
1.03 The operating time of the protective device for automatic disconnection in s; 1.04 Fault clearing time 1.05 Length and breadth of the earth grid around Substation
If
= =
ts
=
tsc
=
LxB
=
415
V
50
kA
1
sec
1 10
sec x
12
1.06 Area of earth grid around Substation
A
=
120
1.07 Resistivity of the soil
ρ
=
35.1
1.09 Design Ambient temperature
Ta
=
45
°C
m
m
2
Ω-m
2.00 Buried earth conductor (strip) 2.01 Length of burial of Earthing Strip
L
=
4400.0
cm
2.02 Depth of burial of conductor (Strip)
ω
=
80
cm
2.03 Width (Incase of strip) of the conductor (Strip)
t
=
7.50
cm
Pipe
=
G.I.Pipe
2.06 Length of earth electrode rod/pipe
l
=
3
Mtr.
2.07 Diameter of earth electrode rod/pipe
d
=
100
mm
2
2.04 Earth conductor (Rod or Pipe) 2.05 Earth Electrode Material (Rod or Pipe)
2
Resistance of Buried earth conductor (Strip) The resistance of earth grid can be calculated by using the formula As per IS:3043 clause no.9.2.3
L = Length of the Strip (in Cm) ω = Depth of burial of the Earthing strip cm t = Width(incase of Strip) or twice the diameter(fir Conductors) in cm. ρ = Resistivity of the soil in Ω m Rg = Resistance of the earth conductor
Rg =
( 100 x ρ ) ( 2 x ∏ x L)
Rg =
(100 x 35.1) (2 x 3.142 x 4400)
Rg =
0.126946
Rg =
1.41
ln
X
( 2 x L² ) (ωx t) ln
(2 x 19360000) (80 x 7.5)
11.075
The resistance of the earth Conductor (Strip)
Rg =
DOC.NO.-EL00007,REV-02
1.41
ohms
26 OF 42
PARKING STATION-2
Resistance of earth Electrode (Steel Rod Or Pipe) As per IS:3043 clause no.9.2.2 l
= Length of rod or Pipe (in Cm)
d = Diameter of rod or pipe in cm
ρ = Resistivity of the soil in Ω m Re = Resistance of the earth Electrode The resistance of earth electrode is given by
Re =
( 100 x ρ ) ( 2 x ∏ x l)
Re =
(100 x 35.1) (2 x 3.142 x 300)
Re =
1.861871
Re =
8.91
ln
X
4x
l d
ln
4
300 10
X
4.787
The resistance of the earth electrode
Re =
8.91
ohms
2
The overall earth resistance of Electrodes:-
1 = R
1 R1
+ 1
1 = R
1 -----R2
1 8.91
+
8.91
1 Rn-1
1 Rn
+
1
+
---------------------
8.91
1 Rn
Finally we calculate as
2
Add no. of pits n
the Combined value of n pits
R14
R1- Total Resistance of Earth Electrodes(pits)
(Re)
4.46
Ω
R2 - Total Earth Resistance of the buried Conductor
(Rg)
1.41
Ω
=
4.46
Ohms
Refer Annexure-XIV 1 R 1 R
=
1 R1
+
1 4.46
=
2
1 R2 +
1 1.41
Hence the combined resistance of grid + Earth pits R
R
2
DOC.NO.-EL00007,REV-02
=
=
R14A =
R1
x
R2
R1
+
R2
=
4.46 4.46
x +
1.41 1.41
6.27 5.86
1.07
Ohms
27 OF 42
PARKING STATION-2
TRANSFER HOUSE (TH-3) GROUNDING CALCULATION
ANNEXURE-VI REFERENCE IEC:60364-5-54 IS:3043
=
ENTER THE VALUE IN YELLOW COLOR BOXES ONLY
STEP-1 : BASIC DESIGN DATA 1.00 SYSTEM DATA
Vs
1.01 System nominal voltage 1.02
The value (r.m.s) in A of prospective fault current for a fault of negligible impedance, which can flow through the protective device (see IEC 60909-0);
1.03 The operating time of the protective device for automatic disconnection in s; 1.04 Fault clearing time 1.05 Length and breadth of the earth grid around Substation
If
= =
ts
=
tsc
=
LxB
=
415
V
50
kA
1
sec
1 10.265
sec x
9.5
1.06 Area of earth grid around Substation
A
=
97.5175
1.07 Resistivity of the soil
ρ
=
35.1
1.09 Design Ambient temperature
Ta
=
45
°C
2.01 Length of burial of Earthing Strip
L
=
3953.0
cm
2.02 Depth of burial of conductor (Strip)
ω
=
80
cm
2.03 Width (Incase of strip) of the conductor (Strip)
t
=
7.50
cm
Pipe
=
G.I.Pipe
2.06 Length of earth electrode rod/pipe
l
=
3
Mtr.
2.07 Diameter of earth electrode rod/pipe
d
=
100
mm
m
m
2
Ω-m
2.00 Buried earth conductor (strip)
2
2.04 Earth conductor (Rod or Pipe) 2.05 Earth Electrode Material (Rod or Pipe)
2
Resistance of Buried earth conductor (Strip) The resistance of earth grid can be calculated by using the formula As per IS:3043 clause no.9.2.3
L = Length of the Strip (in Cm) ω = Depth of burial of the Earthing strip cm t = Width(incase of Strip) or twice the diameter(fir Conductors) in cm. ρ = Resistivity of the soil in Ω m Rg = Resistance of the earth conductor
Rg =
( 100 x ρ ) ( 2 x ∏ x L)
Rg =
(100 x 35.1) (2 x 3.142 x 3953)
Rg =
0.141301
Rg =
1.53
ln
X
( 2 x L² ) (ωx t) ln
(2 x 15626209) (80 x 7.5)
10.861
The resistance of the earth Conductor (Strip)
2
DOC.NO.-EL00007,REV-02
Rg =
1.53
ohms
28 OF 42
TH-3
Resistance of earth Electrode (Steel Rod Or Pipe) As per IS:3043 clause no.9.2.2 l
= Length of rod or Pipe (in Cm)
d = Diameter of rod or pipe in cm
ρ = Resistivity of the soil in Ω m Re = Resistance of the earth Electrode The resistance of earth electrode is given by
Re =
( 100 x ρ ) ( 2 x ∏ x l)
Re =
(100 x 35.1) (2 x 3.142 x 300)
Re =
1.861871
Re =
8.91
ln
X
4x
l d
ln
4
1 Rn-1
+
300 10
X
4.787
The resistance of the earth electrode
Re =
8.91
ohms
The overall earth resistance of Electrodes:-
1 = R
1 R1
+ 1
1 = R
1 -----R2
1 8.91
+
8.91
1 Rn 1
+
---------------------
8.91
1 Rn
Finally we calculate as
4
Add no. of pits n
the Combined value of n pits
R6
R1- Total Resistance of Earth Electrodes(pits)
(Re)
2.23
Ω
R2 - Total Earth Resistance of the buried Conductor
(Rg)
1.53
Ω
=
2.23
Ohms
Refer Annexure-VI 1 R 1 R
=
1 R1
+
1 2.23
=
2
1 R2 +
1 1.53
Hence the combined resistance of grid + Earth pits R
R
2
DOC.NO.-EL00007,REV-02
=
=
R6A =
R1
x
R2
R1
+
R2
=
2.23 2.23
x +
1.53 1.53
3.42 3.76
0.91
Ohms
29 OF 42
TH-3
TRANSFER HOUSE (TH-5) GROUNDING CALCULATION
ANNEXURE-VII REFERENCE IEC:60364-5-54 IS:3043
=
ENTER THE VALUE IN YELLOW COLOR BOXES ONLY
STEP-1 : BASIC DESIGN DATA 1.00 SYSTEM DATA
Vs
1.01 System nominal voltage 1.02
The value (r.m.s) in A of prospective fault current for a fault of negligible impedance, which can flow through the protective device (see IEC 60909-0);
1.03 The operating time of the protective device for automatic disconnection in s; 1.04 Fault clearing time 1.05 Length and breadth of the earth grid around Substation
If
= =
415
V
50
kA
1
sec
ts
=
tsc
=
1
LxB
=
16.95
sec x
12.5
1.06 Area of earth grid around Substation
A
=
211.875
1.07 Resistivity of the soil
ρ
=
41.94
1.09 Design Ambient temperature
Ta
=
45
°C
2.01 Length of burial of Earthing Strip
L
=
5890.0
cm
2.02 Depth of burial of conductor (Strip)
ω
=
80
cm
2.03 Width (Incase of strip) of the conductor (Strip)
t
=
7.50
cm
Pipe
=
G.I.Pipe
2.06 Length of earth electrode rod/pipe
l
=
3
cm
2.07 Diameter of earth electrode rod/pipe
d
=
100
cm
m
m
2
Ω-m
2.00 Buried earth conductor (strip)
2
2.04 Earth conductor (Rod or Pipe) 2.05 Earth Electrode Material (Rod or Pipe)
2
Resistance of Buried earth conductor (Strip) The resistance of earth grid can be calculated by using the formula As per IS:3043 clause no.9.2.3
L = Length of the Strip (in Cm) ω = Depth of burial of the Earthing strip cm t = Width(incase of Strip) or twice the diameter(fir Conductors) in cm. ρ = Resistivity of the soil in Ω m Rg = Resistance of the earth conductor
Rg =
( 100 x ρ ) ( 2 x ∏ x L)
Rg =
(100 x 41.94) (2 x 3.142 x 5890)
Rg =
0.113312
Rg =
1.32
ln
X
( 2 x L² ) (ωx t) ln
(2 x 34692100) (80 x 7.5)
11.658
The resistance of the earth Conductor (Strip)
2
DOC.NO.-EL00007,REV-02
Rg =
1.32
ohms
30 OF 42
TH-5
Resistance of earth Electrode (Steel Rod Or Pipe) As per IS:3043 clause no.9.2.2 l
= Length of rod or Pipe (in Cm)
d = Diameter of rod or pipe in cm
ρ = Resistivity of the soil in Ω m Re = Resistance of the earth Electrode The resistance of earth electrode is given by
Re =
( 100 x ρ ) ( 2 x ∏ x l)
Re =
(100 x 41.94) (2 x 3.142 x 300)
Re =
2.224698
Re =
10.65
ln
X
4x
l d
ln
4
1 Rn-1
+
X
300 10
4.787
The resistance of the earth electrode
Re =
10.65
ohms
The overall earth resistance of Electrodes:-
1 = R 1 = R
1 R1
+ 1
10.65
1 -----R2
1 10.65
+
1 Rn 1
+
---------------------
10.65
1 Rn
Finally we calculate as
4
Add no. of pits n
the Combined value of n pits
R7
=
2.66
Ohms
Note:- Refer the Earthing Pit & Strip Scheme for overall plant.
R1- Total Resistance of Earth Electrodes(pits)
(Re)
2.66
Ω
R2 - Total T t lE Earth th R Resistance i t off the th buried b i d Conductor C d t
(R ) (Rg)
1 32 1.32
Ω
Refer Annexure-VII 1 R 1 R
=
1 R1
+
1 2.66
=
2
1 R2 +
1 1.32
Hence the combined resistance of grid + Earth pits R
R
2
DOC.NO.-EL00007,REV-02
=
=
R7A =
R1
x
R2
R1
+
R2
=
2.66 2.66
x +
1.32 1.32
3.52 3.98
0.88
Ohms
31 OF 42
TH-5
TRANSFER HOUSE (TH-6) GROUNDING CALCULATION
ANNEXURE-XVI REFERENCE IEC:60364-5-54 IS:3043
=
ENTER THE VALUE IN YELLOW COLOR BOXES ONLY
STEP-1 : BASIC DESIGN DATA 1.00 SYSTEM DATA
Vs
1.01 System nominal voltage 1.02
The value (r.m.s) in A of prospective fault current for a fault of negligible impedance, which can flow through the protective device (see IEC 60909-0);
1.03 The operating time of the protective device for automatic disconnection in s; 1.04 Fault clearing time 1.05 Length and breadth of the earth grid around Substation
If
= =
415
V
50
kA
1
sec
ts
=
tsc
=
1
LxB
=
10.85
sec x
6.5
1.06 Area of earth grid around Substation
A
=
70.525
1.07 Resistivity of the soil
ρ
=
128.94
1.09 Design Ambient temperature
Ta
=
45
°C
2.01 Length of burial of Earthing Strip
L
=
3470.0
cm
2.02 Depth of burial of conductor (Strip)
ω
=
80
cm
2.03 Width (Incase of strip) of the conductor (Strip)
t
=
7.50
cm
Pipe
=
G.I.Pipe
2.06 Length of earth electrode rod/pipe
l
=
3
Mtr.
2.07 Diameter of earth electrode rod/pipe
d
=
100
mm
m
m
2
Ω-m
2.00 Buried earth conductor (strip)
2
2.04 Earth conductor (Rod or Pipe) 2.05 Earth Electrode Material (Rod or Pipe)
2
Resistance of Buried earth conductor (Strip) The resistance of earth grid can be calculated by using the formula As per IS:3043 clause no.9.2.3
L = Length of the Strip (in Cm) ω = Depth of burial of the Earthing strip cm t = Width(incase of Strip) or twice the diameter(fir Conductors) in cm. ρ = Resistivity of the soil in Ω m Rg = Resistance of the earth conductor
Rg =
( 100 x ρ ) ( 2 x ∏ x L)
Rg =
(100 x 128.94) (2 x 3.142 x 3470)
Rg =
0.591319
Rg =
6.27
ln
X
( 2 x L² ) (ωx t) ln
(2 x 12040900) (80 x 7.5)
10.600
The resistance of the earth Conductor (Strip)
2
DOC.NO.-EL00007,REV-02
Rg =
6.27
ohms
32 OF 42
TH-6
Resistance of earth Electrode (Steel Rod Or Pipe) As per IS:3043 clause no.9.2.2 l
= Length of rod or Pipe (in Cm)
d = Diameter of rod or pipe in cm
ρ = Resistivity of the soil in Ω m Re = Resistance of the earth Electrode The resistance of earth electrode is given by
Re =
( 100 x ρ ) ( 2 x ∏ x l)
Re =
(100 x 128.94) (2 x 3.142 x 300)
Re =
6.839593
Re =
32.74
ln
X
4x
l d
ln
4
1 Rn-1
+
300 10
X
4.787
The resistance of the earth electrode
Re =
32.74
ohms
The overall earth resistance of Electrodes:-
1 = R 1 = R
1 R1
+ 1
32.74
1 -----R2
1 32.74
+
2
1 Rn 1
+
---------------------
32.74
1 Rn
Finally we calculate as
4
Add no. of pits n
the Combined value of n pits
R16 =
8.19
Ohms
Note:- Refer the Earthing Pit & Strip Scheme for overall plant.
R1- Total Resistance of Earth Electrodes(pits)
(Re)
8.19
Ω
R2 - Total T t lE Earth th R Resistance i t off the th buried b i d Conductor C d t
(R ) (Rg)
6 27 6.27
Ω
Refer Annexure-XVI 1 R 1 R
=
1 R1
+
1 8.19
=
2
1 R2 +
1 6.27
Hence the combined resistance of grid + Earth pits R R
2
DOC.NO.-EL00007,REV-02
= =
R16A =
R1
x
R2
R1
+
R2
=
8.19 8.19
x +
6.27 6.27
51.31 14.45
3.55
Ohms
33 OF 42
TH-6
PUMP HOUSE-1 GROUNDING CALCULATION
ANNEXURE-VIII REFERENCE IEC:60364-5-54 IS:3043
=
ENTER THE VALUE IN YELLOW COLOR BOXES ONLY
STEP-1 : BASIC DESIGN DATA 1.00 SYSTEM DATA
Vs
1.01 System nominal voltage 1.02
The value (r.m.s) in A of prospective fault current for a fault of negligible impedance, which can flow through the protective device (see IEC 60909-0);
1.03 The operating time of the protective device for automatic disconnection in s; 1.04 Fault clearing time 1.05 Length and breadth of the earth grid around Substation
If
= =
ts
=
tsc
=
LxB
=
415
V
50
kA
1
sec
1 11
sec x
6.5
1.06 Area of earth grid around Substation
A
=
71.5
1.07 Resistivity of the soil
ρ
=
205.51
1.09 Design Ambient temperature
Ta
=
45
°C
2.01 Length of burial of Earthing Strip
L
=
3500.0
cm
2.02 Depth of burial of conductor (Strip)
ω
=
80
cm
2.03 Width (Incase of strip) of the conductor (Strip)
t
=
7.50
cm
Pipe
=
G.I.Pipe
2.06 Length of earth electrode rod/pipe
l
=
3
Mtr.
2.07 Diameter of earth electrode rod/pipe
d
=
100
mm
m
m
2
Ω-m
2.00 Buried earth conductor (strip)
2
2.04 Earth conductor (Rod or Pipe) 2.05 Earth Electrode Material (Rod or Pipe)
2
Resistance of Buried earth conductor (Strip) The resistance of earth grid can be calculated by using the formula As per IS:3043 clause no.9.2.3
L = Length of the Strip (in Cm) ω = Depth of burial of the Earthing strip cm t = Width(incase of Strip) or twice the diameter(fir Conductors) in cm. ρ = Resistivity of the soil in Ω m Rg = Resistance of the earth conductor
Rg =
( 100 x ρ ) ( 2 x ∏ x L)
Rg =
(100 x 205.51) (2 x 3.142 x 3500)
Rg =
0.934391
Rg =
9.92
ln
X
( 2 x L² ) (ωx t) ln
(2 x 12250000) (80 x 7.5)
10.617
The resistance of the earth Conductor (Strip)
2
DOC.NO.-EL00007,REV-02
Rg =
9.92
ohms
34 OF 42
PUMP HOUSE-1
Resistance of earth Electrode (Steel Rod Or Pipe) As per IS:3043 clause no.9.2.2 l
= Length of rod or Pipe (in Cm)
d = Diameter of rod or pipe in cm
ρ = Resistivity of the soil in Ω m Re = Resistance of the earth Electrode The resistance of earth electrode is given by
Re =
( 100 x ρ ) ( 2 x ∏ x l)
Re =
(100 x 205.51) (2 x 3.142 x 300)
Re =
10.90123
Re =
52.19
ln
X
4x
l d
ln
4
1 Rn-1
+
X
300 10
4.787
The resistance of the earth electrode
Re =
52.19
ohms
The overall earth resistance of Electrodes:-
1 = R 1 = R
1 R1
+ 1
52.19
1 -----R2
1 52.19
+
1 Rn 1
+
---------------------
52.19
1 Rn
Finally we calculate as
5
Add no. of pits n
the Combined value of n pits
R8
=
10.44
Ohms
Note:- Refer the Earthing Pit & Strip Scheme for overall plant.
R1- Total Resistance of Earth Electrodes(pits)
(Re)
R2 - Total T t lE Earth th R Resistance i t off the th buried b i d Conductor C d t
(R ) (Rg)
10.44 Ω
Refer Annexure-VIII 1 R 1 R
=
=
1 R1
+
1 10.44
9 92 9.92
Ω
2
1 R2 +
1 9.92
Hence the combined resistance of grid + Earth pits R R
= =
R8A =
DOC.NO.-EL00007,REV-02
R1
x
R2
R1
+
R2
=
10.44 10.44
x +
9.92 9.92
103.55 20.36
5.09
Ohms
35 OF 42
PUMP HOUSE-1
PUMP HOUSE-2 GROUNDING CALCULATION
ANNEXURE-XVII REFERENCE IEC:60364-5-54 IS:3043
=
ENTER THE VALUE IN YELLOW COLOR BOXES ONLY
STEP-1 : BASIC DESIGN DATA 1.00 SYSTEM DATA
Vs
1.01 System nominal voltage 1.02
The value (r.m.s) in A of prospective fault current for a fault of negligible impedance, which can flow through the protective device (see IEC 60909-0);
1.03 The operating time of the protective device for automatic disconnection in s; 1.04 Fault clearing time 1.05 Length and breadth of the earth grid around Substation
If
=
415
V
50
kA
1
sec
=
ts
=
tsc
=
LxB
=
1 9
sec x
7.5
1.06 Area of earth grid around Substation
A
=
67.5
1.07 Resistivity of the soil
ρ
=
228.68
1.09 Design Ambient temperature
Ta
=
45
°C
2.01 Length of burial of Earthing Strip
L
=
3300.0
cm
2.02 Depth of burial of conductor (Strip)
ω
=
80
cm
2.03 Width (Incase of strip) of the conductor (Strip)
t
=
7.50
cm
Pipe
=
G.I.Pipe
2.06 Length of earth electrode rod/pipe
l
=
3
Mtr.
2.07 Diameter of earth electrode rod/pipe
d
=
100
mm
m
m
2
Ω-m
2.00 Buried earth conductor (strip)
2
2.04 Earth conductor (Rod or Pipe) 2.05 Earth Electrode Material (Rod or Pipe)
2
Resistance of Buried earth conductor (Strip) The resistance of earth grid can be calculated by using the formula As per IS:3043 clause no.9.2.3
L = Length of the Strip (in Cm) ω = Depth of burial of the Earthing strip cm t = Width(incase of Strip) or twice the diameter(fir Conductors) in cm. ρ = Resistivity of the soil in Ω m Rg = Resistance of the earth conductor
Rg =
( 100 x ρ ) ( 2 x ∏ x L)
Rg =
(100 x 228.68) (2 x 3.142 x 3300)
Rg =
1.102753
Rg =
11.58
ln
X
( 2 x L² ) (ωx t) ln
(2 x 10890000) (80 x 7.5)
10.500
The resistance of the earth Conductor (Strip)
2
DOC.NO.-EL00007,REV-02
Rg =
11.58
ohms
36 OF 42
PUMP HOUSE-2
Resistance of earth Electrode (Steel Rod Or Pipe) As per IS:3043 clause no.9.2.2 l
= Length of rod or Pipe (in Cm)
d = Diameter of rod or pipe in cm
ρ = Resistivity of the soil in Ω m Re = Resistance of the earth Electrode The resistance of earth electrode is given by
Re =
( 100 x ρ ) ( 2 x ∏ x l)
Re =
(100 x 228.68) (2 x 3.142 x 300)
Re =
12.13028
Re =
58.07
ln
X
4x
l d
ln
4
1 Rn-1
+
X
300 10
4.787
The resistance of the earth electrode
2
Re =
58.07
ohms
The overall earth resistance of Electrodes:-
1 = R 1 = R
1 R1
+ 1
58.07
1 -----R2
1 58.07
+
1 Rn 1
+
58.07
---------------------
1 Rn
Finally we calculate as
7
Add no. of pits n
the Combined value of n pits (RB)
R1- Total Resistance of Earth Electrodes(pits)
(Re)
R2 - Total Earth Resistance of the buried Conductor
(Rg)
8.30
=
8.30
Ohms
2
Ω
Refer Annexure-XVII 1 R 1 R
=
1 R1
+
1 8.30
=
11.58 Ω
2
1 R2 +
1 11.58
Hence the combined resistance of grid + Earth pits R
2
DOC.NO.-EL00007,REV-02
=
R
=
RB
=
R1
x
R2
R1
+
R2
=
8.30 8.30
x +
11.58 11.58
96.06 19.87
8.30
Ohms
37 OF 42
PUMP HOUSE-2
DHC AT NEAR AREA HTP-2 (TR-64) CALCULATION
ANNEXURE-IX REFERENCE IEC:60364-5-54 IS:3043
=
ENTER THE VALUE IN YELLOW COLOR BOXES ONLY
STEP-1 : BASIC DESIGN DATA 1.00
SYSTEM DATA Vs
1.01 System nominal voltage 1.02
The value (r.m.s) in A of prospective fault current for a fault of negligible impedance, which can flow through the protective device (see IEC 60909-0);
If
= =
415
V
50
kA
1.03 The operating time of the protective device for automatic disconnection in s;
ts
=
1
sec
1.04 Fault clearing time
tsc
=
1
sec
LxB
=
A
=
800
1.07 Resistivity of the soil at DHC HTP-2
ρ
=
70.15
1.09 Design Ambient temperature
Ta
=
45
°C
2.01 Length of burial of Earthing Strip
L
=
18000.0
cm
2.02 Depth of burial of conductor (Strip)
ω
=
80
cm
t
=
7.50
cm
1.05 Length and breadth of the earth grid around Substation 1.06 Area of earth grid around Substation
2.00
x
10 m2
Ω-m
Buried earth conductor (strip)
2.03 Width (Incase of strip) of the conductor (Strip) 2.04
80
Earth conductor (Rod or Pipe) Pipe
=
G.I.Pipe
2.06 Length of earth electrode rod/pipe
l
=
3
Mtr.
2.07 Diameter of earth electrode rod/pipe
d
=
100
mm
2.05 Earth Electrode Material (Rod or Pipe)
R i t Resistance off Buried B i d earth th conductor d t (Strip) (St i ) The resistance of earth grid can be calculated by using the formula As per IS:3043 clause no.9.2.3
L = Length of the Strip (in Cm) ω = Depth of burial of the Earthing strip cm t = Width(incase of Strip) or twice the diameter(fir Conductors) in cm. ρ = Resistivity of the soil in Ω m Rg = Resistance of the earth conductor
Rg =
( 100 x ρ ) ( 2 x ∏ x L)
Rg =
(100 x 70.15) (2 x 3.142 x 18000)
Rg =
0.062018
Rg =
0.86
ln
X
The resistance of the earth Conductor (Strip)
Rg =
0.86
ohms
( 2 x L² ) (ωx t) ln
13.892
(2 x 324000000) (80 x 7.5)
m
Resistance of earth Electrode (Steel Rod Or Pipe) As per IS:3043 clause no.9.2.2 l
= Length of rod or Pipe (in Cm)
d = Diameter of rod or pipe in cm
ρ = Resistivity of the soil in Ω m Re = Resistance of the earth Electrode The resistance of earth electrode is given by
Re =
( 100 x ρ ) ( 2 x ∏ x l)
Re =
(100 x 70.15) (2 x 3.142 x 300)
Re =
3.721091
Re =
17.81
4x
l d
ln
4
1 Rn-1
+
ln
X
300 10
X
4.787
The resistance of the earth electrode
Re =
17.81
ohms
The overall earth resistance of Electrodes:-
1 = R
1 R1
+ 1
1 = R
17.81
1 -----R2
1 17.81
+
1 Rn 1
+
---------------------
17.81
1 Rn
Finally we calculate as Add no. of pits
20
n
the Combined value of
n pits
=
0.89
Ohms
Note:- Refer the Earthing Pit & Strip Scheme for overall plant.
R1 Total R1T t lR Resistance i t off Earth E th Electrodes(pits) El t d ( it )
R1
(R ) (Re)
0 89 0.89
Ω
R2 - Total Earth Resistance of the buried Conductor
R2
(Rg)
0.86
Ω
Refer Annexure-IX 1 R 1 R
=
1 R1
+
1 0.89
=
1 R2 +
1 0.86
Hence the combined resistance of grid + Earth pits R
=
R
=
R3
=
R1
x
R2
R1
+
R2
0.89 0.89
=
x +
0.86 0.86
0.77 1.75
0.44
Ohms
Resistance of earth conductor (Strip) riser & DHC gantry strip at HTP-3 to HTP-6 The resistance of earth grid can be calculated by using the formula As per IS:3043 clause no.9.2.3
l = Length of the Strip (in m)
1950.0
=
A = Area of the earth conductor strip =
75
ρ = Resistivity of the GI conductor in Ω m
x
m 10
138 x 10-9
Rg = Resistance of the earth conductor
Rg =
Rg = Rg =
(lxρ) A (1950 x 138 x 10-9) -6 750 x 10 0.36
The resistance of the earth Conductor (Strip)
R4 =
0.359
ohms
750
Sqmm
R3- Total Resistance of Earth Electrodes(pits)+Grid Strip
R3 =
(Re)
0.44
Ω
R4 - Total Earth Resistance of the along the conveyor earth strip
R4 =
(Rg)
0.36
Ω
R
=
R3
+
R4
=
0.44
+
0.36
=
0.80
Hence the combined resistance of grid + Earth Strip
R9A =
0.80
Ohms
CLIENT CONSULTANT CONTRACTOR PROJECT: PACKAGEII : DOCUMENT NAME : DOCUMENT NO.
REV.
SIZING OF PLANT EARTHING CONDUCTOR SR.NO.
DESCRIPTION
A 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21
Main Grid and Connectivity to Plant earthing Substation‐1 (SS‐1) Substation‐2 (SS‐2) S b t ti 3 (SS 3) Substation‐3 (SS‐3) Transfer House (TH‐1) Transfer House (TH‐2) Transfer House (TH‐2A) Silo Building Tail drive House Transfer House (TH‐3) Transfer House (TH‐4) Transfer House (TH‐5) Transfer House (TH‐6) Transfer House (TH 6) Parking station (PS‐1) Parking station (PS‐2) Along the conv‐718 gallary cable Tray Along the conv‐719 gallary cable Tray Along the conv‐721 gallary cable Tray Along the conv‐727 gallary cable Tray Along the conv‐727‐1 gallary cable Tray Along the conv‐727‐2 gallary cable Tray Along the conv‐723 gallary cable Tray
B 1 2
Transformer Transformer Body Earthing Transformer Neutral Earthing
C 1 2 D 1 1.1 1.2 1.3 1.4 1.5 1.6 1.8 19 1.9
SIZE OF NO. OF EARTH EARTHING CONNECTION CONDUCTOR (SQMM)
NO OF RUN PER CONDUCTOR TYPE REMARKS CONNECT ION
75 x 10 mm 75 x 10 mm 75 10 75 x 10 mm 75 x 10 mm 75 x 10 mm 75 x 10 mm 75 x 10 mm 75 x 10 mm 75 x 10 mm 75 x 10 mm 75 x 10 mm 75 x 10 mm 75 x 10 mm 75 x 10 mm 75 x 10 mm 50 x 6 mm 50 x 6 mm 50 x 6 mm 50 x 6 mm 50 x 6 mm 50 x 6 mm 50 x 6 mm
1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1
GI Flat GI Flat GI Fl t GI Flat GI Flat GI Flat GI Flat GI Flat GI Flat GI Flat GI Flat GI Flat GI Flat GI Flat GI Flat GI Flat GI Flat GI Flat GI Flat GI Flat GI Flat GI Flat GI Flat
2 separate 2 separate
65 x 10 mm 65 x 10 mm
1 1
GI Flat GI Flat
HT Equipment 6.6kv HT panel at SS‐1 11kv HT panel at SS‐2
2 separate 2 separate
50 x 6 mm 50 x 6 mm
1 1
GI Flat GI Flat
LT E i LT Equipment t LT Power & Control Panels PMCC at SS‐1 PMCC at SS‐2 AC VENT MCC at SS‐1 AC VENT MCC at SS‐2 DFDS board at Pump House‐1 DFDS board at Pump House‐2 Hydraulic System Control Panels body earth Lubrication System Control Panels body earth Lubrication System Control Panels body earth
2 separate 2 separate 2 separate 2 separate 2 separate 2 separate 2 separate 2 separate 2 separate
60 x 10 mm 60 x 10 mm 60 x 10 mm 60 x 10 mm 60 x 10 mm 60 x 10 mm 25 x 6 mm 25 x 6 mm 25 x 6 mm
1 1 1 1 1 1 1 1
GI Flat GI Flat GI Flat GI Flat GI Flat GI Flat GI Flat GI Flat GI Flat
DOC.NO.-EL00007,REV-02
4 OF 42
PLANT CONCUCTOR
SR.NO.
SIZE OF NO. OF EARTH EARTHING CONNECTION CONDUCTOR (SQMM)
DESCRIPTION
2 2.1 2.2 2.3 2.4 2.5 2.6 2.7
LT Distribution Board Main Lighting Distribution Board Welding Distribution Board Auxiliary Power Distribution Board Lighting Distribution Board Field Power Distribution Board Local Push Buttons Board UPS ,UPS distribution Board Battery Charger & DCDB Battery Charger & DCDB
3 3.1 3.2 3.3 3.4 3.5 3.6 3.7 3.8 3.9
Electrical items 3 Phase Welding socket ‐Body earthing Exaust fan Lighting Fixture Celling Fan Socket 3 Pin Lighting JB Street Lighting pole Earthing g gp g Control Junction Box Power Junction Box
2 separate 2 separate 2 separate 2 separate 2 separate 2 separate 2 separate 2 separate 2 separate
50 x 6 mm 50 x 6 mm 50 x 6 mm 25 x 6 mm 25 x 6 mm 25 x 6 mm 25 x 6 mm 25 x 6 mm 25 x 6 mm
1 1 1 1 1 1 1 1
GI Flat GI Flat GI Flat GI Flat GI Flat GI Flat GI Flat GI Flat GI Flat
2 separate
16Sqmm
1
Stranded GI wire
Same size as phase conductor
2 2 separate 2 separate p 2 separate 2 separate
E 1 2 3 4
LT Motors LT Motors up to 2.2kw LT Motors 3.7kw to 15kw LT Motors 15 kw to 45kw LT Motors above 45kw
2 separate 2 separate 2 separate 2 separate
F 1 2 3 4 5 6 7 8 9
Field Instrument Pull cord switches Belt Sway Switches Zero speed Switches Chute Jam Switches Belt Weigh Switch Slip Switches Monoral Hoist PJB for Motors CJB for Motors CJB for Motors
2 separate 2 separate 2 separate 2 separate 2 separate 2 separate 2 separate 2 separate 2 separate 2 separate
DOC.NO.-EL00007,REV-02
NO OF RUN PER CONDUCTOR TYPE REMARKS CONNECT ION
16 Sq.mm 16 Sq.mm q 6 Sq.mm 6 Sq.mm
1 1 1 1
GI Wire GI Wire Stranded GI wire Stranded GI wire
6 Sq.mm 16 Sq.mm 25 x 3 mm 50 x 6 mm
1 1 1 1
Stranded GI wire Stranded GI wire GI Flat GI Flat
1 1 1 1 1 1 1 1 1
Stranded GI wire Stranded GI wire Stranded GI wire Stranded GI wire Stranded GI wire Stranded GI wire GI Flat GI Flat Stranded GI wire Stranded GI wire
6 Sq.mm 6 Sq.mm 6 Sq.mm 6 Sq.mm 6 Sq.mm 6 Sq.mm 25 x 6 mm Same as Motor 6 Sq.mm 6 Sq mm
5 OF 42
PLANT CONCUCTOR