SITE TEST REPORT
Replacement of 132/11kV Transformers, Transformers, Transformer Protection Panels and 110 V Batteries at W13 Substation (CONTRACT No. N6399)
Consultant
Name Name of the the Equipm Equipmen entt Nam amee of the the Fe Feeder Manufacturer Date
ENERGO
Main Contractor
40MV 40MVA A Power Power Transf Transform ormerer-T2 T201 01 E03 / K09 K09 Tra Transfo sforme rmer Fe Feeder ABB 20.02.2013
Page 1 – 10
40 MVA Power Transformer Stability Test 1. TRANSFORMER DETAILS:
MAKE
: ABB
SERIAL NO.
:4359245110
FREQUENCY
: 50Hz
TYPE OF COOLING
: ONAN/ONAF
VECTOR GROUP
: YN yn0+d11
NO OF TAPS
: 25
NOMINAL TAP
: 13
Feeder name- Bay- E03 at 132kV side and Bay K09 at 11kV side RATING WINDING
RATED POWER(MVA)
RATED VOLTAGE
RATED CURRENTS
ONAN/ONAF
(KV)
(A)
HV
31.5/40
132
137.8/175.0
MV
31.5/40
11.5
1581/2008
SW
10.5/13.3
8
757.7/962
IMPEDANCE VOLTAGE
IMPEDANCE
WINDING
POWER
HV VOLTAGES(KV)
%
HV-LV
AT 40MVA
Tap1—151.8
19.51
Tap13---132.0
17.69
Tap25---112.2
16.28
VOLTAGE
The CT T1 used For Differential protection (F87T)
CT ratio for 132kV Line side CT’s = 300/1A
Relay- RET670- ABB
CT ratio for 11kV Line side CT’s = 2500/1A The CT T3 used For REF protection at HV side side (F64HV)
Date Name Signature
Tested by
Witnessed by
ABB Transmission & Distribution
ENERGO
20.02.2013 R.Krishna Murthy
20.02.2013 Mohammad Rasheed
Approved by
SITE TEST REPORT
Replacement of 132/11kV Transformers, Transformer Protection Panels and 110 V Batteries at W13 Substation (CONTRACT No. N6399)
Consultant
Name of the Equipment Name of the Feeder Manufacturer Date
ENERGO
Main Contractor
CT ratio for 132kV Line side CT’s = 300/1A
40MVA Power Transformer-T201 E03 / K09 Transformer Feeder ABB 20.02.2013
Page 2 – 10
Relay- RET615- ABB
CT ratio for HV neutral side= 300/1A The CT5 used For REF protection at MV side (F64MV)
CT ratio for 11kV Line side CT’s = 2500/1A
Relay- RET615- ABB
CT ratio for MV neutral side= 2500/1A The CT1 used For SBEF protection at HV Neutral side (F51NHV )
CT ratio for HV neutral side= 300/1A
Relay- REF615- ABB
The CT4 used For SBEF protection at MV neutral side (F51NMV)
CT ratio for MV neutral side= 2500/1A
Relay- REF615- ABB
The CT9 used For SBEF protection at tertiary side (F51NT)
CT ratio for Tertiary neutral side= 300/1A
Relay- REF615- ABB
The CT T1 used For O/C & E/F protection at HV Line side (F51/51NHV)
CT ratio for 132kV Line side CT’s = 300/1A
Relay- REF615- ABB
Relay used for Over Voltage protection (F59)
VT Ratio 11kV/√3/110V/√3
Relay- REF615- ABB
A. Transformer Stability Test( RET 670) 1a) STABLE CONDITION (132kV BB2 Earth Q25 Closed)
Three phase voltage injected in 11kV side thru Bay K09(I/C-1), K11 and all CTs are normal
Date Name Signature
Tested by
Witnessed by
ABB Transmission & Distribution
ENERGO
20.02.2013 R.Krishna Murthy
20.02.2013 Mohammad Rasheed
Approved by
SITE TEST REPORT
Replacement of 132/11kV Transformers, Transformer Protection Panels and 110 V Batteries at W13 Substation (CONTRACT No. N6399)
Consultant
ENERGO
Main Contractor
PHASE
Name of the Equipment Name of the Feeder Manufacturer Date
Primary current (A) 132kV 11kV 111 112 109
R Y B
40MVA Power Transformer-T201 E03 / K09 Transformer Feeder ABB 20.02.2013
Relay Display Measurement (A) 132kV 11kV
151 150 151
34.17 34.55 33.98
Diff. Display Measurement (A) Diff. Rest
392 392 387
0 0 0
34.32
Page 3 – 10
CT Terminals Sec Current (A) 132kV 11kV 0.103 0.107 0.104
0.186 0.192 0.187
N 1b) UNSTABLE CONDITION (132kV side CT Bypassed by closing the Earth switch Q8 ) a)Three phase voltage injected in 11kV side thru Bay K09(I/C-1)**and all CT’s are Normal
Three phase voltage injected in 11kV side thru Bay K09(I/C-1)** and all CTs are normal PHASE Primary Test Plug (A) Diff. Display Relay Display (A) current (A) Measurement (A) 132kV 11kV 132kV 11kV Diff. Rest 132kV 11kV 111 152 110 151 0 34.2 34.2 193 R 111 110 -
Y B N REMARKS:
150 151 -
111 110 -
153 151 -
0 0 -
-
34.2 33.0 -
40 MVA Transformer diff Stability circuit found :- OK
B. 40 MVA TRANSFORMER HV REF PROTECTION STABILITY / SENSITIVITY TEST
Phase CT Ratio
Date Name Signature
: 300/1 A Tested by
Witnessed by
ABB Transmission & Distribution
ENERGO
20.02.2013 R.Krishna Murthy
20.02.2013 Mohammad Rasheed
Approved by
389 388 -
SITE TEST REPORT
Replacement of 132/11kV Transformers, Transformer Protection Panels and 110 V Batteries at W13 Substation (CONTRACT No. N6399)
Consultant
Name of the Equipment Name of the Feeder Manufacturer Date
ENERGO
Main Contractor Neutral CT Ratio
: 300/1 A
Relay Setting (Is)
:. A
Stabilizing resistor (final setting)
:_
Stabilizing resistor set at
:
Transformer Tap position
: 13
Primary current measured
:
40MVA Power Transformer-T201 E03 / K09 Transformer Feeder ABB 20.02.2013
Page 4 – 10
Ohm Ohm A
(132kV Earth switch Q25 (BB2 ESW) Close (BUSBAR -2 under Shutdown)
Winding Temperature CT Measurements: Phases R Y B RYB
HV Temp Sec.Current 0 245 0 270
MV Temp Sec. Current 0 462 0 370.9
HV Temp CT Ratio: 250/2A
MV Temp CT Ratio: 2050/2A Injection
LCC
RCC
Main Tariff
Check Tariff
R
Y
B
N
R
Y
B
N
R
Y
B
R
Y
B
R
30/154
0/48
0/47
-
30/150
0/47
0/47
-
0.5
0
0
0.5
0
0
Y
0/48
30/157
0/48.2
-
0/46
30/153
0/48
-
0
0.5
0
0
0.5
0
B
0/47
0/47
30/152
-
0/47
0/47
30/151
-
0
0
0.5
0
0
0.5
RYB
30/165
30/167
30/166
-
30/162
30/164
30/163
-
0.4
0.4
0.4
0.4
0.4
0.4
N
RTU
R
Y
B
R
153
47
47
Y
47
157
48
Date Name Signature
-
Tested by
Witnessed by
ABB Transmission & Distribution
ENERGO
20.02.2013 R.Krishna Murthy
20.02.2013 Mohammad Rasheed
Approved by
SITE TEST REPORT
Replacement of 132/11kV Transformers, Transformer Protection Panels and 110 V Batteries at W13 Substation (CONTRACT No. N6399)
Consultant
Name of the Equipment Name of the Feeder Manufacturer Date
ENERGO
Main Contractor B
47
47
152
-
RYB
164
168
165
-
40MVA Power Transformer-T201 E03 / K09 Transformer Feeder ABB 20.02.2013
Page 11 – 10
Remarks -:- CT circuits for Tr Diff.Stability, HV & MV REF stable confirmed. ** Three phase generator voltage injected through K11 spare bay at 11kV side