DESIGN REPORT-CONTROL BUILDING OF MANNAR TRANSMISSION INFRASTRUCTURE-LOT A-REV-02 CONTROL BUILDING OF MANNAR TRANSMISSION INFRASTRUCTURE
Design Report-Control Building of Mannar Transmission Infrastructure-Lot A-rev-02
1.0
INTRODUCTION
This report is prepared to highlight the Structural Analysis and Design Procedure of the Proposed Control Building of Mannar Transmission Infrastructure-Lot A Project. The Structural Engineering Consultancy Services involves designing of a Three Storey Building with a Basement Floor. The Structural Form of the building is selected as a "Framed Building". The Columns and Beams will resist the gravity loads and Lateral Loads will be resisted by the "Frame Action". Ground Floor is designed as a Part Slab on Grade and Part Part Suspended Slab. All the Other Floors are Designed Designed as Suspended Slabs. Foundations Foundations of the Buildings Buildings is designed as a combination of Beam-Raft Beam-Raft Slab and Individual Footings. Reinforcement detailing of elements were done considering the resistance to moderate earthquakes. This report consists of Load evaluation, structural modeling and Analysis, design calculations procedure for foundations and columns. Designs will be carried out as per relevant British Standards. Structure is analyzed in SAP 2000, version 16, an finite element structural analysis software package.
Prepared by Gihan Chathuranga, BSc.Eng(Hons), PG PG Dip in Strcut.Eng, Strcut.Eng, Design, C.Eng,MIE(SL),MSSE(SL) C.Eng,MIE(SL),MSSE(SL)
Page
1
Design Report-Control Building of Mannar Transmission Infrastructure-Lot A-rev-02
1.0
INTRODUCTION
This report is prepared to highlight the Structural Analysis and Design Procedure of the Proposed Control Building of Mannar Transmission Infrastructure-Lot A Project. The Structural Engineering Consultancy Services involves designing of a Three Storey Building with a Basement Floor. The Structural Form of the building is selected as a "Framed Building". The Columns and Beams will resist the gravity loads and Lateral Loads will be resisted by the "Frame Action". Ground Floor is designed as a Part Slab on Grade and Part Part Suspended Slab. All the Other Floors are Designed Designed as Suspended Slabs. Foundations Foundations of the Buildings Buildings is designed as a combination of Beam-Raft Beam-Raft Slab and Individual Footings. Reinforcement detailing of elements were done considering the resistance to moderate earthquakes. This report consists of Load evaluation, structural modeling and Analysis, design calculations procedure for foundations and columns. Designs will be carried out as per relevant British Standards. Structure is analyzed in SAP 2000, version 16, an finite element structural analysis software package.
Prepared by Gihan Chathuranga, BSc.Eng(Hons), PG PG Dip in Strcut.Eng, Strcut.Eng, Design, C.Eng,MIE(SL),MSSE(SL) C.Eng,MIE(SL),MSSE(SL)
Page
1
Design Report-Control Building of Mannar Transmission Infrastructure-Lot A
2.0
DESIGN INFORMATION AND REFERENCES
Design Information 2.1
Materials Density of Concrete
3
24kN/m
Characteristic Strength of Concrete (f cu ) For All Structural Elements of S ub Structure (Up to Ground
2 35N/m
Floor Level). For All Structural Elements Elements of Super Structure (From
2 25N/m
Ground Floor to Roof Level).
2.2
2
Yield Strength of Tor Steel (f y )
460N/mm
Yield Strength of Mild Steel (f vy )
250N/mm
2
Fire rating 2 hr fire rating
2.3
Exposure Conditions Severe Exposure Conditions
2.4
Cover to reinforcement
2.5
Slabs
25mm
Beams and Columns
30mm
Foundations
50mm
Loads 2.5.1
Dead Loads Dead load due to floor finishes
2 1.25kN/m
Prepared by Gihan Chathuranga, BSc.Eng(Hons), PG Dip in Strcut.Eng, Strcut.Eng, Design, C.Eng,MIE(SL),MSSE(SL) C.Eng,MIE(SL),MSSE(SL)
Page 2
Design Report-Control Building of Mannar Transmission Infrastructure-Lot A
Design Information 2.5.2
2.5.3
Live Loads Cable Basement
2 5kN/m
36kV Switch Gear Room
2 11.5kN/m
220kV Panel Room
2 11.5kN/m
Control Room
2 11.5kN/m
Auxiliary Room
2 11.5kN/m
Office Room
2 3.0kN/m
Roof Slab
2 1.5kN/m
Basic wind speed
47m/s
(This wind load complies to Zone 2 of Sr i Lanka)
2.5.4
2.6
Surcharge Loads for Retaining Walls
2 10kN/m
Soil Properties Bearing Capacity (refer to Annex 1-Extract from Soil Report)
2 175kN/m φ' 28 =
Friction Angle
Prepared by Gihan Chathuranga, BSc.Eng(Hons), PG Dip in Strcut.Eng, Strcut.Eng, Design, C.Eng,MIE(SL),MSSE(SL) C.Eng,MIE(SL),MSSE(SL)
Page 3
Design Report-Control Building of Mannar Transmission Infrastructure-Lot A
References Code of Practices 1
BS 8110:Part 1:1997 Structural use of Concrete
2
BS 8110:Part 2:1995 Structural use of Concrete
3
BS 8007:1987 Design of Concrete Structures Str uctures for retaining aqueous liquids.
4
BS 6399: PART 1: 1984 Imposed loads on Buildings
5
CP3 : Chapter V : Part II, 1972 Basic data for design of buildings – Wind loads
6
BS 8002:1994 Earth Retaining Structures
Other References 1
Reinforced Concrete Designer’s Hand Book (Eleventh Edition) C. E. Reynolds & James C. Steedman
2
Manual for the Design of Reinforced Concrete Building Structures Published by the Institute of Structural Engineers (UK)
3
Standard Method of detailing structural concrete Published by the Institute of Structural Engineers (UK)-August 1985
4
Standard Method of detailing structural concrete-Third edition Published by the Institute of Structural Engineers (UK
5
Reinforced Concrete Design to BS 8110 Simply Explained, by A.H. Allen.
6
Reinforced concrete design-Fifth edition W.H. Mosley,J.H. Bungey and R.Hussle
Prepared by Gihan Chathuranga, BSc.Eng(Hons), PG Dip in Strcut.Eng, Strcut.Eng, Design, C.Eng,MIE(SL),MSSE(SL) C.Eng,MIE(SL),MSSE(SL)
Page 4
Design Report-Control Building of Mannar Transmission Infrastructure-Lot A
References Other References cont’d. 7
Graded Example in Reinforced Concrete Design Prof.W.P.S Dias
8
Design of Buildings for High Winds in Sri Lanka Published by Ministry of local Government Housing and Construction
9
Reinforcement Detailing to mitigate seismic effects Published by Society of Structural Engineers, Sri Lanka
10
Examples of the design of Reinforced Concrete Buildings to BS 8110-Fourth Edition C. E. Reynolds & James C. Steedman
11
Reinforced and Prestressed Concrete Design-The Complete Process Eugene J.O’Brien & Andre S.Dixion
Prepared by Gihan Chathuranga, BSc.Eng(Hons), PG Dip in Strcut.Eng, Design, C.Eng,MIE(SL),MSSE(SL)
Page 5
Design Report-Control Building of Mannar Transmission Infrastructure-Lot A
3.0
STRUCTURAL MODELING IN SAP 2000
3.1
INTRODUCTION
Super Structure is modeled in SAP 2000, a Finite Element Structural Analysis package popular among Structural Engineers. Main steps in the modeling procedure are as follows. (1) Definition of Grids In this step building grid lines are defined in the model. (2) Definition of Materials Following material properties of the Concrete is defined as per given in Table 3.1 & Table 3.2
Table 3.1: Material Properties of Grade 25 Concrete
Property
Value
Density
24kN/m3
Young Modulus
6 2 25 × 10 kN/m
Coefficient of Thermal Expansion
10 × 10
Poisson’s Ration
0.2
Characteristic strength
2 25N/mm
-6
Table 3.2: Material Properties of Grade 35 Concrete
Property
Value
Density
24kN/m3
Young Modulus
6 2 27 × 10 kN/m
Coefficient of Thermal Expansion
10 × 10
Poisson’s Ration
0.2
Characteristic strength
2 35N/mm
-6
Prepared by Gihan Chathuranga, BSc.Eng(Hons), PG Dip in Strcut.Eng, Design, C.Eng,MIE(SL),MSSE(SL)
Page 6
Design Report-Control Building of Mannar Transmission Infrastructure-Lot A
(3) Definition of Frames and Area Sections Beams and columns were modeled as frame elements. Initial sizes of the members were determined carrying out a preliminary member size design calculations. Raft Slabs and Basement Walls are modeled as Shell Elements. (4) Assignment of Loading Vertical and lateral loads is assigned to model (5) Analysis of Structure Structure is analyzed as a rigid frame structure. 3D model of the Structure is shown in Figure 3.1.
Figure 3.1: 3D Model of the Super Structure
Prepared by Gihan Chathuranga, BSc.Eng(Hons), PG Dip in Strcut.Eng, Design, C.Eng,MIE(SL),MSSE(SL)
Page 7
Design Report-Control Building of Mannar Transmission Infrastructure-Lot A
3.2
SPECIAL CONSIDERATIONS IN STRUCTURAL MODELING
3.2.1
BEAM RAFT SLAB MODELLING
Foundation is modeled as a Beam-Raft Slab with Soil Springs. The Basement Slab and Basement Walls are modeled as Thin Shells of approximately 0.75mx0.75m and thicknesses are 350mm and 225 mm respectively. Basement Slab and the Basement Walls are manually meshed to ensure the proper connectivity between elements. The Ground Beams are modeled as Frame Elements. In order to simulate the propped cantilever action due to presence of Ground Floor Slab, the Ground Floor Slab is also modeled.
Modulus of Sub Grade Reaction (K)
The Modulus of Sub grade Reaction is given by following equation. K = SF × 40 × Q allowable
SF is the Factor of Safety and usually taken as 2. According to the Soil Report, the allowable bearing capacity is Q allowable Hence K = SF × 40 × Q allowable
=
2 × 40 × 175 = 14000kN/m
=
2 175kN/m
3
Hence Corresponding Spring Constant at Joints is, K = 14000 × 0.75 × 0.75 = 7875kN/m
Prepared by Gihan Chathuranga, BSc.Eng(Hons), PG Dip in Strcut.Eng, Design, C.Eng,MIE(SL),MSSE(SL)
Page 8
Design Report-Control Building of Mannar Transmission Infrastructure-Lot A
3.3
LOAD EVALUATION
3.3.1
GRAVITY LOADS
3.3.1.1 DETERMINATION OF LOADS TRANSFERRED ON TO BEAMS FROM SLABS
Slab loads were assigned to supporting Beams as per Shear Force Coefficients given in Table 3.16 of BS 8110 -1:1997. Slab loads were assigned to SAP 2000 model under following load cases as given in Table 3.2 Consider "Unit_Slab FF" Load case assigned to First Floor L evel is shown in Figure 3.2. The Loads on the First Floor Slab are as follows. Self Weight of 175mm thick slabs
=
0.175 × 24 = 4.2kN/m2
Finishes
=
1.25kN/m2
Live Loads on first floor slab
=
11.5kN/m2
Hence "Unit_Slab FF" Load case was scale multiplied as given in Table 3.3 to represent actual loads. Similar Procedure was carried to model the floor loads of other floors as well.
Table 3.3: Load Cases defined in SAP 2000
"Load Case" Name
Represent
Unit_Slab GF
Slab Load due to Unit Load Intensity acting on Ground Floor Slabs
Unit_Slab FF
Slab Load due to Unit Load Intensity acting on First Floor Slabs
Unit_Slab RF
Slab Load due to Unit Load Intensity acting on Roof Floor Slabs
Mass-Concrete Fill
Mass Concrete Filling on First Floor
Water_Tank
Slab Load due to Unit Load Intensity acting on Water Tank Level Slabs
Wall
Wall Loads
Prepared by Gihan Chathuranga, BSc.Eng(Hons), PG Dip in Strcut.Eng, Design, C.Eng,MIE(SL),MSSE(SL)
Page 9
Design Report-Control Building of Mannar Transmission Infrastructure-Lot A
Figure 3.2: "Unit_Slab FF" Load Case assigned on First Floor Beams
Table 3.4: Scale Multiplier for "Load Cases"
"Load Case" Name
Scale Multiplier for Load Cases
Self Weight
Finishes
Live Loads
Unit_Slab GF
4.2
1.25
11.5
Unit_Slab FF
4.2
1.25
115
Unit_Slab RF
3.6
1.25
1.5
Mass-Concrete Fill
10
-
-
Water_Tank
3.0
-
2
Wall
-
-
-
Prepared by Gihan Chathuranga, BSc.Eng(Hons), PG Dip in Strcut.Eng, Design, C.Eng,MIE(SL),MSSE(SL) Page 10
Design Report-Control Building of Mannar Transmission Infrastructure-Lot A
3.3.1.2 WALL LOADS
Walls are basically 225mm thick brick walls. Weight of walls on elevation is 5kN/m2 . Floor to floor height of the structure is 3900mm For example assume beam height is 75 0mm. Hence height of the wall is 3150mm. = 15.75kN/m . Hence load on a beam due to wall is 5 × 3.150
Wall loads assigned to first floor level are shown in Figure 3.3.
Figure 3.3 : Wall Loads assigned to First Floor Beams
Prepared by Gihan Chathuranga, BSc.Eng(Hons), PG Dip in Strcut.Eng, Design, C.Eng,MIE(SL),MSSE(SL) Page 11
Design Report-Control Building of Mannar Transmission Infrastructure-Lot A
3.3.1.3 ROOF LOADINGS
Roof will be a double pitch steel portal frame roof. The portals will be span between Columns on Grid A and Columns on Grid C. Hence Roof Loads are assigned to Modal as Point Loads to Columns. (Please refer to Figure 3.4). The Wind Loads usually will generate uplifts, hence it will have beneficiary effects for the axial loads in columns, as such roof loads due to dead and live loads are considered as follows. Weight of Asbestos Roofing Sheets with Insulations 0.25kN/m Weight of Purlins 0.04kN/m
2
2
2 Imposed load on roof is 0.5kN/m Hence Serviceability Load Intensity of the Roof is n sls Hence Ultimate Load Intensity of the Roof is n uls
=
=
2 0.25 + 0.04 + 0.5 = 0.79kN/m
1.4[0.25 + 0.04 ] + 1.6 × 0.5 = 1.206kN/m
2
The Plan area of the Roof is 19.8mx15.6m. There will be Total 12 Columns to support Roof Loads. (Column grid is approximately equal and roof reactions are compared to other loads).
0.79 × 19.8 × 15.5
Hence Serviceability Point Load
=
Hence Ultimate Point Load
=
12
=
20kN
1.206 × 19.8 × 15.5 12
=
30kN
Figure 3.4 : Roof Loads assigned to Columns
Prepared by Gihan Chathuranga, BSc.Eng(Hons), PG Dip in Strcut.Eng, Design, C.Eng,MIE(SL),MSSE(SL) Page 12
Design Report-Control Building of Mannar Transmission Infrastructure-Lot A
3.3.2
LATERAL LOADS
3.3.2.1 WIND LOADS
3.3.2.1.1
INTRODUCTION
A wind force on Structure is calculated as per CP3: Chapter V: Part 2: 1972 .According to “Design of Buildings for High Winds in Sri Lanka” Country is divided in to t hree wind zones. (See Figure 3 .5).
Figure 3.5: Wind Zones in Sri Lanka
Prepared by Gihan Chathuranga, BSc.Eng(Hons), PG Dip in Strcut.Eng, Design, C.Eng,MIE(SL),MSSE(SL) Page 13
Design Report-Control Building of Mannar Transmission Infrastructure-Lot A
Basic wind speeds for each zone is given in Table 3.5 below
Table 3.5: Basic Wind Speeds in Sri Lanka
Zone
Basic Wind Speed Post Disaster Structure
Normal Structure
1
53.5 m/s
49 m/s
2
47 m/s
42.5 m/s
3
38 m/s
33.5 m/s
Structure is located in Mannar and is designed as a “Post Disaster Structure”. Hence corresponding Basic Wind Speed (V) is 47m/s. Wind force calculation can be done as follows.
Figure 3.6: Wind Loads directions on Structure
Prepared by Gihan Chathuranga, BSc.Eng(Hons), PG Dip in Strcut.Eng, Design, C.Eng,MIE(SL),MSSE(SL) Page 14
Design Report-Control Building of Mannar Transmission Infrastructure-Lot A
Reference
Calculations
Out Put
Basic Wind Speed V = 47m/s (Corresponds to Post Disaster Structure located in Wind Zone 2 of Sri Lanka). Clause 4.3
Design Wind Speed (V ) s
CP3: Chapter V
V s
Clause 5.4
Topography Factor (S ) 1
CP3: Chapter V
S 1
Clause 5.5
Ground roughness, building size and height above ground
CP3: Chapter V
factor (S ) 2
Clause 5.5.2
Building is located in a Open Country with No Obstructions.
=
=
V×S ×S ×S 1 2 3
1
CP3: Chapter V Consider the Wind along Y direction.
b-dimension of the Building normal to wind d-dimension of the building measured in the direction perpendicular to wind b = 19.8m and d = 15.5m
(See Figure 3.6) Hence greatest horizontal dimension of the building is 19.8m. Height of the building above ground is 8.375m Hence neither the greatest horizontal dimension nor the vertical dimension of the building exceeds 50m. Clause 5.5.2
Hence Building Class-Class B
CP3: Chapter V
Consider the Second floor level. Height above ground is 8.375m
Prepared by Gihan Chathuranga, BSc.Eng(Hons), PG Dip in Strcut.Eng, Design, C.Eng,MIE(SL),MSSE(SL) Page 15
Design Report-Control Building of Mannar Transmission Infrastructure-Lot A
Reference Table 3
Calculations S
0.91
=
2
Out Put
CP3: Chapter V Clause 5.6 CP3: Chapter V
Probability Factor (S ) 3 S
=
3
1
Hence design wind speed is, V s
=
47 × 1 × 0.91 × 1 = 42.77m/s
Clause 4.3
Dynamic Pressure (q)
CP3: Chapter V
q = kVs
2
k = 0.613
2 q = 0.613 × 42.77 Table 3.10
Clause 4.3
l
b
CP3: Chapter
H Table 10.
w
d
b
=
=
=
19.8 15.5 19.8 15.5
1.27 ≈ 1.5
=
1.27 ≈ 1.5
=
15.5 f
2 1121N/mm
=
8.375
Hence C
=
=
0.54 ≈ 1/2
0.95
Floor to Floor Height from First to Second is 3.475m Hence effective area (A ) corresponds to second floor level is e A
e
=
19.8 × 3.475 ×
1 2
=
2 34.40m
Clause 7.3
Hence Wind force (F) on Second Floor level is
CP3: Chapter
F = C qA e f
=
0.95 × 1121 × 34.40 = 36.63kN
Similarly wind load is calculated for other floors and results are given in Table 3.6 & 3.7.
Prepared by Gihan Chathuranga, BSc.Eng(Hons), PG Dip in Strcut.Eng, Design, C.Eng,MIE(SL),MSSE(SL) Page 16
Design Report-Control Building of Mannar Transmission Infrastructure-Lot A
Table 3.6 : Summary of Wind Load Calculations-X Direction Level
F.F
Elevation
E.Height
Ae
2.45
38.22
S2
Vs
Q
Fx
0.78
36.66
823.8448
25.82
Height
1
1
3.9
4.9
3.6875
57.525
0.8
37.6
866.6349
40.88
3.475
8.375
1.7375
27.105
0.91
42.77
1121.344
24.92
Vs
Q
0.78
36.66
792.9338
36.54
Ground First Second
Table 3.7 : Summary of Wind Load Calculations-Y Direction Level
F.F
Elevation
E.Height
Ae
2.45
48.51
S2
Fy
Height Ground First Second
1
1
3.9
4.9
3.6875
73.0125
0.8
37.6
834.1184
57.86
3.475
8.375
1.7375
34.4025
0.91
42.77
1121.34
36.63
Prepared by Gihan Chathuranga, BSc.Eng(Hons), PG Dip in Strcut.Eng, Design, C.Eng,MIE(SL),MSSE(SL) Page 17
Design Report-Control Building of Mannar Transmission Infrastructure-Lot A
3.3.2.1 EARTH PRESSURE
Figure 3.7 : Lateral Loads on Basement Walls
Active Pressure Coefficient- Ka
Ka
=
1 − sinφ 1 + sinφ
=
1 − sin28 1 + sin28
=
0.36
Hence Active Soil Pressure at the Bottom of the Wall is ,
σ
A
=
2 K γh = 0.36 × 18 × 2 = 19.44kN/m a
The Pore Water Pressure at the Bottom of the Wall is,
σ
A
=
δ
2 h = 9.81 × 3 = 29.43kN/m water
Prepared by Gihan Chathuranga, BSc.Eng(Hons), PG Dip in Strcut.Eng, Design, C.Eng,MIE(SL),MSSE(SL) Page 18
Design Report-Control Building of Mannar Transmission Infrastructure-Lot A
2
As per Clause 3.3.4.1 of BS 8002:1994, the minimum surcharge load should be 10kN/m .
σ
A
4.0
=
2 Ka × Surcharge = 0.36 × 10 = 3.63kN/m
LOAD COMBINATIONS
Following ULS and SLS Combinations were defined in SAP 2000 as per Table 2.1 of BS 8110-1:1997. (Please refer to Figure 3.8). ULS Com 1
-1.4 Dead Loads + 1.6 Live Loads+1.2 Earth Pressure
ULS Com 2
-1.0 Dead Loads + 1.4 Wind Loads in X direction+1.2 Earth Pressure
ULS Com 3
-1.0 Dead Loads + 1.4 Wind Loads in Y direction+1.2 Earth Pressure
ULS Com 4
-1.2 Dead Loads + 1.2 Live Loads + 1.2 Wind Loads in X direction+1.2 Earth Pressure
ULS Com 5
-1.2 Dead Loads + 1.2 Live Loads + 1.2 Wind Loads in Y direction+1.2 Earth Pressure
ULS Com 6
-1.4 Dead Loads + 1.4 Wind Loads in X direction+1.2 Earth Pressure
ULS Com 7
-1.4 Dead Loads + 1.4 Wind Loads in Y direction+1.2 Earth Pressure
SLS Com 1
-1.0 Dead Loads + 1.0 Live Loads
SLS Com 2
-1.0 Dead Loads + 1.0 Wind Loads in X direction+1.0 Earth Pressure
SLS Com 3
-1.0 Dead Loads + 1.0 Wind Loads in Y direction+1.0 Earth Pressure
SLS Com 4
-1.0 Dead Loads + 1.0 Live Loads + 1.0 Wind Loads in X direction+1.0 Earth Pressure
SLS Com 5
-1.0 Dead Loads + 1.0 Live Loads + 1.0 Wind Loads in Y direction+1.0 Earth Pressure
Figure 3.8 : Extract of Table 2.1 of BS 8110-1:1997.
Prepared by Gihan Chathuranga, BSc.Eng(Hons), PG Dip in Strcut.Eng, Design, C.Eng,MIE(SL),MSSE(SL) Page 19
Design Report-Control Building of Mannar Transmission Infrastructure-Lot A
5.0
STRUCTURAL DESIGN OF BASEMENT WALLS-SPECIMEN CALCULATION
References
Calculation
Out Put
Consider a Long Wall Panel on Grid A. The Serviceability Vertical Bending Envelop (In the Vertical Direction) is 28 kNm/m. (See Figure 5.1). Cover to reinforcement
= 50 mm
Diameter of main bar (φ )
= 12 mm
(The Reinforcement Diameter was measured from the c ore cutter sample). The Spacing of the Main Reinforcement = 150mm
Assessment of Flexural Crack Width
2 A s = 754 mm /m d = 250 –50 – 12/2 = 194mm
A 754 = 3.887 × 10 − 3 ρ= s = bd 1000 × 194
X- Depth to the Neutral Axis α
e
X d
-Modular Ratio take as 15.
= α eρ 1 + 2
X 194
α eρ
− 1
2
− 15 × 3.887 × 10 3
= 15 × 3.887 × 10 − 3 × 1 +
− 1
X = 55.90 mm
Z- Lever arm
Z = d−
X 3
= 194 −
55.90 3
= 175.36mm
Prepared by Gihan Chathuranga, BSc.Eng(Hons), PG Dip in Strcut.Eng, Design, C.Eng,MIE(SL),MSSE(SL)
Design Report-Control Building of Mannar Transmission Infrastructure-Lot A
Figure 5.1 : Serviceability Bending Moments (Vertical) in Long Wall Panel
Prepared by Gihan Chathuranga, BSc.Eng(Hons), PG Dip in Strcut.Eng, Design, C.Eng,MIE(SL),MSSE(SL)
Design Report-Control Building of Mannar Transmission Infrastructure-Lot A
References
Calculation
Out Put
Ms- Serviceability Moment of the Wall Base is 28kNm/m
f s -Steel Stress f s =
M A Z s
=
28 × 106 754 × 175.36
= 211.77N/mm2
B:2
Limiting Steel Stress = 0.8f y = 0.8 × 460 = 368N/mm
BS 8007:1987
Hence Steel stress is within acceptable limits.
2
f -concrete Stress cb 2M
2 × 28 × 106
2 f = 5.71N/mm = = cb Zbx 175.36 × 1000 × 55.90 B:2
Limiting Concrete Stress = 0.45f cu = 0.45 × 35 = 15.75N/mm
BS 8007:1987
Hence Concrete stress is within acceptable limits.
2
f (h − x) (250 − 55.90) 211.77 ε1 = s × = × = 1.488 × 10 − 3 3 (194 − 55.90) E s d − x 200 × 10 For a Limiting design crack width of 0.2mm,
b (h − x)(a′ − x) ε = t 2 3Es A s (d − x) ε = 2
1000 × (250 − 55.90)(250 − 55.90) −4 = 6 × 10 3 3 × 200 × 10 × 754 × (194 − 55.90)
εm = ε1 − ε2 = 1.488 × 10
− 3 − 6 × 10 − 4 = 8.88 × 10 − 4
2 150 2 12 12 acr = + 50 + − = 87.60mm 2 2 2 4 3acrεm 3 × 87.60 × 8.88 × 10 − = = 0.17mm < 0.2mm w= 87.60 − 50 acr − Cmin 1 + 2 1+2 h − x 250 − 55.90 Hence Crack with is Ok.
Prepared by Gihan Chathuranga, BSc.Eng(Hons), PG Dip in Strcut.Eng, Design, C.Eng,MIE(SL),MSSE(SL)
Design Report-Control Building of Mannar Transmission Infrastructure-Lot A
References
Calculation
Out Put
Assessment of Crack Width Due to Thermal and Moisture Effects
ρ -Reinforcement Ratio for a Surface Zone Clause 2.2.3.3 BS 8007:1987
ρ=
As bh
=
754 1000 × 0.5x250
= 0.006032
The minimum Reinforcement ratio is 0.0035 Hence minimum reinforcement ratio is satisfactory.
S-Crack Spacing
f φ smax = ct × f 2ρ b Table A.1 BS 8007:1987
f ct = 0.67 f b smax = 0.67 ×
12 2 × 0.006032
= 666.45mm
W-Crack Width
Wmax = Smax R α(T + T ) 1 2
R-Restraint Factor is taken as 0.5.
T1 = 30 C and T2 = 10 C for Sri Lankan context.
α = 10 × 10
−6
Wmax = 666.45 × 0.5 × 10 × 10
− 6 (30 + 10) = 0.13mm < 0.2mm
Hence Crack width is satisfactory.
Prepared by Gihan Chathuranga, BSc.Eng(Hons), PG Dip in Strcut.Eng, Design, C.Eng,MIE(SL),MSSE(SL)
Design Report-Control Building of Mannar Transmission Infrastructure-Lot A
6.0
STRUCTURAL DESIGN OF GROUND BEAMS-SPECIMEN CALCULATION
Reference
Calculations
Out Put
Consider the Ground Beam on Grid 3. The Bending Moments and Shear Forces for ULS ENVELOP are shown in Figure 6.1 and Figure 6.2.
Checks for Bending
Consider the B/3 Support, the support moment is 315kNm Assume T20 Main Reinforcement, T10 Links and 50mm cover .
d = 600 − 50 − 10 − Cl.3.4.4.4 BS 8110:1-1997
k=
M f b d2 cu f
=
20
35 × 450 × 5302
As
= 530mm
315 × 10 6
z = d 0.5 + 0.25 −
z = d 0.5 +
2
0.25 −
= 0.070
0.9 K
0.070 0.9
= 0.92d < 0.95d
M
=
0.95f y z
=
6 315 × 10 0.95 × 460 × 0.92 × 530
2
= 1478mm
3T20+3T20 has been provided at bottom. A
s,provided
= 1884mm2
(See the Reinforcement Detailing in Annex 2)
Prepared by Gihan Chathuranga, BSc.Eng(Hons), PG Dip in Strcut.Eng, Design, C.Eng,MIE(SL),MSSE(SL)
Design Report-Control Building of Mannar Transmission Infrastructure-Lot A
Figure 6.1 : Ground Beam Bending Moment
Figure 6.2 : Ground Beam Shear Force
Prepared by Gihan Chathuranga, BSc.Eng(Hons), PG Dip in Strcut.Eng, Design, C.Eng,MIE(SL),MSSE(SL) Page 25
Design Report-Control Building of Mannar Transmission Infrastructure-Lot A
Reference
Table 3.25 BS 8110:1-1997
Calculations
Out Put
Checks for Minimum area of reinforcement
100A
s
bh
100 × 1884
=
=
450 × 600
0.70 > 0.13
Hence minimum steel requirement is satisfied. Clause 3.12.6
Checks for Maximum area of reinforcement
BS 8110:1-1997
Neither the area of tension reinforcement nor compression
Minimum r/f Ok.
Maximum r/f Ok
reinforcement should exceed 4% of cross sectional area of the concrete.
Checks for Shear at RHS Support
Maximum shear at support =297 kN (From SAP Model) 3 297× 10
Cl.3.4.5.2 BS 8110:1-1997
Cl.3.4.5.2 BS 8110:1-1997
vmax =
2
= 1.25N/mm
(450 × 530)
Maximum permissible shear stress is lesser of 2
0.8 f cu or 5N/mm
2 2 0.8 35 = 4.73N/mm > 1.25N/mm
Hence maximum shear is O.K
Cl. 3.4.5.4 BS 8110:1-1997
Maximum Shear Ok
Concrete shear Stress
The area of tension reinforcement at a distance “d” from the
2
face of the support is 1884mm
Table 3.8
100As
BS 8110:1-1997
bd
400 d
=
100 × 1570 450 × 530
14
= 0.78 < 3
1
400 4 = 0.93 < 1 = 530
Prepared by Gihan Chathuranga, BSc.Eng(Hons), PG Dip in Strcut.Eng, Design, C.Eng,MIE(SL),MSSE(SL)
Design Report-Control Building of Mannar Transmission Infrastructure-Lot A
Reference
Calculations
Out Put
Hence design concrete shear stress is,
1
1
1
100As 3 × 400 4 × 1 × f cu 3 = 0.79 × δm 25 d bd
vc
1
35 3 = 0.79 × (0.78 ) 3 × 0.93 × × 1.25 25 1
1
= 0.60N/mm2 Table 3.7 BS 8110:1-1997
Spacing of the shear links 2 vc + 0.4 = 0.60 + 0.4 = 1.0N/mm vc + 0.4 < v < v d max
We have provided 10 Links at supports. Number of shear legs is 2.
π × 102 2 Asv = 2 × = 157mm 4 Hence maximum possible shear link spacing at the support is,
Sv ≤
A sv × 0.95 × f yv
(
bv × v − v
c
)
=
157 × 0.95 × 460 = 235mm 450 × (1.25 - 0.6)
We have provided T10 @ 200mm. Cl. 3.4.5.5
Maximum possible spacing of links is 0.75d = 397.5mm
BS 8110:1-1997
Hence maximum spacing is satisfied.
Cl.3.4.6
Checks for Deflection
Table 3.9
The Span of the Beam in 4575 mm and beam is continuous
T10@ 200mm Links
over supports. BS 8110:1-1997 Basic
Span = 26 Effective Depth
4750 = 8.96 = Effective Depth 530
Actual
Span
Hence Deflection of the Beam is Satisfactory.
Prepared by Gihan Chathuranga, BSc.Eng(Hons), PG Dip in Strcut.Eng, Design, C.Eng,MIE(SL),MSSE(SL)
Design Report-Control Building of Mannar Transmission Infrastructure-Lot A
7.0
STRUCTURAL DESIGN OF BASEMENT SLAB-SPECIMEN CALCULATION
7.1
CHECKS FOR BEARING
Maximum Serviceability Joint Reaction (Corresponds to SLS Combination 01) is 73kN. This is corresponds to a area of 0.75mx0.75m. Hence Maximum Serviceability Pressure is
73
Q = applied
7.2
= 130kN/m2 < 175kN/m2
2 0.75
CHECKS FOR BENDING
Maximum Moment for any direction is 90kNm/m. (See Figure 7.1 and 7.2). Assume T16 is to be used. Effective depth (d)
d = 300 − 50 − 16 −
K=
M 2 f cubd
=
16 2
= 226mm
6 90 × 10 2 35 × 1000 × 226
= 0.050 < 0.156
Hence section can be designed as a singly reinforced section.
d 0.9
0.050
z = 0.5 + 0.25 −
z = 0.5 + 0.25 −
K
0.9
d = 0.94d < 0.95d
Hence Area of reinforcement required , A s,req
=
M 0.95f y Z
=
90 × 10
6
0.95 × 460 × 0.95 × 226
=
969
2 mm m
Hence provide T16 @ 150mm C/C.
A
s,provided
= 1340
2 mm m
Prepared by Gihan Chathuranga, BSc.Eng(Hons), PG Dip in Strcut.Eng, Design, C.Eng,MIE(SL),MSSE(SL)
Design Report-Control Building of Mannar Transmission Infrastructure-Lot A
Figure 7.1 : M11 Bending
Figure 7.1 : M22 Bending
Prepared by Gihan Chathuranga, BSc.Eng(Hons), PG Dip in Strcut.Eng, Design, C.Eng,MIE(SL),MSSE(SL)
Design Report-Control Building of Mannar Transmission Infrastructure-Lot A
7.3
CHECKS FOR SHEAR
Maximum possible shear , lesser of
0.8 f cu or 5N/mm2 2 0.8f cu = 0.8 × 35 = 4.73N/mm
1
1
1
100As 3 400 4 1 f cu 3 vc =0.79× × × δ × 25 b d d v m
100As 100× 1340 = = 0.59 < 3 b d 1000 226 × v 1 400 4
d
1 400 4
=
226
= 1.15 > 0.67
δm = 1.25 1 1 1 35 3 2 vc = 0.79 × [0.59] 3 × 1.15 × × = 0.68N/mm 1.25 25
Maximum Shear Stress as per SAP Model is 0.53N/mm^2 (See Figure 7.3 and Figure 7.4).
v < vc
Prepared by Gihan Chathuranga, BSc.Eng(Hons), PG Dip in Strcut.Eng, Design, C.Eng,MIE(SL),MSSE(SL)
Design Report-Control Building of Mannar Transmission Infrastructure-Lot A
Figure 7.3 : S13 Shear
Figure 7.4 : S23 Shear
Prepared by Gihan Chathuranga, BSc.Eng(Hons), PG Dip in Strcut.Eng, Design, C.Eng,MIE(SL),MSSE(SL)
Design Report-Control Building of Mannar Transmission Infrastructure-Lot A
8.0
SPECIMEN CALCULATION FOR A INDIVIDUAL FOOTING
The Specimen Calculations for the Column Footing at Grid C/4 presented here. The SLS and ULS reactions of the Column are given in Figure 8.1 and Figure 8 .2.
Reference
Calculation
Out Put
General Data
Columns are pinned at the base. Figure 4.1
Axial load at SLS
= 598kN
Figure 4.2
Axial load at ULS
= 863kN
Soil Report
Bearing Capacity at 2.0 m below EGL
= 175kN/m2
Cover to reinforcement
= 50mm
Grade of Concrete f cu
=
2 35N/mm
Sizing of the footing
Assume an initial thickness of 300mm.
2 Hence Allowable bearing capacity = 175 − 0.30 × 24 = 167.8kN/m Hence Required Width (B),
B=
598 167.8
= 1.89m
Hence Provide a 2.0mx2.0m Square Footing.
Design for Flexure
Ultimate pressure
=n =
863 = 215.8kN/m2 22
Dimension of the Stub Column 500mmx500mm Maximum moment at Column face (For a Unit Width)
M = 215.8 ×
2 (2 − 0.50) 8
= 60.70kNm/m
Prepared by Gihan Chathuranga, BSc.Eng(Hons), PG Dip in Strcut.Eng, Design, C.Eng,MIE(SL),MSSE(SL)
Design Report-Control Building of Mannar Transmission Infrastructure-Lot A
Figure 8.1 : SLS Joint Reactions
Figure 8.2 : ULS Joint Reactions
Prepared by Gihan Chathuranga, BSc.Eng(Hons), PG Dip in Strcut.Eng, Design, C.Eng,MIE(SL),MSSE(SL)
Design Report-Control Building of Mannar Transmission Infrastructure-Lot A
Reference
Calculation
Out Put
Diameter of the main reinforcement to be used =12mm d = 300 − 50 − 16 −
16 2
= 226mm
Consider a Unit Width of the footing
k=
M f bd2 cu
=
60.70 × 106 35 × 1000 × 2262
0.9
0.034
z = d0.5 + 0.25 −
z = d0.5 + 0.25 −
k
As =
M
=
0.95f y z
= 0.034 < 0.156
0.9
= 0.96d ,but should not be greater than 0.95d
60.70 × 10
6
0.95 × 460 × 0.95 × 226
= 647mm2 /m
Provide T16@ 150mm C/C A
s,provided
T16 @ 150mm
= 1340mm2 /m
Checks for minimum reinforcement
100A bh Table 3.25
3.11.4.5
s
=
100 × 1340 1000 × 300
=
0.45 > 0.13
Hence minimum steel requirement is o.k.
Checks for Maximum shear
Maximum shear stress at column face
=
863 × 10
3
2(500 + 500) × 226
= 1.91N/mm2
Maximum possible shear 0.8
2
f cu or 5N / mm which is lesser
Hence v
max
= 0.8 f cu = 0.8 35 = 4.73N/mm2
Hence Maximum Shear is OK.
Prepared by Gihan Chathuranga, BSc.Eng(Hons), PG Dip in Strcut.Eng, Design, C.Eng,MIE(SL),MSSE(SL)
Design Report-Control Building of Mannar Transmission Infrastructure-Lot A
Reference
Calculation
Out Put
Shear at 1.0 d from the face of the Column
215.8 × v= Table 3.8
(2 − 0.50) − 0.226 × 1000 2 = 0.50N/mm2 1000 × 226
Design concrete shear strength 100As
=
bd
100 × 1340 (1000 × 226)
1
= 0.59 < 3
1
400 4 = 400 4 = 1.15 d 226 Hence design concrete shear strength is,
1
vc
1
100As 3 × 400 4 × 1 = 0.79 × δm bd d 1
35 3 = 0.79 × (0.59 ) 3 × 1.15 × × = 0.68N/mm2 1.25 25 1
1
2
vc=0.68N/mm
Hence shear at 1.0 d is OK. Checks for Punching shear at 1.5 d
Critical Perimeter = 4(0.50 + 3d) = 4(0.50 + 3 × 0.226) = 4 × 1.178 = 4.712m Force outside the critical perimeter
= 215.8 × (22 − 1.1782 ) = 563.74kN Hence Punching shear stress
=
563.74 × 1000 4712 × 226
= 0.53N/mm2
Hence Punching Shear is OK.
Prepared by Gihan Chathuranga, BSc.Eng(Hons), PG Dip in Strcut.Eng, Design, C.Eng,MIE(SL),MSSE(SL) Page 35
Design Report-Control Building of Mannar Transmission Infrastructure-Lot A
8.0
COLUMN DESIGN-SPECIMEN CALCULATIONS
Column layout is determined as per the Client's requirements and initial member sizes were estimated carrying out a preliminary design. Then structure was modeled in SAP 2000 and each column is designed to withstand the bending and axial loads for ULS combination. Specimen Calculation is provided for Column at grid B/3 (Type C2).Columns are designed as unbraced by assuming all the lateral loads are taken by the columns.
Prepared by Gihan Chathuranga, BSc.Eng(Hons), PG Dip in Strcut.Eng, Design, C.Eng,MIE(SL),MSSE(SL)
Design Report-Control Building of Mannar Transmission Infrastructure-Lot A
Reference
Calculations
Output
Specimen Calculation for Column Type "C2"
The Column size is 450x450 Consider a Column Segment from Ground to First Floor Level. Determination of Short or Slender Column
Bending about X-X Axis Dimension of column about XX axis Bending h = 450mm Depth of the Beam along Y direction is 750mm. Cl.3.8.1.6.2
Hence Top Condition is 1.
BS 8110-1:1997
Slab Thickness at Ground Level is 175mm. Hence Bottom Condition -2
Table 3.2
Hence β = 1.3
BS 8110-1:1997
L ex L ex h
= βL ox = 1.3 × (3900 − 750) = 4095mm =
4095 450
= 9 < 10
Hence Column is Short for X-X axis Bending.
Bending about Y-Y Axis Dimension of column about YY axis Bending h = 450mm Depth of the Beam along X direction is 500mm. Cl.3.8.1.6.2
Hence Top Condition is 1.
BS 8110-1:1997
Ground Beam Depth is 450mm. Hence Bottom Condition -1
Table 3.2
Hence β
BS 8110-1:1997
L ey L ey b
=
1.2
= βL oy = 1.2 × (3900 − 500) = 4080mm
=
408 450
= 9 < 10
Hence Column is Slender for YY axis Bending.
Short Column
Hence "C2" Column is a short Column.
Prepared by Gihan Chathuranga, BSc.Eng(Hons), PG Dip in Strcut.Eng, Design, C.Eng,MIE(SL),MSSE(SL)
Design Report-Control Building of Mannar Transmission Infrastructure-Lot A
Figure 9.1: ULS Axial Loads on Column at B/3
Figure 9.2: ULS XX Bending Moment of the Column
Prepared by Gihan Chathuranga, BSc.Eng(Hons), PG Dip in Strcut.Eng, Design, C.Eng,MIE(SL),MSSE(SL)
Design Report-Control Building of Mannar Transmission Infrastructure-Lot A
Figure 9.3: ULS YY Bending Moment of Column at B/3
Prepared by Gihan Chathuranga, BSc.Eng(Hons), PG Dip in Strcut.Eng, Design, C.Eng,MIE(SL),MSSE(SL)
Design Report-Control Building of Mannar Transmission Infrastructure-Lot A
Reference
Calculations
Output
Design Loads from SAP 2000 Model
Column is designed for ULS 1 Load Combination.(Critical)
N
=
2223kN
Mxx
= 165kNm
Myy
=
57kNm
Cl.3.8.2.4
Minimum Moments
BS 8110-1:1997
e xx
=
0.05 × 450
=
22.5mm > 20mm
= 2223 × 0.020 = 45kNm < 165kNm M xx, min
e yy
=
0.05 × 450 = 22.5mm
>
20mm
= 1800 × 0.020 = 36kNm < 57kNm M yy,min
Design Moments
Cl.3.8.4.5 BS 8110-1:1997
M xx
= 165kNm
M
= 57kNm
YY
Biaxial Bending
25
b' = 450 − 30 − 10 −
2 25
h' = 450 − 30 − 10 −
β =1−
M xx h′ M yy b′ M xx h′
=
=
>
7N 6bhf cu
165 397.5 57 397.5
=1−
2
=
397.5mm
=
397.5mm
7 × 2223 × 103 6 × 450 × 450 × 25
= 0.49
= 0.42
= 0.14
M YY b′
Hence Column is bending about XX axis.
Prepared by Gihan Chathuranga, BSc.Eng(Hons), PG Dip in Strcut.Eng, Design, C.Eng,MIE(SL),MSSE(SL)
Design Report-Control Building of Mannar Transmission Infrastructure-Lot A
Reference
Calculations
M′x Column Design
=M
h′
M b′ y
+β
x
= 165 + 0.49 ×
397.5 397.5
Output
× 57 = 193kNm
Design of Main Reinforcement
Charts by IstructE d
397.5
=
h
N
=
bhf cu
M 2 bh f cu Hence
ρ=
2223 × 10
3
450 × 450 × 25
=
193 × 10
= 0.44
6
2 450 × 450 × 25
ρf y
=
f cu
= 0.08
0.2
0.2 × 25 460
A
sc bh
=
A
sc bh
=
A
sc 2
0.90
≈
450
=
0.2 × 25 460 0.2 × 25 460
×
2 450 × 450 = 2201mm
2 1100mm
Provided Reinforcement per Face is 5T25. A
sc, provided
=
5T25 per Face
2 2455mm
Hence provided Reinforcement is Satisfactory.
Prepared by Gihan Chathuranga, BSc.Eng(Hons), PG Dip in Strcut.Eng, Design, C.Eng,MIE(SL),MSSE(SL)
Design Report-Control Building of Mannar Transmission Infrastructure-Lot A
Reference
Calculations
Table 3.25
Checks for Minimum Area of Reinforcement
BS 8110-
100A sc
1:1997
bh A sc
=
=
Output
0.4
0.4 × 450 × 450 100
=
2 810mm
Hence provided reinforcement satisfied the minimum reinforcement requirement. Checks for Maximum Area of Reinforcement
Cl.3.12.6.1 BS 8110-
100Asc bh
=
6
1:1997 A sc
=
6 × 450 × 450 100
2
= 12150mm
>
2 4910mm
Hence Maximum Area of Reinforcement is Ok. At Laps At a Lap 6T25 bars are lapped. A sc
=
A sc
=
2 6 × 491 = 2946mm (4910 + 2946) 450 × 450
× 100 = 3.87 < 10%
Cl.3.12.7.1
Design of Links
BS 8110-
Largest Compression bar
1:1997
Hence Diameter of the shear link should be larger than 25/4=6mm.
=25mm
Hence T10 Links were provided. Shear Link spacing should be less than 12 times smallest compression bar. (12x25=300mm)
T10-150
Links are provided at 150mm Spacing.
Links
Prepared by Gihan Chathuranga, BSc.Eng(Hons), PG Dip in Strcut.Eng, Design, C.Eng,MIE(SL),MSSE(SL)
Design Report-Control Building of Mannar Transmission Infrastructure-Lot A
ANNEX 1-LOADINGS
Prepared by Gihan Chathuranga, BSc.Eng(Hons), PG Dip in Strcut.Eng, Design, C.Eng,MIE(SL),MSSE(SL)
LEGENDS 5 kN/m2
LEGENDS
11.5kN/m2
LEGENDS
11.5kN/m2
LEGENDS
11.5 kN/m2
3kN/m2
LEGENDS
11.5 kN/m2
3kN/m2
1.5kN/m2
1.5kN/m2
Design Report-Control Building of Mannar Transmission Infrastructure-Lot A
Design Report-Control Building of Mannar Transmission Infrastructure-Lot A
ANNEX 2-EXTRACT FROM SOIL REPORT
Prepared by Gihan Chathuranga, BSc.Eng(Hons), PG Dip in Strcut.Eng, Design, C.Eng,MIE(SL),MSSE(SL)
6.4 Recommendations
Giving due regard to the above factors and inferring similar subsurface conditions throughout the site, it is recommended that individual pad footings be used at each tower leg. The footings can be placed at a depth of 2 m, and designed for an allowable bearing capacity of 175kPa. The above shallow foundation option is based on the presumption that there would be no significant interference between the zones of influence of the designed footings. This condition shall be met if the clear distance between the foundations should be more than the width of the larger footing. Further, it recommended that the stability of the foundation shall checked against possible uplifting and sliding. For the purpose the following design p arameters shall be used: shear strength parameters of the soils above footing level can be taken as c’ = 8 kN/m 2, ф’ = 28. The frictional resistance at the base of the footing can be taken as ca = 5 kN/m, δ= 19.5
16thSeptember 2015
12