Calculation Sheet
Calculation for Short Circuit Fault Current PROJECT:- STEP ERC office
Fault Location:
At the Main Switchboard.
Service Voltage:
400
Volts
Generator No-Load Voltage:
420
Volts
Supply Cable Parameters:
From Generator to Main Distribution Board
Busbar Length:
15
mtr
Busbar CSA:
400
sqmm
No. of bars per Phase:
1
+5% of the Service Voltage
Transformer Impedance: Transformer kVA:
1500
kVA
For a 1500kVA Transformer: Usc = 6%
Transformer Impedance:
7.06
mΩ
(Based on only 1No. Transformer feeding the Main Board)
Elements contributing to the Fault:
X (mΩ)
R (mΩ)
Transformer: (Reactance)
7.06
Transformer: (Resistance)
X trafo = Z trafo 1.41
R trafo = X trafo x 0.2
Circuit Breaker:
0.15
Average Reactance for an MCB = 0.15mΩ
Busbar: (Reactance)
2.25
Average Reactance per Metre of a Busbar = 0.15mΩ
X cable = 0.15 x Length
Conductor Resistivity per Metre (with an MCB) = 0.023Ω