Controller Model OCR400 Controller.
Emerson Process Management Confidential
1
What do you get vs the OCR161 z
50% speed improvement
z
50mS Copy to Backup
z
Double RAM, Quadruple Flash
z
More integrated NIC ports
z
60% Smaller Overall Package and Power Usage – All without using fans
z
Greater Hardware I/O connectivity concurrently – Local Ovation, Local Q Line and Remote Q or Ovation I/O concurrently
z
Same config tools, Same controls, Same database
Emerson Process Management Confidential
2
Ovation Redundant Controller Processor Modules
z
1:1 functional replacement of existing controller – 60% smaller DIN rail mountable package – Same I/O interfaces
z
Same Control Builder and Developer Studio configuration – Minimal controller configuration changes only
z
z
Control schemes, database, etc remain the same Same Environmental requirements – But without Fans
z
Same 24V Power scheme
I/O Interface Modules Emerson Process Management Confidential
3
Processor Module z
Control Processor & Highway Interface – 400MHz Processor – 64MB expandable to 128MB DRAM – 128Mb Flash memory accessible under cap
z
4 On Board Fast Ethernet Ports – Network connections – Fieldbus and 3rd Party virtual I/O device capability
z
z
z
Fits in an I/O module housing with new cap Uses PCI to interconnect with the I/O Interface Module LED’s for Power and 4 NIC’s
Emerson Process Management Confidential
4
OCR400 Network Connections Single Dual Attach
Ethernet 3rd Party Link #1
● ●
● ●
Ovation Network Connection #1
●
●
(Foundation Fieldbus*, Modbus/TCP, Profibus*, GE Mk V/VI, A-B DF1, etc)
Ovation Network #2 Connection or Ethernet 3rd Party Link #3 50mS Copy to Backup or Ethernet 3rd Party Link #2
● ● ● ●
●
● ●
●
* Not supported on Solaris 1.7 Emerson Process Management Confidential
5
Hardwired and Virtual I/O Devices z
Controller supports 5 I/O Devices – 1 Hardwired I/O which includes redundancy
Virtual I/O
Hardwired I/O
– All 5 can be virtual I/O devices z
Hardwired I/O Device – Single Device to handle all Hardwired I/O – Connections made via Backplane and I/O Interface Module
z
Virtual I/O Device – Up to 5 Devices used to handle each of the Virtual (3rd party) I/O Device types • GE MkV/VI, Modbus, Ff, A-B, etc
– Connections made via Ethernet Ports z
The same controller limits apply – Approximately 2000 maximum field I/O points per Controller Emerson Process Management Confidential
6
I/O Interface Module z
Provides internal power – internal 12V, 5VDC from 24VDC
z
Interfaces to all hardwired I/O types – Local Ovation I/O – Remote Ovation I/O – Local Q Line I/O – Remote Q Line I/O
z
z
z
Local Ovation I/O connections are the same as the current controller Q Line and Remote I/O connections are via RJ45 ports on top of the module Fits in an I/O module housing with new cap
Emerson Process Management Confidential
7
IO Interface Module Connections Valid Combinations Q5
Local Q Line DIOB 0
R4
Local Q Line DIOB 1 OR Remote Ovation I/O Nodes 1-4 OR Remote Q Line I/O
R3
●
●
● ● ●
Remote Ovation I/O Nodes 5-8 OR Remote Q Line I/O
Local Ovation I/O always 16 branches with 4778 hardware addresses
●
● ●
●
●
●
More I/O Flexibility Emerson Process Management Confidential
8
Ovation I/O Bus
OCR400 Controller I/O Architectures The IO interface only deals with two types of interfaces Local Ovation I/O and AUI connected I/O New OCR400 Controller Kit 5X00247
Local Ovation I/O
CTRL IOIC
●●●●●
Remote Ovation I/O
CTRL IOIC
●●●●●
Ovation
AUI
5X00238
Ovation OCR400 I/O has the same drawing numbers and is Ovation fully interchangeable
I/O
MAU
FO ●●●●●
RNC
Ovation ●●●●●
Ovation I/O
Existing AUI & RNC components New OCR400 Migration Kit 5X00251 5X00230
Local Q Line I/O Remote Q Line I/O
CTRL IOIC CTRL IOIC
AUI ●●●●●
5X00238 AUI
QOL MAU
●●●●●
5X00238
DIOB
●●●●●
FO ●●●●●
Qline I/O
QOR
DIOB ●●●●●
Qline I/O
Existing AUI & RNC components All other components are existing drawing numbers FO cable is supplied by the project Emerson Process Management Confidential
9
I/O Driver Types & I/O Device Types z
Hardwired I/O – OVATION (I/O Driver) - Local Ovation, Remote Ovation, Local Q Line, Remote Q Line (I/O Device)
z
3rd Party I/O – – – – – – – – – –
ALLEN BRADLEY - Allen Bradley PLC MODBUS - Modbus Master RTP IO - RTP IOBC6700 GE MARK V/VI - GE Mark V, GE Mark VI EXTERNAL OVATION NETWORK - External Ovation Network MHI - MHI TOSHIBA - Toshiba FIELDBUS - Foundation Fieldbus GE Genius - GE Genius PROFIBUS - Profibus Emerson Process Management Confidential
10
I/O Driver Types & Simulator Driver Types z z
Some valid combinations of an I/O Driver, and a Sim Driver OVATION, NO ENTRY – Ovation I/O used with no simulation points – Standard configuration for controller
z
OVATION, OVATION – Ovation I/O used with Ovation Points from Simulator Model • Allows Mix and Match of Ovation Real I/O and Simulated I/O
– Controller expects to interface with a SimServer z
NO ENTRY, FAKE – Ovation I/O used with Ovation Points from same controller – Model implemented in additional control sheets – No SimServer involvement
z
MODBUS, OVATION (One of many unexpected combinations) – Modbus I/O used with Ovation Points from Simulator Model • Allows Mix and Match of Modbus I/O and Simulated I/O
– Controller expects to interface with a SimServer Emerson Process Management Confidential
11
Virtual I/O Device Capabilities Type
Device Type
Systems
Allen Bradley PLC
5
5
25
Modbus Master
5
5
25
MHI
5
1
5
Toshiba
5
1
5
RTP IOBC6700
1
5
5
GE Mark V or GE Mark VI
1
2
2
External Ovation Network
1
1
1
Foundation Fieldbus
1
16 (64 segments)
16
GE Genius
1
8
8
Profibus (Future)
1
8
8
I/O
z
Max Devices
Max Addresses Per Device
Max per Controller*
Remember 1 Hardwired I/O Device is required for redundancy – *This reduces the above Max per Controller numbers.
Emerson Process Management Confidential
12
LED Indications Power OK
P N1
Single Attach
N2 N3 N4
Power OK Communication Backup (Fl) Alive Error (Red) Local I/O 1-8 Local I/O 9-16 Remote I/O #1 Remote I/O #2 Qline I/O
P Cm Ct A E O1 O2 R3 R4 Q5
Backup Controller
Power OK Communication Primary (Solid) Alive
Local I/O 9-16 Remote I/O #1
Primary Controller
z
1 Red Error LED instead of 4 Char display
z
5 Lowest LEDs cyclically indicate error code Emerson Process Management Confidential
13
Controller Capabilities z
Lots of Hardwired I/O – 4778 Max
z
And Lots of Virtual I/O capability – 2048 x 4 = 8192 Max
z
Plus Lots of ports & connections
z
Plus Lots of control sheets – Multiplies Field I/O x 6, 8, or 10
z
However the maximum overall originated I/O point limit per controller is still 16,000 points Emerson Process Management Confidential
14