Quick Installation Guide
The information in this document i s subject to change without notice and descri bes only the product defined in the introduction of this documentation. This documentation is in tended for the use of Nokia Siemens Networks c ustomers only for the purposes of the agreement under which the document is submitted, and no part of it may be used, reproduced, modified or transmitted in any form or means without the prior written permission of Nokia Siemens Networks. The documentation has been prepared to be used by pr ofessional and properly trained personnel, and the customer assumes full responsibility when using it. Nokia Siemens Networks welcomes customer comments as part of the pr ocess of continuous development and improvement of the documentation. The information or statements given in this documentation concerning the suitability, capacity, or performance of the mentioned hardware or so ftware products are given "as is" and all liability arising in connection with such hardware or software products shall be defined conclusively and finally in a separate agreement between Nokia Siemens Networks and the customer. However , Nokia Siemens Networks has made all reasonable efforts to ensure that the instructions contained in the document are adequate and free of m aterial errors and omissions. N okia Siemens Networks will, if deemed necessary by Nokia Siemens Networks , explain issues which may not be covered by the document. Nokia Siemens Networks will correct errors in this documentation as soon as possible. IN NO EVENT WILL NOKIA SIEMENS NETWORKS BE LIABLE FOR ERRORS IN THIS DOCUMENTATION OR FOR ANY DAMAGES, INCLUDING BUT NOT LIMITED TO SPECIAL, DIRECT, INDIRECT, INCIDENTAL OR CONSEQUENTIAL OR ANY LOSSES, SUCH AS BUT NOT LIMITED TO LOSS OF PROFIT, REVENUE, BUSINESS INTERRUPTION, BUSINESS OPPORTUNITY OR DATA,THAT MAY ARISE FROM THE USE OF THIS DOCUMENT OR THE INFORMATION IN IT. This documentation and the product it desc ribes are considered protected by copyrights and other intellectual property rights according to the applicable laws. The wave logo is a trademark of Nokia Siemens Networks Oy. Nokia is a registered trademark of Nokia Corporation. Siemens is a registered trademark of Siemens AG. Other product names mentioned in this document may be trademarks of their respective owners, and they are mentioned for identification purposes only. Copyright © Nokia Siemens Networks 2009. All rights reserved.
f
Important Notice on Product Safety This product may present safety risks due to laser, electricity, heat, and other sources of danger. Only trained and qualified personnel may i nstall, operate, maintain or otherwise handle this product and only after having carefully read the safety information applicable to this product. The safety information is pr ovided in the Safety Information section in the “ Legal, Safety and Environmental Information” part of this document or documentation set.
The same text in German:
f
Wichtiger Hinweis zur Produktsicherheit Von diesem Produkt können Gefahren durch Laser, Elektrizität, Hitzeentwicklung oder andere Gefahrenquellen ausgehen. Installation, Betrieb, Wartung und sonstige Handhabung des Pr oduktes darf nur durch geschultes und qualifiziertes Personal unter Be achtung der anwendbaren Sicherheitsanforderungen erfolgen. Die Sicherheitsanforderungen finden Sie unter „Sicherheitshinweise“ im Teil „Legal, Safety and Environmental Information“ dieses Dokuments oder dieses Dokumentationssatzes.
2
A25000-A900-A32-2-76P1 Issue: 2 Issue date: September 2009
Quick Installation Guide
Table of Contents This document has 10 pages. 1 1.1
Flexi Outdoor Case Quick Installation Guide. . . . . . . . . . . . . . . . . . . . . . 5 Generic Information . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
1.2 1.3 1.4
Installing on the floor . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6 Installing on the pole . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7 Installing on the wall . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8
1.5 1.6
General rules for IDU cabling. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8 Final Operation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10
A25000-A900-A32-2-76P1 Issue: 2 Issue date: September 2009
3
Quick Installation Guide
4
A25000-A900-A32-2-76P1 Issue: 2 Issue date: September 2009
Quick Installation Guide
Flexi Outdoor Case Quick Installation Guide
1 Flexi Outdoor Case Quick Installation Guide 1.1
Generic Information Dimension of Flexi Outdoor Case
Standard tools
8 mm Allen key TX 10 screwdriver for M3 screw TX 25 screwdriver for M5 screw 7 mm spanner and 13 mm spanner Adjustable wrench (56 to 64 mm) Fish tape and Thread locking compound (medium strength non-permanent)
g This product may need to be installed on a high-rise structure such as a mast or roof. When installing the product, wear a safety h arness and other relevant protective gear. In addition, follow all occupational health and safety regulations applicable to the installation.
Minimum clearances Wall measurements
Top min 30 mm
min 105 mm measured from back cover (needed for fresh air)
Fan maintenance space from the back 145mm Fan maintenance space from the back 145mm Between FOCs min 100 mm
min 145 mm measured from plinth Front min 600 mm To side min 400 mm
To side min 75 mm Front min 600 mm Plinth
Preparation of installation
1.The cable output must be placed depending on the installation needs. This evaluation must be made before starting the installation procedure. 2. Besides the type of the IDU, its placement into the FOC should be considered. The installation technician is charged to choose how the IDU must be installed.
A25000-A900-A32-2-76P1 Issue: 2 Issue date: September 2009
5
Flexi Outdoor Case Quick Installation Guide
Quick Installation Guide
Install the adapter mechanics a
Install Flexi Outdoor Case to the plinth Thread locking compound (medium strength non-permanent)
Thread locking compound (medium strength, non-permanent)
c
Bottom
a1 b b
Thread locking compound (medium strength, non-permanent)
The installation of the two squares depends on the right/left positioning of the front side with respect to the pole/wall.
1.2
Fix the outdoor case to the plinth with two torx M5x8 screws and thread locking compound.
Installing on the floor Install the Plinth and the FOC case
1. Check the clearances around the plinth. Facility wall
Plinth
min 250 mm (9.8 in.)
Fan maintenance space from the back 145 mm (5.7 in.)
2. Place the plinth on the floor, grouding points facing forward. 3. Bolt on the floor with two bolts.
13.5 (4 pcs)
4. Fix the outdoor case on the plinth.
g Do not connect the cables before having carried out the fixing of the case on the plinth.
The two-outputs configuration
In the floor installation, the two-outputs configuration can be used.
6
Stacking of more FOCs
More FOCs can be stacked and this option is only possible for the floor installation. And maximum 5 FOCs can be stacked for zone 4 and maximum 11 FOCs for zone 2 (earthquake measures).
A25000-A900-A32-2-76P1 Issue: 2 Issue date: September 2009
Quick Installation Guide
1.3
Flexi Outdoor Case Quick Installation Guide
Installing on the pole Safety washers position
Hole Numbering
Fix the mounting screws
g Note that the blue safety washers hold the screws in place during installation. They should be installed to the screws after the screws are through the bracket.
Fix the lower bracket
Lift the plinth and Tighten the screws
Fix the lower bracket
g Before mounting the outdoor case on the pole, install the IDU. The IDU can be installed after having placed FOC on the pole. Do not connect the cables before having carried out the lifting of the IDU on the pole.
Tighten the screws
Back-to-back Installation
g A second unit can be installed back to back using the same brackets. And maximum 2 units can be stacked on the pole.
A25000-A900-A32-2-76P1 Issue: 2 Issue date: September 2009
7
Flexi Outdoor Case Quick Installation Guide
1.4
Quick Installation Guide
Installing on the wall Prepare the wall installation
Lift the plinth and Tighten the screws
g Do not connect the cables before having carried out the lifting of the IDU on the wall.
Fix the lower adapter mechanics and Tighten the screws
Two cases on the wall
Front min 600mm
g Before mounting the outdoor case on
To side min 400mm
the wall, install the IDU. The IDU can be installed after having placed FOC on the wall.
8
1.5
General rules for IDU cabling
g
Connect the grouding cable to the IDU before inserting the I DU into the case. Make sure that the fans power supply cables can be easily reached for their successive connection to fan controller board.
A25000-A900-A32-2-76P1 Issue: 2 Issue date: September 2009
Quick Installation Guide
Flexi Outdoor Case Quick Installation Guide
Insert the cables
Bend and Hose for Floor Installation
Detail for inner cover, side panel and hose
Hose for Pole/Wall Installation
Example for the FlexiHybrid
Before connecting the cables, the plate has to be fixed to the inner cover by 4 M3 screws. And the plate has not to be removed any more.
Power and Alarm cable o ptions
Another power cable T55248.30 OR T55248.31 for 2nd IDU installed /power redundancy
Power cable T55248.30 from FlexiBTS/FPMA OR T55248.31 from general power source
A25000-A900-A32-2-76P1 Issue: 2 Issue date: September 2009
9
Flexi Outdoor Case Quick Installation Guide
1.6
Quick Installation Guide
Final Operation Final taping
Connection of the GND cables and Install the covers
C
Connect the cable to IDU/FOC, taping the cables at the end of th hose and fix the cable by ties. After that, close the FOC.
FOC is equipped with two grounding cables. Connect always both the cables to the grounding point inside the cover. The unused cable can be used in a future expansion. (a) IDU grouding cable (b) external FOC grounding cable (c) site grounding cable
Installation of the cable output block
10