EEPB383,Semester22011/2012 EEPB383,Semester2201 1/2012
COLLEGEOFENGINEERING PUTRAJAYACAMPUS FINALEXAMINATION SEMESTER22011/2012 PROGRAMME
: Bachelor of Electrical Power Engineering (Honours)
SUBJECT CODE
: EEPB 383
SUBJECT
: Electrical Power System II
DATE
: December 2011
TIME
: 2 ½ hours
INSTRUCTIONSTOCANDIDATES:
1.
ThispapercontainsFIVE(5)questionsinSEVEN(7)pages.
2.
AnswerALLquestions.
THISQUESTIONPAPERCONSISTSOF7PRINTEDPAGESINCLUDINGTHIS COVERPAGE. COVERPAGE.
Page1of17
EEPB383,Semester22011/2012
QUESTION1[15MARKS]
The9–buspowersystemnetworkofanelectricutilitycompanyisshownintheFigure1 below. Plant 3 and 5 are shut-down for maintenance leaving plant 1, 2 and 7 generating powertofeedtheloadsateachofthebusesshownintheFigure1.Theproductioncostsfor plant1,2and7in$/hisgivenasfollows: C 1
=
240 + 6.7 P1 + 0.009 P12
C 2 = 220 + 6.1P2 + 0.005 P22 C 7 = 240 + 6.5 P7 + 0.008P72
whereP1,P2andP7 are in MW.
Figure1 Withoutconsideringpowerlossesinnetwork,answerthefollowingquestions. a) Findtheincrementalcostsforpowerplant1,2and7intermsofitspowergenerated. [3marks]
b) Assumingallthreepowerplants1,2and7generatewithinitspowergenerationlimits; determine the optimum dispatch of generation.
[8marks]
c) Ifthepowergenerationlimitforplantno.1isbetween80MWand300MW,determine the new optimum dispatch of generation. Page2of17
[4marks]
EEPB383,Semester22011/2012
QUESTION2[15MARKS]
a) Drawtheequivalentcircuitforsub-transientperiodofasynchronousgenerator.Labelall components of the circuit.
[5marks]
b) A100-MVA,20-kVsynchronousgeneratorisconnectedthroughatransmissionlinetoa 100-MVA,20-kVsynchronousmotor.Theperunittransientreactancesofthegenerator andmotorare0.25and0.20,respectively.Thelinereactanceonthebaseof100MVAis 0.1perunit.Themotoristaking50MWat0.8powerfactorleadingataterminalvoltage of 20kV. A three-phaseshortcircuit occurs at the generator terminals. Determine the transientcurrentsineachofthetwomachinesandintheshortcircuit. [10marks]
QUESTION3[25MARKS]
G1
G2 T1
T2
1
2 CB1
CB2
3
4
Figure2
Page3of17
EEPB383,Semester22011/2012
A 4-bus power system network aboveis representedas a Thevenin equivalent network in termsofitsimpedancevalues.Detailedvaluesareasfollows(allvaluesareinpu): Item
Base MVA
Voltage
X0
Rating
X1
X2
G1
100
20kV
j0.08
j0.25
j0.25
G2
100
20kV
j0.07
j0.2
j0.2
T1
100
20/275kV
j0.09
j0.1
j0.1
T2
100
20/275kV
j0.09
j0.1
j0.1
L12
100
275kV
j0.4
j0.12
j0.12
L13
100
275kV
j0.6
j0.14
j0.14
L23
100
275kV
j0.7
j0.16
j0.16
L34
100
275kV
j0.8
j0.18
j0.18
Theneutralforeachgeneratorisconnectedtogroundviaacurrentlimitingreactorofj0.3per unit. The Generators are operating at no-load, producing voltages at rated values at a frequencyof50Hz.Thesystemvoltagesareatratedvalues.Allvaluesareexpressedinper unitonacommon100MVAbase.CircuitBreaker1(CB1)andCircuitBreaker2(CB2)are in the OPEN position.A bolted3 phase to ground fault occurred at Bus 4. Please dothe following:
a)
Determine the Admittance Matrix
[2marks]
b)
Calculate the fault current at Bus 4 in per unit
[4marks]
c)
DeterminethevoltagesatBus1,Bus2,Bus3andBus4duringfault [10marks]
d)
Calculatethefaultcurrentflowinginline2–3,1–3and3-4
e)
Atreefalls downandshortsall 3phases ina transmissionline toground. Isthisa bolted or non-bolted fault? Explain why?
Page4of17
[6marks]
[3marks]
EEPB383,Semester22011/2012
QUESTION4[25MARKS]
RefertothepowersystemshowninFigure3andtheparametersgiven.
Figure3
GeneratorsG1andG2: X 1
= X
TransformersT1andT2: X 1 Line: Z 1
= Z
2
=
2
= 2
0
j 0.1 p.u; X = j 0.05 p.u; 0
= X = X =
j 0.15 p.u;
0
j 0.05 p.u, Z = j 0.1 p.u ;
Voltage:11kV Voltage: 11/275 kV Voltage: 275 kV
Allperunitvaluesareonabaseof100MVA,andpre-faultvoltageis1.0perunit.
a) Drawthepositive,negativeandzerosequenceimpedancenetworksforthepowersystem. Stateinyourdrawingthenumericalvaluesofalltheimpedance.
[2+2+2marks]
b) Determinethefaultcurrentinperunitforaboltedsingle–line-groundfaultatbusB. [4marks] c) Determinethecurrentinperunitflowinginthefaultedphaseoftheoverheadlinefora bolted single-line-ground fault at busbar B.
[10marks]
d)DeterminethecurrentflowingintheneutralofT1andT2forasingle-line-groundfaultat bus B given the fault impedance is j0.5 per unit.
Page5of17
[5marks]
EEPB383,Semester22011/2012
QUESTION5[20MARKS]
Figure3 A50Hz,H=5MJ/MVAgeneratorisconnectedthroughparalleltransmissionlinestoa grid system. The machine is delivering 1.0pu power and both the terminal voltage and the infinite-busare1.0pu.Thevaluesofthereactanceonacommonsystembasearegivenasin thediagram.Thetransientreactanceofthegeneratoris0.20puasindicated. Determine: a) Thepower-angleequationduringsteadystatecondition. b) Find the initial operating angle.
[15marks] [2marks]
c) A temporary fault occurs at a distance of 20% of the line length away from the sending end terminal of the line. When the fault is cleared by an auto-reclose protection,bothlinesareintact.Determinethecriticalclearingangleandthecritical fault clearing time.
[3marks]
ENDOFQUESTIONPAPER
Page6of17
EEPB383,Semester22011/2012
FormulaSheet n
P D +
n
P D =
λ − β i ; 2 γ i =1 i
∑
λ =
i =1
n
+ D
π f 0 dt 2
d ∆δ
+
dt
i
1
∑ 2γ i =1
H d 2 ∆δ
β i
∑ 2γ i
PS ∆δ = 0
2
H d δ
=
π f 0 dt 2 δ = δ 0
∆δ 0
+
2
ω n ∆δ 0
−
2
−ξω nt
e
D
π f 0
2
HPS
π f 0
=
ω d
= ω n
H
sin (ω d t + θ )
−ξω nt
1 − ξ
ω n
sin ω d t
PS
1 − ξ 2
I a0 = I a1 = I a2 =
I 1a = − I a2 =
θ = cos −1 ξ
E a 1
2
Z + Z + Z 0 + 3 Z f E a
1
2
Z + Z + Z f
:
:
Singlelinetogroundfault
Line-Line fault
1 1
0
I a = −
I a2
e
1 − ξ
ω = ω 0
ξ =
Pm − Pe
=−
E a − Z I a 0
Z + 3 Z f
E a
:
Double Line to Ground Fault
:
Double Line to Ground Fault
1 1
− Z I a
Z 2
Page7of17
EEPB383,Semester22011/2012
I a1 =
E a 1 Z + 2 0 Z + Z +3 Z f Z 2 Z 0 +3 Z f
V a 1 1 b 2 V = 1 a V c 1 a iasy (t ) =
S pu =
S S B
SCC =
:
Double Line to Ground Fault
1 V a0
a V a1 2 2 a V a
1 E 0 1 −t τ d '' 1 1 −t τ d ' 1 e e ( t ω − + − + + δ ) + 2 sin sin δ e −t τ a '' X '' X ' X ' X X d X d d d d d
2 E 0
,
S B X kk
V pu =
V V B
,
new old Z pu = Z pu
I pu =
I I B
,
S Bnew V Bold
Z pu =
Z Z B
2
S Bold V Bnew
Page8of17
,
Z B =
(V B )2 S B
, I B
=
S B
3V B
EEPB383,Semester22011/2012
Solution
Question1[15marks] a) dC 1
λ 1 =
dP1
λ 2
=
λ 7
=
dC 2 dP2 dC 7 dP7
= 6.7 + 0.018 P1 $/MWh
= 6.1 + 0.010 P2 $/MWh
= 6.5 + 0.016 P7 $/MWh
b) Neglectinglosses,totalpowerdemand, P D = P1 + P2 + P3 + ...... + P9
= 0 + 20 + 25 + 10 + 40 + 60 + 10 + 80 + 100 = 345 MW P D +
λ =
β i i =1, 2, 7 2γ i
∑
1 i =1, 2 ,7 2γ i
6 .7 6.1 6.5 + + 2(0.009) 2(0.005) 2(0.008) =7.95$/MWh 1 1 1 + + 2(0.009) 2(0.005) 2(0.008)
345 + =
∑
SolveforPbasedonoptimaldispatch, 6.7 + 0.018P1 P1
= 7.95
= 69.44 MW
6.1 + 0.010 P2 = 7.95 P2 = 185 MW 6.5 + 0.010 P7
= 7.95
P7 = 90.625 MW
c) Set P1
= 80 MW,optimise P2 and P7
Page9of17
EEPB383,Semester22011/2012
6 .1 6.5 + 2(0.005) 2(0.008) =7.885$/MWh 1 1 + 2(0.005) 2(0.008)
345 − 80 +
λ =
6.1 + 0.010 P2 = 7.885 P2 = 178.5 MW 6.5 + 0.010 P7
= 7.885
P7 = 86.56 MW
Total=80+178.5+86.56=345MW
Questions2[15marks] a)
Xl:leakagereactance Xad:reactanceduetoarmaturereaction Xf :reactanceduetofiledwinding b)
Sm
=
50∠ − 36.87° 0.8 ×100
= 0.625∠ − 36.87° p.u
[1 mark]
Vm
=
20 20
= 1∠0° p.u
[1 mark] Before the fault, *
I m
=
Sm V m
=
0.625∠36.870 1
=
0.625∠36.87 0 p.u [1 mark]
Page10of17
EEPB383,Semester22011/2012
Generator emf behind transient reactance is,
E g '
= Vm +
' j ( X dg
+
X l )I m
= 1∠ 0 +
j (0.25 + 0.1) *0.625∠ 36.87° = 0.8688 + j 0.175 = 0.8862∠11.39° p.u [2 marks]
Motor emf behind transient reactance is, ' Em ' = Vm − j ( X dm ) I m = 1∠0 − j (0.2) *0.625∠36.87 ° = 1.075 − j 0.10 = 1.0796 ∠ − 5.32 ° p.u
[2 marks]
During fault, the generator short circuit current is, '
I g
=
'
0.8862∠11.390 = ' j ( X dg j 0.25 ) E g
= 3.545∠ − 78.61° p.u
[1 mark] During fault, the motor short circuit current is,
I
' m
=
E m '
'
=
1.0796∠ − 5.320
j ( X dm + X l )
= 3.5988∠ − 95.32° p.u
j 0.30
[1 mark] The short circuit current is
I f' = I g' + Im' = 3.545∠ − 78.61° + 3.5988∠ − 95.32° = 7.0679∠ − 87.03° p.u
Questions3[25marks] a) Determine the Admittance Matrix
Converting to Admittance values Item
[2 marks]
X1
Y1
G1
j0.25
-j4
G2
j0.2
-j5
T1
j0.1
-j10
T2
j0.1
-j10
L12
j0.12
-j8.333
L13
j0.14
-j7.143
L23
j0.16
-j6.25
L34
j0.18
-j5.556
Page 11of17
EEPB383,Semester22011/2012
b) Calculate the fault current at Bus 4 in per unit
[4 marks]
Calculating Z 44: Item
X1
G1
j0.25
G2
j0.2
T1
j0.1
T2
j0.1
L12
j0.12
L13
j0.14
L23
j0.16
L34
j0.18
Calculating Fault Current at Bus 4
c) DeterminethevoltagesatBus1,Bus2,Bus3andBus4duringfault marks]
Page 12of17
[10
EEPB383,Semester22011/2012
d) Calculatethe faultcurrentflowinginline2–3,1–3and3-4
[6marks]
e) Atreefallsdownandshortsall3phasesinatransmissionlinetoground.Isthisa bolted or non-bolted fault?. Explain why?
It is a non-Bolted Fault because the tree has impedance.
Question4[25marks] a)
Positivesequencenetwork
Negativesequencenetwork
Page 13of17
[3 marks]
EEPB383,Semester22011/2012
Zerosequencenetwork
b) 0
I a
1
E a
2
= I a = I a =
1
2
0
Z B + Z B + Z B
+ 3 Z f
1
Z B = ( j 0.1 + j 0.15 + j 0.05) //( j 0.15 + j 0.1) =j0.1364 2
Z B
=
1
Z B =j0.1364
0
Z B = ( j 0.15 + j 0.1) //( j 0.15) =j0.09375 0
I a
1
2
= I a = I a =
0
I B ( F ) = 3 I a
1.0 =-j2.728.pu j 0.1364 + j 0.1364 + j 0.09375 + 0
= − j8.1844 p.u
c) PositivesequencevoltageatbusesAandB,
1
1
∆V A = ( j 0.1 + j 0.15) * I B ( F )(
1
1
0.25 ) = j 0.25 * j 2.728 * 0.4545 =-0.31 0.55
1
V A ( F ) = V A (0) + ∆V A =1.0–0.31=0.69p.u 1
1
∆V B = ( j 0.1 + j 0.15 + j 0.05) * I B ( F )(
0.25 ) =-0.372 0.55 Page 14of17
EEPB383,Semester22011/2012
1
1
1
V B ( F ) = V B (0) + ∆V B =1.0–0.372=0.628p.u
NegativesequencevoltagebusesAandB, V A2 ( F ) = V A2 (0) + ∆V A2 =0.0–0.31=-0.31 2
2
2
V B ( F ) = V B (0) + ∆V B =0.0–0.372=-0.372
ZerosequencevoltagebusesAandB,
0
0
∆V A = ( j 0.15) * I B ( F )(
0
0
0.25 ) =-0.186 0.55
0
V A ( F ) = V A (0) + ∆V A =0.0–0.186=-0.186p.u
0.25 ) =-0.31p.u 0.55 0 0 0 V B ( F ) = V B (0) + ∆V B =0.0–0.31=-0.31p.u 0
0
∆V B = ( j 0.15 + j 0.1) * I B ( F )(
012
I AB
V A0 ( F ) − V B0 ( F ) − 0.186 − (−0.31) 0 z AB j 0.1 − j1.24 V A1 ( F ) − V B1 ( F ) 0.69 − 0.628 = − j1.24 p.u = = 1 j 0.05 z AB 1 . 24 − j V A2 ( F ) − V B2 ( F ) − 0.31 − (−0.372) 2 j 0.05 z AB
Page15of17
EEPB383,Semester22011/2012
1 1 abc 012 I AB ( F ) = AI AB ( F ) = 1 a 2 1 a
1 − j1.24 a − j1.24
a − j1.24 2
a I AB = 3( − j1.24) =-j3.72p.u b I AB = 1.24∠ − 90° + 1.24∠ − 90 + 240° + 1.24∠ − 90° + 120° =0.0p.u c I AB = 1.24∠ − 90° + 1.24∠ − 90 + 120° + 1.24∠ − 90° + 240° =0.0p.u
Question5[20marks]
AtinfinitenodeH=α Thereactancebetween1and3,X=j(0.1+0.5/2)=j0.35pu
1mar
Outputpowerofgenerator Powerangleequation: 2mar
, which is equivalent to Vtanglerelativetotheinfinitebus 2mar Theterminalvoltage:Vt=1∠20.5°pu=0.94+j0.35pu
1mar
Theoutputcurrentofthegenerator:
2mar
Thetransientinternalvoltage: Page16of17
EEPB383,Semester22011/2012
2mar
Thetotalseriesresistance: 1mar
ThepowerangleequationrelatingE’andV: 2mar
b)&c) Theinitialoperatingangleisgivenby: 2mar
Sincebothlinesareintactwhenthefaultiscleared,thepower-angleequationbeforeandafter thefaultremainsthesame: 2mar
1mar
Page17of17