The values given in Table VB show (for information) the present practice in the United States •of America and Canada. TABLE VB (under consideration) Co-ordination of rated values for rated voltages Series II: 4.76 KV to 38.0KV (Indoor disconnectors)
Rated voltage
Rated short– time withstand current (r.m.s.
Rated peak withstand
Rated normal current (r.m.s)
(KV)
(KA)*
(KA)
(A)
4.76
12.5 25 38.1 50 62.5
33.8 67.5 102.9 135 168.8
200 -
400 -
630 -
1250 -
2000 -
3150
-
-
-
8.25
12.5 25 38.1 50 62.5 75 100 125
33.8 67.5 102.9 135 168.8 202.5 270 337.6
200 -
400 -
630 -
1250 -
2000 -
3150 -
4000 -
5000
6300
15 and 15.5
12.5 25 38.1 50 62.5 75 100 125
33.8 67.5 102.9 135 168.8 202.5 270 337.6
200 -
400 -
630 -
1250 -
2000 -
3150 -
4000 -
5000
6300
25.8
12.5 25 38.1 50 62.5 75 100
33.8 67.5 102.9 135 168.8 202.5 270
-
400 -
630 -
1250 -
2000 -
3150 -
4000 -
5000
-
38
12.5 25 38.1 50 62.5 75
33.8 67.5 102.9 135 168.8 202.5
-
400 -
630 -
1250 -
2000 -
3150 -
4000
-
-
Values more in the with IEC Publication are under consideration
Note: - The co-ordination table is intended to be used as a guide for preferred values and is not mandatory. Therefore a disconnector or earthing switch with another combination of the rate values is not outside this specification