HYDRAULIC CALCULATIONS FOR WATER STORAGE TANK
DM Water
Storage Tank Service Manhole
Vent
Freefloat, L8
Overflow nozzle
Top Capacity Level (TCL) - L7 High High Level (HHL) - L6 High Level (HL) - L5 Normal Level (NL) - L4
Working Capacity
Low Alarm (LA) - L3
Parameters Nominal Tank Diameter, D
UOM feet
Value 26.00
Silt allowance, L0
inch
0
Largest size of nozzle in bottom plate Bottom Capacity Level, L1 Top of Lowest Suction Nozzle Low Low Trip, L2 Low Alarm, L3 Working Capacity / Usable volume
inch inch inch inch inch gal
4 6 10 16 22 75,000
Top Capacity Level, L7
inch
233
Size of overflow nozzle Freefloat level, L8 High High Level, L6 High Level, L5 Normal level, L4 Tank Height (H) Adjusted Height H/D ratio Max. inflow Max. outflow Residence time between HL to LLT Dead storage Reserved fire water storage Max. fire water demand Volume available for non-fire users
Minimum 4 inch, only recommended for tanks storing suspended solids
Note-3 Check site limitations, Note-2 Should be between 0.6 to 0.8, Note-1
Note-5 Note-4 Between Normal and Hi-Hi level
Input Cells Low Low Trip (LLT) - L2 TOP OF LOWEST SUCTION NOZZLE Pump Suction nozzle
Bottom Capacity Level (BCL) - L1 Drain
Silt Allowance (SL) - L0
Notes 1) H/D ratio shall be maintained 0.6 to 0.8 for reservoirs and 1 to 4 for standpipe 2) Check maximum allowable nominal diameter (D) and height (H) per site conditions 3) For combined fire / service water tank, normal level is replaced by reserved fire water level 4) Resolve all "RED" cells, except fire water storage for non-fire water tanks 5) If inflow is more than outflow, residence time is with inflow closed