Test Report of Generator Protection Relay Rel ay (G60-A) for Engro Powergen Project
Customer Relay Type Panel Identification Relay Identification Relay Make Model Serial No. Firmware Revision Auxiliary Voltage Test Starting Date Test Set Used
Generator Genout Voltage Connection Type CT Ratio Genout Side (CT-6) CT Ratio Neutral Side (CT-1) VT Ratio (VT-G) Aux. Neutral VT(NET)
11.0 kV WYE 8000/1 8000/1 13.8kV/100V 13.8kV/200V
Testing Procedure
1. 2. 3. 4. 5. 6. 7.
Verify that the relay rear connection/wiring is according to referred drawings. Power up relay at its rated voltage mentioned on face plate of relay. Verify that “ In Service” green LED on face plate is lit up. Verify that different protection units inside the relay are configured on desired settings. Isolate the relay from field side wiring as per referred drawing. Inject different voltage & current values (according to relay trip settings) to relay and check its functionality and behavior. Note down all test results in tables given below.
EPESOL (PVT) LTD SHT 1 OF 14
Partner GE Energy
Test Report of Generator Protection Relay (G60-A) for Engro Powergen Project
1.
2
Measuring / Metering Accuracy
Source
Phase Involved
Ratio
Applied Analog Signals (Secondary)
Measured Value (Primary)
Source 2,Line Side Source 2, Line Side Source 2, Line Side Source 1, Neutral Side Source 1, Neutral Side Source 1, Neutral Side Main PTs (VTG-P) Main PTs (VTG-P) Main PTs (VTG-P) NET