Fault Code Booklet R410a Non Inverter and Inverter R22 Fixed Speed
2016 Version 1.2
Products That Perform…By People Who Care
FAULT CODE BOOKLET Index
2016 Version 1.2
R22 Type Split Units High Wall Split Type
Page 1
Cassee Split Type
Page 2
Ducted Split Type
Page 3
Under Ceiling Split Type
Page 5
R22 Type Rooftop Units DBRT Rooop Type
Page 6
R410A Non-Inverter Type Split Units High Wall Split Type
Page 7
Cassee Split Type
Page 8
Ducted Split Type
Page 9
Under Ceiling Split Type
Page 10
R410A Non-Inverter Type Rooftop Units DBRT Rooop Type
Page 11
R410A Inverter Type Split Units High Wall Split Type
Page 13
Cassee Split Type
Page 17
Ducted Split Type
Page 20
Under Ceiling Split Type
Page 24
FAULT CODE BOOKLET R22 Fixed Speed High Wall Split
2016 Version 1.2
F Series High Wall Split Type Sensor Resistance Table
TX (⁰C) 15 16 17 18 19 20 21 22 23 24 25 26 27 28 29 30 31 32 33 34
KΩ 16.1156 15.3418 14.6181 13.9180 13.2631 12.6431 12.0561 11.5000 10.9731 10.4736 10.000 9.55074 9.12445 8.71983 8.33566 7.97078 7.62411 7.29464 6.98142 6.68355
Display
Fault Descripon
DUNHAM-BUSH Reserve the right to change any specicaons and design without prior noce for product improvement
Ed
EEPROM error
E1
Communicaon error
E2
No over zero signal (EEPROM error)
E3
Indoor fan motor fan speed abnormal
E5
Outdoor temperature sensor abnormal/EEPROM error
Note:
E6
Room or coil temperature sensor abnormal
Indoor fan motor fan
E7
Outdoor fan motor fan speed abnormal
speed abnormal faults
P0
Over current of compressor protecon
P1
Voltage protecon
reading the feedback
P2
Compressor temperature protecon
circuit
P3
Low outdoor temperature protecon
can be caused by a faulty PC Board not or
a
faulty
indoor fan. A slow ash on the F series operaon lamp indicates that the unit is in standby mode, a quick ash indicates that the indoor coil
Fravega High Wall Split Type
temperature sensor is abnormal.
Sensor Resistance Table
TX (⁰C) 15 16 17 18 19 20 21 22 23 24 25 26 27 28 29 30 31 32 33 34
KΩ 7.464 7.164 6.877 6.603 6.342 6.092 5.854 5.626 5.408 5.199 5.000 4.811 4.630 4.456 4.291 4.132 3.98 3.835 3.695 3.562
Display
Fault Descripon The wired controller on the F series will not
dF
Defrosng
E1
Room temperature sensor abnormal
occurs and will not
E2
Outdoor coil temperature sensor abnormal
display a fault code,
E3
Indoor coil temperature sensor abnormal
please revert to the
E4
Indoor fan motor fan speed abnormal
E6
No over zero signal (EEPROM error)
funcon
if
a
fault
display board of the unit for fault codes. The standard value for
Thermocold High Wall Split Type
the three sensors on the F series is 10k Ω at 25˚C and 5kΩ at 25 ⁰C
Display
Fault Descripon
on the Fravega and Thermocold units.
dF
Defrosng
E1
Room temperature sensor abnormal
the
Room temperature sensor abnormal for second generaon
Thermocold units the
Outdoor coil temperature sensor abnormal
cleaning funcon has
E2 E3 E4
Indoor coil temperature sensor abnormal
If CL is displayed on Fravega
been selected on the infrared remote.
Outdoor coil temperature sensor abnormal for second generaon Indoor fan motor fan speed abnormal
E5
Indoor fan motor fan speed abnormal for rst and second generaon
E6
No over zero signal (EEPROM error)
and
Page 1 of 25
FAULT CODE BOOKLET R22 Fixed Speed Cassee Split
2016 Version 1.2
Compact Cassette Split Type DUNHAM-BUSH Reserve the right to change any specicaons and design without prior noce for product improvement
Note: A
slow
ash
operaon
on lamp
Indicates that the unit
Run
Timer
Defrost
Alarm
O
Flash
O
O
Room temperature sensor abnormal
Flash
O
O
O
Indoor coil temperature sensor abnormal
O
O
Flash
O
Outdoor coil temperature sensor abnormal
Flash
Flash
Flash
O
Over current of compressor protecon
Flash
Flash
Flash
Flash
Flash
Flash
O
O
O
O
O
Flash
Fault Descripon
Outdoor unit protecon No over zero signal/EEPROM error Water level alarm
is in standby mode, a quick ash indicates that the indoor coil temperature sensor is
Cassette Split Type Display
Fault Descripon
abnormal. The wired controller
E1
Communicaon error
fault occurs and will
E2
Room temperature sensor abnormal
not display a fault
E3
Indoor coil temperature sensor abnormal
E4
Outdoor coil temperature sensor abnormal
E5
Pump sensor abnormal
codes.
E6
Outdoor unit protecon
The standard value for
E7
No over zero signal/EEPROM error
the three sensors is
E8
Water level alarm
will not funcon if a
code, please revert to
Sensor Resistance Table
TX (⁰C) 15 16 17 18 19 20 21 22 23 24 25 26 27 28 29 30 31 32 33 34
KΩ 16.1156 15.3418 14.6181 13.9180 13.2631 12.6431 12.0561 11.5000 10.9731 10.4736 10.000 9.55074 9.12445 8.71983 8.33566 7.97078 7.62411 7.29464 6.98142 6.68355
the display board of the
unit
for
fault
T2 Low Temperature 0⁰C 5⁰C
Cut Out Cut In
10kΩ at 25˚C. The water ow switch must
be
normally
closed if it is open it is seen as a fault. The ow switch does not
Outdoor Unit
regulate the condensaon pump and only
LED1
LED2
LED3
O
Flash
Flash Outdoor coil temperature sensor abnormal
O
Flash
O
HP/HDT switch open or ambient sensor abnormal
dry mode when the
Flash
O
O
Phase rotaon or phase failure
compressor is ener-
O
O
O
Over current of compressor protecon
Flash
Flash
O
LP switch open
Fault Descripon
T3 High Temperature
acts as an safety . The
condensaon
pump will run connuously in cooling and
gized. The pump will run for 2 minutes stopped
and
Low Pressure Switch: High Pressure Switch:
: 150Kpa
Cut Out : 3300Kpa Cut In
of 25
Cut Out Cut In
<-7⁰C/>43⁰C >-7⁰C/<43⁰C
Cut Out : 50Kpa Cut In
then switch o.
Page 2
T4 Ambient Temperature
HDT Pipe Temperature
aer the compressor have
65⁰C 52⁰C
Cut Out Cut In
: 2400Kpa
Cut Out Cut In
115⁰C 90⁰C
FAULT CODE BOOKLET R22 Fixed Speed Ducted Split
2016 Version 1.2
Ducted Split Type T2 Low Temperature 0⁰C 5⁰C
Cut Out Cut In T2B High Temperature
60⁰C 54⁰C
Cut Out Cut In
Run
Timer
Defrost
Alarm
O
Flash
O
O
Room temperature sensor abnormal
Flash
O
O
O
Indoor coil temperature sensor abnormal
O
O
Flash
O
Outdoor coil temperature sensor abnormal
Flash
Flash
Flash
O
Over current of compressor protecon
Flash
Flash
Flash
Flash
Flash
Flash
O
O
O
O
O
Flash
Fault Descripon
DUNHAM-BUSH Reserve the right to change any specicaons and design without prior noce for product improvement
Note:
Outdoor unit protecon A No over zero signal/EEPROM error Water level alarm
slow
ash
operaon
on lamp
Indicates that the unit is in standby mode, a quick ash indicates that the indoor coil temperature sensor is
Outdoor Unit (12 000Btu to 60 000Btu) LED1
T3 High Temperature 65⁰C 52⁰C
Cut Out Cut In T4 Ambient Temperature Cut Out Cut In
<-7⁰C/>43⁰C >-7⁰C/<43⁰C
LED2
LED3
Fault Descripon
The wired controller will not funcon if a fault occurs and will
Flash Outdoor coil temperature sensor abnormal
not display a fault
O
Flash
O
Flash
O
HP/HDT switch open or ambient sensor abnormal
Flash
O
O
Phase rotaon or phase failure
the
O
O
O
Over current of compressor protecon
codes.
Flash
Flash
O
LP switch open
The standard value for
HDT Pipe Temperature Cut Out Cut In
abnormal.
code, please revert to the display board of unit
for
fault
the three sensors is 115⁰C 90⁰C
Outdoor Unit (75 000Btu to 200 000Btu)
10kΩ at 25˚C. On the 75 000Btu to
LED1
LED2
LED3
Fault Descripon
200 000Btu units the phase failure relay is wired in on ether the
Sensor Resistance Table
TX (⁰C) 15 16 17 18 19 20 21 22 23 24 25 26 27 28 29 30
KΩ 16.1156 15.3418 14.6181 13.9180 13.2631 12.6431 12.0561 11.5000 10.9731 10.4736 10.000 9.55074 9.12445 8.71983 8.33566 7.97078
Flash
Flash O
O
Flash O
O
O
Communicaons error
LP circuit or ambient
HP, LP or Coil sensor open on 150 000Btu system A
sensor circuit.
LP switch open
On the 200 000Btu
Phase rotaon protecon on 150 000Btu
double
Flash HP/HDT switch open or ambient sensor abnormal
condenser
units with communicaon error inspect
O
Flash
O
Outdoor coil temperature sensor abnormal
P Q E connecon,
HP, LP or Coil sensor open on 150 000Btu system B
measure
Flash
Flash
Flash Phase rotaon or phase failure
O
Flash
Flash High temperature protecon on 150 000Btu
Low Pressure Switch:
Cut Out : 50Kpa Cut In
High Pressure Switch:
: 150Kpa
Cut Out : 3300Kpa Cut In
: 2400Kpa
between
(P to E) and (Q to E). Voltage
readings
between (P to E) and (Q to E) is between 2.5
to
2.7V
Screened cable is used.
Page 3 of 25
DC.
0.5mm
FAULT CODE BOOKLET R22 Fixed Speed Ducted Split
2016 Version 1.2
Outdoor Unit (75 000Btu to 200 000Btu) DUNHAM-BUSH Reserve the right to change any specicaons and design without prior noce for product improvement
LED1
LED2
On
1 quick and 1 slow ash
Phase rotaon or phase failure
On
2 quick and 1 slow ash
Communicaon error
On
3 quick and 1 slow ash
HDT switch open
On
4 quick and 1 slow ash
Ambient temperature sensor abnormal
O
1 quick and 1 slow ash
LP switch open
Flash
1 quick and 1 slow ash
LP switch open 3 mes in 20 minutes
includes all errors
O
2 quick and 1 slow ash
HP switch open
The Room tempera-
O
3 quick and 1 slow ash
Over current of compressor protecon
ture sensor’s range of
O
4 quick and 1 slow ash
Outdoor coil temperature sensor abnormal
Note: Total accuracy of the MiniGen
controller
Fault Descripon
T3 High Temperature 65⁰C 52⁰C
Cut Out Cut In T4 Ambient Temperature
<-7⁰C/>43⁰C >-7⁰C/<43⁰C
Cut Out Cut In
HDT Pipe Temperature 115⁰C 90⁰C
Cut Out Cut In
the MiniGen is from –30 to +100 ° C
MiniGen II, III and IIII universal controller The MiniGen controller’s room temperature
sensor
LED
Fault Descripon
dri
strongly depends on
Switch O
the operang condi-
1 ash and 1 second pause
Sensor failure
on. At room temper-
2 ash and 1 second pause
Air ow switch failure
4 ash and 4 second pause
Water ow switch failure
8 ash and 7 second pause
Communicaon failure
ature this dri is very low (< 0.05 °C can be expected). However, at
higher
DIP Switch Settings
tempera-
Switch On
DIP1 : Cooling only
Heang enabled
DIP2: 4 –way valve on in cooling
4 –way valve on in Heang
DIP3: Air ow switch
Not used
tures the dri will be worse,
mainly
because of changes in
3
mechanical stress. The MiniGen controller’s sensor can be
1.
Status Indicaon LED
extended to approxiIf the controller have power
mately 50 m, but this
1
depends enrely on
the LED will be lit , see above table for fault code sequence
ler’s room temperature
sensor’s
4
and descripon.
2 2.
Six Pole Dip Switch
operang voltage is
Used to select preferred
4.75 to 5.5V at a
sengs, see table on right for
supply
dip switch sengs
current
of
200uA.
Page 4 of 25
DIP5: Electric heang
and is funconing without fault
the applicaon. The MiniGen control-
DIP4: Water ow switch
3.
Air Flow Switch Connecon
4.
Water Flow Switch Connecon
DIP6: Compressor Lead/lag on
Not used
Reverse cycle heang Compressor lead/lag o
FAULT CODE BOOKLET R22 Fixed Speed Under Ceiling Split
2016 Version 1.2
Under Ceiling Split Type T2 Low Temperature 0⁰C 5⁰C
Cut Out Cut In T2B High Temperature
60⁰C 54⁰C
Cut Out Cut In
Run
Timer
Defrost
Alarm
O
Flash
O
O
Room temperature sensor abnormal
Flash
O
O
O
Indoor coil temperature sensor abnormal
O
O
Flash
O
Outdoor coil temperature sensor abnormal
Flash
Flash
Flash
O
Over current of compressor protecon
Flash
Flash
Flash
Flash
Flash
Flash
O
O
O
O
O
Flash
Fault Descripon
DUNHAM-BUSH Reserve the right to change any specicaons and design without prior noce for product improvement
Note:
Outdoor unit protecon A No over zero signal/EEPROM error Water level alarm
slow
ash
operaon
on lamp
Indicates that the unit is in standby mode, a quick ash indicates
Outdoor Unit
that the indoor coil temperature sensor is
T3 High Temperature 65⁰C 52⁰C
Cut Out Cut In T4 Ambient Temperature Cut Out Cut In
<-7⁰C/>43⁰C >-7⁰C/<43⁰C
LED1
LED2
LED3
O
Flash
Flash Outdoor coil temperature sensor abnormal
O
Flash
O
HP/HDT switch open or ambient sensor abnormal
Flash
O
O
Phase rotaon or phase failure
O
O
O
Over current of compressor protecon
the display board of
Flash
Flash
O
LP switch open
the
Fault Descripon
The wired controller will not funcon if a fault occurs and will not display a fault code, please revert to unit
for
fault
codes.
HDT Pipe Temperature Cut Out Cut In
abnormal.
115⁰C 90⁰C
The standard value for Low Pressure Switch: High Pressure Switch:
Sensor Resistance Table
Cut Out : 50Kpa
the three sensors is
Cut In
10kΩ at 25˚C.
: 150Kpa
Cut Out : 3300Kpa Cut In
: 2400Kpa
If
the
display
PCB
LED’s are randomly lit or if commands send
TX (⁰C) 15 16 17 18 19 20 21 22 23 24 25 26 27 28 29 30 31 32 33 34
KΩ 16.1156 15.3418 14.6181 13.9180 13.2631 12.6431 12.0561 11.5000 10.9731 10.4736 10.000 9.55074 9.12445 8.71983 8.33566 7.97078 7.62411 7.29464 6.98142 6.68355
to the unit is not received inspect
please the
display
PCB for physical damage such as water damage or damaged interconnecng cable between
main
and display PCB.
Page 5 of 25
PCB
FAULT CODE BOOKLET R22 Fixed Speed Rooop Package
2016 Version 1.2
DBRT Rooftop Package Type (18kW) DUNHAM-BUSH Reserve the right to change any specicaons and design without prior noce for product improvement
LED1
LED2
LED3
Flash
Flash
Flash
Flash
Flash
O
Flash
O
Flash
Evaporator coil sensor abnormal
O
Flash
Flash
Condenser coil sensor abnormal
On
Flash
Flash
Ambient sensor abnormal
O
Flash
O
Evaporator low temperature protecon
controller
Flash
On
On
Evaporator high temperature protecon
press the UP key, the
Flash
O
O
Condenser high temperature protecon
O
O
Flash
Over current of compressor protecon
the backlight key for
Flash
On
Flash
Compressor inner LP protecon
3 seconds to clear the
On
Flash
Flash
Defrosng
Note: To
reset
the
lter
alarm clock on the KJR25B
display will blink FILT and run me. Press
Fault Descripon
Phase rotaon or phase failure HP switch, vent protecon or room sensor abnormal
clock. Ensure that dip switch SW3 is set to ON for KJR25B use and for KJR12B the dip switch
DBRT Rooftop Package Type (28kW to 88kW) Display
Sensor Resistance Table
TX (⁰C) 15 16 17 18 19 20 21 22 23 24 25 26 27 28 29 30 31 32 33 34
KΩ 16.1156 15.3418 14.6181 13.9180 13.2631 12.6431 12.0561 11.5000 10.9731 10.4736 10.000 9.55074 9.12445 8.71983 8.33566 7.97078 7.62411 7.29464 6.98142 6.68355
Fault Descripon
must be set to 1. The
phase
relay is wired the
E0
Phase rotaon or phase failure
in on
E1
Condenser coil sensor abnormal in A
fan
E2
Condenser coil sensor abnormal in B
E5
Evaporator coil sensor abnormal in A
E6
Evaporator coil sensor abnormal in B
E9
Room temperature sensor abnormal
EA
Ambient temperature sensor abnormal
Eb
Wired controller output fault
P0
Over current of compressor protecon in A
P1
Over current of compressor protecon in B
P2
Over current of supply fan protecons
P3
Comprehensive protecon of condenser fan(s)
P4
HP, LP or HDT switch open in A
P5
HP, LP or HDT switch open in B
P6
HP protecon iniated in T2 evaporator, stopped condenser fan
P7
HP protecon iniated in T2 evaporator, stopped condenser
P8
Condenser high temperature protecon in A
P9
Condenser high temperature protecon in B
Pc
An-freeze protecon in A
Pd
An-freeze protecon in B
Df
Defrosng
failure
condenser
motors safety circuit.
Page 6 of 25
T2 Low Temperature 0⁰C 5⁰C
Cut Out Cut In
T3 High Temperature 65⁰C 52⁰C
Cut Out Cut In T4 Ambient Temperature Cut Out Cut In
<-7⁰C/>43⁰C >-7⁰C/<43⁰C
HDT Pipe Temperature Cut Out Cut In
Low Pressure Switch: Cut Out : 50Kpa Cut In
: 150Kpa
High Pressure Switch: Cut Out : 3300Kpa Cut In
: 2400Kpa
115⁰C 90⁰C
FAULT CODE BOOKLET R410A Non Inverter High Wall Split
2016 Version 1.2
F Series High Wall Split Type Sensor Resistance Table
TX (⁰C) 15 16 17 18 19 20 21 22 23 24 25 26 27 28 29 30 31 32 33 34
KΩ 16.1156 15.3418 14.6181 13.9180 13.2631 12.6431 12.0561 11.5000 10.9731 10.4736 10.000 9.55074 9.12445 8.71983 8.33566 7.97078 7.62411 7.29464 6.98142 6.68355
Display
DUNHAM-BUSH Reserve the right to change any specicaons and design without prior noce for product improvement
Fault Descripon
E1
EEPROM error
E2
No over zero signal (EEPROM error)
E3
Indoor fan motor fan speed abnormal
E5
Room temperature sensor abnormal
E6
Indoor coil temperature sensor abnormal
E7
Outdoor coil temperature sensor abnormal
E8
Phase rotaon or phase failure
can be caused by a
E9
Communicaon error
faulty PC Board not
EC
Refrigerant leak detecon
P0
Over current of compressor protecon
P1
Voltage protecon
P2
Compressor temperature protecon
on the F series will not
P3
Low outdoor temperature protecon
funcon
Note: Indoor fan motor fan speed abnormal faults
reading the feedback circuit
or
a
faulty
indoor fan. The wired controller if
a
fault
occurs and will not display a fault code, please revert to the display board of the
Fravega and Thermocold High Wall Split Type Sensor Resistance Table
TX (⁰C) 15 16 17 18 19 20 21 22 23 24 25 26 27 28 29 30 31 32 33 34
KΩ 7.464 7.164 6.877 6.603 6.342 6.092 5.854 5.626 5.408 5.199 5.000 4.811 4.630 4.456 4.291 4.132 3.98 3.835 3.695 3.562
Display
unit for fault codes. The standard value for
Fault Descripon
the three sensors on the F series is 10k Ω at
dF
Defrosng
E1
Room temperature sensor abnormal
E2
Outdoor coil temperature sensor abnormal
E3
Indoor coil temperature sensor abnormal
E4
Indoor fan motor fan speed abnormal
cleaning funcon have
E6
No over zero signal (EEPROM error)
been selected on the
25˚C If CL is displayed on the
Fravega
Thermocold units the
infrared remote.
E4 Fault: NO
Is the fan motor voltage normal? 134V -160V AC
YES
NO
Is fan motor capacitor normal?
YES
and
PCB Failed
Replace FAC
Replace Fan Motor
Check CN8 connecon
Page 7 of 25
FAULT CODE BOOKLET R410A Non Inverter Cassee Split
2016 Version 1.2
Compact Cassette Split Type DUNHAM-BUSH Reserve the right to change any specicaons and design without prior noce for product improvement
Note: A
slow
ash
operaon
on lamp
Indicates that the unit
Run
Timer
Defrost
Alarm
O
Flash
O
O
Room temperature sensor abnormal
Flash
O
O
O
Indoor coil temperature sensor abnormal
O
O
Flash
O
Outdoor coil temperature sensor abnormal
Flash
Flash
Flash
O
Over current of compressor protecon
Flash
Flash
Flash
Flash
Flash
Flash
O
O
O
O
O
Flash
Fault Descripon
Outdoor unit protecon No over zero signal/EEPROM error Water level alarm
is in standby mode, a quick ash indicates that the indoor coil temperature sensor is
Cassette Split Type Display
Fault Descripon
abnormal. The wired controller
E2
Room temperature sensor abnormal
fault occurs and will
E3
Indoor coil temperature sensor abnormal
not display a fault
E4
Outdoor coil temperature sensor abnormal
E5
Pump sensor abnormal
E6
Outdoor unit protecon
codes.
E7
No over zero signal/EEPROM error
The standard value for
E8
Water level alarm
will not funcon if a
code, please revert to the display board of the
unit
for
fault
Sensor Resistance Table
TX (⁰C) 15 16 17 18 19 20 21 22 23 24 25 26 27 28 29 30 31 32 33 34
KΩ 16.1156 15.3418 14.6181 13.9180 13.2631 12.6431 12.0561 11.5000 10.9731 10.4736 10.000 9.55074 9.12445 8.71983 8.33566 7.97078 7.62411 7.29464 6.98142 6.68355
T2 Low Temperature 0⁰C 5⁰C
Cut Out Cut In
the three sensors is 10kΩ at 25˚C. The water ow switch must
be
normally
Outdoor Unit
closed if it is open it is
LED1
LED2
LED3
O
Flash
Flash Outdoor coil temperature sensor abnormal
O
Flash
O
HP/HDT switch open or ambient sensor abnormal
Flash
O
O
Phase rotaon or phase failure
O
O
O
Phase failure (C)
O
O
Flash
Flash
Flash
O
gized. The pump will
Flash
Flash
run for 2 minutes
Flash
O
seen as a fault. The
Fault Descripon
T3 High Temperature
ow switch does not regulate the condensaon pump and only acts as an safety . The
condensaon
pump will run connuously in cooling and dry mode when the compressor is ener-
Over current of compressor protecon LP switch open
Flash High temperature protecon of outdoor unit Flash Communicaon error
aer the compressor have
stopped
then switch o.
and Low Pressure Switch:
Cut Out : 50Kpa Cut In
High Pressure Switch:
Cut In
Page 8 of 25
: 150Kpa
Cut Out : 4800Kpa : 3200Kpa
65⁰C 52⁰C
Cut Out Cut In T4 Ambient Temperature Cut Out Cut In
<-7⁰C/>43⁰C >-7⁰C/<43⁰C
HDT Pipe Temperature Cut Out Cut In
115⁰C 90⁰C
FAULT CODE BOOKLET R410A Non Inverter Ducted Split
2016 Version 1.2
Ducted Split Type T2 Low Temperature 0⁰C 5⁰C
Cut Out Cut In T2B High Temperature
60⁰C 54⁰C
Cut Out Cut In
Low Pressure Switch:
Run
Timer
Defrost
Alarm
O
Flash
O
O
Room temperature sensor abnormal
Flash
O
O
O
Indoor coil temperature sensor abnormal
O
O
Flash
O
Outdoor coil temperature sensor abnormal
Flash
Flash
Flash
O
Over current of compressor protecon
Flash
Flash
Flash
Flash
Flash
Flash
O
O
O
O
O
Flash
Fault Descripon
A No over zero signal/EEPROM error Water level alarm
operaon
on lamp
Indicates that the unit
that the indoor coil temperature sensor is
: 3200Kpa
Outdoor Unit (12 000Btu to 60 000Btu) LED1
T3 High Temperature 65⁰C 52⁰C
Cut Out Cut In T4 Ambient Temperature
<-7⁰C/>43⁰C >-7⁰C/<43⁰C
HDT Pipe Temperature Cut Out Cut In
ash
quick ash indicates
Cut Out : 4800Kpa
Cut Out Cut In
slow
is in standby mode, a
: 150Kpa
High Pressure Switch: Cut In
Note:
Outdoor unit protecon
Cut Out : 50Kpa Cut In
DUNHAM-BUSH Reserve the right to change any specicaons and design without prior noce for product improvement
115⁰C 90⁰C
abnormal.
Fault Descripon
The wired controller
LED2
LED3
O
Flash
Flash Outdoor coil temperature sensor abnormal
O
Flash
O
HP/HDT switch open or ambient sensor abnormal
Flash
O
O
Phase rotaon or phase failure
O
O
O
Phase failure (C)
codes.
O
O
Flash
Over current of compressor protecon
The standard value for
Flash
Flash
O
LP switch open
the three sensors is
Flash
Flash
Flash
O
will not funcon if a fault occurs and will not display a fault code, please revert to the display board of the
unit
for
fault
Flash High temperature protecon of outdoor unit
10kΩ at 25˚C.
Flash Communicaon error
On the 75 000Btu to 200 000Btu units the phase failure relay is
Sensor Resistance Table
TX (⁰C) 15 16 17 18 19 20 21 22 23 24 25 26 27 28 29 30
KΩ 16.1156 15.3418 14.6181 13.9180 13.2631 12.6431 12.0561 11.5000 10.9731 10.4736 10.000 9.55074 9.12445 8.71983 8.33566 7.97078
wired in on ether the
Outdoor Unit (75 000Btu to 200 000Btu)
LP circuit or ambient sensor circuit.
LED1
LED2
On
1 quick and 1 slow ash
Phase rotaon or phase failure
On
2 quick and 1 slow ash
Communicaon error
On
3 quick and 1 slow ash
HDT switch open
On
4 quick and 1 slow ash
Ambient temperature sensor abnormal
O
1 quick and 1 slow ash
LP switch open
Flash
1 quick and 1 slow ash
LP switch open 3 mes in 20 minutes
O
2 quick and 1 slow ash
HP switch open
O
3 quick and 1 slow ash
Over current of compressor protecon
O
4 quick and 1 slow ash
Outdoor coil temperature sensor abnormal
Fault Descripon
Page 9 of 25
FAULT CODE BOOKLET R410A Non Inverter Under Ceiling Split
2016 Version 1.2
Under Ceiling Split Type DUNHAM-BUSH Reserve the right to change any specicaons and design without prior noce for product improvement
Note: A
slow
ash
operaon
on lamp
Indicates that the unit
Run
Timer
Defrost
Alarm
O
Flash
O
O
Room temperature sensor abnormal
Flash
O
O
O
Indoor coil temperature sensor abnormal
O
O
Flash
O
Outdoor coil temperature sensor abnormal
Flash
Flash
Flash
O
Over current of compressor protecon
Flash
Flash
Flash
Flash
Flash
Flash
O
O
O
O
O
Flash
Fault Descripon
Outdoor unit protecon No over zero signal/EEPROM error Water level alarm
is in standby mode, a quick ash indicates that the indoor coil temperature sensor is
New Under Ceiling Split Type Display
Fault Descripon
abnormal. The wired controller
E2
Room temperature sensor abnormal
fault occurs and will
E3
Indoor coil temperature sensor abnormal
not display a fault
E4
Outdoor coil temperature sensor abnormal
E5
Pump sensor abnormal
E6
Outdoor unit protecon
codes.
E7
No over zero signal/EEPROM error
The standard value for
E8
Water level alarm
will not funcon if a
code, please revert to the display board of the
unit
for
fault
Sensor Resistance Table
TX (⁰C) 15 16 17 18 19 20 21 22 23 24 25 26 27 28 29 30 31 32 33 34
KΩ 16.1156 15.3418 14.6181 13.9180 13.2631 12.6431 12.0561 11.5000 10.9731 10.4736 10.000 9.55074 9.12445 8.71983 8.33566 7.97078 7.62411 7.29464 6.98142 6.68355
T2 Low Temperature 0⁰C 5⁰C
Cut Out Cut In
the three sensors is 10kΩ at 25˚C. If
the
display
PCB
LED’s are randomly lit
Outdoor Unit
or if commands send
LED1
LED2
LED3
O
Flash
Flash Outdoor coil temperature sensor abnormal
age such as water
O
Flash
O
HP/HDT switch open or ambient sensor abnormal
damage or damaged
Flash
O
O
Phase rotaon or phase failure
O
O
O
Phase failure (C)
O
O
Flash
Flash
Flash
O
Flash
Flash
Flash
O
to the unit is not received inspect
the
display
PCB for physical dam-
interconnecng cable between
Fault Descripon
T3 High Temperature
please
main
PCB
and display PCB.
Over current of compressor protecon LP switch open
Flash High temperature protecon of outdoor unit Flash Communicaon error
Low Pressure Switch:
Cut Out : 50Kpa Cut In
High Pressure Switch:
Cut In
Page 10 of 25
: 150Kpa
Cut Out : 4800Kpa : 3200Kpa
65⁰C 52⁰C
Cut Out Cut In T4 Ambient Temperature Cut Out Cut In
<-7⁰C/>43⁰C >-7⁰C/<43⁰C
HDT Pipe Temperature Cut Out Cut In
115⁰C 90⁰C
FAULT CODE BOOKLET R410A Non Inverter Rooop Package
2016 Version 1.2
DBRT Rooftop Package Type (18kW) Display
Sensor Resistance Table
TX (⁰C) 15 16 17 18 19 20 21 22 23 24 25 26 27 28 29 30 31 32 33 34
KΩ 16.1156 15.3418 14.6181 13.9180 13.2631 12.6431 12.0561 11.5000 10.9731 10.4736 10.000 9.55074 9.12445 8.71983 8.33566 7.97078 7.62411 7.29464 6.98142 6.68355
Fault Descripon
DUNHAM-BUSH Reserve the right to change any specicaons and design without prior noce for product improvement
E0
Phase rotaon or phase failure
E1
Condenser coil sensor abnormal T3-1
E2
Condenser coil sensor abnormal T3-2
E5
Evaporator coil sensor abnormal T2-1
E6
Evaporator coil sensor abnormal T2-2
E9
Room temperature sensor abnormal
EA
Ambient sensor abnormal
KJR25B
Eb
Wired controller output fault
press the UP key, the
P0
Over current protecon
P3
Comprehensive protecon of condenser fan
the backlight key for
P4
HP, LP or HDT sensor abnormal
3 seconds to clear the
P5
HP, LP or HDT sensor abnormal
P8
High condenser temperature protecon
Note: To reset the lter alarm clock on the controller
display will blink FILT and run me. Press
clock. Ensure that dip switch SW3 is set to ON for
DBRT Rooftop Package Type (28kW to 88kW)
KJR25B use and for KJR12B the dip switch
Display
T2 Low Temperature
Fault Descripon
must be set to 1. The
0⁰C 5⁰C
Cut Out Cut In
T3 High Temperature 65⁰C 52⁰C
Cut Out Cut In T4 Ambient Temperature Cut Out Cut In
<-7⁰C/>43⁰C >-7⁰C/<43⁰C
HDT Pipe Temperature Cut Out Cut In
Low Pressure Switch: Cut Out : 50Kpa Cut In
: 150Kpa
High Pressure Switch: Cut Out : 4800Kpa Cut In
: 3200Kpa
115⁰C 90⁰C
E0
Phase rotaon or phase failure
E1
Condenser coil sensor abnormal in A
E2
Condenser coil sensor abnormal in B
E5
Evaporator coil sensor abnormal in A
E6
Evaporator coil sensor abnormal in B
E9
Room temperature sensor abnormal
EA
Ambient temperature sensor abnormal
Eb
Wired controller output fault
P0
Over current of compressor protecon in A
P1
Over current of compressor protecon in B
P2
Over current of supply fan protecons
P3
Comprehensive protecon of condenser fan(s)
P4
HP, LP or HDT switch open in A
P5
HP, LP or HDT switch open in B
P6
HP protecon iniated in T2 evaporator, stopped condenser fan
P7
HP protecon iniated in T2 evaporator, stopped condenser
P8
Condenser high temperature protecon in A
P9
Condenser high temperature protecon in B
Pc
An-freeze protecon in A
Pd
An-freeze protecon in B
Df
Defrosng
phase
failure
relay is wired the
condenser
in on fan
motors safety circuit.
Page 11 of 25
FAULT CODE BOOKLET R410A Inverter High Wall Split
2016 Version 1.2
N, R and F series High Wall Split Type Display
Sensor Resistance Table
Fault Descripon
T1,T2,T3 and T4
TX (⁰C) 20 21 22 23 24 25 26 27 28 29 30
KΩ 12.6431 12.0561 11.5000 10.9731 10.4736 10.000 9.55074 9.12445 8.71983 8.33566 7.97078
T2 Low Temperature 0⁰C 5⁰C
Cut Out Cut In
T5 Sensor Resistance Table
TX (⁰C) 20 21 22 23 24 25 26 27 28 29 30
KΩ 68.66 65.62 62.73 59.98 57.37 54.89 52.53 50.28 48.14 46.11 44.08
DUNHAM-BUSH Reserve the right to change any specicaons and design without prior noce for product improvement
E0
EEPROM error
E1
Communicaon error
E2
No over zero signal
E3
Indoor fan motor fan speed abnormal
E4/E6
Room temperature sensor abnormal
E5/E6
Indoor coil temperature sensor abnormal
E7/F5
Outdoor fan motor fan speed abnormal
can be caused by a
EC
Refrigerant leak detecon
faulty PC Board not
F1
Ambient temperature sensor abnormal
F2
Outdoor coil temperature sensor abnormal
F3
Discharge pipe temperature sensor abnormal
F4
Outdoor EEPROM error
the three sensors on
P0
IPM or IGBT protecon
the F series is 10k Ω at
P1
Voltage protecon
P2
Compressor top temperature sensor abnormal
P3
Low ambient temperature protecon
Note: Indoor fan motor fan
Communicaon Error: Measure between N and S. Voltage readings will uctuate between negave and
speed abnormal faults
reading the feedback circuit
or
a
faulty
indoor fan. The standard value for
25˚C
1Phase Power Supply: Min:
210VAC/50Hz
Max:
240VAC/50Hz
P-N:
277¬356 VDC
posive AC readings, if it is not uctuang in posive readings the indoor PCB must be inspected. If the voltage uctuates only in posive values the outdoor PCB must
Ref. Charging Table:
be inspected. Pipe
Refrigerant
Size
per Meter
xed in its sleeve, please note that an imbalance in R410A
1/4’’
23g per m
refrigerant due to vapour charging or gas leak can cause this fault.
3/8’’
60g per m
1/2’’
120g per m
Refrigerant Leak Detected: Check refrigerant charge, is there any gas leaks present. Ensure that T2 coil sensor is
IPM/EGBT Module Protecon: T3 High Temperature 1. 65⁰C 52⁰C
Cut Out Cut In
2.
T4 Ambient Temperature Cut Out Cut In
Check the IPM connuity from P to UVW, all readings must be equal and N
The
to UVW. Place the black test lead on P and red test lead on U, V or W. Use
charged for a 5m pipe
the red test lead for N and the black test lead for U,V or W.
run if the piping ex-
Ensure that the IPM PC board is securely installed on the heat sink, ensure that sucient heat past is used and that the heat sink is clean.
<-7⁰C/>43⁰C >-7⁰C/<43⁰C
3.
Check if the condenser fan motor rotaon is correct and if it is turning freely. Test the running capacitor of the fan motor, ensure that the macro fared reading do not exceed the allowed over/under tolerance as indicated on the
HDT Pipe Temperature Cut Out Cut In
capacitor. 115⁰C 90⁰C
4.
Check compressor windings, resistance must be equal across U-V, U-W and
unit
ceeds
5m
is
use
pre -
the
table above for correct charging values. Please do not charge vapour,
only
liquid
and use a charging scale
V-W. Resistance will be between 0.5 Ω and 5.9Ω
Page 13 of 25
FAULT CODE BOOKLET R410A Inverter High Wall Split
2016 Version 1.2
Fravega and Thermocold High Wall Split Type DUNHAM-BUSH Reserve the right to change any specicaons and design without prior noce for product improvement
Display
Fault Descripon
T1 and T4
E1
Room temperature sensor abnormal
E2
Outdoor coil temperature sensor abnormal
E3
Indoor coil temperature sensor abnormal
E4
Indoor fan motor fan speed abnormal
E5
Communicaon error
F1
IPM modular protecon
can be caused by a
F2
PFC modular protecon
faulty PC Board not
F3
Compressor drive abnormal
F4
Discharge pipe temperature sensor abnormal
F5
Compressor top temperature sensor abnormal
F6
Ambient temperature sensor abnormal
F7
Over under voltage protecon
F8
Outdoor modular communicaon error
F9
EEPROM error
F0
Outdoor fan motor fan speed abnormal
FA
Sucon pipe temperature sensor abnormal
P6
Evaporator high temperature protecon
Note: Indoor fan motor fan speed abnormal faults
reading the feedback circuit
or
a
faulty
indoor fan. The standard value for the three is Ω at 25˚C
1Phase Power Supply: Min:
210VAC/50Hz
Max:
240VAC/50Hz
P-N:
277¬356 VDC
Ref. Charging Table:
Communicaon Error 1.
Check if the ODU main PCB board’s three LED lights all light up and o while the relay pulls in, if not it is a power supply problem.
Unit
Refrigerant
Size
per Meter
2.
20g per m
12 000 20g per m 18 000 30g per m
2.
Check the power supply it must be within 10% of the rated voltage.
24 000 30g per m
3.
Check if the IPM board is xed to the heatsink and clean.
4.
Check the IPM connuity of IPM, compressor and reactor, all readings on
is
IPM and compressor must be equal.
pre -
charged for a 5m pipe
PFC Modular Protecon
run if the piping exceeds 5m use the
1.
Check if power supply voltage uctuates or i f the voltage is less than 135V.
table above for cor-
2.
Check whether there is any damage to the reactor and the wire connecons.
rect charging values.
3.
Check for lighng damaged on the PFC board.
Please do not charge
4.
Test the power supply of 15 V, 5 V (3.3 V) on PFC board from main PCB.
vapour,
only
liquid
Page 14 of 25
T2 and T3
TX (⁰C) 20 21 22 23 24 25 26 27 28 29 30
KΩ 25.01 23.90 22.85 21.85 20.90 20.00 19.14 18.13 17.55 16.80 16.05
Refrigerant Discharge Table
table below is the amount that must be recovered, do not add this amount to the factory charge !
Pipe Length
Refrigerant
1m 2m 3m 5m
240g 180g 120g 60g
If a P6 fault is displayed check for any air restricons, dirty coils, dirty
Outdoor Modular Communicaon Error
and use a charging scale
Sensor Resistance Table
The amount of refrigerant in the Check the wiring on compressor and IPM red-U, blue-V and black-W.
unit
KΩ 18.75 17.93 17.14 16.39 15.68 15.00 14.36 13.74 13.16 12.60 12.04
displayed the ODU main PCB board is faulty.
1.
The
TX (⁰C) 20 21 22 23 24 25 26 27 28 29 30
Connect the black signal line S to terminal N of ODU. Turn the unit on if 5E is
IPM Modular Protecon 9 000
Sensor Resistance Table
1.
Check the communicaon wire between module and main control board.
2.
Check if the 5V on the module board is normal.
lters, unit is mounted to close to the ceiling or the unit is overcharged.
FAULT CODE BOOKLET R410A Inverter High Wall Split
2016 Version 1.2
L Series High Wall Split Type Sensor Resistance Table
Display
Fault Descripon
Sensor Resistance Table T1 and KΩ T4 TX (⁰C) 20 18.75 21 TX (⁰C) 17.93 KΩ 20 22 17.1418.75 21 23 16.3917.93 22 24 15.6817.14 23 25 15.0016.39 26 24 14.3615.68 27 25 13.7415.00 28 26 13.1614.36 29 27 12.6013.74 30 28 12.0413.16 29 12.60 30 12.04
Sensor Resistance Table Sensor Resistance Table T2 and KΩ T3 TX (⁰C) 20 25.01 21 TX (⁰C) 23.90 KΩ 20 22 22.8525.01 21 23 21.8523.90 22 24 20.9022.85 23 25 20.0021.85 26 24 19.1420.90 27 25 18.1320.00 28 26 17.5519.14 29 27 16.8018.13 30 28 16.0517.55 29 16.80 30 16.05
Sensor Resistance Table
E1
High pressure protecon
E2
An-freezing protecon
E2
Low pressure protecon
E4
High discharge temperature protecon
E5
Over current protecon
E6
Communicaon error
E8
High discharge temperature protecon
can be caused by a
EE
EEPROM error
faulty PC Board not
EU
Decreasing frequency due to high temperature of IPM PC board
C5
Malfuncon of jumper cap
Fo
Gathering of refrigerant
F1
Room temperature sensor abnormal
the sensors at 25˚C is
F2
Indoor coil temperature sensor abnormal
15kΩ for T1 and T4,
F3
Ambient temperature sensor abnormal
F4
Outdoor coil temperature sensor abnormal
F5
Discharge pipe temperature sensor abnormal
F6
Decreasing frequency due to overload
F8
Decreasing frequency due to over current
F9
Decreasing frequency due to high discharge
FH
Decreasing frequency due to an freezing
PH/PL
TX (⁰C) 20 21 22 23 24 25 26 27 28 29 30
KΩ 61.48 58.77 56.19 53.74 51.41 49.19 47.08 45.07 43.16 41.34 39.52
High DC voltage on bus bar/low DC voltage on bus bar protecon Over current of compressor protecon
PU
Capacitor charging malfuncon
speed abnormal faults
reading the feedback circuit
or
a
faulty
indoor fan. The standard value for
20kΩ for T2 and T3 and 49.19kΩ for T5.
1Phase Power Supply: Min:
210VAC/50Hz
Max:
250VAC/50Hz
P-N:
277¬356 VDC
Ref. Charging Table: Pipe
Refrigerant
Size
per Meter
1/4’’
20g per m
3/8’’
50g per m
1/2’’
150g per m
IPM Temperature sensor abnormal/IPM PCB temperature protecon
H3
Overload of compressor protecon
H5
IPM module protecon
H6/L3
Note: Indoor fan motor fan
P5
P7/P8 T5
DUNHAM-BUSH Reserve the right to change any specicaons and design without prior noce for product improvement
Indoor fan motor fan speed/outdoor fan motor fan speed abnormal The
unit
is
pre -
H7
Compressor desynchronizing fault
HC
PFC protecon
L9
High voltage protecon
ceeds
LP
Indoor-outdoor compability fault
table above for cor-
LC
Start-up failure
U1
Compressor phase current detecon abnormal
Please do not charge
U3
DC voltage on bus bar abnormal
vapour,
U5
Unit current detecon abnormal
U7
Four-way valve abnormal
U8
Zero -crossing circuit detecon abnormal
charged for a 5m pipe run if the piping ex5m
use
the
rect charging values.
only
liquid
and use a charging scale
Page 15 of 25
FAULT CODE BOOKLET R410A Inverter High Wall Split
2016 Version 1.2
L Series High Wall Split Type DUNHAM-BUSH Reserve the right to change any specicaons and design without prior noce for product improvement
T2 Low Temperature
Communicaon Error Measure between N and S. Voltage readings will uctuate between negave and
0⁰C 5⁰C
Cut Out Cut In
posive AC readings, if it is not uctuang in posive readings the indoor PCB must be inspected. If the voltage uctuates only in posive values the outdoor PCB must
T2B High Temperature
be inspected.
Refrigerant Leak Detected:
60⁰C 54⁰C
Cut Out Cut In
Check refrigerant charge, is there any gas leaks present. Ensure that T2 coil sensor is xed in its sleeve, please note that an imbalance in R410A refrigerant due to vapour charging or gas leak can cause this fault.
Capacitor Charging Malfuncon Check if the voltage is normal , voltage on the capacitor must be higher then 200VDC and power supply voltage bust be within 210 VAC to 250VAC. Measure the micro fared reading of capacitor and inspect the reactor.
Malfuncon Of Jumper Cap
T3 High Temperature 65⁰C 52⁰C
Cut Out Cut In T4 Ambient Temperature Cut Out Cut In
<-7⁰C/>43⁰C >-7⁰C/<43⁰C
Check if the jumper cap is installed correctly and if it is xed ghtly on the PC board, ensure that the jumper cap is not damaged
IPM Modular Protecon 1.
Check the wiring on compressor and IPM module for loose or incorrect
T5 Pipe Temperature Cut Out Cut In
connecons. 2.
Check the power supply it must be within 210VAC to 250VAC and if DC voltage is higher then 250VDC
3.
Check if the IPM module is xed to the heatsink and clean.
Cut Out : 50Kpa
4.
Check if the condenser and evaporator coils are clean and free from
Cut In
obstructions 4.
Check the IPM connuity of IPM, compressor and reactor, all readings on IPM and compressor must be equal.
PFC Modular Protecon Check whether there is any damage to the reactor and the wire connecons. Test the capacitor micro fared reading and test if the ohm reading is around zero .
Start up failure/out of step of compressor Ensure that the wiring connecons on the compressor is correct and secure, the connecon sequence must be in a clockwise direcon. Inspect the outdoor fan connecons and check the fan capacitor micro fared readings.
Page 16 of 25
Low Pressure Switch
: 150Kpa
High Pressure Switch Cut Out : 4800Kpa Cut In
: 3200Kpa
115⁰C 90⁰C
FAULT CODE BOOKLET R410A Inverter Cassee Split
2016 Version 1.2
Compact Cassette 12 000Btu Split Type Sensor Resistance Table
Timer
Defrost
Alarm
O
Flash
O
O
Communicaon error
Flash
O
O
O
Room temperature sensor abnormal
O
O
Flash
O
Coil temperature sensor abnormal
O
O
O
Flash
Flash
Flash
O
O
EEPROM error
Flash
O
O
On
IPM module protecon
Flash
On
O
O
Outdoor coil or ambient sensor abnormal
can be caused by a
Flash
On
O
On
Outdoor voltage protecon
faulty PC Board not
Flash
Flash
O
Flash
Outdoor over-current protecon
Flash
Flash
Flash
Flash
Compressor top sensor abnormal
Flash
Slow
O
O
Inverter compressor drive protecon
Flash
O
On
O
Compressor discharge sensor abnormal
Fault Descripon
T1,T2,T3 and T4
TX (⁰C) 20 21 22 23 24 25 26 27 28 29 30
KΩ 12.6431 12.0561 11.5000 10.9731 10.4736 10.000 9.55074 9.12445 8.71983 8.33566 7.97078
DUNHAM-BUSH Reserve the right to change any specicaons and design without prior noce for product improvement
Run
Water level alarm
Note: Indoor fan motor fan speed abnormal faults
reading the feedback circuit
or
a
faulty
indoor fan. The standard value for T1, T2, T3 and T4 is 10KΩ at 25˚C T5 is 54.89KΩ at 25⁰C
New Compact Cassette 12 000Btu Split Type Run
Timer
1 Flash
O
EEPROM error
2 Flashes
O
Communicaon error
4 Flashes
O
Indoor fan motor fan speed abnormal
5 Flashes
O
Room temperature sensor abnormal
6 Flashes
O
Indoor coil temperature sensor abnormal
discharged
7 Flashes
O
Refrigerant leak detecon
working on electrical
8 Flashes
O
Water level alarm
2 Flashes
On
Ambient temperature sensor abnormal
3 Flashes
On
Outdoor coil temperature sensor abnormal
12 000Btu Condenser LED Error Codes
4 Flashes
On
Compressor discharge sensor abnormal
LED6
LED5
Fault
5 Flashes
On
Outdoor EEPROM error
Flash
O
IGBT over current
1 Flash
Flash
IPM module protecon
charged for a 5m pipe
2 Flashes
Flash
Over/under voltage protecon
run if the piping ex-
3 Flashes
Flash
Compressor top sensor abnormal
4 Flashes
Flash
Inverter compressor drive error
T5 Sensor Resistance Table
TX (⁰C) 20 21 22 23 24 25 26 27 28 29 30
KΩ 68.66 65.62 62.73 59.98 57.37 54.89 52.53 50.28 48.14 46.11 44.08
On
On
Over/under voltage
Flash
Flash
Communicaon
New Type Condenser
Fault Descripon
1Phase Power Supply: Min:
210VAC/50Hz
Max:
240VAC/50Hz
P-N:
277¬356 VDC
Please insure that the DC
capacitors
are
before
components
Ref. Charging Table: 1/4’’ The
23g per m unit
ceeds
5m
is
use
pre -
the
table above for cor-
LED2
LED1
Fault
On
Flash
EEPROM error
Flash
O
IPM/IGBT overcurrent
The water ow switch must be normally closed if it is open it is seen as a fault. The
Please do not charge
On
On
Over/under voltage
out switch does not regulate the condensaon pump and only acts as an safety .
vapour,
O
Flash
Compressor drive
Flash
On
Compressor drive
The condensaon pump will run connuously in cooling and dry mode when the
Outdoor coms error
compressor is energized. The pump will run for 2 minutes aer the compressor have
on main to driver PCB
stopped and then switch o.
Flash
Flash
rect charging values.
only
liquid
and use a charging scale
Page 17 of 25
FAULT CODE BOOKLET R410A Inverter Cassee Split
2016 Version 1.2
Compact Cassette Split Type DUNHAM-BUSH Reserve the right to change any specicaons and design without prior noce for product improvement
Note: A
slow
ash
operaon
on lamp
Indicates an EEPROM error code a quick ash
indicates
Run
Timer
Defrost
Alarm
O
Flash
O
O
Communicaon error
Flash
O
O
O
Room temperature sensor abnormal
Flash
O
O
O
Indoor coil temperature T2 sensor abnormal
Flash
O
O
O
Indoor coil temperature T2B sensor abnormal
O
O
O
Flash
Slow
O
O
O
O
O
O
Slow
Flash
Flash
O
O
Fault Descripon
Sensor Resistance Table T1,T2,T3 and T4
Water level alarm EEPROM error Outdoor unit abnormal Indoor fan motor fan speed abnormal
that
TX (⁰C) 20 21 22 23 24 25 26 27 28 29 30
KΩ 12.6431 12.0561 11.5000 10.9731 10.4736 10.000 9.55074 9.12445 8.71983 8.33566 7.97078
the indoor sensors is abnormal.
Cassette Split Type
The wired controller will not funcon if a
Display
Fault Descripon
fault occurs and will not display a fault
E1
Communicaon error
E2
Room temperature sensor abnormal
E3
Indoor coil temperature T2 sensor abnormal
codes.
E4
Indoor coil temperature T2B sensor abnormal
The standard value for
EE
Water level alarm
E7
EEPROM error
Ed
Outdoor unit abnormal
code, please revert to the display board of the
unit
for
fault
T1, T2, T3 and T4 sensors is 10kΩ at 25˚C T5 is 54.89kΩ at 25⁰C The water ow switch must
be
normally
closed if it is open it is
Outdoor Unit Display
Fault Descripon
seen as a fault. The ow switch does not
E0
EEPROM error
E2
Communicaon error
E3
Communicaon error between IPM and main PC board
E4
Outdoor coil /ambient temperature sensor abnormal
pump will run conn-
E5
Voltage protecon
uously in cooling and
P0
Compressor top temperature sensor abnormal
P1
High pressure protecon
P2
Low pressure protecon
run for 2 minutes
P3
Compressor over current protecon
aer the compressor
P4
Compressor discharge temperature sensor abnormal
P5
High condenser temperature protecon
regulate the condensaon pump and only acts as an safety . The
condensaon
dry mode when the compressor is energized. The pump will
have
stopped
and
then switch o.
P6/E6 P7
Page 18 of 25
IPM module protecon/PFC module protecon High Evaporator temperature protecon
T5 Sensor Resistance Table
TX (⁰C) 20 21 22 23 24 25 26 27 28 29 30
KΩ 68.66 65.62 62.73 59.98 57.37 54.89 52.53 50.28 48.14 46.11 44.08
T2 Low Temperature Cut Out Cut In
0⁰C 5⁰C
T2B High Temperature Cut Out Cut In
60⁰C 54⁰C
FAULT CODE BOOKLET R410A Inverter Cassee Split
2016 Version 1.2
P6 Fault Code Table First Gen.
T3 High Temperature
T4 Ambient Temperature <-7⁰C/>43⁰C >-7⁰C/<43⁰C
HDT Pipe Temperature 115⁰C 90⁰C
Cut Out Cut In
LED1
LED2
LED1
LED2
LED3
On
O
On
O
On
Normal running mode
Flash
On
O
On
On
Normal standby mode
8 Flashes
On
o
Flash
On
Over current of IPM output
9 Flashes
On
On
On
On
Low voltage protecon
10 Flashes
On
On
On
On
High voltage protecon
12 Flashes
On
Flash
On
On
Control chip failure
13 Flashes
On
On
Flash
On
Zero speed of compressor
15 Flashes
On
On
Flash
On
Lack of phase or speed uctuates
Communicaon Error:
Transformer RT1
Measure between (P to E) and (Q to E). Voltage
Brown Brown Yellow Yellow
13.5 VAC 9.0 VAC
Transformer RT2 Blue Blue Blue Blue
DUNHAM-BUSH Reserve the right to change any specicaons and design without prior noce for product improvement
Note:
Ref. Charging Table: Pipe
Refrigerant
Size
per Meter
1/4’’
23g per m
3/8’’
60g per m
1/2’’
120g per m
readings between (P to E) and (Q to E) is between 2.5 to 2.7VDC. Screened 0.5mm cable must be used
The
unit
and ensure that the aluminium lm is earthed on the
charged for a 5m pipe
unit’s body. The maximum length for communicaon
run if the piping ex-
cable is 1200 m from outdoor to last indoor unit,
ceeds
5m
is
pre -
use
the
please ensure that the 120k Ω resistor is connected
table above for cor-
14.5 VAC
across P to Q on the last unit.
rect charging values.
14.5 VAC
P6 IPM Module Protecon:
Please do not charge
Over current of IPM output signal
1 Phase IPM Module Posive P Negave N
Fault Descripon
65⁰C 52⁰C
Cut Out Cut In
Cut Out Cut In
Second and Third Gen.
Check the running amps of compressor and ensure wiring from IPM to compressor is correct. Test the IPM
277-356 VDC
vapour,
only
liquid
and use a charging scale .
connuity from P/N to UVW, all readings must be equal. Ensure that the neutral direcon through the CT is cor-
3 Phase IPM Module
rect. Inspect the IPM PC board is it securely installed on Main Posive P Main Negave N Posive + Negave -
the heat sink and is the heat paste sucient. Check the
535-600 VDC ±310 VDC
condenser fan motor(s) rotaon and running capacitors.
Low/High voltage protecon
LC will be displayed when the unit is running in low ambient cooling mode or alternate between running frequency and LC.
Check the commutang part assembly and IPM voltages and if all wire connecons is
Low Pressure Switch Cut Out : 50Kpa Cut In
: 150Kpa
High Pressure Switch
secure and correct, + and - on the IPM PCB is a input from the lter board.
Control chip failure Check transformer(s) input and output voltages.
Zero speed/speed uctuates or lack of phase on compressor
Please ensure that the DC
capacitors
discharged
are
before
working on electrical components.
The
Cut Out : 4800Kpa
Check wire connecons between the compressor and IPM. Check the IPM connuity
capacitors is charged
Cut In
from p to UVW, all readings must be equal and N to UVW. Ensure that the IPM PC
with 600DC volts and
board is securely installed on the heat sink and it is clean. Check the condenser fan
can
motors rotaon. Check compressor windings, resistance must be equal across U -V, U-
shock !
: 3200Kpa
cause
W and V-W. Resistance will be between 0.5 Ω and 5.9Ω.
Page 19 of 25
electric
FAULT CODE BOOKLET R410A Inverter Ducted Split
2016 Version 1.2
Low Static Ducted 12 000Btu Split Type DUNHAM-BUSH Reserve the right to change any specicaons and design without prior noce for product improvement
Run
Timer
Defrost
Alarm
O
Flash
O
O
Communicaon error
Flash
O
O
O
Room temperature sensor abnormal
O
O
Flash
O
Coil temperature sensor abnormal
O
O
O
Flash
Flash
Flash
O
O
EEPROM error
Flash
O
O
On
IPM module protecon
can be caused by a
Flash
On
O
O
Outdoor coil or ambient sensor abnormal
faulty PC Board not
Flash
On
O
On
Outdoor voltage protecon
Flash
Flash
O
Flash
Outdoor over-current protecon
Flash
Flash
Flash
Flash
Compressor top sensor abnormal
Flash
Slow
O
O
Inverter compressor drive protecon
Flash
O
On
O
Compressor discharge sensor abnormal
Note: Indoor fan motor fan speed abnormal faults
reading the feedback circuit
or
a
faulty
indoor fan. The standard value for T1, T2, T3 and T4 is
Fault Descripon
Sensor Resistance Table T1,T2,T3 and T4
TX (⁰C) 20 21 22 23 24 25 26 27 28 29 30
Water level alarm
KΩ 12.6431 12.0561 11.5000 10.9731 10.4736 10.000 9.55074 9.12445 8.71983 8.33566 7.97078
10KΩ at 25˚C T5 is 54.89KΩ at 25⁰C
New Low Static Ducted 12 000Btu Split Type Run
Timer
1 Flash
O
EEPROM error
(E0)
2 Flashes
O
Communicaon error
(E1)
4 Flashes
O
Indoor fan motor fan speed abnormal
(E3)
5 Flashes
O
Room temperature sensor abnormal
(E4)
before
6 Flashes
O
Indoor coil temperature sensor abnormal
(E5)
working on electrical
7 Flashes
O
Refrigerant leak detecon
(EC)
8 Flashes
O
Water level alarm
(EE)
2 Flashes
On
Ambient temperature sensor abnormal
(F1)
3 Flashes
On
Outdoor coil temperature sensor abnormal
(F2)
4 Flashes
On
Compressor discharge sensor abnormal
(F3)
5 Flashes
On
Outdoor EEPROM error
(F4)
charged for a 5m pipe
1 Flash
Flash
IPM module protecon
(P0)
run if the piping ex-
2 Flashes
Flash
Over/under voltage protecon
(P1)
3 Flashes
Flash
Compressor top sensor abnormal
(P2)
4 Flashes
Flash
Inverter compressor drive error
(P4)
1Phase Power Supply: Min:
210VAC/50Hz
Max:
240VAC/50Hz
P-N:
277¬356 VDC
Please insure that the DC
capacitors
discharged
are
components
Ref. Charging Table: 1/4’’ The
23g per m unit
is
pre -
ceeds 5m use the table above for correct charging values.
Fault Descripon
T5 Sensor Resistance Table
TX (⁰C) 20 21 22 23 24 25 26 27 28 29 30
KΩ 68.66 65.62 62.73 59.98 57.37 54.89 52.53 50.28 48.14 46.11 44.08
12 000Btu Condenser LED Error Codes LED6
LED5
Fault
Flash
O
IGBT over current
On
On
Over/under voltage
Flash
Flash
Communicaon
New Type Condenser LED2
LED1
Fault
On
Flash
EEPROM error
Please do not charge
The water ow switch must be normally closed if it is open it is seen as a fault. The
Flash
O
IPM/IGBT overcurrent
vapour,
ow switch does not regulate the condensaon pump and only acts as an s afety .
On
On
Over/under voltage
O
Flash
Compressor drive
The condensaon pump will run connuously in cooling and dry mode when the
Flash
On
Compressor drive
compressor is energized. The pump will run for 2 minutes aer the compressor have
Flash
Flash
Outdoor coms error
only
liquid
and use a charging scale
stopped and then switch o.
Page 20 of 25
on main to driver PCB
FAULT CODE BOOKLET R410A Inverter Ducted Split
2016 Version 1.2
Low Static Ducted Split Type Sensor Resistance Table
Run
Timer
Defrost
Alarm
O
Flash
O
O
Communicaon error
Flash
O
O
O
Room temperature sensor abnormal
Flash
O
O
O
Indoor coil temperature T2 sensor abnormal
Flash
O
O
O
Indoor coil temperature T2B sensor abnormal
O
O
O
Flash
Slow
O
O
O
O
O
O
Slow
Flash
Flash
O
O
Fault Descripon
T1,T2,T3 and T4
TX (⁰C) 20 21 22 23 24 25 26 27 28 29 30
KΩ 12.6431 12.0561 11.5000 10.9731 10.4736 10.000 9.55074 9.12445 8.71983 8.33566 7.97078
Water level alarm
DUNHAM-BUSH Reserve the right to change any specicaons and design without prior noce for product improvement
Note: A
slow
ash
on
EEPROM error
operaon
Outdoor unit abnormal
Indicates an EEPROM
Indoor fan motor fan speed abnormal
lamp
error code a quick ash
indicates
that
the indoor sensors is abnormal.
Ducted Split Type
The wired controller
Display
Fault Descripon
will not funcon if a fault occurs and will
T5 Sensor Resistance Table
TX (⁰C) 20 21 22 23 24 25 26 27 28 29 30
KΩ 68.66 65.62 62.73 59.98 57.37 54.89 52.53 50.28 48.14 46.11 44.08
E2
Room temperature sensor abnormal
E3
Indoor coil temperature T2 sensor abnormal
the
E4
Indoor coil temperature T2B sensor abnormal
codes.
EE
Water level alarm
The standard value for
E7
EEPROM error
Ed
Outdoor unit abnormal
code, please revert to the display board of unit
for
fault
T1, T2, T3 and T4 sensors is 10kΩ at 25˚C T5 is 54.89kΩ at 25⁰C
Display
Fault Descripon
The water ow switch must
be
normally
closed if it is open it is seen as a fault. The
0⁰C 5⁰C
T2B High Temperature Cut Out Cut In
Communicaon error
Outdoor Unit (18 000Btu to 60 000Btu)
T2 Low Temperature Cut Out Cut In
not display a fault
E1
60⁰C 54⁰C
E0
EEPROM error
E2
Communicaon error
E3
Communicaon error between IPM and main PC board
E4
Outdoor coil /ambient temperature sensor abnormal
E5
Voltage protecon
pump will run conn-
P0
Compressor top temperature sensor abnormal
uously in cooling and
P1
High pressure protecon
P2
Low pressure protecon
P3
Compressor over current protecon
run
P4
Compressor discharge temperature sensor abnormal
aer the compressor
P5
High condenser temperature protecon
P6/E6 P7
ow switch does not regulate the condensaon pump and only acts as an safety . The
condensaon
dry mode when the compressor is energized. The pump will
have
for
2
minutes
stopped
then switch o.
IPM module protecon/PFC module protecon High Evaporator temperature protecon
Page 21 of 25
and
FAULT CODE BOOKLET R410A Inverter Ducted Split
2016 Version 1.2
Outdoor Unit (68 000Btu to 200 000Btu + DBV condensers) DUNHAM-BUSH Reserve the right to change any specicaons and design without prior noce for product improvement
Note: For E8 error check outdoor address dial
Display
Fault Descripon
P6 protecon will displayed 60 secE0
Outdoor communicaon error
onds then disappear, aer that, press
E1
Phase sequence or failure
the check buon the amount of
E2
Communicaon error
E4
Coil, ambient, or discharge temperature sensor abnormal
E5
Low voltage protecon
E7
Discharge temperature sensor abnormal
E8
Outdoor address seng error
address sengs.
E9
Voltage malfuncon, driver module mismatching
For H2 and H3 errors
H0
Communicaon error between control chip and inverter drive chip
check
H1
Communicaon error between control chip and communicaon chip
H2
Outdoor decreasing error
interconnecng
H3
Outdoor increasing error
cable for any fault.
H7
Indoor decreasing error
H8
HP switch abnormal
readings
H9
P9 fault 3 mes in 30 minutes
between (H1 to E) and
P0 P1
switch
for
unit
correct
address
sengs and inspect H1/H2 and
connecons
Measure between (H1 to E) and (H2 to E). Voltage
(H2 to E) is between 2.5
to
2.7VDC.
Screened
0.5mm
cable must be used and ensure that the aluminium
lm
is
earthed on the unit’s
P2/H5 P3 P4/H6 P5 P6/H4
body.
P6 Debugging
mes as indicated on the wiring diagram, the digital indicator will display last saved error
Error L0 L1 L2 L4 L8
Descripon Modular protecon Low voltage protecon High voltage protecon MEC malfuncon Speed higher between front and back clock
L9
Speed higher between real and set speed
DBV Indoor Fault codes (old display) LED Status
Fault
Compressor temperature protecon
Timer and run
Without address
High pressure protecon
All four ash
MS module and Control box is not
Low pressure protecon/P2 fault 3 mes in 30 minutes Over current of inverter compressor protecon
matched Defrost ash
EEPROM error
Compressor discharge temperature protecon/P4 3 mes in 100 min. Condenser high temperature protecon IPM module protecon/P6 3 mes in 30 minutes
Mode conict or
Timer ash
Communicaon error
Run ash
Indoor sensors
Alarm ash
Outdoor abnormal or water level alarm
P7
Over current of xed speed compressor 1
P8
Over current of xed speed compressor 2
DBV Indoor Fault codes (new display)
sors Fault codes P3
P9
Fan module protecon
Display
Fault
and P6 will display 1
L0
Inverter module protecon
FE
Without address
H0
MS module and
For DBV units with two inverter compres-
or 2 in front of the error for example (1P3/1P6 or 2P3/2P6) For E9 1 will be sys-
L1
DC low voltage protecon
L2
DC high voltage protecon
Control box is not matched E0
Mode conict
E1
Communicaon error
L4
MCE protecon
L5
Zero speed protecon
E2
Room sensor
L7
Phase sequence fault
E3
Coil sensor
L8
Speed dierence higher then 15Hz between front and back clock
E4
Coil sensor (T2B)
L9
Speed dierence higher then 15Hz between real and set speed
E7
EEPROM error
Ed
Outdoor abnormal
C7
PL fault 3 mes in 100 minutes
EE
Water level alarm
in front of the error
Hd
Slave unit abnormal
code
PL
Inverter module protecon
tem A and 2 system B error for example (1E9 or 2E9) For a Hd fault the number of the slave units will be displayed for
example
(2Hd)
Page 22 of 25
FAULT CODE BOOKLET R410A Inverter Ducted Split
2016 Version 1.2
P6 Fault Code Table (18 000Btu to 60 000Btu) First Gen.
T3 High Temperature
Fault Descripon
LED1
LED2
LED1
LED2
LED3
8 Flashes
On
O
Flash
On
Over current of IPM output
9 Flashes
On
On
On
On
Low voltage protecon
10 Flashes
On
On
On
On
High voltage protecon
12 Flashes
On
Flash
On
On
Control chip failure
13 Flashes
On
On
Flash
On
Zero speed of compressor
15 Flashes
On
On
Flash
On
Lack of phase or speed uctuates
65⁰C 52⁰C
Cut Out Cut In T4 Ambient Temperature Cut Out Cut In
Second and Third Gen.
<-7⁰C/>43⁰C >-7⁰C/<43⁰C
HDT Pipe Temperature 115⁰C 90⁰C
Cut Out Cut In
DUNHAM-BUSH Reserve the right to change any specicaons and design without prior noce for product improvement
Note:
Ref. Charging Table: Pipe
Refrigerant
Size
per Meter
1/4’’
23g per m
3/8’’
60g per m
1/2’’
120g per m
P6 Fault Code Table (68 000Btu to 100 000Btu) LED1
Transformer RT1 Brown Brown Yellow Yellow
13.5 VAC 9.0 VAC
LED2
Fault Descripon
8 Flashes
On
Inverter modular malfuncon
9 Flashes
On
Low voltage protecon
charged for a 5m pipe
10 Flashes
On
High voltage protecon
run if the piping ex-
The
unit
ceeds
Transformer RT2
5m
14.5 VAC
Condenser DC Fan P9 Fault Code Table RED
14.5 VAC
GREEN
Fault Descripon
O
O
O
Flash
On then O
On
Drive port or signal feedback malfuncon
On then Flash
On
Lightning protecon plate malfuncon
On
On
Outdoor unit capacity seng conict
277-356 VDC
3 Phase IPM Module
Check power supply for fan module
the
Please do not charge
±310 VDC
140 000Btu to 200 000Btu condensers and DBV condensers
and use a charging scale .
LC will be displayed when the unit is running in low ambient
Cut Out : 50Kpa
Running indicator lamp of network centralized control chip. The lamp will be on if the system is running normal.
LED 3:
Malfuncon indicator lamp of network centralized control chip. The lamp will ash in three me intervals to indicate a fault on the network.
LED 4:
Malfuncon indicator lamp of inverter module. The lamp will ash if the
Cut Out : 4800Kpa
inverter module is faulty and the fault code will be displayed on the
Cut In
digital tube, please see P6 debugging table for P6 fault code.
: 3200Kpa
LED 5:
nate between running frequency and LC.
Power supply indicator lamp of network centralized control chip. The lamp will be on if the power supply is normal.
LED 2:
High Pressure Switch
liquid
cooling mode or alter-
Low Pressure Switch
: 150Kpa
only
Fan module power malfuncon
535-600 VDC
LED 1:
Cut In
use
rect charging values.
vapour, 1 Phase IPM Module
Main Posive P Main Negave N Posive + Negave -
pre -
table above for cor-
Blue Blue Blue Blue
Posive P Negave N
is
Running indicator lamp of inverter module. The lamp will be on if the compressor is running.
Please ensure that the DC
capacitors
discharged
are
before
working on electrical components.
The
capacitors is charged with 600DC volts and can
cause
shock !
Page 23 of 25
electric
FAULT CODE BOOKLET R410A Inverter Under Ceiling Split
2016 Version 1.2
Under Ceiling Split Type DUNHAM-BUSH Reserve the right to change any specicaons and design without prior noce for product improvement
Note: A
slow
ash
operaon
on lamp
Indicates an EEPROM error code a quick ash
indicates
Run
Timer
Defrost
Alarm
O
Flash
O
O
Communicaon error
Flash
O
O
O
Room temperature sensor abnormal
Flash
O
O
O
Indoor coil temperature T2 sensor abnormal
Flash
O
O
O
Indoor coil temperature T2B sensor abnormal
O
O
O
Flash
Slow
O
O
O
O
O
O
Slow
Flash
Flash
O
O
Fault Descripon
Sensor Resistance Table T1,T2,T3 and T4
Water level alarm EEPROM error Outdoor unit abnormal Indoor fan motor fan speed abnormal
that
TX (⁰C) 20 21 22 23 24 25 26 27 28 29 30
KΩ 12.6431 12.0561 11.5000 10.9731 10.4736 10.000 9.55074 9.12445 8.71983 8.33566 7.97078
the indoor sensors is abnormal.
New Under Ceiling Split Type
The wired controller will not funcon if a
Display
Fault Descripon
fault occurs and will not display a fault
E1
Communicaon error
E2
Room temperature sensor abnormal
E3
Indoor coil temperature T2 sensor abnormal
codes.
E4
Indoor coil temperature T2B sensor abnormal
The standard value for
EE
Water level alarm
E7
EEPROM error
Ed
Outdoor unit abnormal
code, please revert to the display board of the
unit
for
fault
T1, T2, T3 and T4 sensors is 10kΩ at 25˚C T5 is 54.89kΩ at
T2 Low Temperature 0⁰C 5⁰C
Cut Out Cut In T2B High Temperature
60⁰C 54⁰C
Cut Out Cut In
25⁰C
Outdoor Unit Display
E0
EEPROM error
E2
Communicaon error
E3
Communicaon error between IPM and main PC board
E4
Outdoor coil /ambient temperature sensor abnormal
E5
Voltage protecon
P0
Compressor top temperature sensor abnormal
P1
High pressure protecon
P2
Low pressure protecon
P3
Compressor over current protecon
P4
Compressor discharge temperature sensor abnormal
P5
High condenser temperature protecon
P6/E6 P7
Page 24 of 25
Fault Descripon
IPM module protecon/PFC module protecon High Evaporator temperature protecon
T5 Sensor Resistance Table
TX (⁰C) 20 21 22 23 24 25 26 27 28 29 30
KΩ 68.66 65.62 62.73 59.98 57.37 54.89 52.53 50.28 48.14 46.11 44.08
FAULT CODE BOOKLET R410A Inverter Under Ceiling Split
2016 Version 1.2
P6 Fault Code Table First Gen.
T3 High Temperature
T4 Ambient Temperature <-7⁰C/>43⁰C >-7⁰C/<43⁰C
HDT Pipe Temperature 115⁰C 90⁰C
Cut Out Cut In
LED1
LED2
LED1
LED2
LED3
On
O
On
O
On
Normal running mode
Flash
On
O
On
On
Normal standby mode
8 Flashes
On
o
Flash
On
Over current of IPM output
9 Flashes
On
On
On
On
Low voltage protecon
10 Flashes
On
On
On
On
High voltage protecon
12 Flashes
On
Flash
On
On
Control chip failure
13 Flashes
On
On
Flash
On
Zero speed of compressor
15 Flashes
On
On
Flash
On
Lack of phase or speed uctuates
Communicaon Error:
Transformer RT1
Measure between (P to E) and (Q to E). Voltage
Brown Brown Yellow Yellow
13.5 VAC 9.0 VAC
Transformer RT2 Blue Blue Blue Blue
DUNHAM-BUSH Reserve the right to change any specicaons and design without prior noce for product improvement
Note:
Ref. Charging Table: Pipe
Refrigerant
Size
per Meter
1/4’’
23g per m
3/8’’
60g per m
1/2’’
120g per m
readings between (P to E) and (Q to E) is between 2.5 to 2.7VDC. Screened 0.5mm cable must be used
The
unit
and ensure that the aluminium lm is earthed on the
charged for a 5m pipe
unit’s body. The maximum length for communicaon
run if the piping ex-
cable is 1200 m from outdoor to last indoor unit,
ceeds
5m
is
pre -
use
the
please ensure that the 120k Ω resistor is connected
table above for cor-
14.5 VAC
across P to Q on the last unit.
rect charging values.
14.5 VAC
P6 IPM Module Protecon:
Please do not charge
Over current of IPM output signal
1 Phase IPM Module Posive P Negave N
Fault Descripon
65⁰C 52⁰C
Cut Out Cut In
Cut Out Cut In
Second and Third Gen.
Check the running amps of compressor and ensure wiring from IPM to compressor is correct. Test the IPM
277-356 VDC
vapour,
only
liquid
and use a charging scale .
connuity from P/N to UVW, all readings must be equal. Ensure that the neutral direcon through the CT is cor-
3 Phase IPM Module
rect. Inspect the IPM PC board is it securely installed on Main Posive P Main Negave N Posive + Negave -
the heat sink and is the heat paste sucient. Check the
535-600 VDC ±310 VDC
condenser fan motor(s) rotaon and running capacitors.
Low/High voltage protecon
LC will be displayed when the unit is running in low ambient cooling mode or alternate between running frequency and LC.
Check the commutang part assembly and IPM voltages and if all wire connecons is
Low Pressure Switch Cut Out : 50Kpa Cut In
: 150Kpa
High Pressure Switch
secure and correct, + and - on the IPM PCB is a input from the lter board.
Control chip failure Check transformer(s) input and output voltages.
Zero speed/speed uctuates or lack of phase on compressor
Please ensure that the DC
capacitors
discharged
are
before
working on electrical components.
The
Cut Out : 4800Kpa
Check wire connecons between the compressor and IPM. Check the IPM connuity
capacitors is charged
Cut In
from p to UVW, all readings must be equal and N to UVW. Ensure that the IPM PC
with 600DC volts and
board is securely installed on the heat sink and it is clean. Check the condenser fan
can
motors rotaon. Check compressor windings, resistance must be equal across U -V, U-
shock !
: 3200Kpa
cause
W and V-W. Resistance will be between 0.5 Ω and 5.9Ω.
Page 25 of 25
electric