Minimum Chiller Plant Performance *Type of building: Large commercial buildings (150,000 ft2 and above) in Singapore Ashrae 90.1-2007 Baseline building Type Condition Min eff Units Remarks Chillers
Full load @ ARI std condn
Part load
CHWP
Full load
Part load
6 .1
COP
0 .5 8
Kwi / TON
6 .4
COP
0 .5 5
Kwi / TON
22
W / GPM
0 . 0 44
KWi / TON
-
Refer to table 6.8.1J for non std conditions
IPLV @ ARI std condn Refer to table 6.8.1J for non std conditions
CHW 44/56F
Decoupled system where sec pumps must
Minimum Chiller Plant Performance *Type of building: Large commercial buildings (150,000 ft2 and above) in Singapore GMv3 Reference building Type Condition Min eff Units Remarks Chillers
Full load @ ARI std condn
Part load
6.1
COP
0.58
Kwi / TON
-
No requirement for part load performance
-
CHWP
Full load
Part load
30
KWc / Kwi
0.117
Kwi / TON
-
No requirement for part load performance
Minimum Chiller Plant Performance Type of building: Large commercial buildings (150,000 ft2 and above) in Singapore Ashrae 90.1-2007 Baseline building Type AHU / FCU < 20,000cfm & constant volume
AHU>= 20,000cfm & constant volume
AHU / FCU < 20,000cfm & variable volume
AHU >= 20,000cfm & variable volume
Condition Full load
Full load
Full load
Min Eff 1.2
Units HP/1000cfm
Remarks HP refers to motor nameplate
0.90
KWi / 1000cfm
Assumes HP ~ HPi
1.1
HP/1000cfm
0.82
KWi / 1000cfm
1.7
HP/1000cfm
1.27
KWi / 1000cfm
Part load
-
Full load
1.5
HP/1000cfm
1.12
KWi / 1000cfm
Part load
-
1 Hp = 0.746 kW I cmh = 0.5885778 cfm
GreenMark v3 Reference building Type Constant volume system