Digital Differential Protection G. Ziegler
Differential Protection Symposium
Belo Horizonte, 7 to 9 Nov. 2005
No.: 1
Differential Protection: Discussion Subjects Ø
Mode of operation
Ø
Measuring technique
Ø
Current transformers
Ø
Communications
Ø
Generator and motor differential protection
Ø
Transformer differential protection
Ø
Line differential protection
Ø
Busbar differential protection
Differential Protection Symposium
Belo Horizonte, 7 to 9 Nov. 2005
No.: 2
Digital Differential Protection Principles and Application Gerhard Ziegler
Differential Protection Symposium
Belo Horizonte November 2005
G. Ziegler, 10/2005
page 1
Contents Pages Mode of operation
3 - 27
Measuring technique
28 - 45
Current transformers
46 - 86
Communications
87 - 115
Generator and motor differential protection
116 - 122
Transformer differential protection
123 - 178
Line differential protection
179 - 216
Busbar differential protection
217 - 247
7UT6 product features
248 - 264
Differential Protection Symposium
Belo Horizonte November 2005
G. Ziegler, 10/2005
page 2
Digital Differential Protection Mode of operation Gerhard Ziegler
Differential Protection Symposium
Belo Horizonte November 2005
G. Ziegler, 10/2005
page 3
Comparison protection - Principles Absolute selectivity by using communications IA
IB B
A
Exchange of YES / NO signals (fault forward / reverse)
protection range reverse
forward
Relay
forward
communication
reverse
• Current comparison | ∆I |
Relay
Sampled values Phasors Binary decisions
t
•Directional comparison
IA
IB
•comparison of momentary values or phasors B
• | ∆I | = | IA - IB | > limiting value
A Differential Protection Symposium
Belo Horizonte November 2005
G. Ziegler, 10/2005
page 4
Protection Criterion “current difference“ (differential protection) n Kirchhoff‘s law: II1 + I2 + I3 + ... InI= Idiff = 0;
Current difference indicates fault
n Security by through-current dependent restraint
|I1|+|I2|+ ... |In| = IRes
protection object
n Characteristic:
Idiff Trip Ires n Absolute zone selectivity (limits: CT locations)
No “back-up“ for external faults n Differential protection: for generators, motors, transformers, lines and busbars
Differential Protection Symposium
Belo Horizonte November 2005
G. Ziegler, 10/2005
page 5
Current differential protection: Basic principle
I1 i1
I2 Protection object
i2 ∆I>
∆I=I1 + I2 =0
external fault or load
Differential Protection Symposium
I1
I2
Protection object
i1
i2 i1
∆I>
∆I=I1 + I2
i2
internal fault
Belo Horizonte November 2005
G. Ziegler, 10/2005
page 6
Differential protection: Connection circuit Traditional technique
Digital technique
L1
L1
L2 L3
L2 L3
∆I
∆I
∆I
Galvanically connected circuits must only be earthed once!
Different CT ratios need to be adapted by auxiliary CTs!
Differential Protection Symposium
∆I
CT circuits of digital relays are segregated and must each be earthed !
Digital relays have integrated numerical ratio adaptation !
Belo Horizonte November 2005
G. Ziegler, 10/2005
page 7
Generator and transformer differential protection
L1 L2 L3
L1 L2 L3
∆I
∆I
∆I
Differential Protection Symposium
Yd5
Matching transformer
Belo Horizonte November 2005
∆I
∆I
∆I
G. Ziegler, 10/2005
page 8
Transformer differential protection
Yd5 L1 L2 L3
Matching transformer
Differential Protection Symposium
∆I
∆I
∆I
Belo Horizonte November 2005
G. Ziegler, 10/2005
page 9
Current transformer: Principle, transformation ratio, polarity
i1
i2
i1 w1
u1 i2
1 Φ
u2
i1 ⋅ w1 = i2 ⋅ w2
Function principle i1
u2
u1 u 2 = w1 w2
2
w2
u1
Polarity marks
P1
P2
i2 i1
u1
i2
u2 S1 Equivalent electrical circuit
Differential Protection Symposium
S2
Designation of CT terminals according to IEC 60044-1
Belo Horizonte November 2005
G. Ziegler, 10/2005
page 10
Busbar differential protection Digital protection 7SS52
Analog protection 7SS10/11/13 7SS600 with digital measuring relay (∆I)
∆I Central Unit 2
4
3
Optic fibres
0
∆I
BU
BU
BU
BU
0
G
M Grid infeed
BU: bay unit
G
Load
Differential Protection Symposium
M Grid infeed
Belo Horizonte November 2005
Load
G. Ziegler, 10/2005
page 11
Line differential protection
50/60 Hz current comparison through wire connection I1
Phasor with digital communication via OF, microwave or pilot wires I1
I2 I2
∆I
DI
∆I
∆I
∆I
I1
I2
dedicated O.F. up to about 35 km Other services
PCM MUX
PCM MUX
Other services
O.F. or Microwave
Differential Protection Symposium
Belo Horizonte November 2005
G. Ziegler, 10/2005
page 12
Two wire (pilot wire) line differential protection Voltage comparison principle I2
I1
Grid
G ∆I
RS
U1
∆U
∆I
U2
RS
3
3
∆I
Differential Protection Symposium
∆I
Belo Horizonte November 2005
G. Ziegler, 10/2005
page 13
False differential currents during load or external faults
I∆ / In te
ri st ic
4
ac
∆IGF = total false current
re
la
y
ch
ar
3 2
∆IWF = CT false current ∆IAF = Inaccurate adaptation (CT ratios, tap changer)
1
∆IWF = Transformer magnetising current
1
10
Differential Protection Symposium
15
ID / In
Belo Horizonte November 2005
G. Ziegler, 10/2005
page 14
Percentage differential relay
A = I1− I2 operate stabilise
B S = I1+ I2
I1 Basicpick-up value (B) I2 I1+ I2
Differential Protection Symposium
Belo Horizonte November 2005
G. Ziegler, 10/2005
page 15
Differential protection: analog measuring circuit Rectifier bridge comparator with moving coil relay
I2
I1 protection object
i1
Fault characteristic (single side infeed)
i2
ΔI =
W2
W1 W3
k1 ⋅ I Re s
k1 ⋅ I Re s
I1 − I 2
Relay characteristic
W1
k 2 ⋅ I Op
= k1 ⋅ (I 1 − I 2 ) k1 =
I1 + I 2 > k ⋅ I1 − I 2
W4
w1 w2
Differential Protection Symposium
k=
k2 ⋅ I Op
Σ I = I1 + I 2
= k2 ⋅ (I1 + I 2 ) k2 =
w3 w4
k1 k2
with digital relays: ΣI = I1 + I 2
Belo Horizonte November 2005
G. Ziegler, 10/2005
page 16
Multi-end differential protection: Analog measuring principle
1
n
2
Iop = I1 + I 2 + .... + I n = Σ I
Differential Protection Symposium
k ⋅ I Re s
I Op
I Res = I1 + I 2 + .... + I n = Σ I
Belo Horizonte November 2005
G. Ziegler, 10/2005
page 17
Optimised relay characteristic
G R 2000A
Ideal fault characteristic
∆Ι
IOp = I1 − I 2
internal fault
300A
F
Load RL
IOp = 2000 A
relay characteristic
IS = 2600 A
I F1
I F2
G
G
CT saturation
∆Ι I Res = I1 + I 2
Healthy protection object
δ I Op = 2 ⋅ I F ⋅ cos
Differential Protection Symposium
I Re s = 2 ⋅ I F
δ 2
Belo Horizonte November 2005
G. Ziegler, 10/2005
page 18
Digital differential protection: Relay characteristic IOp Positive current polarity k2 ∆I
k1
Id > IR0
I Op = ΣI = I1 + I 2
Settings:
I Res = Σ I = I1 + I 2
• slope k1
IRes
• Pick-up value Id >
• slope k2 with footing point IR0
Differential Protection Symposium
Belo Horizonte November 2005
G. Ziegler, 10/2005
page 19
∆I / ΣI und I1 / I2 diagram ΔI = I1 + I 2
I1 Internal faults IS0 1+ k + ⋅B 2 2⋅k
k [% / 100 ] slope
B
IS0
IS0 1− k ⋅B + 2 2⋅k
Σ I = I1 + I 2
(
1
I1 + I 2 > k I1 + I 2 − I S 0
2
I1 + I 2 > B
Differential Protection Symposium
)
IS0 2
Belo Horizonte November 2005
G. Ziegler, 10/2005
page 20
I2
Polar diagram of differential protection I1 + I 2 > k ⋅ I1 − I 2
β-Plane (remote/local current)
I 1+ 2 1+β I1 > k or >k I2 1- β 1− I1
I Im 2 I1
I β= 2 I1
I2 Protection object ∆Ι
I with β = 2 I1 −
I1
1+ k 1− k
+1
-1 (k=0,5)
−
1− k 1+ k
I Re 2 I1
Restraint area
Differential Protection Symposium
Belo Horizonte November 2005
G. Ziegler, 10/2005
page 21
Polar diagram of digital differential protection: Basic pick-up value B > 0
90
I 2 jϕ e I1
120
I1 + I 2 > k ⋅ ( I1 + I 2 ) + B or I2 > k ⋅ 1 + 1+ I1
I2 I1
B + I 1
60
ϕ
150
30
180
0 5
210
10
330
300
240 270 B/I1= 0,3
a1(Φ): k=0,3 a2(Φ): k=0,6 a3(Φ): k=0,8
Differential Protection Symposium
Belo Horizonte November 2005
G. Ziegler, 10/2005
page 22
Mixing transformer of composed current differential protection
IL1
IL2
IL3 IL1
Composed current during symmetrical 3-ph fault or load
IM
2
IL3
7SD503: IM = 100 mA 7SS600: IM = 100 mA 7SD502: IM = 20 mA
1
IE 3 Mixing transformer
IM =
IL3
1 ⋅ 3 ⋅ I Ph −3 w
2 ·IL1
IL3
IL1
I M = 2 ⋅ I L1 + 1 ⋅ I L3 + 3 ⋅ I E IL3
IL2
Differential Protection Symposium
= 5 ⋅ I L1 + 3 ⋅ I L2 + 4 ⋅ I L3 ⇒ composed current (vector sum) Belo Horizonte November 2005
G. Ziegler, 10/2005
page 23
Mixing transformer: Pickup sensitivity of standard connection (IM= 2IL1+IL3+3IE )
Fault type
Per unit composed current related to 3-phase symmetrical current
Composed current
L1-E
IML1-E = 5 IL1
IL2 = IL3 = 0
IML1-E / IM = 5 / √ 3 = 2.9
L2-E
IML2-E = 3 IL2
IL1 = IL3 = 0
IML2-E / IM = 3 / √3 = 1.73
L3-E
IML3-E = 4 IL3
IL1 = IL2 = 0
IML3-E / IM = 4 / √3 = 2.3
L1-L2
IML12 = 5 I L1 + 3 I L2
IL3 = 0
IML12 / IM = 2 / √3 = 1.15
L2-L3
IML23 = 3 I L2 + 4 I L3
IL1 = 0
IML23 / IM = 1 / √3 = 0.58
L1-L3
IML13 = 5 I L1 + 4 I L3
IL2 = 0
IML13 / IM = 1 / √3 = 0.58
L1-L2-L3
IML123 = 5 IL1 + 3IL2 + 4IL3
|IL1| = |I L2| = |I L3|
IML123 / IM = √3 / √3 = 1
Differential Protection Symposium
Belo Horizonte November 2005
Highest sensitivity
G. Ziegler, 10/2005
page 24
Composed current differential protection Behaviour during cross country fault (isolated/compensated network) ∆I
A
B L1 L2 L3
IF
L1 internal und L3 external: IM-A= 5⋅IF - 4⋅IF = 1⋅IF und IM-B= + 4⋅IF ∆I = |IM-A + IM-B| = 5IF und ΣI = |IM-A| + |IM-B| = 5⋅IF ∆I/ΣI = 5/5 = 1.0
Tripping
L2 internal, L3 external IM-A= - 1⋅IF und IM-B= + 4⋅IF ∆I = |IM-A + IM-B| = 3 ⋅IF und ΣI = |IM-A| + |IM-B| = 5⋅IF ∆I/ΣI = 3/5 = 0.6
Tripping if k-setting < 0.6
Differential Protection Symposium
Belo Horizonte November 2005
G. Ziegler, 10/2005
page 25
Composed current differential protection Through current stabilisation with unsymmetrical earthing conditions
2
1
3
3
2
IM2=2·IL1 + 1·IL3+ 3 ·IE =2·IF + 1 ·IF+ 3·3IF = +12 ·IF
IM1=2·IL1 + 1·IL3 + 3 ·IE =2 ·(–IF) + 1 ·(–IF) + 3·0= –3·IF IOp=| IM1 + IM2 | = 9 ·IF IRes=|IM1| +|IM2| = 15 ·IF
1
k=9/15 = 0.6
IOp
Fault L2-E
k=0.5
Faults in other phases: Fault L1-E: IOp = (3+12) ·IF = 15 ·IF, IRes= (3+12) ·IF = 15 ·IF,
k=1
Fault L3-E: IOp = (0+12) ·IF = 12 ·IF, IRes= (0+12) ·IF = 12 ·IF,
k=1
Differential Protection Symposium
IRes Belo Horizonte November 2005
G. Ziegler, 10/2005
page 26
High impedance differential protection: Principle Behaviour during external fault with CT saturation
with ideal current transformers
ISC
RCT
RCT
ISC
ISC
ISC
UR
ECT −1 = (RL + RCT ) ⋅ iSC
ECT −1 = 2 ⋅ (RL + RCT ) ⋅ iSC
UR = 0 ECT −2 = (RL + RCT ) ⋅ iSC
Differential Protection Symposium
U R = (RL + RCT ) ⋅ iSC
Belo Horizonte November 2005
G. Ziegler, 10/2005
page 27
High impedance differential protection: Calculation example (busbar protection)
Given:
n = 8 feeders rCT = 600/1 A UKN = 500 V RCT = 4 Ohm ImR = 30 mA (at relay pick-up value)
Pick-up sensitivity:
(
600 ⋅ (0.02 + 0.05 + 8 ⋅ 0.03) 1
I F − min = 186 A ⋅ (31% )
Differential Protection Symposium
RR = 10 kOhm Ivar = 50 mA (at relay pick-up value)
Stability:
I F −min = rCT ⋅ I R − pick −up + IVar + n ⋅ I mR
I F − min =
RL= 3 Ohm (max.) IR-pick-up.= 20 mA (fixed value)
)
I F −through − max < rCT ⋅
I F −throuh − max <
RR ⋅ I R − pick −up RL + RSW
600 10,000 ⋅ ⋅ 0.02 1 3+4
I F −through − max < 17kA = 28 ⋅ I n Belo Horizonte November 2005
G. Ziegler, 10/2005
page 28
Digital Differential Protection Measuring Technique Gerhard Ziegler
Differential Protection Symposium
Belo Horizonte November 2005
G. Ziegler, 10/2005
page 28
Merz and Price differential protection Patent dated 1904
a: feeder, b: generator, c: substation, d: primary winding of CT, e: secondary winding of CT, f: earth or return conductor, g: pilot wire, h: relay windings, i: circuit breakers, k,l: movable and fixed relay contacts, m: circuit, n: battery, o: electromagnetic device with armature p.
Differential Protection Symposium
Belo Horizonte November 2005
G. Ziegler, 10/2005
page 29
Electro-mechanical differential protection based on induction relay I2
I1 Schutzobjekt
i1
Differential Protection Symposium
∆i
i2
Belo Horizonte November 2005
G. Ziegler, 10/2005
page 30
Electro-mechanical differential protection Rectifier bridge comparator with moving coil relay I1
Protection object
i1
I Re s
ΔI = I
Op
−I
i2
IOp
∆I
I Re s = k ⋅ (I 1 − I 2 )
I2
I Op = I 1 + I 2
+ Re s
Differential Protection Symposium
N
S
Belo Horizonte November 2005
G. Ziegler, 10/2005
page 31
Differential protection Analog static measuring circuit
I1
I2
Protection object
i1
I Re s = k ⋅ (I 1 − I 2 )
i2 I Re s ⋅ R S
RS V1 RS
I Op = I 1 + I 2
V3 V2
I Op ⋅ R S
URef
Differential Protection Symposium
Belo Horizonte November 2005
G. Ziegler, 10/2005
page 32
Digital differential protection Measuring value acquisition and processing
0.67 ms (18 degr. el.)
MI
1.2 kHz clock
Filter
1 IL1 IL2 IL3 IE UL1 UL2 UL3 UE a.s.o.
Processor system
S&H
CPU A D
RAM
MUX
ROM
n
Differential Protection Symposium
Belo Horizonte November 2005
G. Ziegler, 10/2005
page 33
Digital protection: Measurement based on momentary values
I=
IRMS 0
I
n
∆Tsamp. corresponds to ∆ϕ ( 60Hz: 0.67 ms = 18O el.)
I= n −1 cos ( ⋅ ∆ϕ ) 2 Iˆ I RMS = 2
Iˆ =
Differential Protection Symposium
when n sampled values exceed the pick-up limit I= f ∆ϕ = ω ⋅ ∆Tsamp. = N ⋅ 360O fA
Belo Horizonte November 2005
G. Ziegler, 10/2005
page 34
Digital differential protection: Measurement based on momentary values 4 3
∆I
5
5
6
2
4 7
3 2
8
1
∆I>
9 10
0
1
6
trip
7 8
restrain
9
0 10
18O = 1 ms (50 Hz) = 0.67 ms (60 Hz)
ΣI
IA
IB
∆I
∆I
Operating quantity :
∆I = I A + I B
Restraining quantity : ΣI = I A + I B Differential Protection Symposium
Belo Horizonte November 2005
G. Ziegler, 10/2005
page 35
Discrete Fourier-Transformation (Principle) sin 2π ⋅i n 0 1 2 . .
i( k −n+i )
.
Correlate: Multiply samples and add for one cycle n
Correlate IS(k)
i k-n
I (k) = I S(k) + j ⋅ I C(k) k
Correlate IC(k)
I (k )
j
IC(k)
cos 2π ⋅i n
Differential Protection Symposium
Belo Horizonte November 2005
ϕ IS(k)
G. Ziegler, 10/2005
page 36
Discrete Fourier-Transformation (calculation formulae) i 0
i1 i2 i 3 iN ∆t
N
I = 2 ∑ sin(ω ⋅n⋅ Δt )⋅in S N n=1
N
i i N-1 I = 2 O + N + ∑ cos(ω ⋅n ⋅ Δt)⋅in C N 2 2 n=1
N-1
0 1 2 3 .... n
0 1 2 3 ...
Differential Protection Symposium
Belo Horizonte November 2005
G. Ziegler, 10/2005
page 37
Orthogonal components of a current phasor dependent on the position of the data window Data window
Φ = ωt IS =
Φ 1 ⋅ ∫ I (ω ⋅ t ) ⋅ sin ωt ⋅ dt 2π Φ −360
IC =
Φ 1 ⋅ ∫ I (ω ⋅ t ) ⋅ cos ωt ⋅ dt 2π Φ −360
I Φ = I S + j ⋅ IC I0 = 1+ j ⋅ 0 I
O
O
O
I30 3 1 = + j⋅ I 2 2 O
I 60 1 3 = + j⋅ I 2 2 O
jIC
I IS
ωt t=0
I90 = 0 + j ⋅1 I O
Differential Protection Symposium
Belo Horizonte November 2005
G. Ziegler, 10/2005
page 38
Transfer function of a one cycle Fourier-filter Hrel 1,0 0,75 0,5 0,25 0 0
1
Differential Protection Symposium
2
3
4
5
6
f/fn
Belo Horizonte November 2005
G. Ziegler, 10/2005
page 39
Digital protection Fast current phasor estimation N
k-N
i(t)
k
Data window i(t) = A ⋅ sin( ωt ) +
Task: Method:
Delta =
t − B ⋅ cos( ωt) - e τ + C ⋅ cos( ωt)
Estimation of the coefficients A, B, C on basis of measured currents and voltages Gauß‘s Minimization of error squares: Delta = quality value k = sampling number k N = length of data window 2 ∑ i(n ⋅ ∆T) - f (n) MIN n = variable n=k-N ∆T = sampling interval sampled values
(
)
Differential Protection Symposium
Belo Horizonte November 2005
G. Ziegler, 10/2005
page 40
Differential protection with phasors (principle) A
∆I
B
IAC , IAS IBC , IBS
∆I
∆I
trip
∆I>
restraint
j·IAS
ΣI Operating quantity :
∆I = I A + I B
Restrainin g quantity : Σ I = I A + I B
IBC IAC j·IBS
Differential Protection Symposium
Belo Horizonte November 2005
G. Ziegler, 10/2005
page 41
Digital line differential protection Synchronisation of phasors (ping-pong time alignment) A
tA1 tA2
∆I
∆I
curre n phas t o rs
α ...
tPT1
tAR
tA5
tA1
tPT2 tV tB3 tA1
tBR
tB2
α=
tB3 nt curre . . . rs ph aso
Differential Protection Symposium
t B3 - t A3 ⋅ 360 ° TP
tB4
Signal transmission time: t PT1 = t PT2 = Sampling instant:
IB( tB3 )
tB1 tD
tA3 tA4
IB( tA3 )
B
1 (t A1 - t AR - t D ) 2
t B3 = t A3 - t PT2
Belo Horizonte November 2005
G. Ziegler, 10/2005
page 42
Split path data transmission Impact of unsymmetrical propagation time I1
I2
∆I
∆I
180o ∆T[ms ]⋅ α 10ms ∆I = I ⋅ sin = I ⋅ sin 2 2
α I2 I1
Example: Transmit channel time 3 ms Receive channel time 4.2 ms → time difference ∆ = 1.2 ms
180o 1.2ms ⋅ 10ms = I ⋅ 0.19 ∆I = I ⋅ sin 2
∆I α/2
∆I = 19%!
To keep the false differential current below about 2 to 5%, the propagation time difference should not exceed about 0.1 to 0.25 ms! Otherwise: → more insensitive relay setting → or GPS synchronisation Differential Protection Symposium
Belo Horizonte November 2005
G. Ziegler, 10/2005
page 43
Synchronisation of Differential relays via GPS Line end 1
Line end 2
GPS-Antenna RS232
GPS-Antenna GPS
RS232
UH
DC GPS-Empfänger supply DCF-SIM A B LWL LWL IRIG-B 24V
GPS
GPS-Empfänger Hopf DC supply DCF-SIM A B LWL LWL IRIG-B 24V
IRIG-B Telegram Sec. impulse (highly accurate)
LWL K1
LWL
BE2
K2
IRIG-B Telegram Sec. impulse (highly accurate)
LWL
K2
K1
7XV5654 Sync-Trans. K1 X1 K2 K2
LWL
BE2
K2
K2
7XV5654 Sync-Trans. K1 X1 K2 K2
+ - 24V + 1 3 8 4
+ - 24V + 1 3 8 4
Y-cable 7XV5105
1 3 8 4
RUN
7SD52
SIEMENS
ERR OR
L1 402,1A L2 402,1A L3 402,1A E 00.0A
to max.
Differential Protection Symposium
SIEMENS
ERR OR
L1 402,1A L2 402,1A L3 402,1A E 00.0A
7SD52
6
V4
SIPROTEC RUN
Max450.1A Max450.1A Max450.1A
Anr. L1 Anr. L2 Anr. L3 Anr. Erde Automat
1 3 8 4
V4
SIPROTEC
RUN
Max450.1A Max450.1A Max450.1A
Anr. L1 Anr. L2 Anr. L3 Anr. Erde Automat
1
1 3 8 4
V4
SIPROTEC
L1 402,1A L2 402,1A L3 402,1A E 00.0A
Y-cable 7XV5105
1 3 8 4
V4 SIEMENS
UH
SIEMENS
ERR OR
SIPROTEC
RUN
Max450.1A Max450.1A Max450.1A
L1 402,1A L2 402,1A L3 402,1A E 00.0A
Anr. L1 Anr. L2 Anr. L3 Anr. Erde Automat
ERR OR Max450.1A Max450.1A Max450.1A
Anr. L1 Anr. L2 Anr. L3 Anr. Erde Automat
1
t0 max.
Belo Horizonte November 2005
6
G. Ziegler, 10/2005
page 44
Devices for GPS time synchronisation n GPS receiver with 2 optical outputs (7XV5664-0AA00). Output for IRIB-B telegram and output for second/ minute pulse n Galvanic separation between the receiver and the tranceiver 7XV5654 n Optic/electric signal conversion in the tranceiver n Distribution of the electrical signals via Y-bus cable to port A of the relays (telegram) n Electronic contact for the minute pulse in case of synchronisation through binary input with battery voltage
Differential Protection Symposium
Outdoor antenna FG4490G10 for GPS
GPS receiver 7XV5664 Tranceiver 7XV5654 Belo Horizonte November 2005
G. Ziegler, 10/2005
page 45
Additional components for SICAM SAS GPS-System
• • • •
Differential Protection Symposium
24 satellites move in a height of 20 000km on 6 different paths Transmission frequency 1,57542GHz For a continuous time reception min. 4 satellites is necessary High accuracy : 1 usec
Belo Horizonte November 2005
G. Ziegler, 10/2005
page 46
Operating characteristic of digital differential relays
I∆ =|I1+ I2|
I1
I2
b%
∆I
I∆>
a%
I∑ b
Differential Protection Symposium
I∑ = |I1|+ |I2|
Belo Horizonte November 2005
G. Ziegler, 10/2005
page 47
Differential protection CT saturation with internal and external faults ∆I Protection object
I2
I1 Internal fault
External fault
I1 I2 Σ I= |I1| + |I2| ∆I=|I1 +I2| t=0
t=10
Differential Protection Symposium
t=20 ms
t=0
t=10
t=20 ms
Belo Horizonte November 2005
G. Ziegler, 10/2005
page 48
Saturation detector:
Locus of ∆I/ΣI for external faults without and with CT saturation
i Op( n ) = i1( n ) + i 2( n ) 6' 7'
saturation
3'
re s
i 2( n )
in tra
n
8'
External fault
5' 4' with CT
i1( n )
e rat e op
i1( n ) + i 2( n )
9'
0 10
External fault (ideal CTs)
1
2
3
4 5
9
8
7
6
i Re s ( n ) = i1(n ) + i 2( n )
Differential Protection Symposium
i1(n ) + i 2( n )
n=0
n=10
Belo Horizonte November 2005
n=20
G. Ziegler, 10/2005
page 49
Differential current caused by transient CT saturation (ext. fault) with operating and restraint current of busbar protection 7SS5 I1 100
50
I2
0
50
IRes.= |I1| + |I2|
IOp=|I1 +I2|
Differential current appears only every second half wave!
Differential Protection Symposium
Belo Horizonte November 2005
G. Ziegler, 10/2005
page 50
Tripping logic of digital busbar protection 7SS600/7SS5 with saturation detector (simplified) di Re s > k s [A / ms] dt
i Op > iset i Op > k ⋅ i Re s
A N D
A N D
A N D
3 ms A N D
Transient blocking
Differential Protection Symposium
1-out-of-1
2 150 ms
Saturation detected
3 ms
Trip
n=2
Adaptive restraint
A N D
O R
Trip
2-out-of-2 Trip
Belo Horizonte November 2005
G. Ziegler, 10/2005
page 51
Transformer differential protection 7UT6: Saturation detection and automatic increase stabilisation
Internal faults
Trip
Restrain
Area of add-on restraint
Differential Protection Symposium
Belo Horizonte November 2005
G. Ziegler, 10/2005
page 52
Transient CT saturation causes false differential currents
IF
IF
+I1
+I2
87
I1
IF
I2
+∆I
∆I
Wave shape similar to transformer inrush current ?
Differential Protection Symposium
Belo Horizonte November 2005
G. Ziegler, 10/2005
page 53
Adaptive restraint against CT errors (7SD52/61) Detection of CT saturation (wave shape analysis)
CT Error approximation (no-saturation)
Error %
Load range
Fault range
fL
fF 10%
ALF‘/ALFN • IN-CT
Differential Protection Symposium
ALF’ •IN-CT
Belo Horizonte November 2005
G. Ziegler, 10/2005
page 54
Adaptive 87 restraint (7SD52/61) considers current CT- errors IDiff
I1
Trip Area
Trip level With saturation Block-Area
IDiff> 0 0 Current summation:
Trip level Without saturation
I2
External Fault
I2
I1
Max. error (ε) without saturation
IDiff = │I1+ I2│
Max. error (ε) with saturation.
IRest
Max. error summation: IRestraint = ΣIError = IDiff> + εCT1 ·I1 + fSat· εCT2 ·I2
Differential Protection Symposium
Belo Horizonte November 2005
G. Ziegler, 10/2005
page 55
External fault Increase of stabilisation after detection of saturation Begin of saturation ∆Ι
(K1:iE = -K1:iL1)
Increase of restraint
I∆
IRestraint
ΣΙ Differential Protection Symposium
Belo Horizonte November 2005
G. Ziegler, 10/2005
page 56
Fast charge comparison supplement speeds up phasor based line differential protection (7SD52/61) Q2
Q1
iL1/kA 20 10 0 -10
-0,02
-0,01
-0,00
0,01
0,02
0,03
0,04
0,05
0,06
0,07
0,08
-0,02
-0,01
-0,00
0,01
0,02
0,03
0,04
0,05
0,06
0,07
0,08
-0,02
-0,01
-0,00
0,01
0,02
0,03
0,04
0,05
0,06
0,07
0,08
t/s
-0,02
-0,01
-0,00
0,01
0,02
0,03
0,04
0,05
0,06
0,07
0,08
t/s
t/s
-20 -30 -40
iL2/kA 20 10 0 -10
Q3
t/s
-20 -30 -40
iL3/kA 20 10 0 -10 -20 -30
Diff G-AUS
Q 1/4 cycle
1 cycle data windows for phasor comparison •Synchronized with fault inception ¼ cycle data windows of fast charge comparison
Differential Protection Symposium
•Released by Idiff >>
Belo Horizonte November 2005
G. Ziegler, 10/2005
page 57
Generator, Motor and Transformer protection: Adaptive algorithms to upgrade relay stability and dependability with CT saturation (7UT6) Measured value processing i1L i2L
Side 1 Side 2
Sampled momentary values iRes = | i1 | + | i2 | iOp = i1 + i2
Mean values IRes = Mean(iRes) Fundamental wave IOp = RMS(iDiff)60Hz
87 algorithm Operating characteristic IOp
IDiff>
IRes.
Motor start DC component
&
Trip IOp>
Saturation detector
For security:
Harmonic Analysis: -2nd Harmon. Blocking -Cross Blocking
Adaptive restraint
IOp IDiff> >
For dependability: Fast tripping using sampled momentary values ensures fast operation with very high currents before extreme CT saturation occurs!
Differential Protection Symposium
iOp
≥1
Trip IOp>>
IDiff>>>
Belo Horizonte November 2005
G. Ziegler, 10/2005
page 58
Current Transformers for Differential Relaying Requirements and Dimensioning Gerhard Ziegler
Differential Protection Symposium
Belo Horizonte November 2005
G. Ziegler, 10/2005
page 46
Equivalent current transformer circuit I2′ = I1 ⋅ I1
jX1 R1
N1 N2
Im
P1 N1
P2
jX2
N2 U2
Ideal transformer
R2
I2 S1
Zm
Zb
S2
X1 = Primary leakage reactance R1 = Primary winding resistance X2 = Secondary leakage reactance Z0 = Magnetising impedance R2 = Secondary winding resistance Zb = Secondary load Note:
Normally the leakage fluxes X 1 and X2 can be neglected
Differential Protection Symposium
Belo Horizonte November 2005
G. Ziegler, 10/2005
page 47
Current transformer: Phase displacement (δ) and current ratio error (ε) w1 . I1 w 2
w1:w2 j·X2
R2 U2
I2
I1
ZB
ε
I2 δ
I‘1=
w1 ·I w2 1
Im
I2
Em
I1 Em
R2
U2
RB
Xm
Differential Protection Symposium
Im
Im
Belo Horizonte November 2005
G. Ziegler, 10/2005
page 48
Dimensioning of CTs for differential protection Pi = I sec .2 × R CT
CT classes to IEC 60044-1: 5P or 10P Specification:
300/1 A
5P10, 30 VA RCT ≤ 5 Ohm Rated burden (nominal power) PN
Ratio In -Prim / In -Sek. 5% accuracy at I= n x In Actual accuracy limit factor in operation is higher as the CT is normally under-burdened : Operating ALF: ALF‘
Accuracy limit factor ALF Dimension criterium:
P + PN ALF ' = ALF × i Pi + PB
I ALF ' ≥ SC − max × KTF In
KTF (over-dimensioning factor) considers the single sided CT over-magnetising due to the d.c. component in short circuit current I SC. KTF values required in practice depend on relay type and design. Recommendations are provided by manufacturers (see Application Guide) Differential Protection Symposium
Belo Horizonte November 2005
G. Ziegler, 10/2005
page 49
Current transformer, Standard for steady-state performance
IEC 60044-1 specifies the following classes:
Accuracy class
Current error at nominal current (In)
5P
±1%
10P
± 5%
Differential Protection Symposium
Angle error δ at rated current In
Total error at n x In (rated accuracy limit)
± 60 minutes
5% 10 %
Belo Horizonte November 2005
G. Ziegler, 10/2005
page 50
Current transformers, Standard for transient performance IEC 60044-6 specifies four classes:
Class
Error at rated current Ratio error
TPX (closed iron core)
TPY with anti-remanence air-gap
TPZ linear core
TPS closed iron core
Maximum error at rated accuracy limit
Remanence
Angle error
± 0,5 %
± 30 min
εˆ ≤ 10 %
± 1,0 %
± 30 min
εˆ ≤ 10 %
± 1,0 %
± 180 ± 18 min
εˆ ≤ 10% (a.c. current only)
Special version for high impedance protection (Knee point voltage, internal secondary resistance)
Differential Protection Symposium
Belo Horizonte November 2005
no limit < 10 %
negligible
No limit
G. Ziegler, 10/2005
page 51
Definition of the CT knee-point voltage (BS and IEC)
British Standard BS3938: Class X
U2 10 %
or IEC 60044-1 Amendment 2000/07: Class PX
UKN 50 %
Specify: Knee point voltage Secondary resistance RCT Im
I U KN ≥ K TF ⋅ (R CT + R B − connected ) ⋅ SC − max . I n − CT Differential Protection Symposium
Belo Horizonte November 2005
G. Ziegler, 10/2005
page 52
CT specification according to ANSI C57.13
w1 I‘1= w ·I1 2
I2
Im
Em
ANSI C57.13 specifies:
RCT RB
U2
• Secondary terminal voltage U2 at 20 times rated current (20x5=100 A) and rated burden • Error <10% Example: 800/5 A, C400 (RB= 4 Ω)
U2, Em
Resulting magnetising voltage:
E al ≈ (U ANSI + 20 ⋅ 5 ⋅ R CT )
= (20 ⋅ 5 ⋅ Z B − rated + 20 ⋅ 5 ⋅ R CT )
Im Differential Protection Symposium
Belo Horizonte November 2005
G. Ziegler, 10/2005
page 53
Current transformer saturation
Steady-state saturation with a.c. current
Transient saturation with offset current
Differential Protection Symposium
Belo Horizonte November 2005
G. Ziegler, 10/2005
page 54
CT saturation Currents and magnetising IP
t
φ saturation flux
t
IS
t
Differential Protection Symposium
Belo Horizonte November 2005
G. Ziegler, 10/2005
page 55
Transient CT saturation due to DC component
ISC
Short circuit current
DC flux non-saturated ΦS
Φ
Im
Differential Protection Symposium
AC flux
Magnetising current
Belo Horizonte November 2005
G. Ziegler, 10/2005
page 56
Course of CT-flux during off-set short-circuit current
ΙP primary current d.c. component
i p (t) =
Φ
Total flux
t ωTp Ts - t Φ max Tp K td (t) = = (e - e Ts ) + 1 ˆ Φ Tp - Ts a.c.
Ktd(t) transient d.c. flux
− cos( ωt)
t ωTp Ts - t Φ = (e Tp - e Ts ) - sin ωt ˆ Φ a.c. Tp - Ts
t Tp
- t 2 ⋅ I p ⋅ e Tp
Φ max ˆ Φ a.c.
a.c. flux
ˆ a.c. Φ
Differential Protection Symposium
t
K td − max = 1 + ωTp = 1 +
Belo Horizonte November 2005
Xp Rp
G. Ziegler, 10/2005
page 57
Theoretical CT over-dimensioning factor KTF KTF
∞ (KTF ≈1+ωTN)
60 5000
Closed iron core
50 1000 40
TS
T N TS − TN KTF = 1+ ωTS TS
TS [ms] 500
30 250 20 100
Linear core
10 TN = network time constant (short-circuit time constant) 50
100
150
200
TN [ms] TS = CT secondary time constant
Differential Protection Symposium
Belo Horizonte November 2005
G. Ziegler, 10/2005
page 58
CT with closed iron core, Over-dimensioning factor KTF‘ for specified time to saturation (tM) 20
tM → ∞
tM
15
2.5 cycles
K‘td
2.0 cycles 10
1.5 cycles
8
1.0 cycles
−tTM Ktd' = 1+ ωTp ⋅ 1− e p
5
0.5 cycles
0
20
40
60
80
100
Tp (ms)
Differential Protection Symposium
Belo Horizonte November 2005
G. Ziegler, 10/2005
page 59
Transient dimensioning factor K’’td for short time to saturation tM
t − M T K td − Envelop = 1 + ωTp ⋅ 1 − e p
15
t − M ' K 'td (Θ, t M ) = ω ⋅ Tp ⋅ cos θ ⋅ 1 − e Tp
+ sin Θ − sin (ωt M + Θ )
3
15
2.5
Ktd( 0 , tM) 10
Ktd( 80 , tM)
2 1.5
Ktd( 90 , tM) Ktd_Envelop( tM)
5
1 0.5
0
0
0 0
20
40
60 tM
Differential Protection Symposium
80
100 100
0
0 0
1
2
3
4
Belo Horizonte November 2005
5 6 tM
7
8
9 10 10
G. Ziegler, 10/2005
page 60
CT over-dimensioning factor KTF (tM,TN) in the case of short time to saturation (tM)
KTF
4
tM
Θ (tM,TN)
10 ms
3.5
(el. degree)
180 160 140
3 8 ms
2.5
120 100
2 6 ms
1.5
tM 10 ms 8 ms 6 ms 4 ms 2 ms
80 60
1
4 ms
0.5
40 20
2 ms
0
0
20
40
60
80
100
0
0
20
40
80
100
TN in ms
TN in ms
Differential Protection Symposium
60
Belo Horizonte November 2005
G. Ziegler, 10/2005
page 61
Current transformer Magnetising and de-magnetising ΙP
B t
B
BMax BR
BMax BR Ιm t
Differential Protection Symposium
Belo Horizonte November 2005
Ιm
G. Ziegler, 10/2005
page 62
Current transformer Course of flux in the case of non-successful auto-reclosure B
t F1 = duration of 1st fault
Bmax
t DT dead time t F2 =duration of 2nd fault
t tF1
tDT
tF2
tF1 tDT + tF2 tF2 tF1 tF2 − − − − − Bmax ω ⋅ TN ⋅TS ω ⋅ TN ⋅ TS TS = 1 + (e TN − e TS ) ⋅ e (e TN − e T S ) + 1 + TN − TS TN − T S Bˆ ~
Differential Protection Symposium
Belo Horizonte November 2005
G. Ziegler, 10/2005
page 63
Current transformer Magnetising curve and point of remanence I
II
III
B up to about 80%
< 10% negligible
H = im ⋅ w I: closed iron core (TPX) II: core with anti-remanence air-gaps (TPY) III: Linearised core (TPZ)
Differential Protection Symposium
Belo Horizonte November 2005
G. Ziegler, 10/2005
page 64
Current transformers TPX und TPY Course of the flux with non-successful auto-reclosure
BR
BR tF1
tDT
Differential Protection Symposium
tF2
closed iron core (TPX)
core with antiremanence air-gaps (TPY)
t
Belo Horizonte November 2005
G. Ziegler, 10/2005
page 65
Current transformer with linear core (TPZ), Course of the flux with non-successful auto-reclosure ΙP
t
ΙS B
Ιm t tF1
Differential Protection Symposium
tDT
tF2
Belo Horizonte November 2005
t
G. Ziegler, 10/2005
page 66
Dimensioning of CTs for protection application Rated CT burden: PN Internal CT burden: Pi=Ri ⋅ I2N2
Pi + P N Ri + RN ALF' = ALF ⋅ = n⋅ Pi + PB Ri + RB
Actually connected burden :
P + PB Ri + RB = ALF'⋅ ALF = ALF' ⋅ i Pi + PN Ri + RN
I with ALF ' ≥ K OD ⋅ SC IN
with:
Theory:
No saturation for the specified time tM:
K OD ≥ KTF ⋅ K Re m K Re m = 1 +
% remanence 100
Differential Protection Symposium
RB=RL+RR= total burden resistance RL= resistance of connecting cable RR= relay burden resistance
No saturation during total fault duration:
Where KOD is the total over-dimensioning factor:
Practice:
K OD = KTF
PB= RB ⋅ I2N2
BMax XN = 1 + ω TN = 1 + RN Bˆ ~ tM tM − − ω ⋅ T N ⋅ TS (e T N − e T S K ' 'TF = 1 + TN − TS
K' TF =
Remanence only considered in extra high voltage systems (EHV) KTF-values acc. to relay manufacturers‘ guides
Belo Horizonte November 2005
G. Ziegler, 10/2005
page 67
Practical CT dimensioning using dimensioning factors Ktd (required minimum time to saturation) IEC 60044-1 and 60044-6
ANSI C57.13
300/5 A, 5P20, VA (Rb= 1.0 Ω), Rct= 0.15 Ω
300/5 A, C100 (Rb= 1 Ω)
E al ≈ (U ANSI + 20 ⋅ 5 ⋅ Rct )
= (20 ⋅ 5 ⋅ Z b − rated + 20 ⋅ 5 ⋅ Rct )
ALF' ≥ K SSC ⋅ K td ALF' =
R ct + R b − rated ⋅ ALF R ct + R b − connected
20 ≥ K td ⋅
I R + R b − connected ALF ≥ K td ⋅ F − max ⋅ ct I pn R ct + R b − rated
Transient dim. factor: Ktd
BS 3839 (IEC: 60044-1 addendum)
I E al = F − max ⋅ K td ⋅ (R ct + R b − con. ) ⋅ Isn − CT I pn U KN ≈ (0.8...0.85) ⋅ E al
Differential Protection Symposium
I F − max R ct + R b − connected ⋅ I pn R ct + R b − rated
No saturation:
1+X/R =1+ω·Tp
Differential relays:
1 (87BB: 0.5)
Distance relays:
2 to 4 close-in faults 5 to 10 zone end
faults O/C relays: I>> ALF‘ > (I>>set / In) Belo Horizonte November 2005
G. Ziegler, 10/2005
page 68
Coordination of CTs and digital relays Summary ü Digital relays use intelligent algorithms and are therefore highly tolerant against CT saturation. ü In particular differential relays allow short time to saturation of ¼ cycle and below. ü Determination of transient dimensioning factors for short time to saturation must consider the real flux course after fault inception. ü With time to saturation < 10 ms, the critical point on wave of fault inception is not close to voltage zero-crossing (fully offset current), but varies and is closer to voltage maximum (a.c. current). ü CT dimensioning is normally based on relay specific Ktd factors provided by manufacturers ü In practice, fully offset s.c. current has been assumed while remanence has been widely neglected for CT dimensioning. ü A new dimensioning factor is discussed in CIGRE WG B5.02, composed of more probable transient and remanence factors. Differential Protection Symposium
Belo Horizonte November 2005
G. Ziegler, 10/2005
page 69
CT dimensioning for differential protection (1) 1. Calculation of fault currents 110/20 kV F1 40 MVA 110 kV, 3 GVA uT=12%
F2
OH-line: l = 8 km, zL‘= 0,4 Ω/km
F3
Net 300/1A
7SD61
7UT61
Impedances related to 20 kV:
Impedances related to 110 kV:
Transf. :
∆ IL
∆ IL
∆ IT
Net :
200/1A
200/1A
1200/1A
F4
U N 2 kV 2 110 2 ZN = = = 4.03 Ω S SC ' ' [MVA ] 3000
Net :
U N 2 kV 2 uT [% ] 110 2 12 % ZT = ⋅ = ⋅ = 36.3 Ω PN -T [MVA ] 100 40 100
Transf. :
U N 2 kV 2 20 2 ZN = = = 0.13 Ω SSC ' ' [MVA ] 3000 U N 2 kV 2 uT [% ] 20 2 12 % ZT= ⋅ = ⋅ = 1.2 Ω PN - T [MVA ] 100 40 100
Line : Z L = l[km ] ⋅ z L ' [Ω/km ] = 8 ⋅ 0,4 = 3,2 Ω
Differential Protection Symposium
Belo Horizonte November 2005
G. Ziegler, 10/2005
page 70
CT dimensioning for differential protection (2)
F1
I F1 =
1.1 ⋅ U N / 3 1.1 ⋅ 110kV/ 3 = = 17.3 kA ZN 4.03 Ω
F2
I F2 =
1.1 ⋅ U N / 3 1,1 ⋅ 110kV/ 3 = = 1.73 kA Z N + ZT 4.03 Ω + 36.3 Ω
F3 I F3 = F4
I F4 =
1.1 ⋅ U N / 3 1.1 ⋅ 20kV/ 3 = = 9.55 kA Z N + ZT 0.13Ω + 1.2Ω
1.1 ⋅ U N / 3 1,1 ⋅ 20kV/ 3 = = 2.8 kA Z N + Z T + Z L 0.13Ω + 1.2Ω + 3.2Ω
Dimensioning of the 110 kV CTs for the transformer differential protection: Manufacturer recommends for relay 7UT61:
1) Saturation free time ≥ 4ms for internal faults 2) Over-dimensioning factor KTF ≥ 1,2 for through flowing currents (external faults)
The saturation free time of 3 ms corresponds to KTF≥ 0,75 See diagram, page 59 Criterion 1) therefore reads:
I 17300 ALF' ≥ K TF ⋅ F1 = 0,75 ⋅ = 43 IN 300
For criterion 2) we get: I 1730 ALF' ≥ K TF ⋅ F2 = 1,2 ⋅ =7 IN 300
The 110 kV CTs must be dimensioned according to criterion 1).
Differential Protection Symposium
Belo Horizonte November 2005
G. Ziegler, 10/2005
page 71
CT dimensioning for differential protection (3) We try to use a CT type: 300/1, 10 VA, 5P?, internal burden 2 VA.
ALF ≥
Pi + Poperation 2 + 2.5 ⋅ ALF ' = ⋅ 43 = 16.1 (Connected burden estimated to about 2.5 VA) Pi + Prated 2 + 10
Chosen, with a security margin : 300 /1 A, 5P20, 10 VA, R2≤ 2 Ohm (Pi ≤ 2VA) Specification of the CTs at the 20 kV side of the transformer: It is good relaying practice to choose the same dimensioning as for the CTs on the 110 kV side: 1200/1, 10 VA, 5P20, R2≤ 2 Ohm (Pi ≤ 2VA) Dimensioning of the 20 kV CTs for line protection: For relay 7SD61, it is required: The saturation free time of 3 ms corresponds to KTF≥ 0.5 See diagram, page 59 Criterion 1‘) therefore reads: I 9550 ALF' ≥ K TF ⋅ F3 = 0.5 ⋅ = 24 IN 200
1‘) Saturation free time ≥ 3ms for internal faults 2‘) Over-dimensioning factor KTF ≥ 1.2 for through flowing currents (external faults)
For criterion 2‘) we get:
I 2800 ALF' ≥ KTF ⋅ F4 = 1.2 ⋅ = 16 .8 IN 200
The 20 kV line CTs must be dimensioned according to criterion 1‘).
Differential Protection Symposium
Belo Horizonte November 2005
G. Ziegler, 10/2005
page 72
CT dimensioning for differential protection (4)
For the 20 kV line we have considered the CT type: 200/5 A, 5 VA, 5P?, internal burden ca. 1 VA
Pi + Poperation 1+1 ⋅ ALF ' = ⋅ 24 = 8 ALF ≥ Pi + Prated 1+ 5
(Connected burden about 1 VA)
Specification of line CTs: We choose the next higher standard accuracy limit factor ALF=10 : Herewith, we can specify: CT Type TPX, 200/5 A, 5 VA, 5P10, R2≤ 0.04 Ohm ( Pi≤ 1 VA)
Differential Protection Symposium
Belo Horizonte November 2005
G. Ziegler, 10/2005
page 73
Interposing CTs, Basic versions
w1
i1
separate winding connection
i2
i1
w2
wa
i2
wb
i1 -i2
Relay
i2 =
w1 ⋅ i1 w2
auto-transformer connection Relay
i2 =
wb ⋅ i1 wa + wb
No galvanic separation!
Differential Protection Symposium
Belo Horizonte November 2005
G. Ziegler, 10/2005
page 74
Interposing CTs, Example
1A W1= 21 turns
600/1 A
1A
600/1 A
Differential Protection Symposium
1,5 A W2= 14 turns
1A
Wa=16 turns
0,5 A
Wb=32 turns
RB
1,5 A
RB
Belo Horizonte November 2005
G. Ziegler, 10/2005
page 75
Interposing CTs in Y-∆-connection
Yd5
-I1c
I1a
I2a-c
I1b
I2b-a I2c-b
I1c
w1
I2a
I1a
-I1b
I2c
I1b I1c
w1 = w2
w2 I1 =
Differential Protection Symposium
150O
I2b I2b
I2c
-I1a I2a
o 1 w ⋅ I 2 ⋅ 2 ⋅ e j ⋅( n⋅30 ) w1 3
Belo Horizonte November 2005
G. Ziegler, 10/2005
page 76
False operation during external fault of transformer differential protection without zero-sequence current filter
L1 L2 L3
∆I
Differential Protection Symposium
∆ I
∆I
∆I>0 without delta winding!
Belo Horizonte November 2005
G. Ziegler, 10/2005
page 77
Zero-sequence current filter
I1a
I3a
I2a
I1b
I3b
I2b
I1c
I3c
I2c
I 1a ⋅ w1 + I 2a ⋅ ww2 + I 3a ⋅ w3 = 0 I 1b ⋅ w1 + I 2b ⋅ ww2 + I 3b ⋅ w3 = 0 I 1c ⋅ w1 + I 2c ⋅ ww2 + I 3c ⋅ w3 = 0 I 3a = I 3b = I 3c I 2a + I 2b + I 2c = 0
Differential Protection Symposium
Relay
I w I +I +I I 3a = I 3b = I 3c = 1 ⋅ 1a 1b 1c = E w3 3 3 I +I +I w I 2a = 1 I 1a − 1a 1b 1c w2 3 I 1a + I 1b + I 1c w1 I 2b = I − 3 w2 1b I +I +I w I 2c = 1 I 1c − 1a 1b 1c 3 w2 Belo Horizonte November 2005
G. Ziegler, 10/2005
page 78
Biasing of transformer differential protection during external earth fault with zero-sequence current filter (closed delta winding)
L1 L2 L3
With delta winding: ∆I=0 !
Differential Protection Symposium
∆I
∆ I
∆I
Belo Horizonte November 2005
G. Ziegler, 10/2005
page 79
Current matching with interposing CTs (1) Calculation example 110 kV ±16% L1
75 / 1 A
Yd5
6.3 kV
53.9A
915A
1200 / 5 A
L2 L3 0.719A
3.81A
∆I
3,81 = 2,20 3
Differential Protection Symposium
∆I
∆I
In-Relay = 5A
Belo Horizonte November 2005
G. Ziegler, 10/2005
page 80
Current matching with interposing CTs (2) Calculation example Current transformation ratio: We take through flowing rated current as reference: : 110kV-side: Mean current value of upper and lower tap changer position:
I1 =
10,000kVA = 45.2A 3 ⋅ (110kV + 16%
6 kV-side:
I2 =
10,000kVA = 62.5A 3 ⋅ (110kV − 16%
I1' =
I1− mean =
45.2 + 62.5 = 53.9A 2
10.000kVA = 915A 3 ⋅ 6.3kV
The corresponding secondary currents are:
i1 = 53 . 9 ⋅
1 = 0 . 719 A 75
and
i 2 = 915 ⋅
5 = 3.813 1200
. The current in the star connected winding of the interposing transformer is The current in the delta connected winding is:
i.1
i2 / 3 .
The ratio of the interposing CT must be :
w1 i 2 / 3 3.813 / 3 2.202 = = = = 3.06 w2 i1 0.719 0.719
Differential Protection Symposium
Belo Horizonte November 2005
G. Ziegler, 10/2005
page 81
Link selectable interposing CT 4AM5170-7AA
P1
S1
i2
A B C DE
1 0,013
2
F G H I
7
0,025 0,08
S2
P2
i1
K L
M N O P Q
16
1
2
7
16
Windings
0,75
0,013
0,025
0,08
0,75
R in Ohm
2
4
14
32
2
4
14
32
U-max. in V
5
5
5
1
5
5
5
1
Rated current in A
w1 i2 / 3 3,813 / 3 2, 202 = = = = 3.06 w2 i1 0,719 0,719
chosen :
w1 16 + 16 + 2 34 = = = 3,09 w 2 7 + 2 + 1 + 1 11 Connection and links as shown.
Differential Protection Symposium
Belo Horizonte November 2005
G. Ziegler, 10/2005
page 82
Designation of transformer or CT vector groups (1) Clock-wise notation according to IEC 60076-1
11
12 0
1
0
2
10 9
3 8
4 7 6
4 8
0
6
0
6
4
1 0
4
1 0
8
2
8
2
5 9 1 (13)
5
Differential Protection Symposium
Belo Horizonte November 2005
G. Ziegler, 10/2005
page 83
Designation of transformer or CT vector groups (2) Clock-wise notation according to IEC 60076-1, examples
I
II
III
12
I
II
12
III
I
I
III II
III II
HS
I I
II
III
NS
II
12
III
11 12 I III II
I III II I
II
III
Dyn11
12 II
III I 5
Yny0d5
Differential Protection Symposium
Belo Horizonte November 2005
G. Ziegler, 10/2005
page 84
Frequently used vector groups (IEC 60076-1)
Differential Protection Symposium
Belo Horizonte November 2005
G. Ziegler, 10/2005
page 85
Finding the vector group by using the clock principle
Proceed in the following steps: 1. Starting on the high voltage winding, the phase connection terminals are numbered with 0, 4, 8 (always 4 x 30 O= 120O phase shift). 2. The opposite end of each winding is labelled with a number incremented by +6 relative to the phase connection (6x 30 O =180O). 3. The secondary windings are numbered the same. In this context it is assumed that the polarity of the windings is the same in the diagram. (If in doubt, polarity marks may also be applied.) 4. The phase connection is labelled with the average value of the corresponding terminal designations belonging to the winding terminals connected to this phase terminal, e.g. (6+4)/2= 5 5. The difference between the high and low voltage side terminal numbers of same phases corresponds each with the vector group number, being Yd5 in this case.
Differential Protection Symposium
Belo Horizonte November 2005
G. Ziegler, 10/2005
page 86
Checking the connections of transformer differential protection using the clock-wise notation method
Yd5 L1 L2 L3
6
0
10 4 2
0
6
0
6
5
4
10
4
10
9
5 11
8
2
8
2
1
9
3
1
7
8
6
12
6
12 11
10
4 8
10
4 3
2
8 7
2
Yd5
Differential Protection Symposium
∆I
∆I
∆I
Belo Horizonte November 2005
G. Ziegler, 10/2005
page 87
Current distribution in Y-∆-transformer circuits for different external fault types
3
1
3
G
G
G
3 1
Differential Protection Symposium
Belo Horizonte November 2005
G. Ziegler, 10/2005
page 88
Checking the connections of transformer differential protection using the arrow method (two-phase fault)
Yd5
1
3
L1
3
L2 L3 3 3
= 3
3
∆I
∆I
Differential Protection Symposium
∆I
3
Dy5
Belo Horizonte November 2005
G. Ziegler, 10/2005
page 89
Checking the connections of transformer differential protection using the arrow method (single-phase earth fault)
Yd5
1
L1 L2 L3
∆I
∆I
Differential Protection Symposium
∆I
3
Dy5
3
Belo Horizonte November 2005
G. Ziegler, 10/2005
page 90
Digital Differential Protection Communications Gerhard Ziegler
Differential Protection Symposium
Belo Horizonte November 2005
G. Ziegler, 10/2005 page 87
Comparison protection Absolute selectivity by using communication
IA
A
IB
B
• Directial comparison distance protection Exchange of YES/NO signals (e.g. fault forward / reverse) • Current comparison (phasors) differential protection
Protection Relay
Communication samples, phasors, binary signals
| ∆I |
Protection Relay
IA
IB
| ∆I | = | IA - IB | > Ipick-up
Differential Protection Symposium
Belo Horizonte November 2005
G. Ziegler, 10/2005 page 88
Signal transmission channels for differential relaying Pilot wires - AC (50/60 Hz), voice frequency and digital communication (128 - kbit/s) - for short distances (< about 20 km) - influenced by earth short-circuit currents! Optical fibres - wide-band communication (n · 64 kbit/s) - digital signal transmission (PCM) - up to about 150 km without repeater stations - noise proof Digital microwave channels 2 - 10 GHz - wide-band communication (n · 64 kbit/s) - digital signal transmission (PCM) - up to about 50 km (sight connection) - dependent on weather conditions (fading) Differential Protection Symposium
Belo Horizonte November 2005
G. Ziegler, 10/2005 page 89
Analog pilot wire differential relaying
3
3
87L
87L
• Pilot wires are normally operated insulated form earth • Voltage limiters (glow dischargers) connected to earth , as used with telephone lines, are not allowed!
Differential Protection Symposium
Belo Horizonte November 2005
G. Ziegler, 10/2005 page 90
Relay-to-Relay pilot wires communication New technology on existing (copper-) pilots Traditional:
Composed current measurement Comparison of analogue values
Modern:
E
O
O
E
Phase segregated measurement
Digital data transmission 64 kbps bi-directional 4 value digital code (2B1Q) Amplitude and phase modulation Spectrum mid frequency: 80 kHz
Differential Protection Symposium
Belo Horizonte November 2005
G. Ziegler, 10/2005 page 91
Wire pilot cables Longitudinal voltage induced by earth currents Relay B
Relay A
G IF
Φ E
F1
E/2 F2
Differential Protection Symposium
A) Symmetrical coupling along the pilot cable
E/2
F2
F1
E
Belo Horizonte November 2005
B) Unsymmetrical Coupling along the pilot cable
G. Ziegler, 10/2005 page 92
Disturbance voltage caused by rise in station potential
RG STP STP
E Ω = I SC − G ⋅ R G
PGA RGP Legend: RG STP PGA RGP E
station grounding resistance station potential potential gradient area remote ground potential station potential rise against remote ground (ohmic coupled disturbance voltage )
Differential Protection Symposium
Belo Horizonte November 2005
G. Ziegler, 10/2005 page 93
HV insulated protection pilot cable (example) core diameter
pilot resistance Core Loop
pilot capacitance
mm
Ω/km
Ω/km
nF/km
1,4 0,8
11,9 ---
--73,2
--60
test voltage (r.m.s. value) triple pair pair to core- coretriple to core core shield core pair to triple core kV kV kV kV kV 2,5 8 8 8 2 2 2
Symmetry: better 10–3 (60 db) at 800/1000 Hz better 10–4 (80 db) at 50/60 Hz (Uq <10–4·Ul)
Differential Protection Symposium
Belo Horizonte November 2005
G. Ziegler, 10/2005 page 94
American practice Neutralising reactor to compensate potential rise at the station Gas tube Relay neutralising reactor Relay potential gradient potential at insulating transformer and relay Voltage profile at the neutralising reactor
Differential Protection Symposium
potential of the pilot wires
Belo Horizonte November 2005
potential of the remote earth
G. Ziegler, 10/2005 page 95
Optic fibre (OF) Cable
Differential Protection Symposium
Belo Horizonte November 2005
G. Ziegler, 10/2005 page 96
Optic fibers and connectors Multi-mode fiber (IEC 793-2) Type 62.5 / 125 µm for 850 and 1300 nm Cladding
Mono-mode fiber (IEC 793-2) Type 10/125 µm for 1300 and 1550 nm ST connector
Core
Coating
62,5 µm 125 µm 250 µm
Refractive index
LC connector
Differential Protection Symposium
10 µm 125 µm 250 µm
Belo Horizonte November 2005
G. Ziegler, 10/2005 page 97
Optic fibres: Principle of light wave propagation r
n2 n1 rL n
A) Graded index fibre
AA
AE γA
t
EingangsInput impulse
Output impulse
impuls
Refractive index profile
r
B) Mono-mode fibre
Geometric design
Wave propagation
n2 n1 r L
AE
AA
n t
t EingangsInput impulse impuls
Differential Protection Symposium
Belo Horizonte November 2005
Output impulse
G. Ziegler, 10/2005 page 98
Optic attenuation of a mono-mode fibre
10,0 5,0
Attenuation (dB/km)
Infrared absorption
1,0
Rayleigh dispersion 0,85
0,1 0,8
1,3 1,0
1,2
1,55 1,4
1,6
1,8
Wave length (µm)
Differential Protection Symposium
Belo Horizonte November 2005
G. Ziegler, 10/2005 page 99
Optic fibre connections: Coarse planning rules Optic component:
Attenuation:
Mono-mode fibre at 1300 nm
αOFC = 0.45 dB/km
at 1550 nm
αOFC = 0.30 dB/km
at 850 nm
αOFC = 2,5 to 3,5 dB/km
at 1300 nm
αOFC = 0.7 to 1.0 dB/km
Gradient fibre
αSPL = 0.1 dB
Per splice Per connector
Reserve
FSMA
αCON = 1.0 dB
FC
αCON = 0.5 dB αRES = 0.1 to 0.4 dB/km
Total attenuation of the OF cable system:
αTOT = l ⋅ αOFC + n ⋅ αSPL + 2 ⋅ αCON + l ⋅ αRES Differential Protection Symposium
Belo Horizonte November 2005
G. Ziegler, 10/2005 page 100
Optic Fibre signal transmission system: Calculation example Task:
Optic fibre signal transmission device 7VR500 Estimation of maximum reach
Given:
Device data:
Seached:
Maximum distance that can be bridged
Solution:
The cable length is: l=x⋅2 km The number of splices is: n=x-1 The admissible system attenuation: −14− (−46)=32 dB Therefore: dB dB 32dB = x ⋅ 2km ⋅ 0,45 + ( x − 1) ⋅ 0,1dB + 2 ⋅ 0,5dB + x ⋅ 2km ⋅ 0,2 km km
Sending power of laser diode: αS= –14 dB Minimum reception power: αE= -46 dB Optic wave length: 1300 nm The optic fibre cable is shipped in sections of each 2 km. For reserve, 0.2 dB/km have been chosen.
we get:
x=22 and l=44 km
Differential Protection Symposium
Belo Horizonte November 2005
G. Ziegler, 10/2005 page 101
Radio (Micro-wave) Signalling
repeater station
terminal station
radiolink
terminal station
• Line-of-sight path (up to about 50 km without repeater) • 150 MHz to 20 GHz, n times 4 kHz channels analog and n times 64 (56) kbit/s digital (PCM) • Advantage: Independent of line short-circuit and switching disturbances • Disadvantage: Fading and reflections during bad weather conditions Additional pilot links necessary to sending/receiver stations
Differential Protection Symposium
Belo Horizonte November 2005
G. Ziegler, 10/2005 page 102
Digital communication
u Wide-band communication via optic fibre or digital microwave u n times 64 (56) kbit/s channels u pulse code modulation (PCM) u transmission via dedicated channels or communication network u access through time division multiplexers u interface standard for synchronous data transmission: CCITT G.703 or X.21 (wired connection) u interface standard for asynchronous data transmission: V.24/V.28 to CCITT or RS485 to EIA (wired connection)
Differential Protection Symposium
Belo Horizonte November 2005
G. Ziegler, 10/2005 page 103
Function sequence of message transmission Sending side
Message Digital coding Segmentation into information blocks
wide band transmission
Error control Parallel-to-serial conversion
modulation block synchronisation
Differential Protection Symposium
coding base band transmission
Belo Horizonte November 2005
G. Ziegler, 10/2005 page 104
Structure of a remote control telegram
Start
Control
Start sign
Kind of telegram
Block limit
Transmission cause
Identification
Information
Error check
Address
User data
Checking
Origin
Measuring values
Check bits
Destination
Telegram length
Status
etc.
Commands
End
End sign
etc.
Information field Block length Transmitted frame
Differential Protection Symposium
Belo Horizonte November 2005
G. Ziegler, 10/2005 page 105
Digital communication Synchronous transmission mode • all bits follow a fixed time frame • synchronism between sending and receiving station. (separate clocking line or signal codes with clock regain) • block (frame) synchronising by opening and closing flags • suitable for high data rates • used protocol: HDLC (high-level data link control) • cyclic redundancy check (CRC) or frame check sequence (FCS) by 16 or 32 added check-bits (probability of non-detected telegram block errors: 10–5 (CRC-16) or 10–10 (CRC-32)) • used for high speed teleprotection
HDLC telegram frame format to ISO 3309:
Opening Flag
Address Field
Control Field
01111110
8 or more bits
8 or 16 bits
Differential Protection Symposium
Information Field any length
Belo Horizonte November 2005
Frame Check FCS
Closing Flag
16 or 32 bits
01111110
G. Ziegler, 10/2005 page 106
Multiplexing Frequency Multiplexing f1 f2 Coded voice tones 300 to 4000 Hz
FC +f1+f2
M U X
Carrier frequency, FC e.g. 100 kHz with PLC
M U X
f1 f2
FC
Time Divison Multiplexing (TDM) 125 µs M U X
64 kbit/s channels
Clock
M U X
> 2 Mbit/s
Differential Protection Symposium
Clock Belo Horizonte November 2005
G. Ziegler, 10/2005 page 107
Communication through transmission networks
M U X
A User / Source
Modem Network node circuit / packet switching trunk
Modem
Station user terminal point
M U X
line Transmission path
B loop
Differential Protection Symposium
User / Destination
Belo Horizonte November 2005
G. Ziegler, 10/2005 page 108
Structure of a modern data communication network
622 Gbit/s
ØNetworks are plesiochronous (PDH), synchronous (SDH) or asynchronous (ATM) ØData terminal devices (e.g. relays) are synchronised through the network ØRings guarantee redundance. ØData of different services (e.g. telephone and protection are commonly transmitted (time multiplexed) ØProtection relays must be adapted to the given network conditions (e.g. changing propagation time due to path witching.
622 Gbit/s
POTS: Plain Old Telephone Services ISDN: Integrated Services Digital Network STM-n: Synchronous Transport Module level n SMA: Synchronous Module Access ATM: Asynchronous Transmission Mode ISP: Internet Service Provider
Differential Protection Symposium
Belo Horizonte November 2005
G. Ziegler, 10/2005 page 109
Comparison of Switching Methods Circuit Switching
Packet switching
The physically assigned channel is established before and disconnected after communication
Data stream is segmented to packets
POT (Plain old telephony), ISDN Digital networks on basis of PCM with plesiochronous digital hierarchy (PDH) Reliable and fast transmission possible when connection is established. Circuit establishment requires a free channel from A to B Connection occupies channel also when no data is exchanged Deterministic data transmission (fixed data transmission time per channel)
Differential Protection Symposium
Transmission runs connection-oriented or connection-less Synchronous digital hierarchy (SDH), ATM Backbone Cannel not occupied during whole connection time Channels can be used quasi-simultaneously Data transmission by principle time is random. SDH and ATM can provide virtual circuitswitched channels. However, split path signal routing may however result in unsymmetrical signal transmission times.
Belo Horizonte November 2005
G. Ziegler, 10/2005 page 110
SDH network: Split path routing
Node F
Node E
Node D
Standby path
Node A tP2‘ Node B Relay End 1
Differential Protection Symposium
tP1
Node C
tP1‘
tP2 Healthy path
Relay End 2
Belo Horizonte November 2005
G. Ziegler, 10/2005 page 111
Digital Transport Systems: Bundling of channels PCM 7680
PDH Hierarchy
PCM 1920
Plesiochronous (almost synchronous) PCM 480 PCM 120 PCM 30
M U X
M U X
M U X
M U X
M U X
565 Mbit/s
140 Mbit/s
32 Mbit/s
8 Mbit/s
2 Mbit/s
64 kbit/s
SDH Hierarchy Synchronous SMT-1 155 Mbit/s
SMT-4 622 Mbit/s
1
SMT-16 2.5 Gbit/s 1 2
1 2
2 3
3
3 4
Differential Protection Symposium
SMT-64 10 Gbit/s 1
4
4 Belo Horizonte November 2005
G. Ziegler, 10/2005 page 112
PDH (Plesiochronous Digital Hierarchy)
Multiplexing structure: ØBase rate 64 kbit/s (digital equivalent of analogue telephone channel) ØEquipments may generate slightly different bit rates due to independent internal clocks ØBit stuffing is used to bring individual signals up to the same rate prior to multiplexing (Dummy bits are inserted at the sending side and removed at the receiving side) ØIntermediate inserting and extracting of individual channels is not possible, but the full multiplexing range has always to be run through. Hierarchical level 0 1 2 3 4
Europe 64 kbit/s 2‘048 Mbit/s 8‘448 Mbit/s 34‘368 Mbit/s 139‘264 Mbit/s
Differential Protection Symposium
USA 56 kbit/s 1‘544 Mbit/s 6‘312 Mbit/s 44‘736 Mbit/s 139‘264 Mbit/s
Belo Horizonte November 2005
G. Ziegler, 10/2005 page 113
SDH (Synchronous Digital Hierarchy) Multiplexing structure Ø SONET (Synchronous Optical Network) first appeared in USA (1985) Ø ITU-T (formerly CCITT) issued B-ISDN as world wide standard (1988) Ø All multiplexing functions operate synchronously using clocks derived from a common source Ø Designed to carry also future ATM SDH STM level STM-1 STM-4 SZM-16 STM-64
Aggregate Rate 155,520 Mbit/s 622,080 Mbit/s 2‘488,320 Mbit/s 9‘953,280 Mbit/s
Differential Protection Symposium
SONET OC level
STS level
Aggregate Rate
OC-1 OC-3 OC-12 OC-48 OC-192
STS-1 STS-3 STS-12 STS-48 STS-192
51,840 Mbit/s 155,520 Mbit/s 622,080 Mbit/s 2‘488,320 Mbit/s 9‘953,280 Mbit/s
Belo Horizonte November 2005
G. Ziegler, 10/2005 page 114
ATM (Asynchronous Transfer Mode) and Broadband B-ISDN Features of ATM: Ø Synchronisation individually per packet
Voice Audio
Fax
Data
Video
Ø Packets carry each complete address of destination so that each can be separately delivered (Datagrams, here called Cells) Ø Information stream is segmented into cells that are 53 octets long Ø ATM sets up a virtual switched connection and sends data along a switched path from source to destination
ISDN
Ø Requirements on bandwidth, bounded delay and delay variation can be set by the user ØSingle cells can be inserted or removed at the nodes, as required Ø The predominant use is for net backbones
Differential Protection Symposium
Belo Horizonte November 2005
G. Ziegler, 10/2005 page 115
TDM over optical fiber
Hicom
FO MUX >2 Mbit/s L1-L2 21,3 KA 73,6 kW
I O
Optic fibres in the core of earth wires
x 64 kbit/s
V
Differential Protection Symposium
Belo Horizonte November 2005
G. Ziegler, 10/2005 page 116
Bit error rate (of data channels) Bit error rate:
p=
number of faulty bits total number of sent bits
Typical bit error rates of public services: Telephone circuits ca. 10 -5 Digital data networks (Germany) ca. 10 -6 to 10-7 Coaxial cables (LAN) ca. 10 -9 Fiber optic communication ca. 10 -12 Utility conditions (CIGRE SC34 Report 2001): Fiber optic communication ca. 10 -6 Data networks (PDH, SDH, ATM) ca. 10-6 Microwave ca. 10 -3 Requirements acc. to CIGRE report: Protection and control in general: < 10-6 Function guaranteed up to < 10 -3 however downgraded (reduced operating speed) Line differential protection < 10 -6 and < 10-5 during power system faults
Differential Protection Symposium
Belo Horizonte November 2005
G. Ziegler, 10/2005 page 117
Error detection methods: Cyclic redundancy check 01111110 Flag
01111110 Address
Control
I(x)
Data field
Check field
Flag
I(x) + R(x) Receiver
Sender
Division by G(x)
R(x) = CRC
error free data block
CRC 16: G(x) = X16 + X15 + X2 + 1 binary: 1 1000 0000 0000 0101 Reduction of the block failure rate by the factor > 10 -5 against the bit failure rate! (CRC 32: > 10-10)
Differential Protection Symposium
Division by G(x)
R(x) = 0
faulty data block
Belo Horizonte November 2005
G. Ziegler, 10/2005 page 118
Data integrity (line differential protection 7SD52/61)
Received data
Block failure rate P = 10-5
Error detection e.g. CRC = 32
Residual data
Block failure rate R = 10-15
Differential Protection Symposium
Belo Horizonte November 2005
G. Ziegler, 10/2005 page 119
Residual error rate
Residual error rate:
R=
number of not detected faulty telegrams (data blocks) total number of sent telegrams (data blocks)
Practical range of protection and control systems: Time between 2 not detected errors:
T=
R < 10 -10 to 10-15
n v⋅R
n= length of telegram (data block) v= transmission speed in bit/s
Example: Telegrams of n =200 bit are continuously transmitted at 64 kbit/s. R
T
10-7
20 hours
10-10
2.3 years
10-15
230000 years
typical application cyclic transmission (metering)
remote control and protection
Differential Protection Symposium
Belo Horizonte November 2005
G. Ziegler, 10/2005 page 120
Protection of a short line lines Differential relay using direct digital relay-to-relay communication
A
B
D 7SA6
D 7SA6
Communication via direct relay-relay connection Fibre type
optical wave length
maximum attenuation
permissible distance
Multi-mode 62.5/125 µm
820 nm
16 dB
ca. 3.5 km
Monomode 9/ 125 µm
1300 nm
29 dB
ca. 60 km
9/ 125 µm
1500 nm
29 dB
ca. 100 km
Differential Protection Symposium
Belo Horizonte November 2005
G. Ziegler, 10/2005 page 121
Line differential relaying using digital communication A
B
D 7SD52
D 7SD52 D 7SD52
Chain topology or redundant ring topology
typical <1.5 km multimode fibre 62.5/ 9/ 125 µm
C
O
Communication network
E
X21 or G703.1
Differential Protection Symposium
O
E
Communication converter
X21 or G703.1
Belo Horizonte November 2005
G. Ziegler, 10/2005 page 122
Differential protection with communication through data net l Microsecond exact time keeping in the relays Each relay has its individual time keeping n Sent and received telegrams get microsecond accurate time stamps n
l Special relay properties for network communication Measurement of propagation times and automatic correction 0 - 30 ms Detection of channel switching in the network Unique address for each relay (1 - 65525) to detect signal misdirection (channel cross-over of loop-back) Measurement of channel quality (availability, error rate)
l Change of the network path -> Adaptive add-on stabilisation Settable time difference to consider given data transmission asymmetry
l Adaptive topology recognition Automatic recognition of connections and remote end devices Automatic re-routing from ring to chain topology if one data connection fails In case of multi-terminal protection, remaining relay system continues operation if one line end is switched off and the relay is logged out for maintenance
Differential Protection Symposium
Belo Horizonte November 2005
G. Ziegler, 10/2005 page 123
Individual time references by synchro-phasors Definition of a synchrosynchro-phasor: phasor: SynchroSynchro-phasors, phasors, are phasors, phasors, which are measured at different network locations by independent devices and referred to a common time basis
Time reference iB
iA
Ort : A
Ort : B IM
IA
relay A
RE
IB relay B
Differential Protection Symposium
Belo Horizonte November 2005
G. Ziegler, 10/2005 page 124
Phasor synchronisation between line ends
A
tA1 tA2
∆I
∆I
curre n phas t o rs
tAR
tA5
B
α ...
tA1
tPT1
tB2
tBR
α=
tB3
tPT2 ...
tV tB3 tA1
nt curre rs ph aso
Signal transmission time: Sampling instant:
Differential Protection Symposium
IB( tB3 )
tB1 tD
tA3 tA4
IB( tA3 )
t B3 - t A3 ⋅ 360 ° TP
tB4
t PT1 = t PT2 =
1 (t A1 - t AR - t D ) 2
t B3 = t AR - tTP2 Belo Horizonte November 2005
G. Ziegler, 10/2005 page 125
Specification of data channel for line differential protection based on Cigre Report: Protection using Telecommunication *)
Data rate
64 kbit/s (min.)
Channel delay time:
< 5 ms
Channel delay time unsymmetry:
< 0.2 ms
Bit error rate normal:
< 10 -6
during power system fault Availability:
< 10-5 *) > 99.99 %
*) Report of WG34/35.11, Brochure REF. 192, Cigre Central Office, Paris, 2001, *) It is suggested that for a BER of less than 10-6 the dependability shall not suffer a noticeable deterioration . For a BER of 10-6 to 10-3 the teleprotection may still able to perform its function although a loss in dependability is to be expected.
Differential Protection Symposium
Belo Horizonte November 2005
G. Ziegler, 10/2005 page 126
Digital Protection of Generators and Motors Gerhard Ziegler
Differential Protection Symposium
Belo Horizonte November 2005
G. Ziegler, 10/2005
Seite 116
Generator differential protection
a a c
S
S S A
IA/In 3 2
S S A
1 S A
Connection circuit
Differential Protection Symposium
1
2
3
4
5
6
IS/In
Operating characteristic
Belo Horizonte November 2005
G. Ziegler, 10/2005
Seite 117
Generator HI differential protection
a b c
A
Differential Protection Symposium
A
A
Belo Horizonte November 2005
G. Ziegler, 10/2005
Seite 118
Transverse differential protection
a
b
c
S
S S
S S
A
Differential Protection Symposium
A
S A
Belo Horizonte November 2005
G. Ziegler, 10/2005
Seite 119
HI earth current differential protection
L1 L2 L3
∆IE>
Differential Protection Symposium
Belo Horizonte November 2005
G. Ziegler, 10/2005
Seite 120
Earth current differential protection for generators
L1 L2 L3
U0>
∆IE> Tripping
Differential Protection Symposium
Belo Horizonte November 2005
G. Ziegler, 10/2005
Seite 121
Motor starting current
20
IRush /IN
TRush
15
Tst 10
Ist/IN
5 0 5
0
50
100
150
200
250
300
tst (ms)
Differential Protection Symposium
Belo Horizonte November 2005
G. Ziegler, 10/2005
Seite 122
Transformer Differential Protection Gerhard Ziegler
Differential Protection Symposium
Belo Horizonte November 2005
G. Ziegler, 10/2005
page 123
Transformer: Function principle and equivalent circuits I1
w1
w2
I2
U1
Xσ1
R1
Φ
U2 Φ σ1
Φ σ2
U1
I1
I ⋅ w + I ⋅ w = I µ ⋅ w1 1 1 2 2
I µ << I 1, 2 '
Differential Protection Symposium
Xµ
R2 '
I2'
U 2'
Equivalent electric circuit
Equivalent electromagnetic circuit
At load and short-circuit:
Iµ
X σ 2'
RTK
U1
X TK
I1 = I 2 '
I1 ⋅ w1 = I 2 ⋅ w 2
U 2'
Belo Horizonte November 2005
X TK = X σ 1 + X σ 2 ' RTK = R1 + R 2 '
G. Ziegler, 10/2005
page 124
Typical Transformer data
kV/kV
Short-circuit voltage % UN
No-load magnetizing current % In
850
850/21
17
0.2
600
400/230
18.5
0.25
300
400/120
19
0.1
300
230/120
24
0.1
40
110/11
17
0.1
16
30/10.5
8.0
0.2
6.3
30/10.5
7.5
0.2
0.63
10/0.4
4.0
0.15
Rated power
Ratio
MVA
Differential Protection Symposium
Belo Horizonte November 2005
G. Ziegler, 10/2005
page 125
Transformer Inrush current
IRush
Flux
φ
φ φRem
Im
Inrush-current of a single phase transformer
U t
Source: Sonnemann, et al.: Magnetizing Inrush phenomena in transformer banks, AIEE Trans., 77, P. III, 1958, pp. 884-892
Differential Protection Symposium
Belo Horizonte November 2005
G. Ziegler, 10/2005
page 126
Inrush currents of a Y-∆-transformer Neutral of Y-winding earthed
ΦC
IA
ΦB ΦA
IB
I mC
ID
IC
I mA
Oscillogram: IA
5 1 I A = ⋅ I mA − ⋅ I mC 6 6
IA
IB
1 1 I B = − ⋅ I mA − ⋅ I mC 6 6
IB
IC
5 1 IC = ⋅ I mC − ⋅ I mA 6 6
IC
Source: Sonnemann et al. : Magnetizing Inrush phenomena in transformer banks, AIEE Trans., 77, P. III, 1958, pp. 884-892
Differential Protection Symposium
Belo Horizonte November 2005
G. Ziegler, 10/2005
page 127
Inrush current : Content of 2nd und 3rd harmonic I m (ν ) I m (1)
%
100 B
80
B
360O 60
I m (2) 40
I m (1)
I m (3) 20
I m (1) 90O
17,5%
180O
270O
360O Width of base B
240O
Differential Protection Symposium
Belo Horizonte November 2005
G. Ziegler, 10/2005
page 128
Inrush currents of a three-phase transformer recorded with relay 7UT51
Differential Protection Symposium
Belo Horizonte November 2005
G. Ziegler, 10/2005
page 129
Transformer Inrush current: Amplitude and time constant
ˆI Rush ˆI N
12
Rated power in MVA
time constant in seconds
8
0,5....1,0
0,16....0,2
6
1,0
0,2 .....1,2
10
10
>10
4
1,2 ....720
2
5
10
50
100
500
Rated transformer power in MVA
Differential Protection Symposium
Belo Horizonte November 2005
G. Ziegler, 10/2005
page 130
Sympathetic Inrush Wave form:
Transient currents:
I1
I
I1
I2
I2
IT IT I1
IT T1
G resistance
I2
Current circulating between transformers
Transformer being closed
G
RS
IT
Transformer already closed T2
Differential Protection Symposium
t
XS
Belo Horizonte November 2005
I1
I2 T1
T2
G. Ziegler, 10/2005
page 131
Transformer overfluxing
Deduction of wave form
Harmonic content Im
B 1,5
× 10 4 Gauß
U
1,0
% 100 80
I150/I50
60
I250/I50
40
I350/I50
I50/InTr
20 0
0,5
5
10
15 A Im
0
Differential Protection Symposium
10
100
120
20 ms
% 160
140
U/Un
t
Belo Horizonte November 2005
G. Ziegler, 10/2005
page 132
Vector group adaptation with matching CTs Current distribution with external ph-ph fault IR
I1
R
Ir
r
1
3
IS
I2
IT
I3
S
T
Is It
s
G
t
3 /1 87T
Differential Protection Symposium
87T
87T
Belo Horizonte November 2005
G. Ziegler, 10/2005
page 133
Vector group adaptation and I0-elimination with matching CTs Current distribution with external ph-E fault A B
Yd1
IA
Ia
r
IB
Ib
s
IC
Ic
t
C
G
cp
Ic = 3
IT=3
cn
3 /1
87T
87T
87T
Ia = 3
Cn
Cp
A0 B0 C0
30O
cp
cn
bp Bp
Ap
An
Bn
Differential Protection Symposium
ap
ap an
30O bn
an
Belo Horizonte November 2005
G. Ziegler, 10/2005
page 134
Traditional I0-elimination with matching CTs Current distribution in case of an external earth fault
a A b B c
C
87T
Differential Protection Symposium
G
87T
87T
Belo Horizonte November 2005
G. Ziegler, 10/2005
page 135
Traditional I0-elimination with matching CTs Current distribution in case of an internal earth fault
a A b B
G
c
C
! 87T
Differential Protection Symposium
87T
87T
Ø Sensitivity only 2/3 I F! Ø Non-selective fault indication!
Belo Horizonte November 2005
G. Ziegler, 10/2005
page 136
Traditional I0-correction with matching CTs Current distribution with external ph-E fault
a A b B
G
c
C
3/1
87T
Differential Protection Symposium
87T
87T
Belo Horizonte November 2005
G. Ziegler, 10/2005
page 137
Traditional I0-correction with matching CTs Current distribution with internal ph-E fault
a A b B
G
c
C
3/1
87T
Differential Protection Symposium
87T
87T
Belo Horizonte November 2005
G. Ziegler, 10/2005
page 138
Transformer differential protection, connection
L1
IA1
IB1
UA
L2
IA2
IB2
UB
(110 kV)
L3
IA3
IB3
(20 kV)
Digital protection contains: Adaptation to
7UT6
∆I
∆I
∆I
• Ratio UA / UB • Vector group
Software replica of matching transformers
Differential Protection Symposium
Belo Horizonte November 2005
G. Ziegler, 10/2005
page 139
Digital transformer protection Adaptation of currents for comparison (1) CT 1
JR-sec JS-sec JT-sec
W2
W1 JR-prim
Jr-prim
JS-prim
Js-prim
JT-prim
Jt-prim
N o r m
I N − Transf − W1 =
IR IS IT
IR* I0elim. IS* IT*
Comparison ∆I
SN
J R −sec I N − Prim − CT 1 IS = ⋅ J S −sec = kCT −1 ⋅ I N − Transf - W1 IT JT −sec
Differential Protection Symposium
It**
Vector group adapt.
Ir* Is* It*
I0elim.
Ir Is It
N o r m
I N − Transf − W2 =
3 ⋅ U N -1
IR
Ir** Is**
J R −sec J S −sec JT −sec
CT 2
Jr-sec Js-sec Jt-sec
SN 3 ⋅ U N -2
Ir J r − sec I N − Prim − CT 2 Is = ⋅ J s − sec = k CT − 2 ⋅ I N − Transf -W2 It J t − sec
Belo Horizonte November 2005
J r − sec J s − sec J t − sec
G. Ziegler, 10/2005
page 140
Digital transformer protection Adaptation of currents for comparison (2) CT 1
JR-sec JS-sec JT-sec
1 ⋅ (I R + I S + I T ) 3 IR * = IR − I0
W2
W1 JR-prim
Jr-prim
JS-prim
Js-prim
JT-prim
Jt-prim
N o r m
IR IS IT
IR* I0elim. IS* IT*
Com_ parison ∆I
I0 =
Ir** Is** It**
Vector group adapt.
Ir* Is* It*
I0elim.
Ir Is It
N o r m
IS * = IS − I0 IT * = IT − I0
I ∆ −T
IT *
Differential Protection Symposium
It **
Ir ** −1 0 1 1 Is ** = 1 −1 0 ⋅ 3 0 1 −1 It * *
Belo Horizonte November 2005
Jr-sec Js-sec Jt-sec
I0 =
Example Yd5:
I∆−R IR * Ir ** I∆−S = IS * + Is **
CT 2
Ir * Is * It *
1 ⋅ (I r + I s + I t ) 3
Ir * = Ir − I0 I s * = Is − I 0 I t * = I t − I0
G. Ziegler, 10/2005
page 141
Adaptation of currents for comparison Relay input data Input data: •n times 30O
vector group number (only for 2nd and 3rd winding, 1st winding is reference)
Winding 1 (reference) is normally: •High voltage side
•UN (kV)
Rated winding voltage
•SN (MVA)
rated winding power
•INW (A)
Primary rated CT current
At windings with tap changer:
•Line or BB
direction of CT neutral
UN = 2⋅
•Elimination / Correction / without
I0-treatment
•Side XX
Assignment input for REF
•INW S (A)
Primary rated current of neutral CT
•Neutral CT
Earth side connection to relay: Q7 or Q8?
Differential Protection Symposium
U max ⋅ U min U max + U min
Belo Horizonte November 2005
G. Ziegler, 10/2005
page 142
Digital transformer protection Current adaptation, Example (1) SN = 100 MVA UN1= 20 kV W2
3000/5 A
UN2= 110 kV
Yd5
W1
600/1 A 2.400 A
7621 A
1A 5A
Differential Protection Symposium
∆I
Belo Horizonte November 2005
G. Ziegler, 10/2005
page 143
Digital transformer protection Current adaptation, Example (2) 110-kV-side
20-kV-side
I N − Trafo − W2 =
100MVA = 2887A 3 ⋅ 20kV
I N − Trafo − W1 =
1 3 = 4,4 3 A ⋅ 13200 3000 3000 3A I Norm = ⋅ 4,4 3 = 4,57 2887 J r,s, t - sek =
J R, S, T -sek = I Norm =
4,57
I A − S = I S * + I s * * = − 2 ⋅ 4,57 I A −T = IT * + I t * * =
Differential Protection Symposium
1 ⋅ 2400 = 4,0 A 600
600 ⋅ 4 = 4,57A 525
Vector group adaptation: Yd5 Ir * 2 −1 −1 0 4 ,57 3 1 I s * = ⋅ − 1 2 − 1 ⋅ − 4,57 = − 2 ⋅ 4 ,57 3 3 It * −1 −1 2 0 4 ,57 3
I0-elimination: Ir ** −1 0 1 4,57 3 − 4,57 / 3 1 Is ** = 1 − 1 0 ⋅ − 4,57 3 = 2 ⋅ 4,57 / 3 3 It ** 0 1 −1 0 − 4,57 / 3
IA −R = IR * + I r * * =
100MVA = 525A 3 ⋅ 110kV
4,57
3 − 4,57
3
3 + 2 ⋅ 4,57 3 − 4,57
=0 3=0
3
=0
Belo Horizonte November 2005
G. Ziegler, 10/2005
page 144
Current adaptation (1) Practical example for the need of matching CTs *)
Matching CTs recommended, if k_Wan_n > 4 or k_Wan_n < 1/4: *)
To keep the specified measuring accuracy of 7UT51. For protectio n only necessary if 8
345 kV, 1050 MVA
1500/5 A
2000/5 A
500 kV, 1050 MVA
1213 A (1050 MVA)
1000/1 A 43.930 A (1050 MVA) 4,04 A 43,43 A
13,8 kV, 30 MVA
1/0.2A 8,786
7UT513 (5A Relay)
Differential Protection Symposium
k CT _ 3* =
8,786 = 1,76 < 4! 5
Belo Horizonte November 2005
G. Ziegler, 10/2005
page 145
Current adaptation (2) Practical example for the need of matching CTs I n −Tr −W 1 = I
1050 ⋅103 3 ⋅ 500
n −Tr −W 1−sec =
1213A = 4,04 A 1500 / 5
4.04 kCT −1 = = 0,809 5 I n −Tr −W 2 = I
1050 ⋅ 103 3 ⋅ 345
n −Tr −W 2− sek =
kCT − 2 =
40·In= 15 Bit +sign = 215 = 32.768 32.768
15
40·In
1
0,122%In
32.36
351,44
= 1757 A
1757 A = 4,39 A 2000 / 5
1050 ⋅103 3 ⋅13,8
n −Tr −W 3 _ sek =
kCT −3 =
Transformer winding 3
4,39 = 0,878 5
I n −Tr −W 3 = I
Transformer winding 1
Relay
= 1213A
= 43.930 A
43.930 A = 43,93 A 1000 / 1
43,93 = 8,786 > 4! 5
Differential Protection Symposium
0,099%
Belo Horizonte November 2005
1,072% G. Ziegler, 10/2005
page 146
7UT6 Operating characteristic
5
I
ST
F = IF
7UT6
7 6
I DIFF >>
AB
8
ID
IDiff/ In
I2
I1
9
IDIFF = |I1+ I2| Tripping area
IStab = |I1| + |I2|
4
2 e op Sl
3
Stable operation
2
Slope
1
I DIFF > 0 0
1
2
Additional stabilisation for high Is.c.
1 3
Differential Protection Symposium
4
5
6
7
8
9
10
Belo Horizonte November 2005
11
Istab / In
G. Ziegler, 10/2005
page 147
I0-elimination / correction: Summary
è I0- elimination necessary at all windings with earthed neutral or with grounding transformer in the protection range Earth fault sensitivity reduced to 2/3 ! Incorrect fault type indication! è I0- correction provides full earth current sensitivity and correct phase selective fault type indication, however requires CT in the neutral-to-earth connection of the transformer. è As an alternative, earth differential protection can be used to enhance earth fault sensitivity.
Differential Protection Symposium
Belo Horizonte November 2005
G. Ziegler, 10/2005
page 148
Transformer winding to earth fault Solid earthed neutral IF per unit 10 8
UR h⋅UR
IF
6
Infeed side
4
IF
IK
2
IK 0
20
40
60
80
100
Short-circuited winding part h in %
Source: P.M. Anderson: Power System Protection, McGraw-Hill and IEEE Press (Book)
Differential Protection Symposium
Belo Horizonte November 2005
G. Ziegler, 10/2005
page 149
Transformer winding to earth fault Resistance or reactance earthed neutral
UR
% 100
h⋅UR
I
Infeed side
50
IF IK
IK
RE 0
20
40 100 60 80 Short-circuited winding part h in %
h ⋅U R RE U 2n h ⋅ w2 = ⋅ IF = h ⋅ ⋅ IF w1 U 1n ⋅ 3
IF =
IK
IF
I Max
1 U 2n U R I K = h2 ⋅ ⋅ ⋅ 3 U 1n R E
Source: P.M. Anderson: Power System Protection, McGraw-Hill and IEEE Press (Book)
Differential Protection Symposium
Belo Horizonte November 2005
G. Ziegler, 10/2005
page 150
Transformer winding short-circuit
100
IK
10
IF , I K x In 80
8
60
6
IP x In
IF 4
40
IK 20
2
IF 0
5
10
15
20
25
Short-circuited winding part h in % Source: Protective Relays, Application Guide, GEC Alstom T&D, 1995
Differential Protection Symposium
Belo Horizonte November 2005
G. Ziegler, 10/2005
page 151
Restricted earth fault protection of relay 7UT6 IR IS IT K0= 4 K0= 2
100
80 2
120
60
1.2
I0 * ⋅ e ϕ (I 0 * /I 0 * *) I 0 * *40
0.8
20
1.6
K0= 1.4
140
160
0.4
K0= 1 180
Blocking
0
ϕ
+ 1 Tripping
200
I>
IN ∆ IE
0
I0*
I0**
340
220
320
240
300 260
280
Polarised earth current differential protection
3.14
Differential Protection Symposium
Belo Horizonte November 2005
G. Ziegler, 10/2005
page 152
Restricted earth fault protection 87N (7UT6) Application aspects
n Increased sensitivity with earth faults near winding neutral
Preferably used in case of resistance or reactance neutral earthing n Sensitive to turns short-circuit n I0 / IN amplitude and angle comparison n 2nd harmonic stabilised n Can protect a separate shunt reactor or neutral earthing transformer in
addition to the two winding transformer differential protection n Not applicable with autotransformers! (as only one stabilising input at transformer terminal side, -- high impedance principle to be used in this case.
Differential Protection Symposium
Belo Horizonte November 2005
G. Ziegler, 10/2005
page 153
Transformer HI-earth fault protection
IR
Ir
IS
Is
IT
It
ZE ∆IE>
Differential Protection Symposium
IN
∆IE>
Belo Horizonte November 2005
G. Ziegler, 10/2005
page 154
HI differential protection of an autotransformer
Ir
IR
Is
IS
It
IT
87
Differential Protection Symposium
87
87
Belo Horizonte November 2005
G. Ziegler, 10/2005
page 155
HI earth fault protection of an autotransformer
Ir
IR
Is
IS
It
IT
IN ∆I>
Differential Protection Symposium
Belo Horizonte November 2005
G. Ziegler, 10/2005
page 156
Transformer tank protection 64T: Principle
IE>
Insulated
Differential Protection Symposium
Belo Horizonte November 2005
G. Ziegler, 10/2005
page 157
Transformer protection, Relay design 7UT6 differential protection for
•Transformers •Generators • Motors •Busbars
7UT612: 7UT613: 7UT633: 7UT635:
for protection objects with 2 ends for protection objects with 3 ends for protection objects with 3 ends for protection objects with 5 ends
Differential Protection Symposium
(1/3 x 19’’ case 7XP20) (1/2 x 19’’ case 7XP20) (1/1 x 19’’ case 7XP20) (1/1 x 19’’ case 7XP20)
Belo Horizonte November 2005
G. Ziegler, 10/2005
page 158
7UT6 Integrated protection functions Function
ANSI No.
Function
ANSI No.
Differential
87T
Overfluxing V/Hz
24
Earth differential
87 N
Breaker failure
50BF
Phase overcurrent,
50/51
Temperature monitoring
38
Neutral overcurrent IN>, t
50N/51N
Ground overcurrent (IE, t)
50G/51G
Hand reset trip
86
Unbalanced current I2>, t
46
Trip circuit supervision
74TC
Thermal overload IEC 60255-8
49
Therm. OL IEC 60354 (hot spot)
49
Differential Protection Symposium
Binary inputs for tripping commands
Belo Horizonte November 2005
G. Ziegler, 10/2005
page 159
Application range (7UT6) ∆ ∆I ∆I Shunt Reactor
G
Three winding transformer
Two winding transformer
∆I
Generator / Motor
Differential Protection Symposium
∆I
∆I
Transformer bank (1-1/2-LS)
∆I
∆I
Busbars
Belo Horizonte November 2005
G. Ziegler, 10/2005
page 160
Digital transformer protection relay 7UT613: Current inputs and integrated protective functions YN
yn0
d5
R S T
ϑ> (2)
ϑ> (1)
Differential Protection Symposium
I>>, I>t
∆ITE
∆IT
Belo Horizonte November 2005
G. Ziegler, 10/2005
page 161
Operating characteristic (7UT6)
Idiff >> I
7 Locus of internal faults 45°
6 Op 5
In
pe o l S
operate
2
restrain
4 3 2
Idiff >
1
S lo p
0 0
2
supplementary restraint
e1
4
6
8
10
12
14
16
IRes In
Differential Protection Symposium
Belo Horizonte November 2005
G. Ziegler, 10/2005
page 162
7SA6: Temperature monitoring
RS485 Interface
7XV5662-(x)AD10
7XV5662-(x)AD10
Two thermo-devices can be connected to the serial service interface (RS485) Monitoring of up to 12 measuring points (6 per thermo-device) - each with two pick-up levels Display of the measured temperatures - directly at the thermo-device (which can also be used stand alone) - at the relay One input is reserved for hot spot monitoring (measurement of oil temperature) Thermistors: Pt100, Ni100 or Ni120
Differential Protection Symposium
Belo Horizonte November 2005
G. Ziegler, 10/2005
page 163
7UT6: Temperature monitoring with hot spot calculation (1) Example: Natural cooling
Θ h = Θ O + H gr ⋅ k Y
Θh= hot spot temperature ΘO= oil temperature Hgr=hot-spot-to-oil temperature gradient k= load factor I/In Y= winding exponent
Aging rate: Oil Temp.
HV LV
V=
Aging at Θh = 2(Θ h −98)/6 Aging at 98°C
98O is reference for the aging of Cellulose insulation
Mean value of aging during a fixed time interval: T
2 1 L= ⋅ ∫ V ⋅ dt T2 − T1 T1
Differential Protection Symposium
Belo Horizonte November 2005
G. Ziegler, 10/2005
page 164
7UT6: Temperature monitoring with hot spot calculation (2)
Θ h = Θ o + H gr ⋅ k Y ≈ 73 + 23 ⋅1.151.6 = 102°C
(L)
V = 2(Θ h −98)/6 = 2(102−98)/6 ≈ 1.6 108°C
k, V, L
98°C 102°C 73°C
Θh Hot spot temp. Θo oil temp. (from thermodevice)
[°C]
Θh Θo
1.6
k (I/In)
V (relative aging) L (mean value of V)
1.15
t
Differential Protection Symposium
Belo Horizonte November 2005
G. Ziegler, 10/2005
page 165
7UT6: Commissioning und service tool (1) WEB-Technology Access to WEB Browser Help system in the INTRANET / INTERNET http://www.siprotec.com
1. Serial connection Directy or with modem to standard DIAL-UP network 2. HTM L page view at IP-address of the relay http://141.141.255.160
Differential Protection Symposium
Relay homepage address of : http://141.141.255.160 IP-address can be set with program DIGSI 4 at the front or service interface of the relay
WEB server in relay firmware Server sends HTML pages and JAVA code to WEB Browser via DIAL-UP connection
Belo Horizonte November 2005
G. Ziegler, 10/2005
page 166
7UT6: Commissioning and service tool (2) Display of current phasors of all terminals
Transformer YNd11d11, 110/11/11kV, 38.1MVA, IL2S2à wrong polarity
Differential Protection Symposium
Belo Horizonte November 2005
G. Ziegler, 10/2005
page 167
7UT6: Commissioning and service tool (3) Display of operating/restraint state
Transformer YNd11d11, 110/11/11kV, 38.1MVA, IL2S2à wrong polarity
Differential Protection Symposium
Belo Horizonte November 2005
G. Ziegler, 10/2005
page 168
Application examples
Differential Protection Symposium
Belo Horizonte November 2005
G. Ziegler, 10/2005
page 169
Protection of a two winding transformer
7SJ600 7UT512 50
51 W1
52
87T
Bu
W1 (OS)
49
W2 (US) W2
52
Differential Protection Symposium
52
51
52
Belo Horizonte November 2005
G. Ziegler, 10/2005
page 170
Protection of a three winding transformer 7SJ600 50
51
52
7UT513 W1 49-1
Bu 87T
W1 W2
W2 49-2
W3
W3
51
52
Load
Differential Protection Symposium
Belo Horizonte November 2005
G. Ziegler, 10/2005
page 171
Restricted earth fault protection for a two winding transformer 7SJ600 7UT513 50
51 W1 49-1
52 Bu
W1 (OS)
87T W2 (US) ZE 51 87TE
52
Differential Protection Symposium
52
W2
52
Belo Horizonte November 2005
G. Ziegler, 10/2005
page 172
Protection of an autotransformer
52
7SJ600 51BF
51N
50 51
7UT513 87 TL Load
52
87 TH
7VH600
49 52
3Y
51 59 7RW600
50 BF
Bu
50 51 50 BF
7SJ600
7SJ600 51 N
Differential Protection Symposium
Belo Horizonte November 2005
G. Ziegler, 10/2005
page 173
Protection of a large transformer bank 52
52
7SA6 49
21
7UT513 87 TL
50 BF 87 TH
7VH6 (3)
49
3
Load
52 52
51 59N 7RW6
50 BF 7SJ6
Differential Protection Symposium
7SA6 21
51N
49
51 BF
7SJ6
Belo Horizonte November 2005
G. Ziegler, 10/2005
page 174
Protection of a phase regulating transformers
Phase regulator
Bu 50/50N
50/50N 51/51N
Exciting transformer
Bu
51/51N 87 TS
87 TP 51N 50N
Differential Protection Symposium
51N
Belo Horizonte November 2005
G. Ziegler, 10/2005
page 175
Protection of a compensation reactor No phase CTs at neutral side
3 52 49-1
50 51
87N
7UT613
1
Differential Protection Symposium
Belo Horizonte November 2005
G. Ziegler, 10/2005
page 176
Protection of a compensation reactor with phase CTs at neutral side
7SJ600
50
3 52
51
7UT613
49
87
87N
3
1
Differential Protection Symposium
Belo Horizonte November 2005
G. Ziegler, 10/2005
page 177
Differential protection of generation units (1) a)
c)
d)
e)
52
52
52
52
∆IT
∆IT
∆IT
∆IT
G
G G
∆IG
52
∆IG
G
Differential Protection Symposium
Belo Horizonte November 2005
∆IG
G. Ziegler, 10/2005
page 178
Differential protection of generation units (2)
52
∆IT 52 *) ∆IT
G
∆IG *) same ratio as generator CTs
52
Differential Protection Symposium
Auxiliaries
Belo Horizonte November 2005
G. Ziegler, 10/2005
page 179
Dimensioning of CTs at the station service transformer
250 MVA 220 /10 kV
T1
∆IT Fault F1: High fault currents in relation to the rated current of the station-service transformer T2 (>100xIN) and long DC time constants (>100 ms) require considerable over-dimensioning of CT cores Œ and • .
IK-T
250 MVA 10 kV
IK-G
Œ •
G F1 25 MVA 10,5 / 5 kV
∆IT
T2
Ž F2
Differential Protection Symposium
EB
7UT61
Fault F2: uncritical as current is limited by short-circuit impedance of station-service transformer T2. CT Ž can have normal dimensions
Belo Horizonte November 2005
G. Ziegler, 10/2005
page 180
Digital Transformer Differential Protection
I0-correction + vector group adaptation
Differential Protection Course
PTD Service Power Training Center
Nürnberg 2005
G. Ziegler, 5/2005
page 1
Copyright © SIEMENS AG PTD SE 2002. All rights reserved.
Transformer differential protection with I0-correction External fault L3
L1 L2 L2
L3
L1
Yd5
3
3
3
L1 L2 L3
1 3
1:3
Vector group adaptation
3
1
I0-correction
Differential Protection Course
1
2
3
2
∆
∆
∆
PTD Service Power Training Center
3 Nürnberg 2005
G. Ziegler, 5/2005
page 2
Copyright © SIEMENS AG PTD SE 2002. All rights reserved.
Transformer differential protection with I0-correction Internal fault L3
L1 L2 L2
L3
L1
Yd5
3
3
3
L1 L2 L3
1 3
1:3
1
I0-correction
Differential Protection Course
Vector group adaptation
1
1
3
2
∆
∆
∆
PTD Service Power Training Center
3 Nürnberg 2005
G. Ziegler, 5/2005
page 3
Copyright © SIEMENS AG PTD SE 2002. All rights reserved.
Digital Line Differential Protection Gerhard Ziegler
Differential Protection Symposium
Belo Horizonte November 2005
G. Ziegler, 10/2005
page 179
Line differential protection, Versions
Line differential protection with wire connection I1
Three-wire (control cables) up to about 15 km
current comparison
∆Ι ∆I
I2
I1
voltage comparison
I2
∆U
∆I
∆I
I2
Two-wire (telefon pilots) up to about 25 km
∆I U2
U1 I1
7SD503
7SD502/ 7SD600
Line differential protection with digital communication I
7SD61 Other services
I2
1
I 2
I1
∆I
∆I
∆I
Up to ca. 200 km line length
∆I
PCM MUX
Data net
PCM MUX
PCM MUX
dedicated optic fibres up to ca. 35 km OF or microwave
PCM MUX
Differential Protection Symposium
Belo Horizonte November 2005
7SD61
G. Ziegler, 10/2005
page 180
Digital pilot wire relay 7SD600
Combines ØTraditional pilot wire protection principle with ØModern digital relay technology Novel features: § Self-monitoring and pilot wire supervision § Saturation detector § Measurement of pilot loop resistance § Add-on functions Differential Protection Symposium
Belo Horizonte November 2005
G. Ziegler, 10/2005
page 181
Relay to Relay pilot wires communication New technology on existing (copper-) pilots Traditional:
Composed current measurement Comparison of analogue values
Modern:
E
O
O
E
Phase segregated measurement
Digital data transmission 64 kbps bi-directional 4 value digital code (2B1Q) Amplitude and phase modulation Spectrum mid frequency: 80 kHz
Differential Protection Symposium
Belo Horizonte November 2005
G. Ziegler, 10/2005
page 182
Digital Relay to Relay Communication (Overview)
Dedicated Optic Fiber
or E O
O
Data Comms net
E
87L
87L E
or ISDN
O
E
O E
or O
O
E
Pilot wires Communication according to given possibilities
Differential Protection Symposium
Belo Horizonte November 2005
G. Ziegler, 10/2005
page 183
Converter for digital communication via pilot wire
7SD52/61
7XV5662-0AC00
5 kV insulated 7XR9516
OF-cable mutli-mode fibre max. 1,5 km
Differential Protection Symposium
Barrier transformer 20 kV (optional)
Belo Horizonte November 2005
Wire connection
up to ca. 8 km
G. Ziegler, 10/2005
page 184
Line differential protection with converter for digital communication 7SD52/61
7XV56 Digital data network
OF Multi-mode fibre max. 1.5 km
Differential Protection Symposium
Interface to data network: X.21 or G.703.1 (wired connection)
Belo Horizonte November 2005
G. Ziegler, 10/2005
page 185
Relay to Relay Communication: Two terminal configuration with hot standby connection
Commsconverter FO 820 nm
O
FO 820 nm X21 or G703.1
Main connection interrupted
Hot standby connection Permanent supervision.
Commsconverter
E
I2 Direct FOconnection. Main connection 512 kBit/s for the 87L function
Loss of main connection
Data Comms network
E X21 or G703.1 (64 kBit/s)
I2 Hot standby connection active Switchover takes 20 ms
I1
O
Data Comms network
I1
O
E
O Main connection re-established
E
Closed ring Differential Protection Symposium
Belo Horizonte November 2005
G. Ziegler, 10/2005
page 186
Relay to Relay Communication: Ring- and Chain topology, loss of one data connection tolerated Closed ring
Chain
side 2
side 2
I2
side 3 I3
side 3
I2
I3+ I1
I3
I2
I1+ I2 I1
I3+ I1
I3
I1
I1+ I2 side 1
side 1 Partial current sums
Differential Protection Symposium
Belo Horizonte November 2005
G. Ziegler, 10/2005
page 187
Line differential relay with digital communication (7SD52) Application to 3-terminal line C
5P20 1600:1 Cable tab 110 kV 8 km, 0.25 µF/km IC=40 A
A
OH-line A-B 110 kV, 60 km 8 nF/km, IC=10 A
10P10 400:1
O E
OF: 820 nm
PCM
5P20 1600:1
Digital communication network
PCM
B
O E
Wired interface: X.21 or G701.1
Differential Protection Symposium
Belo Horizonte November 2005
G. Ziegler, 10/2005
page 188
Line differential relay with digital communication (7SD52) Application to tapped line
87L
7SA52
7SA52
87L
Net
Net 7SA52 87L 7SA52 87L
Differential Protection Symposium
Belo Horizonte November 2005
G. Ziegler, 10/2005
page 189
Line differential relay with digital communication (7SD61) Transformer-line protection
10P10, 10 VA, 200:1
20 MVA, 110 kV / 20 kV, Yd5
10P10, 10 VA, 600:5
8 km 50/51
LWL
7SD61
87T 50/51 50 BF
Differential Protection Symposium
87T 50/51 50 BF
7SD61
Belo Horizonte November 2005
G. Ziegler, 10/2005
page 190
7SD52/61: Bias for CT errors
I1 Error %
i1 10%
fL
fF
Load range
Fault range I1 ALF‘/ALFN • IN-CT
f
: relay setting parameters
Differential Protection Symposium
ALF’ •IN-CT
Example: 10P10, fL < 3%, fF = 10% at ALF‘•IN-CT
Belo Horizonte November 2005
G. Ziegler, 10/2005
page 191
Relays 7SD52/61: Operating characteristic
IDiff
I2
Tripping area Restraint area
IDiff>
Operation
I3
I1
I3
I1 External fault
I2
fCT
IStab IDiff = I1 + I2 + I3
(Calculated differential current)
IStab = IDiff> + Σ Sync.error + |I1| •fCT1 +|I2| • fCT2 + |I3| • fCT3
Differential Protection Symposium
Belo Horizonte November 2005
G. Ziegler, 10/2005
page 192
7SD52/61: Impact of line charging current I1
E1
U1
I2
IC
U2
E2
IDiff = I1 + I2 + IC (currents I1 and I2 counted positive in line direction!) Without charge current compensation: Pick-up value:
IDiff> > 2,5.. 4 • I C
è Senstive setting only for short cables or lines
With charge current compensation: Pick-up value:
IDiff> > 0,2 • IN
Differential Protection Symposium
Belo Horizonte November 2005
G. Ziegler, 10/2005
page 193
7SD52/61: High resistance fault sensitivity 230 kV
A
IL= 1000 A 1000/1 A
1000/1 A
B
Infeed 7SD52
IF
Load RF
7SD52
lline = 120 km Ic = 72 A Channel unsymmetry: 0.2 ms = 4.32 O ≈ 5O (60 Hz) 5P type CT, i.e. 1% error in the load area, set: f CD= 2% Relay pick-up setting about 4xIC: IDiff> = 30% In = 300 A I Op = I A + I B = 1000 A + I F − 1000 A = I F I Re s = I Diff > + Fsync + f CTA ⋅ I A + f CTB ⋅ I B = I Diff > + ( I L + I F ) ⋅ sin
∆ϕ ∆ϕ + I L ⋅ sin + f CTA ⋅ ( I L + I F ) + f CTB ⋅ I L 2 2
I Diff > + (2 ⋅ sin (∆ϕ / 2 ) + f CTA + f CTB ) ⋅ I L 300 A + (2 ⋅ sin 5o / 2) + 0.02 + 0.02) ⋅1000 A IF > = = 457 A o 1 − (sin (∆ϕ / 2 ) + f CTA ) 1 − (sin(5 / 2) + 0.02) R F− max . =
230 kV 230 kV = = 290 Ohm 3 ⋅ I F− min . 3 ⋅ 457A
Differential Protection Symposium
Belo Horizonte November 2005
G. Ziegler, 10/2005
page 194
7SD52/7SD61: Charge comparison protection supplement Q2
Q1
Q
Q3
1/4 cycle
n+4 n+3 n+2 n+1 n n-1
speed 64 kbit/s 128 kbit/s 512 kbit/s (FO)
Calculation of the charge n+5
t +T 4 Q=
∫
i i I(t) ⋅ dt ≈ ( n + n + 5 + 2 2
t
n+4
∑ In ) ⋅ ΔT
QDiff = │Q1+Q2+Q3│
n +1
with ∆T= 1 ms (18O el.)
2 relays 21 ms 16 ms 14 ms
3 relays 21 ms 16 ms 14 ms
Differential Protection Symposium
6 relays 41 ms 24 ms 17 ms
Trip Area Restrain Area
QDiff>> Settable pick-up value 0
Belo Horizonte November 2005
0
Qrest= Σ Q errors
G. Ziegler, 10/2005
page 195
Development of IED processing and communication power
Year
Memory
1986
192 kB
0.5 MIPS
16 bit
19.2 kbps
1992
768 kB
1.0 MIPS
16 bit
115.2 kbps
1998
8.5 MB
35 MIPS
32 bit
1.5 Mbps (LAN)
2004
28 MB
80 MIPS
32 bit
100 Mbps (LAN)
Processing power
Differential Protection Symposium
Bus width
Communication
Belo Horizonte November 2005
G. Ziegler, 10/2005
page 196
21 & 87 Relay United full scheme distance and differential protection 21
87
Copy of well proven features 21, 21N
85 - 21
67N
85 - 67N
68, 68T
27 WI
79
25
59
27
49
81
51/51N
50 BF
21 & 87
2 in 1
87
∆I
IRest
Differential Protection Symposium
Belo Horizonte November 2005
G. Ziegler, 10/2005
page 197
Universal line protection relay 87 Differential 21 Distance
line protection
67 DEF For all kind of lines Short to long lines
For all kind of communication:
Parallel lines
Traditional : PLC, Pilot wires, Microwave
Multi-terminal lines
Dedicated OF
Tapped lines
Digital microwave
Transformer lines
Comms networks
For all kind of operation Single and/or three-pole ARC
Series comp. lines
Differential Protection Symposium
Belo Horizonte November 2005
G. Ziegler, 10/2005
page 198
Line with larger transformer taps Release of 87 by 21 distance overreaching zone 87
87
21
21
Net
Net
87
& 21
Permissive tripping
Differential Protection Symposium
Allows low setting of 87 pick-up!
Belo Horizonte November 2005
G. Ziegler, 10/2005
page 199
Line differential relay with digital communication (7SD61) Application to tapped line, Example 400/1 A
∆I
∆I
400/1 A Net
Net 110 kV SSC1‘‘=2000 MVA ZS1 = 6.05 Ω
l1= 8 km XL1= 3.2 Ω
l2= 10 km XL2= 4.0 Ω
20 MVA uT=12 % XSC-T= 73 Ω 1.1 ⋅ U N / 3 1.1 ⋅ 110/ 3 kV ISC ≈ = = 957 A X SC − T 73 Ω
l3= 5 km XL3 = 2.0 Ω
5 MVA uK=8 % XSC-T= 194 Ω
l4= 4 km XL4= 1.6 Ω
110 kV SSC2‘‘=1000 MVA ZS2= 12.1 Ω
10 MVA uK=10 % XSC-T= 121 Ω
S N −T ∑ ΣI Rush ≈ 5 ⋅ = 5⋅ 3 ⋅U N
35 MVA 3 ⋅110 kV
= 918 A
u Setting pick-up value ∆I > 1.3·957 A u or blocking ∆I via remote signalling when tap protection operates u or release of ∆I by an overreaching distance zone
Differential Protection Symposium
Belo Horizonte November 2005
G. Ziegler, 10/2005
page 200
Fully redundant line protection using dissimilar protection and comms principles
87
MUX
comms net
MUX
87
21
21
87
87 PLC
PLC
21
21
Fully redundant 87 and 21 teleprotection remains in operation in each combination of relay and communication failure!
Differential Protection Symposium
Belo Horizonte November 2005
G. Ziegler, 10/2005
page 201
Phase segregated 87 differential and 21 distance pilot protection: Enhanced selectivity with multiple faults
87 differential and 21 pilot protection
Ph a - E
Ph b - E
Phase selective fault clearance and auto-reclosing also with multiple-faults
Differential Protection Symposium
Belo Horizonte November 2005
G. Ziegler, 10/2005
page 202
Phase segregated 87 differential and 21 distance pilot protection: Enhanced selectivity with multiple faults
87 differential and 21 pilot protection
Ph a - E
Ph b - E
Phase selective fault clearance and auto-reclosing also with multiple-faults
Differential Protection Symposium
Belo Horizonte November 2005
G. Ziegler, 10/2005
page 203
Two-sided fault locator using 87&21 relay communication I1
I2
Grid 1
Grid 2 U1
U2
Digital comms
XL•I1
XL•I2 U2
U1 (I1+I2)•RF Distance
Differential Protection Symposium
Belo Horizonte November 2005
G. Ziegler, 10/2005
page 204
Conclusions
ü Combined distance and differential protection relays , together with modern comms, allow to enhance line protection in a cost saving way. üThe dissimilar protection principles complement each other perfectly. üDistance and differential protection can both be configured as phase segregated teleprotection schemes allowing absolute phase selective fault clearance and autoreclosure even with complex cross county and intercircuit faults. üDigital relay to relay comms allows to exchange data for upgraded two sided fault locating. üUsing a single relay type for distance and/or differential protection also saves on cost in investment and operation.
Differential Protection Symposium
Belo Horizonte November 2005
G. Ziegler, 10/2005
page 205
7SD51: Phase comparison, Dynamic supplement based on delta-quantities I1
I2
PCP
PCP
7SD512
7SD512
i2(t)
i1(t)
∆ i1(t) = i1(t) -i1(t -2T)
−
Differential Protection Symposium
−
+
+
−
−
+
Sign.{ ∆i2 }
Belo Horizonte November 2005
+
Sign.{ ∆i1 }
∆ i1(t) = i1(t) -i1(t -2T)
G. Ziegler, 10/2005
page 206
7SD51: Phase comparison I1
I2
PVS
PVS
PVS
PVS
7SD512
7SD512
7SD512
7SD512
i1(t)
I1
i1(t)
i2(t)
−
−
+
+
−
+
−
no coincidence
+
+
−
−
−
+
+
+
I2
−
no coincidence
i2(t) +
−
+
+
−
+
+ − − Full coincidence
−
Differential Protection Symposium
−
+
+ − − Full coincidence
Tripping
External fault
+
Tripping
Internal fault,
Belo Horizonte November 2005
G. Ziegler, 10/2005
page 207
7SD51: Phase comparison: Impact of charging current
I1=IL+IC
-I2= IL IL
IC
E1
I1
E2
ϕKO IC I1
-I2
Differential Protection Symposium
-I2
undefined range
ϕ
Phase shift ϕ caused by charging current IC
ϕ
I2
Tripping range
undefined range due to discrete sampling : ±1/2∆T = ± 1,66/2 ms= ± 15O
Belo Horizonte November 2005
G. Ziegler, 10/2005
page 208
Phase comparison protection 7SD51: Sampling of the rectangular sign wave and data transmission telegram
i(t)
Sampling interval (1,66 ms) 01
Sign.{ i(t) }
00 11
−+++ START
1 1
···
1 0 1
CHECK
END
Telegram acc. to IEC 60870-5 Hamming distance d= 4
4 directional signs per phase = 12 binary digits
Differential Protection Symposium
Belo Horizonte November 2005
G. Ziegler, 10/2005
page 209
Measurement based on delta quantities, Principle ∆I1, ∆I2: DELTA-quantities
Total situation after fault inception: ZV1 E1
I2
I1
∼
ZV2
RF
∼
E2
∼
E2
Load before fault inception: ZV1 E1
Pure fault part :
I1L
I2L
∼
ZV2
UFL
ZV1
∆I1=I1F
∆I2=I2F RF
Differential Protection Symposium
∼
ZV2
UFL
Belo Horizonte November 2005
G. Ziegler, 10/2005
page 210
Digital Busbar Protection Gerhard Ziegler
Differential Protection Symposium
Belo Horizonte November 2005
G. Ziegler, 10/2005
page 217
Busbar differential protection, Principle (Analog technique) Busbar
1
n
2
Iop
k ⋅ I Res
IOp
Measuring circuit
Tripping area
Operating characteristic
k% Iop> IRes
Differential Protection Symposium
Belo Horizonte November 2005
G. Ziegler, 10/2005
page 218
Part-digital Busbar protection 7SS6
4AM 3
3
2
1
ΣI
100mA∼ /IN
3
n
7SD601
=
7TM70
Differential Protection Symposium
ΣI
=
1,9 mA= /IN
Belo Horizonte November 2005
G. Ziegler, 10/2005
page 219
7SS6: Operating characteristic
IA
Internal faults (k=1) Relay characteristic k= 0.25 to 0.8
Id >
IS
Differential Protection Symposium
Belo Horizonte November 2005
G. Ziegler, 10/2005
page 220
Isolator replica, Principle, (stabilising circuit not shown) BB 1 +
1 _
+
2
+
k
_
_
BB 2
+
_
_
_
+
+
∆I1 ∆I2
_
Differential Protection Symposium
Belo Horizonte November 2005
G. Ziegler, 10/2005
page 221
Decentralised BB-protection 7SS52, Structure
Optic fibre-communication - HDLC protocol - 1,2 MBaud
Wired connections
Differential Protection Symposium
Belo Horizonte November 2005
G. Ziegler, 10/2005
page 222
7SS50/52: Maximum configuration 1
2
3
4
5
6
7
Transfer bus
7SS50 centralised Bays
7SS52 decentralised
32
48
BB-zones
8
12
couplings
4
16
Differential Protection Symposium
Belo Horizonte November 2005
G. Ziegler, 10/2005
page 223
7SS50/52: Acquisition and supervision of isolator positions
Connection to central unit OF
+
Differential Protection Symposium
Belo Horizonte November 2005
G. Ziegler, 10/2005
page 224
Operating characteristic of BB protection 7SS52
Internal faults (k=1)
IOp
Relay characteristic (k =0.1 - 0.8) k
Optional extension for networks with limited earth current (impedance earthing) (release by U0>)
∆I > ∆IE > IRes<
Differential Protection Symposium
IRes
Belo Horizonte November 2005
G. Ziegler, 10/2005
page 225
BB-Protection 7SS52 Performance in networks with earth current limitation 110 /10 kV 40 MVA
IL =
35MVA 10kV ⋅ 3
= 2 kA
I F = I E = 10/ 3kV/6Ω ≈ 1 kA
RE= 6 Ohm (IE = 1 kA)
Restraint current:
I Res = Σ I = (2 + 1) + 2 kA
Operating current:
I Op = ΣI = I E = 1 kA k=
35 MW
k
IOp
I Op I Re s
=
1 = 0.2 5
Relay operating characteristic (k =0.1 - 0.8) Additional, for earth faults (release by U0>)
∆I>
Iop-E= IE = 1kA
∆IE>= 500 A IRes-L= 4kA
IRes
Ihres-E= 1kA
IRes<= 7kA
Differential Protection Symposium
Belo Horizonte November 2005
G. Ziegler, 10/2005
page 226
Check zone of busbar protection
∆ISS1 ∆ISS2 ∆ICheck Check zone: Ø in the past used with HI protection on EHV level (needs separate CT cores) Ø in general not used with traditional low impedance busbar protection (too expensive) Ø However, now integrated as software function in full scheme versions 7SS51 and 7SS52
Differential Protection Symposium
Belo Horizonte November 2005
G. Ziegler, 10/2005
page 227
7SS52: special restraint algorithm avoids over-stabilisation
Check zone
I1
I2
IOp
I4
I3
I3 + I4
IOp I1 +I2 I1 +I2 2·(|I3| +|I4| )
I1 +I2
IRes
Normal restraint: Sum of all current magnitudes
|I3 + I4|
Special restraint algorithm: Positive and negative currents are added separately. Σ I p = I1 + I 2 + I 3 + I 4
I Res = Σ I = I1 + I2 + I3 + I 4 + I3 + I4
IRes
Σ I n = I3 + I 4
Smaller value is then taken: I Res = Σ I n = I3 + I 4
Differential Protection Symposium
Belo Horizonte November 2005
G. Ziegler, 10/2005
page 228
7SS52: Special treatment of dead zone faults (1)
BB-A BB-B
Differential Protection Symposium
Bus coupler CB aux. contacts not connected: • 87-A trips bus coupler • Current inverted in 87-B after T-BF. Subsequently 87-B trips BB-B Coupler CB auxiliary contacts connected: • 87-B trips immediately after opening of bus coupler CB because coupler current is removed from bus protection. → time reduction (T-BF saved)
Belo Horizonte November 2005
G. Ziegler, 10/2005
page 229
7SS52: Special treatment of dead zone faults (2) BB-A
A) Bus coupler CB aux. contacts not connected: • 87-A overfunctions and trips unnecessarily. • 87-B „sees“ an external fault and only trips finally through BF function (delay T-BF!) B) Bus coupler CB aux. contacts connected: • 87-A remains stable („sees“ no fault current) • 87-B trips immediately
BB-B
Coupler CB auxiliary contacts connected to 7SS52: Coupler current is removed from 87-A and 87-B current comparison with open coupler CB.
Differential Protection Symposium
Belo Horizonte November 2005
G. Ziegler, 10/2005
page 230
7SS52: Special treatment of dead zone faults (3) Two CTs in coupling bay, overlapping protection zones BB-A
Coupler CB auxiliary contacts connected: • 87-A „sees“ external fault and remains stable • 67-B correctly trips BB-B
BB-B
87 A
87 B Coupler CB auxiliary contacts connected to 7SS52: Coupler currents are removed from 87-A and 87-B current comparison with open coupler CB.
Differential Protection Symposium
Belo Horizonte November 2005
G. Ziegler, 10/2005
page 231
7SS52: Treatment of switch onto a faulted (earthed) bus
BB-A BB-B
Differential Protection Symposium
Coupler CB close command is detected by bus protection (change of biary input signal): • Coupler current is immediately reincluded in the 87 current comparison before CB contacts close. • Selective tripping of BB-B by 87-B.
Belo Horizonte November 2005
G. Ziegler, 10/2005
page 232
7SS52 : Integral breaker fail protection
Busbar protection7 SS52
Bay protection
& Fault detection
Trip
&
T-BF
Current reversal
∆I 87
Trip
With line fault and CB failure: • Trip command of bay protection hangs on at BB protection • Forced current reversal of the current of concerned bay after T-BF • Zone selective tripping only of the concerned busbar • Advantage: Reset time (overtravel time) of bay protection does not matter Differential Protection Symposium
Belo Horizonte November 2005
G. Ziegler, 10/2005
page 233
External bay dedicated BF protection Zone selective tripping via isolator replica of 7SS52 busbar protection Bay (feeder) protection
trip
7SS52
T-BF
&
I>
&
Isolator replica
Selective bus trip
Fault detection
• • •
BF trip command to busbar protection binary input (for security: fault detection signal as second criterion) Distribution of trip commands via isolator replica to breakers of concerned busbar èzone selective tripping of concerned busbar
Differential Protection Symposium
Belo Horizonte November 2005
G. Ziegler, 10/2005
page 234
Fail safe design: 3-out-of-3 decision per bay
∆I of check zone calculated from all samples
∆I of discriminative zones, calculated from even samples
∆I of discriminative zones, calculated from odd samples
Trip- relay (per bay) L+
L–
Differential Protection Symposium
Belo Horizonte November 2005
G. Ziegler, 10/2005
page 235
Adaptive measurement (Booster circuit) (7SS5)
Odd Samples Even Samples
dI S dt
dI S dt
1 ms
Differential Protection Symposium
dI S dt
Check zone
Belo Horizonte November 2005
G. Ziegler, 10/2005
page 236
Digital busbar protection 7SS5, Measuring technique External fault, symmetrical fault current I1
I2
1 1
IOp= |I1+I2|
I1 0
10
20
0
1
I2
2
1.5 1 0.5 0.5 1 1.5
10
20
t
20
0
10
20
0
10
20
0
1.5
0
10
20
k·IRes = k·(|I1|+|I2|)
1 0.5
1.5
IRes=|I1|+|I2|
1
1
∆I = IOp - IRes
0.5 0
10
Differential Protection Symposium
20
1 0.5 0.5 1 1.5
Belo Horizonte November 2005
G. Ziegler, 10/2005
page 237
Digital busbar protection 7SS5, Measuring technique Internal fault, symmetrical fault current I1
I2 2
1
1
I1
0
10
20
IOp= |I1+I2|
1
I2
)
1.5 1 0.5 0.5 1 1.5
0
10
20
0
10
20
0
10
20
1.5
0
10
20
k·IRes =k·(|I1|+|I2|)
1 0.5
2
1
1
1 0.5
)
0.5 1 1.5
∆I=IOp - IRes
IRes=|I1|+|I2| 0
10
20
Differential Protection Symposium
Belo Horizonte November 2005
Tripping! G. Ziegler, 10/2005
page 238
7SS5/6: Admissible over-burdening - Necessary dimensioning of CTs with regard to symmetrical fault currents Ri
I1 IM
∫
∫
Φ = e2(t ) =(Ri + RB ) i 2(t )
RB
I2
E2
φ
5
1
2
φmax 180O
54O
90O
Im Φ max ≅
180O
180O
180O
0
o
o
∫ ALF'⋅u 2N (t) ⋅dt = (Ri + R B ) ∫ ALF'⋅i2N (t) ⋅ dt = (R i + R B )⋅ ALF'⋅ˆI2 ⋅ ∫ sinx ⋅ dt = (Ri + R B )⋅ ALF'⋅ˆI2N ⋅ 2 O
x 180 ˆI ˆ sinx ⋅ dt = ALF'⋅ˆI 2N ⋅ 2 2F sinx ⋅ dt = ALF'⋅I 2N ⋅
∫ o
∫ o
Differential Protection Symposium
I 2F 2 = ALF'⋅ x I 2N sinx
∫
I I 2 k OB = 2F 2N = x ALF' sinx
o
Belo Horizonte November 2005
∫ o
G. Ziegler, 10/2005
page 239
Required restraining factor k dependent on over-burdening factor KOB (over-dimensioning factor KTF) 1.5 1 1
IRes= |I1|+|I2|
0.5 0
10
IOp < k·IRes
Condition for stability:
1‘
sinx >
0 0
I F < k ⋅ 2 ⋅ I F ⋅ sin x
1 2⋅k
I I 2 2 ü = 2K 2N = = x n' 1 − cosx sinx (from previous transparency)
2
20
2 ⋅ I F ⋅ sin x
x
∫ o
IOp= |I1+I2|
IK
k>
K OB 4 ⋅ K OB − 1
10
20
t
20
1
or
k>
1 4 ⋅ K TF − K 2 TF
KOB= CT over-burdening factor KTF= 1/KOB = CT over-dimensioning factor
Differential Protection Symposium
Belo Horizonte November 2005
G. Ziegler, 10/2005
page 240
Digital busbar protection 7SS5, Measuring technique External fault, fault current with DC offset I1
I2
2 2
I1
IOp= |I1+I2| 0
20
40
1
60
0
20
0
20
40
60
40
60
40
60
2
I2 0
20
40
60
k·IRes =k·(|I1|+|I2|)
1
2
t
2
IRes=|I1|+|I2|
1
∆I=IOp - IRes
1
0
20
1 0
20
40
Differential Protection Symposium
60
2
Belo Horizonte November 2005
G. Ziegler, 10/2005
page 241
Digital busbar protection 7SS5, Measuring technique Internal fault, fault current with DC offset I1
I2 3 2 1
2
IOp= |I1+I2|
I1
0
20
40
60
40
60
1 0
I2
20
40
2
t
2
k·IRes =k·(|I1|+|I2|) 0
20
t
2 3
60
40
1 0
60
20
1 t
2 2 2
∆I=IOp - IRes
IRes=|I1|+|I2| 0
20
40
60
0.75 0.5 0
40
60
1.75 3
Differential Protection Symposium
20
Tripping!
Belo Horizonte November 2005
G. Ziegler, 10/2005
page 242
CT dimensioning for busbar protection 7SS5, Example (1)
25 ⋅ 106 I N −T = = 1440A 10 ⋅103 ⋅ 3
110kV SSC‘‘= 4 GVA 110/10 kV 25 MVA uT= 14% TT= 60 ms
G
1500/1
2MW
600/1 300/1
150/1
5MW
10 kV 10 MVA Xd‘‘= 15% TG= 100 ms
300/1
300/1
ISt= 6·IN Xd‘‘= 17% TM= 35 ms
M
M
5MW
5MW
Differential Protection Symposium
I N −G =
10 ⋅10 6 = 577A 3 10 ⋅ 10 ⋅ 3
5 ⋅10 6 ΣI N − M -HV = 2 ⋅ = 577A 3 10 ⋅ 10 ⋅ 3
IF−T =
1.1 ⋅ 1440 = 11.3 kA 0.14
IF−G =
1.1 ⋅ 577 = 4.2 kA 0.15
ΣI F − M =
Belo Horizonte November 2005
1.1 ⋅ 577 = 3.7 kA 0.17
G. Ziegler, 10/2005
page 243
CT dimensioning for busbar protection 7SS5 and 7SS6, Example (2) As worst case, the CT 150/1 A in bay 1 is considered. Total fault current with a fault at the transformer HV terminals:
ΣI F = I F − T + I F − G + ΣI F − M = 11,3 + 4,2 + 3,7 = 19,2 kA Equivalent time constant:
I ⋅ T + I F − G ⋅ TG + ΣI F − M ⋅ TM 11.3 ⋅ 60 + 4.2 ⋅ 100 + 3.7 ⋅ 35 TEquiv. = F − T T = = 64 ms I F − T + I F − G + ΣI F − M 11.3 + 4.2 + 3.7 We consider a CT type 5P?, 30 VA, internal burden Pi= 15% (4.5 VA): Connected burden Pa= 1 VA CT over-dimensioning factor for 3ms saturation free time: KTF ca. 0.45 Corresponding to an overburdening factor of kOB= 1/KTF = 2.2 Checking of the k-setting (Stability with symmetrical fault currents):
ALF ' =
ΣI F I N − CT
⋅ K TF =
19 .200 ⋅ 0 . 45 = 58 150
k>
k OB 4 ⋅ kOB − 1
ALF =
=
2,2 = 0 .5 (chosen: k=0.6) 4 ⋅ (2 .2 − 1)
Pa + Pi 1 + 4.5 ⋅ ALF ' = ⋅ 58 = 9.3 PN + Pi 30 + 4.5
We finally choose: CT 5P10, 150/1, 30 VA, R2≤ 4.5 Ohm
Differential Protection Symposium
Belo Horizonte November 2005
G. Ziegler, 10/2005
page 244
Transient performance of iron closed CT cores (type TPX) Over-dimensioning factor KTF for short time to saturation
1.5
1.5
KTF
1.4
TM
1.3
KTF
1.4 1.2
1.2
5 ms
1.1
1.1
1
1
0.9
0.9
0.8
4 ms
0.7 0.5
0.5
3 ms
0.3
0.2
0.2
0.1
0.1 10 20 30 40 50 60 70 80 90 100
3 ms
0.4
0.3
0
4 ms
0.7 0.6
0.4
5 ms
0.8
0.6
0
TM
1.3
0
0
1
2
3
4
6
7
8
9
10
TN
TN
Differential Protection Symposium
5
Belo Horizonte November 2005
G. Ziegler, 10/2005
page 245
High impedance busbar protection
RCT
RCT
RCT
RCT
RCT: Resistance of CT secondary winding
RL
RL
RL
RL
RL: Connection cable resistance RRV: Relay series resistance RRS: Relay shunt resistance
RRS
Varistor IV
IS
RRV ∆I
Differential Protection Symposium
IR
Belo Horizonte November 2005
G. Ziegler, 10/2005
page 246
HI busbar protection, calculation example RL= 3 Ohm (max.) IR=20 mA (fixed value) RRV = 10 kOhm RRS = 250 Ohm Iv = 50 mA (at relay pick-up voltage)
Given: :n = 8 feeders rCT = 600/1 A UKN = 500 V RCT = 4 Ohm ImR = 30 mA (at relay pick-up voltage)
Primary pick-up current: I F − min = rCT ⋅ (I R + IS + I V + n ⋅ I mR I F − min =
Stability with external faults:
)
I F − through − max < rCT ⋅
600 ⋅ (0.02 + 0.89 + 0.05 + 8 ⋅ 0.03 ) 1
I F − min = 666A ⋅ (111%I N − CT )
Differential Protection Symposium
I F − through − max <
RR ⋅ IR R L + R CT
600 10.000 ⋅ ⋅ 0.02 1 3+ 4
I F − through − max < 17 kA = 28 ⋅ I n
Belo Horizonte November 2005
G. Ziegler, 10/2005
page 247
Busbar protection, Composite current type (7SS600): Performance under unfavourable system earthing conditions Busbar
2
1
3
3
2
IM=2·IL1 + 1·IL3+ 3 ·IE =2·IF + 1 ·IF+ 3·3IF = +12 ·IF
IM=2·IL1 + 1·IL3 + 3 ·IE =2 ·(–IF) + 1 ·(–IF) + 3·0= –3·IF IOp=| IM1 + IM2 | = 9 ·IF IRes=|IM1| +|IM2| = 15 ·IF
1
k=9/15 = 0.6
IOp
Fault L2-E
k=0.5
Faults in other phases: Fault L1-E: IOp = (3+12) ·IF = 15 ·IF, IRes= (3+12) ·IF = 15 ·IF,
k=1
Fault L3-E: IOp = (0+12) ·IF = 12 ·IF, IRes= (0+12) ·IF = 12 ·IF,
k=1
Differential Protection Symposium
IRes Belo Horizonte November 2005
G. Ziegler, 10/2005
page 248
Busbar protection, Composite current type (7SS600): Performance in networks with earth current limitation IL =
110/10 kV 40 MVA
35MVA 10kV ⋅ 3
= 2 kA
I F = I E = 10/ 3 kV/6Ω ≈ 1 kA RE= 6 Ohm (IE = 1 kA)
Worst case: Fault in phase L2 Restraint current: Operating current:
Ph-E
I Res = 3 ⋅ 3 kA I Op = 3 ⋅ I KE = 3 kA k=
35 MW
I Op I Re s
IL1
IL3
IE
2·IL1
IM-L
IL2
Differential Protection Symposium
3 3⋅ 3
= 0,57
Fault L2-E
IOp IL3
=
k=0.5 |IM-L|
IRes
Load
Belo Horizonte November 2005
IRes G. Ziegler, 10/2005
page 249
Differential Protection 7UT6 Remarkable Features
Differential Protection Symposium
Belo Horizonte November 2005
G. Ziegler, 5/2005
page 248
The 7UT6 Family 7UT6 differential protection for
•Transformers •Generators • Motors •Busbars
7UT612: 7UT613: 7UT633: 7UT635:
for protection objects with 2 ends for protection objects with 3 ends for protection objects with 3 ends for protection objects with 5 ends
Differential Protection Symposium
(1/3 x 19’’ case 7XP20) (1/2 x 19’’ case 7XP20) (1/1 x 19’’ case 7XP20) (1/1 x 19’’ case 7XP20)
Belo Horizonte November 2005
G. Ziegler, 5/2005
page 249
7UT6: Hardware options
Relay version current inputs
(normal) (sensitive)
voltage inputs (Uph / UE) Binary inputs Output contacts Life contact LC Display
7UT612
7UT613
7UT633
7UT635
7 (7)1) 1 --3 4 1 4 rows3)
11 (6) 1) 1 2) 3/1 5 8 1 4 rows3)
11 (6) 1) 1 2) 3/1 21 24 1 Graphic
14 (12 1) 2 2) --29 24 1 Graphic
1)
1A, 5A, (1A, 5A, 0.1A)
2)
link selectable normal/sensitive
3)
alpha-numeric
Differential Protection Symposium
Belo Horizonte November 2005
G. Ziegler, 5/2005
page 250
7UT6: Scope of functions
Function
ANSI No.
Function
Differential
87T/G/M/L
Overfluxing V/Hz
24
Earth differential
87 N
Breaker failure
50BF
Phase overcurrent,
50/51
Temperature monitoring
38
Neutral overcurrent IN>, t
50N/51N
Ground overcurrent (IE, t)
50G/51G
Hand reset trip
86
Unbalanced current I2>, t
46
Trip circuit supervision
74TC
Thermal overload IEC 60255-8
49
Therm. OL IEC 60354 (hot spot)
49
Differential Protection Symposium
ANSI No.
Binary inputs for tripping commands
Belo Horizonte November 2005
G. Ziegler, 5/2005
page 251
7UT6: Application
(1) ∆
∆I ∆I Shunt Reactor
G
Three winding transformer
Two winding transformer
∆I
Generator / Motor
Differential Protection Symposium
∆I
∆I
Transformer bank (1-1/2-LS)
∆I
∆I
Busbars
Belo Horizonte November 2005
G. Ziegler, 5/2005
page 252
7UT6: Application Generation Unit protection (overall differential)
Y ∆
(2)
HI restricted earth fault protection
7UT6xx 7UT635
G 3~
Differential Protection Symposium
Belo Horizonte November 2005
G. Ziegler, 5/2005
page 253
7UT6: selectable: I0-correction or restricted earth fault protection YN
yn0
d5
R S T
49 (1)
49 (2)
50 51
∆ITE
∆IT 7UT613
Differential Protection Symposium
Belo Horizonte November 2005
G. Ziegler, 5/2005
page 254
7UT6: operating characteristic
Idiff >>
7 Locus of internal faults
6
I Op In
45° 5
S
operate
e2 p lo restrain
4
*)
3 2
Idiff >
1
e1 p o l S
0 0
2
supplementary restraint
4
6
8
10
12
14
16
IRes
*) Slope of add on characteristic:
In
7UT6 à as slope 1 (7UT5 à ½ of slope 1)
Differential Protection Symposium
Belo Horizonte November 2005
G. Ziegler, 5/2005
page 255
7UT6: Effect of supplementary restraint in case of CT saturation
Restrain 45°
Trip
Area of add-on restraint
Differential Protection Symposium
Belo Horizonte November 2005
G. Ziegler, 5/2005
page 256
Differential protection functions IDiff> and IDiff>> Sampled momentary values
Measuring value processing i1L
iRes = |i1|+ |i2|
Side 1
i2L
iOp = i1 + i2
Side 2
Average value IStab = iRest Fundamental wave: IDiff = Eff(iDiff)50Hz
Operating characteristic, Saturation detector IDiff IDiff>
IStab
&
Trip IDiff>
≥1
Trip IDiff>>
Motor start, DCcomonent Harmonic Analysis: -2nd Harmon. Blocking -Cross Blocking
iRes IRes
IDiff
IDiff IDiff>>
I / InO
I / InO
iDiff
ms
iDiff 2·IDiff>> ms
Fast tripping using sampled momentary values ensures dependable operation in case of extreme CT saturation!
Differential Protection Symposium
Belo Horizonte November 2005
G. Ziegler, 5/2005
page 257
7SA6: Temperature monitoring
RS485 Interface
7XV5662-(x)AD10
7XV5662-(x)AD10
Two thermo-devices can be connected to the serial service interface (RS485) Monitoring of up to 12 measuring points (6 per thermo-device) - each with two pick-up levels Display of the measured temperatures - directly at the thermo-device (which can also be used stand alone) - at the relay One input is reserved for hot spot monitoring (measurement of oil temperature) Thermistors: Pt100, Ni100 or Ni120
Differential Protection Symposium
Belo Horizonte November 2005
G. Ziegler, 5/2005
page 258
7UT6: Temperature monitoring with hot spot calculation (1) Example: Natural cooling Θ h = Θ O + H gr ⋅ k Y
Θh= hot spot temperature Θh= oil temperature Hgr=hot-spot-to-oil temperature gradient k= load factor I/In Y= winding exponent
Aging rate: Oil Temp.
HV LV
Aging at Θh V= = 2(Θ h −98)/6 Aging at 98°C
98O is reference for the aging of Cellulose insulation
Mean value of aging during a fixed time interval: T
2 1 L= ⋅ ∫ V ⋅ dt T2 − T1 T1
Differential Protection Symposium
Belo Horizonte November 2005
G. Ziegler, 5/2005
page 259
7UT6: Temperature monitoring with hot spot calculation (1) Example: Natural cooling
Θ h = Θ o + H gr ⋅ k Y ≈ 73 + 23 ⋅1.151.6 = 102°C
(L)
V = 2(Θ h −98)/6 = 2(102−98)/6 ≈ 1.6 108°C
k, V, L
98°C 102°C 73°C
Θh Hot spot temp. Θo oil temp. (from thermodevice)
[°C]
Θh Θo
1.6
k (I/In)
V (relative aging) L (mean value of V)
1.15
t
Differential Protection Symposium
Belo Horizonte November 2005
G. Ziegler, 5/2005
page 260
7UT6: Commissioning und service tool
(1)
WEB-Technology Access to WEB Browser Help system in the INTRANET / INTERNET http://www.siprotec.com
Relay homepage address of : http://141.141.255.160 IP-address can be set with program DIGSI 4 at the front or service interface of the relay
1. Serial connection Directy or with modem to standard DIAL-UP network 2. HTM L page view at IP-address of the relay http://141.141.255.160
Differential Protection Symposium
WEB server in relay firmware Server sends HTML pages and JAVA code to WEB Browser via DIAL-UP connection
Belo Horizonte November 2005
G. Ziegler, 5/2005
page 261
7UT6: Commissioning and service tool
(2)
Current phasors of all terminals can be displayed
Transformer YNd11d11, 110/11/11kV, 38.1MVA, IL2S2à wrong polarity
Differential Protection Symposium
Belo Horizonte November 2005
G. Ziegler, 5/2005
page 262
7UT6: Commissioning and service tool (3) Operating/restraint position can be displayed
Transformer YNd11d11, 110/11/11kV, 38.1MVA, IL2S2à wrong Polarität
Differential Protection Symposium
Belo Horizonte November 2005
G. Ziegler, 5/2005
page 263
Power Transmission and Distribution
Differential Protection (7UT)
Determination of the Transformer Vector Group
Transformer with Vector Group Yy0
7UT612
80 MVA Yy0 2500A/1A
20 kV
110 kV 500A/1A
PTD PA13 N. M Tests 7UT 05/03 No. 2
Method of Vector Group Determination (ExampleYy0) IL1,S2
Side 2:
Side 1:
2L1 1L1
IL1,S1
2L2
1L2 2L3 1L3
IL1,S2 = IL1
UL1,S1
UL1,S2
IL1,S1
UL3,S2
UL2,S2
UL3,S1
UL2,S1
0° Vector group is
Yy0 PTD PA13 N. M Tests 7UT 05/03 No. 3
Transformer Protection
7UT612
80 MVA Yd11 2500A/1A
20 kV
110 kV 500A/1A
PTD PA13 N. M Tests 7UT 05/03 No. 4
Method of Vector Group Determination (ExampleYd11) IL1,S2
Side 2:
Side 1:
2L1
IL1,S1
2L2
1L1 1L2
2L3 1L3
IL1,S2 = IL1 - IL2
IL1,S1
UL1,S1
UL1,S2
UL2,S2 UL3,S1
UL2,S1
UL3,S2
Vector group is Y d 11
330° (n * 30°)
PTD PA13 N. M Tests 7UT 05/03 No. 5
Definitions in SIPROTEC 4 Relays
Vector definition to a node is positive The shown vectors or phase angles are transformed in this positive definition The phase angle is displayed mathematics positive. The reference phase is always phase L1 on side 1 How to see the vector group Yd11? Original
Siprotec 4 (Browser)
Phase angles Side 1: 0° (reference phase) Side 2: 210° Please subtract 180°, than you get 30° (360° - 30° = 330°) PTD PA13 N. M Tests 7UT 05/03 No. 6
Web Tool (Browser) Vector group YNd11
PTD PA13 N. M Tests 7UT 05/03 No. 7
Vector Group Determination via Fault Record IL1;Side 2 lags 150° or leads 210°
Star point is towards the protected object
IL1;Side 1
Way 1: IL1 Side: 150° + 180° = 330°
Way 2: IL1 Side: 210° - 180° = 30° leads 30° or lags 330°
Phase shift is according the vector group definition 330° → 11 * 30° PTD PA13 N. M Tests 7UT 05/03 No. 8
Digital Transformer Differential Protection
I0-correction + vector group adaptation
Differential Protection Symposium
Belo Horizonte November 2005
G. Ziegler, 10/2005
page 1
Transformer differential protection with I0-correction External fault L3
L1 L2 L2
L3
L1
Yd5
3
3
3
L1 L2 L3
1 3
1:3
Vector group adaptation
3
1
I0-correction
Differential Protection Symposium
1
2
3
2
∆
∆
∆
3
Belo Horizonte November 2005
G. Ziegler, 10/2005
page 2
Transformer differential protection with I0-correction Internal fault L3
L1 L2 L2
L3
L1
Yd5
3
3
3
L1 L2 L3
1 3
1:3
1
I0-correction
Differential Protection Symposium
Vector group adaptation
1
1
3
2
∆
∆
∆
3
Belo Horizonte November 2005
G. Ziegler, 10/2005
page 3
Power Transmission and Distribution
Differential Protection (7UT)
Determination of the Transformer Vector Group
Transformer with Vector Group Yy0
7UT612
80 MVA Yy0 2500A/1A
20 kV
110 kV 500A/1A
PTD PA13 N. M Tests 7UT 05/03 No. 2
Method of Vector Group Determination (ExampleYy0) IL1,S2
Side 2:
Side 1:
2L1 1L1
IL1,S1
2L2
1L2 2L3 1L3
IL1,S2 = IL1
UL1,S1
UL1,S2
IL1,S1
UL3,S2
UL2,S2
UL3,S1
UL2,S1
0° Vector group is
Yy0 PTD PA13 N. M Tests 7UT 05/03 No. 3
Transformer Protection
7UT612
80 MVA Yd11 2500A/1A
20 kV
110 kV 500A/1A
PTD PA13 N. M Tests 7UT 05/03 No. 4
Method of Vector Group Determination (ExampleYd11) IL1,S2
Side 2:
Side 1:
2L1
IL1,S1
2L2
1L1 1L2
2L3 1L3
IL1,S2 = IL1 - IL2
IL1,S1
UL1,S1
UL1,S2
UL2,S2 UL3,S1
UL2,S1
UL3,S2
Vector group is Y d 11
330° (n * 30°)
PTD PA13 N. M Tests 7UT 05/03 No. 5
Definitions in SIPROTEC 4 Relays
Vector definition to a node is positive The shown vectors or phase angles are transformed in this positive definition The phase angle is displayed mathematics positive. The reference phase is always phase L1 on side 1 How to see the vector group Yd11? Original
Siprotec 4 (Browser)
Phase angles Side 1: 0° (reference phase) Side 2: 210° Please subtract 180°, than you get 30° (360° - 30° = 330°) PTD PA13 N. M Tests 7UT 05/03 No. 6
Web Tool (Browser) Vector group YNd11
PTD PA13 N. M Tests 7UT 05/03 No. 7
Vector Group Determination via Fault Record IL1;Side 2 lags 150° or leads 210°
Star point is towards the protected object
IL1;Side 1
Way 1: IL1 Side: 150° + 180° = 330°
Way 2: IL1 Side: 210° - 180° = 30° leads 30° or lags 330°
Phase shift is according the vector group definition 330° → 11 * 30° PTD PA13 N. M Tests 7UT 05/03 No. 8