DESIGNER’S REFERENCE HANDBOOK
Advanced Protection Unit, APU 200
• • • • •
Product information Protections Functional descriptions Additional information Programming
Document no.: 41893400660A SW version 3.53.0 or later
APU 200
Designer’s Designer’s Reference Handbook Handbook
Table of contents 1.
ABOUT THIS DOCUMENT ........................................................................................... .................................................................................................... ......... 3 GENERAL PURPOSE ...................................................................................................................... 3 INTENDED USERS ..................................................................................... .......................................................................................................................... ..................................... 3 CONTENTS /OVERALL STRUCTURE ..................................................................................................3
2.
WARNINGS AND LEGAL INFORMATION ........................................................................... 4 LEGAL INFORMATION AND RESPONSIBILITY .....................................................................................4 ELECTROSTATIC LECTROSTATIC DISCHARGE DISCHARGE AWARENESS ..................................................................................... 4 S AFETY ISSUES ....................................................................................... ............................................................................................................................ ..................................... 4 DEFINITIONS ............................................................................................ ................................................................................................................................ .................................... 4
3.
PROTECTIONS......................................................................................................................5
M AINS PROTECTION PROTECTION PACKAGE ....................................................................................................... 5 LOSS OF MAINS PROTECTION PACKAGE ......................................................................................... 5 ADDITIONAL PROTECTIONS PACKAGE ............................................................................... ............................................................................................ ............. 6 4TH CURRENT TRANSFORMER INPUT .............................................................................................. 7 NEUTRAL LINE AND GROUND FAULT INVERSE OVERCURRENT .......................................................... 7 4.
SYNCHRONISATION........................................................................................................... SYNCHRONISATION................................. .......................................................................... 10 CLOSE BTB .............................................................................. ............................................................................................................................... ................................................. 10 OPEN BTB................................................................................................................................. ................................................................................................................................ . 10 OPEN/CLOSE FAIL .......................................................................................................................12
5.
DIGITAL INPUT....................................................................................................... INPUT.................................................................................................................... ............. 13 INPUT FUNCTION SELECTION ............................................................................... ....................................................................................................... ........................ 14
6.
ANALOGUE ANALOGUE INPUT .................................................................................. ............................................................................................................. ........................... 15 4-20 M A ..................................................................................... ..................................................................................................................................... ................................................ 15 PT100 ............................................................................................ ....................................................................................................................................... ........................................... 15 VDO INPUTS ............................................................................................ .............................................................................................................................. .................................. 15 DIGITAL. .................................................................................................................... ..................................................................................................................................... ................. 20 W IRE FAIL DETECTION .......................................................................................... ................................................................................................................ ...................... 21
7.
GENERAL SETUP ................................................................................. ............................................................................................................... .............................. 22 22 NOMINAL SETTINGS ................................................................................ .................................................................................................................... .................................... 22 T AP SETTINGS ............................................................................................................................23 F AN CONTROL. ........................................................................................................................... ........................................................................................................................... 24 SUMMER/WINTER TIME ................................................................................................................27 COUNTERS. ............................................................................................................................. ................................................................................................................................ ... 27 L ANGUAGE SELECTION ................................................................................................................ ...................... 28 SELECTION..........................................................................................
8.
POWER MANAGEMENT ..................................................................................................... ..................................................................................................... 29 LOAD MANAGEMENT ............................................................................... ................................................................................................................... .................................... 29 COMMAND TIMERS (TIME-DEPENDENT START/STOP) ..................................................................... 29
9.
ADDITIONAL ADDITIONAL FUNCTIONS .................................................................................................. .................................................................................................. 30
ALARM INHIBIT ............................................................................................................................30 ACCESS LOCK .......................................................................................... ............................................................................................................................ .................................. 31 F AIL CLASS ............................................................................... ................................................................................................................................ ................................................. 32 RELAY OUTPUTS. ........................................................................................................................ ........................................................................................................................ 33 M-LOGIC .................................................................................................................................... .................................................................................................................................. . 33 LVHV PHASE COMPARE VIEW ...................................................................................................... 36 USW COMMUNICATION ............................................................................................................... 37 TCP/IP ........................................................................ ...................................................................................................................................... ..............................................................37
DEIF A/S
Page 2 of 37
APU 200
Designer’s Designer’s Reference Handbook Handbook
1. About this document
This chapter includes general user information about this handbook concerning the general purpose, the intended users and the overall contents and structure.
General purpose This document is the Designer’s Reference Handbook for DEIF’s Advanced Protection Unit, the APU 200. The The document document mainly mainly includes includes functional functional descripti descriptions, ons, presenta presentation tion of of display display unit, unit, menu structure, wiring and the procedure for parameter setup. The general purpose of the Designer’s Reference Handbook is to provide useful overall information about the functionality of the unit and its applications. This handbook also offers the user the information needed in order to successfully set up the parameters needed in the user’s specific application.
Please make sure to read this handbook before working with the controller and the unit to be controlled. Failure to do this could result in human injury or damage to the equipment.
Intended users The handbook is mainly intended for the person responsible for the unit parameter setup. In most cases, this would be a panel builder designer. Naturally, other users might also find useful information in the handbook.
Contents/overall structure The Designer’s Reference Handbook and Installation instructions is divided into chapters and in order to make the structure of the document simple and easy to use, each chapter will begin from the top of a new page. The following will outline the contents of each of the chapters. About this document This chapter includes general information about this handbook as a document. It deals with the general purpose and the intended users of the Designer’s Reference Handbook. Furthermore, it outlines the overall contents and structure of the document. Warnings and legal information This chapter includes information about general legal issues and safety precautions relevant in the handling of DEIF products. Furthermore, this chapter will introduce note and warning symbols, which will be used throughout the handbook.
DEIF A/S
Page 3 of 37
APU 200
Designer’s Reference Handbook
2. Warnings and legal information
This chapter includes important information about general legal issues relevant in the handling of DEIF products. Furthermore, some overall safety precautions will be introduced and recommended. Finally, the highlighted notes and warnings, which will be used throughout this handbook, are presented.
Legal information and responsibility DEIF takes no responsibility for installation or operation of the device connected to the APU 200. If there is any doubt about how to install or operate the device controlled by the unit, the company responsible for the installation or the operation of the set must be contacted.
The units are not to be opened by unauthorised personnel. If opened anyway, the warranty will be lost.
Electrostatic discharge awareness Sufficient care must be taken to protect the terminals against static discharges during the installation. Once the unit is installed and connected, these precautions are no longer necessary.
Safety issues Installing the unit implies work with dangerous currents and voltages. Therefore, the installation should only be carried out by authorised personnel who understand the risks involved in working with live electrical equipment.
Be aware of the hazardous live currents and voltages. Do not touch any AC measurement inputs as this could lead to injury or death.
Definitions Throughout this document, a number of notes and warnings will be presented. To ensure that these are noticed, they will be highlighted in order to separate them from the general text. Notes
The notes provide general information which will be helpful for the reader to bear in mind. Warnings The warnings indicate a potentially dangerous situation which could result in death, personal injury or damaged equipment, if certain guidelines are not followed.
DEIF A/S
Page 4 of 37
APU 200
Designer’s Reference Handbook
3. Protections
This chapter describes the standard DEIF options in the APU 200. The ANSI number refers to the IEEE standard: “Standard Electrical Power System Device Function Numbers and Contact Designations” (IEEE std C37.21996). In combination, the protections cover the requirement for G59/2, such as vector shift, ROCOF (rate of change of frequency), voltage imbalance protection 2 times over/under voltage and 2 times over/under frequency protection levels.
Mains protection package DEIF Option A1 is a software option and therefore not related to any hardware apart from the standard-installed hardware. The Option A1 is a mix of the below listed protections as follows:
-
Vector jump df/dt (ROCOF) Time-dependent undervoltage Undervoltage and reactive power low
Protection
ANSI no.
Vector jump df/dt (ROCOF) Time-dependent undervoltage, Ut < Undervoltage and reactive power low, U Q <
78 81 27t 27Q
The option A1 relates to the parameters 1960, 1420-1430 and 1630-1700, 1970. Detailed information regarding this option can be found in DEIF standard document for option A1: Mains protection package, document no: 4189340434.
Loss of mains protection package DEIF option A4 is a software option and therefore not related to any hardware apart from the standard-installed hardware. This protection prevents malfunctioning due to insufficient or unbalanced supply voltage. The protection is used when running in parallel. Protection
ANSI no.
Positive sequence voltage
47 U1, 27 pos
The option A4 relates to the parameter 1440. Detailed information regarding this option can be found in DEIF standard document for option A4: Loss of mains protection package, document no: 4189340435.
DEIF A/S
Page 5 of 37
APU 200
Designer’s Reference Handbook
Additional Protections package DEIF option C2 is a software option and therefore not related to any hardware apart from the standard-installed hardware. Protection
ANSI no.
Negative sequence current Negative sequence voltage Zero sequence current Zero sequence voltage Power-dependent reactive power Inverse time overcurrent
46 47 51I0 59U0 40 51
The option C2 relates to the parameters 1080-1090, 1540-1590 and 1740-1790. Detailed information regarding this option can be found in DEIF standard document for option C2: Generator add-on protection package, document no: 4189340437.
DEIF A/S
Page 6 of 37
APU 200
Designer’s Reference Handbook
4th current transformer input th
The 4 current transformer input (terminals 59-60) is used for earth current (ground fault) measured in the transformer star point ground connection. rd The function includes a 3 harmonics filtering of the signal. This is selected by activating the alarm in setting 1730.
The setting of the CT is made in setting 6045 (primary) and 6046 (secondary).
Neutral line and ground fault inverse overcurrent These are configurable inverse alarms, based on predefined or user-configurable curve shapes. Settings are found in parameter 1730 (G Ie>> Inverse). Formula and settings used The inverse time overcurrent is based on IEC 60255 part 151. The function used is dependent time characteristic, and the formula used is:
k t(G) = TMS G
α
+c
-1 GS where t(G) k, c, α G GS TMS
is the theoretical operating time constant value of G in seconds are the constants characterising the selected curve is the measured value of the characteristic quantity is the setting value is the time multiplier setting
The constants k and c have a unit of seconds, α has no dimension. There is no intentional delay on reset. The function will reset when G < 2 x G S.
DEIF A/S
Page 7 of 37
APU 200
Designer’s Reference Handbook
Curve shapes Time characteristic:
In the APU 200, the value 2 x G S is called Limit.
There is a choice between seven different curve shapes, of which six are predefined and one is user-definable: IEC Inverse IEC Very Inverse IEC Extremely Inverse IEEE Moderately Inverse IEEE Very Inverse IEEE Extremely Inverse Custom Common settings for all types: Setting
Parameter no.
Factory setting value
Equals
Limit TMS
1722/1732 1723/1733
30/10% 1.0
2 x GS Time multiplier setting
DEIF A/S
Page 8 of 37
APU 200
Designer’s Reference Handbook
The following constants apply to the predefined curves: Curve type
k
c
α
IEC Inverse IEC Very Inverse IEC Extremely Inverse IEEE Moderately Inverse IEEE Very Inverse IEEE Extremely Inverse
0.14 13.5 80 0.515 19.61 28.2
0 0 0 0.1140 0.491 0.1217
0.02 1 2 0.02 2 2
For the custom curve, these constants can be defined by the user: Setting
Parameter no.
Factory setting value
Equals
k c
1724/1734 1725/1735 1726/1736
0.140 s 0.000 s 0.020
k c
α
(a)
α
For the actual setting ranges, please see the parameter list.
Standard curves
The curves are shown for TMS = 1.
DEIF A/S
Page 9 of 37
APU 200
Designer’s Reference Handbook
4. Synchronisation
This chapter describe closing and opening of the BTB and the alarms linked to this function
Close BTB It is not possible to close (synchronise) the BTB if there is live voltage at both sides of the transformer. Close BTB
LV, No voltage
LV, Voltage
HV, No voltage
HV, Voltage
-
NA
Possible
Possible
NA
-
Possible
Not Possible
HV, No voltage
Possible
Possible
-
NA
HV, voltage
Possible
Not Possible
NA
-
LV, No voltage LV, Voltage
Open BTB Open BTB
Q7 ON
Q7 ON
Q7 OFF NA
Q7 OFF
NA
Q5B ON
Not Possible
Possible
O5B OFF
Possible
Possible
Q5B ON Not Possible
O5B OFF Possible
Possible NA NA
It is possible to request open/close BTB by: Display Via the front of the display, it is possible to activate BTB open/close command
M-Logic
DEIF A/S
Page 10 of 37
APU 200
Designer’s Reference Handbook
Inputs Possible to activate BTB open
For additional information, please use the help function in the USW, this is activated by [F1].
Modbus (Option H2)
For additional information, please refer to the Modbus documentation for the APU 200.
DEIF A/S
Page 11 of 37
APU 200
Designer’s Reference Handbook
Open/close fail It is possible to setup the alarm settings for open/close failure. This can be done via the display or via the USW: Display 24 kV 50 Hz A1 B1 C1 2160 Q6 Open fail 2170 Q6 Close fail 2240 Sep synch relay 2300 Section P> 2420 BTB33 os fail
USW
Double-click the requested parameter.
For additional information regarding how to setup the alarm, please use the help function in the USW; this is activated by [F1].
DEIF A/S
Page 12 of 37
APU 200
Designer’s Reference Handbook
5. Digital input
The unit has 10 configurable binary inputs, and they are all available and programmed via the USW’s I/O settings Input function 1 Semi-auto 2 Auto 3 Block 4 Access lock 5 Remote BTB ON 6 Remote BTB OFF 7 BTB close inhibit 8 Enable sep. sync. 9 BTB spring loaded 10 Remote alarm acknowledge
Configurable Configurable Configurable Configurable Configurable Configurable Configurable Configurable Configurable Configurable Configurable
Input type Pulse Pulse Constant Constant Pulse Pulse Constant Constant Constant Constant
Functional description 1. Semi-auto Changes the present running mode to semi-auto. 2. Auto Changes the present running mode to auto. 2. Block Changes the present running mode to block. When block mode is selected, the running mode cannot be changed by activating the digital inputs. 4. Access lock Activating the access lock input deactivates the control display push-buttons. It will only be possible to view measurements, alarms and the log. 5. Remote BTB ON The BTB ON sequence will be initiated and the BTB will synchronise. 6. Remote BTB OFF The BTB OFF sequence will be initiated, followed by a breaker opening. 7. BTB close inhibit When this input is activated, the BTB cannot close. 8. Enable separate sync. Activating this input will split the breaker close and BTB synchronisation functions into two different relays. The BTB close function will remain on the relays dedicated for breaker control. The synchronisation function will be moved to a configurable relay dependent on the options configuration. 9. BTB spring loaded The APU 200 will not send a close signal before this feedback is present. 10. Remote alarm acknowledge Acknowledges all present alarms, and the alarm LED on the display stops flashing. DEIF A/S
Page 13 of 37
APU 200
Designer’s Reference Handbook
Input function selection Digital input alarms can be configured with a possibility to select when the alarms are to be activated. The possible selections of the input function are normally open or normally closed. The drawing below illustrates a digital input used as an alarm input. 1.
Digital input alarm configured to NC, normally closed This will initiate an alarm when the signal on the digital input disappears.
2.
Digital input alarm configured to NO, normally open This will initiate an alarm when the signal on the digital input appears. The relay output function cannot be changed. This will always be a NO relay and will close when the alarm occurs; alarm = CC (closed contact). + V DC Alarm input
AGC 200 Dig. in Relay out Com
DEIF A/S
Page 14 of 37
APU 200
Designer’s Reference Handbook
6.
Analogue input
The APU 200 unit has three multi-inputs (46, 47 and 48) which can be configured to be used as the following input types: •
• • •
4-20 mA Pt100 VDO Digital The function of the multi-inputs can only be configured in the PC utility software.
Two alarm levels are available for each input. The menu numbers of the alarm settings for each multi-input are controlled by the c onfigured input type as seen in the following table. Input type
Multi-input 46
Multi-input 47
Multi-input 48
4-20 mA
4120/4130
4250/4260
4380/4390
0-40V DC
4140/4150
4270/4280
4400/4410
Pt100
4160/4170
4290/4300
4420/4430
VDO 1
4180/4190
4310/4320
4440/4450
VDO 2
4200/4210
4330/4340
4460/4470
VDO 3
4220/4230
4350/4360
4480/4490
Digital
3400
3410
3420
Only 1 alarm level is available for the digital input type.
4-20 mA If one of the multi-inputs has been configured as 4-20 mA, the unit and range of the measured value corresponding to 4-20 mA can be changed in the PC utility software in order to get the correct reading in the display.
Pt100 This input type can be used for heat sensor, e.g. cooling oil temperature. The unit of the measured value can be changed from Celsius to Fahrenheit in the PC utility software in order to get the desired reading in the display.
VDO inputs The unit can contain up to three VDO inputs. The inputs have different functions as the hardware design allows for several VDO types. These various types of VDO inputs are available for all multi-inputs: For each type of VDO input, it is possible to select between different characteristics including a configurable.
DEIF A/S
Page 15 of 37
APU 200
Designer’s Reference Handbook
VDO 1 This VDO input is used to measure the pressure. VDO sensor type Pressure Type 1 Type 2 Bar psi Ω Ω 0 0 10.0 10.0 0.5 7 27.2 1.0 15 44.9 31.3 1.5 22 62.9 2.0 29 81.0 51.5 2.5 36 99.2 3.0 44 117.1 71.0 3.5 51 134.7 4.0 58 151.9 89.6 4.5 65 168.3 5.0 73 184.0 107.3 6.0 87 124.3 7.0 102 140.4 8.0 116 155.7 9.0 131 170.2 10.0 145 184.0
Type configurable Ω
The configurable type is configurable with eight points in the range 0-2500 Ω. The resistance as well as the pressure can be adjusted. If the VDO input is used as a level switch, then please be aware that no voltage must be connected to the input. If any voltage is applied to the VDO input, it will be damaged. Please refer to the Application Notes for further wiring information.
DEIF A/S
Page 16 of 37
APU 200
Designer’s Reference Handbook
VDO 2 This VDO input is used to measure temperature. VDO sensor type Temperature Type 1 Type 2 °C °F Ω Ω 40 104 291.5 480.7 50 122 197.3 323.6 60 140 134.0 222.5 70 158 97.1 157.1 80 176 70.1 113.2 90 194 51.2 83.2 100 212 38.5 62.4 110 230 29.1 47.6 120 248 22.4 36.8 130 266 28.9 140 284 22.8 150 302 18.2
Type 3
Type 4
Ω
Ω
69.3 36.0 19.8 11.7 7.4
The configurable type is configurable with eight points in the range 0-2500 Ω. The temperature as well as the resistance can be adjusted. If the VDO input is used as a level switch, then please be aware that no voltage must be connected to the input. If any voltage is applied to the VDO input, it will be damaged. Please refer to the Application Notes for further wiring information. VDO 3 This VDO input is used for the level sensor. VDO sensor type Type 1 Value Resistance 0% 78.8 Ω 100% 1.6 Ω
Value 0% 100%
VDO sensor type Type 2 Resistance 3Ω 180 Ω
If the VDO input is used as a level switch, then please be aware that no voltage must be connected to the input. If any voltage is applied to the VDO input, it will be damaged. Please refer to the Application Notes for further wiring information.
DEIF A/S
Page 17 of 37
APU 200
Designer’s Reference Handbook
VDO configurable
Value bar, °C or % 0 10 20 30 40 50 60 70 80
VDO sensor type Type configurable Resistance 0 SP 1 SP 2 SP 3 SP 4 SP 5 SP 6 SP 7 SP 8
Resistance (Ω)
Setpoint 8
Setpoint 7
Setpoint 6
Setpoint 5 Setpoint 4 Setpoint 3 Setpoint 2 Setpoint 1
Value (bar, °C or %) 1
2
3
4
5
6
7
8
Setpoints
The configurable type is configurable with eight points in the range 0-2500 Ω. The value as well as the resistance can be adjusted.
DEIF A/S
Page 18 of 37
APU 200
Designer’s Reference Handbook
Configuration The eight curve settings for the configurable VDO inputs cannot be changed in the display, only in the PC utility software. The alarm settings can be changed both in the display and in the PC utility software. In the PC utility software, the configurable inputs are adjusted in this dialogue box:
Adjust the resistance of the VDO sensor at the specific measuring value. In the example above, the adjustment is 10 Ω at 0.0. For additional information regarding how to setup the VDO, please use the help function in the USW; this is activated by [F1].
DEIF A/S
Page 19 of 37
APU 200
Designer’s Reference Handbook
Digital If the multi-inputs are configured to binary “Digital”, they become available as a configurable input.
When the multi-input has been changed to binary, remember to write and upload the parameter. When the parameter has been uploaded, it is possible to configure the input.
For additional information regarding how to setup the digital input, please use the help function in the USW; this is activated by [F1].
DEIF A/S
Page 20 of 37
APU 200
Designer’s Reference Handbook
Wire fail detection If it is necessary to supervise the sensors/wires connected to the multi-inputs, then it is possible to enable the wire break function for each input. If the measured value on the input is outside the normal dynamic area of the input, it will be detected as if the wire has made a short-circuit or a break. An alarm with a configurable fail class will be activated. Input 4-20 mA VDO Oil, type 1 VDO Oil, type 2 VDO Temp, type 1 VDO Temp, type 2 VDO Temp, type 3 VDO Level, type 1 VDO Level, type 2 VDO configurable Pt100 Level switch
Wire failure area Normal range Wire failure area < 3 mA 4-20 mA > 21 mA < 10.0 ohm > 184.0 ohm < 10.0 ohm > 184.0 ohm < 22.4 ohm > 291.5 ohm < 18.3 ohm > 480.7 ohm < 7.4 ohm > 69.3 ohm < 1.6 ohm > 78.8 ohm < 3.0 ohm > 180.0 ohm < lowest resistance > highest resistance < 82.3 ohm > 194.1 ohm Only active if the switch is open
Principle The illustration below shows that when the wire of the input breaks, the measured value will drop to zero. Then the alarm will occur. Input signal (mA, °C, b, %)
Wire failure Upper failure limit
Lower failure limit
Wire failure t Wire break
Intertrip wirebreak (menu 6270) The alarm will occur when the Intertrip is not activated and the input is de-energised.
DEIF A/S
Page 21 of 37
APU 200
Designer’s Reference Handbook
7. General setup
Nominal settings The nominal settings can be changed to match different voltages and frequencies. The APU 200 has four sets of nominal values, and they are adjusted in menus 6000 to 6030 (nominal settings 1 to 4). Activation The switching between the nominal setpoint can be done in four ways: digital input (M-Logic), AOP or menu 6006. Digital input M-Logic is used when a digital input is needed for switching between the four sets of nominal settings. Select the required input among the input events, and select the nominal settings in the outputs. Example: Event A
Event B
Event C
Output
Dig. input no. 77
or
Not used
or
Not used
Set nom. parameter settings 1
Not Dig. input no. 77
or
Not used
or
Not used
Set nom. parameter settings 2
Please refer to the “Help” file [F1] in the PC utility software for details. AOP M-Logic is used when the AOP is used for switching between the four sets of nominal settings. Select the required AOP push-button among the input events, and select the nominal settings in the outputs. Example: Event A
Event B
Event C
Output
Button 07
or
Not used
or
Not used
Set nom. parameter settings 1
Button 08
or
Not used
or
Not used
Set nom. parameter settings 2
Please refer to the “Help” file [F1] in the PC utility software for details. Menu settings In menu 6005, the switching is made between settings 1 to 4 simply by choosing the desired nominal setting. 24kV 50Hz A1 B2 C1 6005 Enable nom. set Nom. Setting 1 Nom. Setting 2 Nom. Setting 3 Nom. Setting 4
DEIF A/S
Page 22 of 37
APU 200
Designer’s Reference Handbook
Tap settings In order to setup the APU correctly, it is necessary to programme the actual settings of the transformers tap. This is done in parameter 6007. Display
USW
24 kV 50 Hz A1 B1 C1 6000 Nom. Settings 1 Current: 365 A Voltage: 6240 V Set: nom. Settings 1 Current E/N/M 100 A Tap: 24kV 50Hz A1 B1 C1
The following tap settings relate to the programmed via the USW Tap setting
Output
Tap setting
Output
0
Tap setting not used
26
24 kV 50 Hz A2 B2 C1
1
14 kV 50 Hz A1 B2 C1
27
24 kV 50 Hz A3 B2 C1
2
14 kV 50 Hz A2 B2 C1
28
24 kV 50 Hz A4 B2 C1
3
14 kV 50 Hz A3 B2 C1
29
24 kV 50 Hz A1 B1 C1
4
14 kV 50 Hz A1 B1 C1
30
24 kV 50 Hz A2 B1 C1
5
14 kV 50 Hz A2 B1 C1
31
24 kV 50 Hz A3 B2 C1
6
14 kV 50 Hz A3 B1 C1
32
24 kV 50 Hz A1 B2 C2
7
14 kV 50 Hz A1 B2 C2
33
24 kV 50 Hz A2 B2 C2
8
14 kV 50 Hz A2 B2 C2
34
24 kV 50 Hz A3 B2 C2
9
14 kV 50 Hz A3 B2 C2
35
24 kV 50 Hz A1 B1 C2
10
14 kV 50 Hz A1 B1 C2
36
24 kV 50 Hz A2 B1 C2
11
14 kV 50 Hz A2 B1 C2
37
24 kV 50 Hz A3 B1 C2
12
14 kV 50 Hz A3 B1 C2
38
24 kV 60 Hz A1 B2 C1
13
14 kV 60 Hz A1 B2 C1
39
24 kV 60 Hz A2 B2 C1
14
14 kV 60 Hz A2 B2 C1
40
24 kV 60 Hz A3 B2 C1
15
14 kV 60 Hz A3 B2 C1
41
24 kV 60 Hz A4 B2 C1
16
14 kV 60 Hz A1 B1 C1
42
24 kV 60 Hz A1 B1 C1
17
14 kV 60 Hz A2 B1 C1
43
24 kV 60 Hz A2 B1 C1
18
14 kV 60 Hz A3 B1 C1
44
24 kV 60 Hz A3 B2 C1
19
14 kV 60 Hz A1 B2 C2
45
24 kV 60 Hz A1 B2 C2
20
14 kV 60 Hz A2 B2 C2
46
24 kV 60 Hz A2 B2 C2
21
14 kV 60 Hz A3 B2 C2
47
24 kV 60 Hz A3 B2 C2
22
14 kV 60 Hz A1 B1 C2
48
24 kV 60 Hz A1 B1 C2
23
14 kV 60 Hz A2 B1 C2
49
24 kV 60 Hz A2 B1 C2
24
14 kV 60 Hz A3 B1 C2
50
24 kV 60 Hz A3 B1 C2
25
24 kV 50 Hz A1 B2 C1
DEIF A/S
Page 23 of 37
APU 200
Designer’s Reference Handbook
Fan Control Four configurable fans can be setup in the APU. The setup of the fans is done in menus 6562 to 6620. It is possible to use the display to setup the fans but it is recommended to setup the fans via the USW, because then it is possible to see all settings. Fan Input Fan temperature input is setup in parameter 6561. This input can be selected between multiinput 46, 47 or 48. Fan priority update At parameter 6562, the priority update rate is selected. If fan priority update is set to 0 hours, the sequence will be fixed to.: Fan A, Fan B, Fan C and Fan D. Fan control Stop/start of the fans is setup in parameter 6563 to 6574.
The following start/stop curve will be generated if a bow setting is used.
It is recommended to use the USW to setup the fans, because then it is possible at the same time to overview all four settings.
DEIF A/S
Page 24 of 37
APU 200
Designer’s Reference Handbook
Fan Output At parameter 6581 to 6584, the output for fan A to D is selected. If two fans are requested to be started at the same time, it is possible to add a start delay between the two fans; this is done in parameter 6586.
Fan A to D Failure It is possible to activate an alarm if the fan output is not energised. At parameter 6590 to 6620, the fan failure is setup.
Fan running hour The running hours is controlled by M-Logic, and each fan output needs to be programmed in order to have correct running hour values.
The running hour can reset by entering parameter 6585 and select the fan output to be reset.
Please note that it is only possible to reset the value, not add new values.
DEIF A/S
Page 25 of 37
APU 200
Designer’s Reference Handbook
Service timers The unit is able to monitor the maintenance intervals. Two service timers are available to cover different intervals. The service timers can be setup: via the display
or via the USW
24 kV 50 Hz A1 B1 C1 SETUP MENU 6110 Service timer 1 6120 Service timer 2 6130 Alarm horn 6270 Intertrip Wirebreak
The function is based on energised hours. When the adjusted time expires, the unit will display an alarm. The energised hours is counting when the energised feedback is present. Setpoints available in menus 6110 and 6170: Enable:
Enable/disable the alarm function.
Energised hours:
The number of energised hours to activate the alarm.
Day:
The number of days to activate the alarm – if the hours are not reached before this number of days, the alarm will be raised.
Fail class:
The fail class of the alarm.
Output A:
Relay to be activated when the alarm is raised.
Reset:
Enabling this will reset the service timer to zero. This has to be done when the alarm is activated.
The service timer is only counting when voltage is detected at the LV side of the transformer.
DEIF A/S
Page 26 of 37
APU 200
Designer’s Reference Handbook
Summer/winter time This function is used to make the APU 200 unit adjust the clock in the unit automatically according to summer and winter time. The function is enabled in menu 6490. This can be done: via the display
or via the USW
24 kV 50 Hz A1 B1 C1 6490 Summer/Winter time OFF ON .
The function only supports the European rules.
Counters Counters for various values are included, and some of these can be adjusted if necessary, for instance if the unit is installed on an existing system or a new circuit breaker has been installed. The table shows the adjustable values and their function in menu 6100: Description 6101 Q6 operations 6102 kWh reset
DEIF A/S
Function Offset adjustment of the number of breaker operations. Resets the kWh counter.
Comment Counting at each Q6 close command. Automatically resets to OFF after the reset. The reset function cannot be left active.
Page 27 of 37
APU 200
Designer’s Reference Handbook
Language selection The unit has the possibility to display different languages. It is delivered with one master language which is English. This is the default language, and it cannot be changed. In addition to the master language, 11 different languages can be configured. This is done via the PC utility software. The languages are selected in the system setup menu 6080. The language can be changed when connected to the PC utility software. It is not possible to make language configuration from the display, but the already configured languages can be selected. 24kV 50Hz A1 B2 C1 6081 Language Language Left Language Right Language 3 Language 4 Language 5
After selecting a language, the unit aux. power must be cycled before the selection takes effect.
DEIF A/S
Page 28 of 37
APU 200
Designer’s Reference Handbook
8. Power Management
In the following chapter, the power management functions of the APU 200 are listed. Power management functions: Load management Command timers CAN flags • • •
Load management The function is used to activate a relay when a specific amount of power is available. Each APU 200 has five levels which are adjusted in menus 8220-8260: • • • • •
Available power 1 Available power 2 Available power 3 Available power 4 Available power 5
These setpoints can activate a relay when the specific amount of available power is reached. The relay output can be used to connect load groups when sufficient power is available. The relays will activate when the available power is higher than the setpoint, but be aware that when the load groups are being connected, the available power will decrease and the relay(s) deactivate again if the available power is below the setpoint. So it is necessary to make an external holding circuit. The function is not depending on the running modes. The relays will activate in all modes including block. To avoid activation, e.g. when the APU is blocked, the inhibit function should be used.
Command timers (time-dependent start/stop) The purpose of the time-dependent start/stop function is to be able to start and stop functions automatically at specific times each weekday or certain weekdays. Up to eight command timers can be used for either start or stop functions. The settings are set up through the PC utility software. Each command can be set for the following time periods: • • • • •
Individual days (MO, TU, WE, TH, FR, SA, SU) MO, TU, WE, TH MO, TU, WE, TH, FR MO, TU, WE, TH, FR, SA, SU SA, SU
The command timers are to be used in M-Logic as events to set the command (start/stop). The time-dependent start and stop commands are pulses that are not sent until the moment the adjusted time is reached. It is necessary to use the PC utility software when setting up the time-dependent start/stop function.
DEIF A/S
Page 29 of 37
APU 200
Designer’s Reference Handbook
9.
Additional functions
This chapter includes functional descriptions of functions. Tables, diagrams and single-line illustrations will be used in order to simplify the information.
Alarm inhibit In order to select when the alarms are to be active, a configurable inhibit setting for every alarm has been made. The inhibit functionality is only available via the PC utility software. For every alarm, there is a drop-down window where it is possible to select which signals that have to be present in order to inhibit the alarm.
Selections for alarm inhibit: Function
Description
Inhibit 1 Inhibit 2 Inhibit 3 BTB ON BTB OFF BA voltage > 30%
M-Logic outputs: Conditions are programmed in M-Logic The bus breaker is closed The bus breaker is open Bus A voltage is above 30% of nominal Bus A voltage is below 30% of nominal
BA voltage < 30%
Inhibit of the alarm is active as long as one of the selected inhibit functions is active.
In this example, inhibit is set to BTB ON . Here, the alarm will be active when the BTB is not closed. When the BTB has been synchronised, the alarm will be disabled again.
DEIF A/S
Page 30 of 37
APU 200
Designer’s Reference Handbook
Access lock The purpose of access lock is to deny the operator the possibility of configuring the unit parameters and changing the running modes. The input to be used for the access lock function is defined in the PC utility software (USW) I/O settings, please use the application help [F1] in the USW for additional information of how to programme the device. The following example is digital input 86 (terminal 86) used for access lock
Access lock will typically be activated from a key switch installed behind the door of the switchboard cabinet. Button Button status Comment Active It is possible to read all alarms, but it is not possible to acknowledge any of them Active
The horn can be silenced
Not active Not active Active
Reading of all values is possible
Active
The log can be read
Active
System setup can be entered, but no changes can be made The tools can be read, but no commands can be sent
Active Active LEFT UP
Active Not active
DOWN ESC
If the access lock is activated when the view menu system is displayed, the button is not active
Active Active Active
RIGHT DEIF A/S
Page 31 of 37
APU 200
Designer’s Reference Handbook
The following digital input functions are affected when access lock is activated: Input name Semi-auto Auto Block Remote BTB ON Remote BTB OFF
Input status Not active Not active Not active Not active Not active
AOP buttons are not locked when access lock is activated.
Fail class All activated alarms m ust be configured with a fail class. The fail classes define the category of the alarms and the subsequent alarm action. Three different fail classes can be used. The tables below illustrate the action of each fail class Action Fail class 1 Block 2 Warning 3 Trip BTB
Alarm horn relay X X X
Alarm display X X X
Trip of BTB
Block for closing x
X
The table illustrates the action of the fail classes. If, for instance, an alarm has been configured with the “Trip BTB” fail class, the following actions occur: The alarm horn relay will activate. The alarm will be displayed in the alarm info screen. The BTB will open instantly. • • •
In addition to the actions defined by the fail classes, it is possible to activate one or two relay outputs if additional relays are available in the unit. Fail class configuration The fail class can be selected for each alarm function either via the display or via the USW. To change the fail class via the USW, the alarm function to be configured must be selected. Select the desired fail class in the fail class scroll-down menu. Display 24 kV 50 Hz A1 B1 C1 1006 HV -P> 1 Block Warning Trip BTB
DEIF A/S
USW
.
Page 32 of 37
APU 200
Designer’s Reference Handbook
Relay outputs The unit has 12 configurable relay outputs, and they are all available and programmed via the USW’s I/O settings. Relay 16 18 20 23 26 28 30 32 34 36 39 43
Output function Not used HC 1 acknowledge HC 2 acknowledge Trip NEL 1 Trip NEL 2 Trip NEL 3 Status OK Horn
Configurable Configurable Configurable Configurable Configurable Configurable Configurable Configurable Configurable Configurable Configurable Configurable Configurable
M-Logic M-Logic functionality is included in the unit and is not an option-dependent function. However, selecting additional options can increase the functionality. M-Logic is used to execute different commands at predefined conditions. M-Logic is not a PLC but substitutes one if only very simple commands are needed. M-Logic is a simple tool based on logic events. One or more input conditions are defined, and at the activation of those inputs, the defined output will occur. A great variety of inputs can be selected, such as digital inputs, alarm conditions and running conditions. A variety of the outputs can also be selected, such as relay outputs, change of modes and change of running modes. The M-Logic is part of the PC utility software 3, and as such it can only be configured in the PC utility software and not via the display. The main purpose of M-Logic is to give the operator/designer more flexible possibilities of operating the system.
Please refer to the “Help” function (F1) in the PC utility software for a full description of this configuration tool. Please refer to DEIF standard application note: “M-Logic” for further functional details.
DEIF A/S
Page 33 of 37
APU 200
Designer’s Reference Handbook
Configurable alarm LEDs The four LEDs on the left side of the display can be controlled via M-Logic. For each LED, there is a choice between three colours (red, green and yellow) with or without blinking.
Example of Alarms LED configuration It is possible to programme the Alarm LEDs, to indicate highest phase current at any alarm. Start by programming the event A to un-acknowledge alarm, then programme event B to look at highest phase (L1, L2 or L3) current at any alarm.
Next step: Alarm LED to be active (LED 1, 2, 3 or 4), also which colour and effect this LED must have.
The following programming will activate (steady red) Alarm LED 1, whenever an un-acknowledge alarm is present, and the current was highest in L1 when the alarm was activated.
DEIF A/S
Page 34 of 37
APU 200
Designer’s Reference Handbook
Templates For each LED, there is a text box, where the indication of the function can be written. This must be done on a piece of stiff paper or a plastic transparent, as the texts are to be sided into a slot at the top of the APU 200 unit. The slide-in paper/transparent template looks like this:
The above template is scale 1:1 when printing on A4 paper size.
DEIF A/S
Page 35 of 37
APU 200
Designer’s Reference Handbook
LvHv Phase compare view At view 14, it is possible to see the phase rotation 24 kV 50 Hz A1 B1 C1 Q6 Operations 1391 U – Supply 24.5 V LV ------- HV ------Energy total 14/20 Run absolut
This can be useful to help troubleshoot or when commissioning the application. View
Commend
LV - - - - - - HV - - - - - -
No voltage is detected
LV
HV
HV has wrong phase rotation
LV
HV
LV has wrong phase rotation
LV
HV
LV and HV have wrong phase rotation
LV
HV
OK, safe to close the BTB
Take precautions that it is safe to close the breaker. Failure to do this may cause personal injury or death.
DEIF A/S
Page 36 of 37