Short Lines: SIR - Definition Definition SIR (S (Source Impedance Ratio) describes the ratio between the source impedance and the line li ne impedance! If ZL
G
E
VF
distance relay
SIR =
V f
=
Z S Z L E
1 + SIR
High SIR = Small loop voltage V F in case of a fault at the end of the line Note: SIR trip time curves are mostly m ostly related to zone 1, i.e. ZL = Z1
Short Lines: Definition of the shortest zone 1 setting The smallest reach setting of the underreaching Zone 1 will be determined with the minimum voltage measured for a fault at this zone boundary! If Z source
Z line
Vf
SIR =
G
Z S Z L
V f
=
E
1 + SIR
To ensure sufficient measuring accuracy a minimum voltage must be available for a fault at the boundary of the zone 1 setting. By definition of the loop impedances a 3ph fault will result in the smallest voltage: Vmin=minimum voltage for measured accuracy in stated tolerance (e.g. 5%)
The shortest line length (zone 1 setting) is i s therefore defined by V min and the SIR.
Short Lines: Lines: Example Example - shortest shortest zone 1 setting setting With minimum short circuit level on the busbar = 4 GVA, GVA, what is the smallest possible zone 1 setting is Vmin = 0.5V secondary? If Z source
Z line
Vf
SIR =
400kV
2
Z source
=
SIRmax
=
U N
S 3 ph E
V min
=
−1 =
400 2 4000 400 3⋅2
=
40Ω
V min_prim
− 1 = 114
Z 1min =
=
Z S
V f
Z L 0.5 100
Z source SIRmax
⋅ 400kV =
=
40 114
=
E
1 + SIR
2kV
= 0.35Ω
The shortest line length (zone 1 setting) is 0.35 Ohm primary. For a typical line reactance of 0.3 Ohm/km this corresponds to a line length of just over 1km.
(Ph-E-loop) (Ph-E-loop) - influence influence of fault resistance resistance with separation separation of fault fault and line resista resistance nce - Not Siemens Siemens method method Ι L
UPh-E
Ι E
XL
RL
XE
RF
RF X
Ι K
RE
U Ph - E = I L (R L + j X L ) - I E (R E + j X E )+ R F ⋅ I L
ZL Ph-E
X TypeC =
Im{U I } 1 + K x
=
X L
with IE = - IL
R
RTypeC = Re{U / I } − X TypeC / tan(ϕ L ) ⋅ K r Note difference in fault resitance coverage with same zone setting!
(Ph-E-loop) (Ph-E-loop) - influence influence of fault resistance resistance with complex complex KO settin setting g - Not Siemen Siemens s method method Ι L
UPh-E
Ι E
XL
This method is not used by SIEMENS
RL Ι K
RF
XE
RE
RF 1+k0
X
∆X
U Ph - E = I L (Z L + Z E ) + R F ⋅ I L
assume
I L = - I E
ZL
ZPh-E
Z E U Ph - E R F Z L Z Ph - E = = Z L ⋅ + 1+ k0 1+ k0 I L − k0 ⋅ I E
1+
If k0 setting adapted to
Z E RF , then Z Ph - E = Z L + Z E Z L 1+ Z L
R
=
RF
Z L +
1+
Z E j(ϕ E -ϕ L) ⋅e Z L
Also an additional measuring error in the X-direction Page 14