Automation of Commercial Refrigeration Plant
REFRIGERATION AND AIR CONDITIONING
Automation of commercial Automation commercial Refrigeration Plant The purpose o this manual is to show some examples o the use o Danoss automatic controls or commercial rerigeration plants. A simple, hand-regulated plant is used as the starting point o a step-by-step automation and a short description o the unction o each control is given. For additional training material we reer to http://rc.danoss.com/SW/RC_Training/En/Index.htm
Contents
Page
Hand-regulated rerigeration plant .....................................................................................................................................................................................................2 Rerigeration Rerigeratio n plant with thermostatic expansion valve and air-cooled air-cooled condenser ................................................................................ .......................... 3 Rerigeration with Finned evaporator ................................................................................................................................................................................................4 Thermostatic expansion valve .......................................................................................................................................................................................................5 Thermostatic expansion valve with distributor .......................................................................................................................................................................5 Expansion valves .................................................................................................................................................................................................................................6 Thermostatic expansion valve, method o operation ...........................................................................................................................................................7 Thermostatic expansion valve with MOP charge....................................................................................................................................................................8 Combined high and low pressure control .................................................................................................................................................................................9 Low-pressure and High-pressure control ..................................................................................................................................................................................9 High-pressure control, control, method o operation operation .................................................................................... .................................................... .................................0 Thermostat .......................................................................................................................................................................................................................................... Filter drier ............................................................................................................................................................................................................................................ Sight glass ........................................................................................................................................................................................................................................... Automatic water valve ....................................................................................................................................................................................................................2 Finned evaporator ............................................................................................................................................................................................................................3 Rerigeration Rerigeratio n plant with oil separator and heat exchanger............................................... ..................................................... .................................................. 4 Oil separator .......................................................................................................................................................................................................................................5 Heat exchanger .................................................................................................................................................................................................................................5 Rerigeration plant or a larger cold store .......................................................................................................................................................................................6 Shut-o valve .....................................................................................................................................................................................................................................7 Solenoid valve ....................................................................................................................................................................................................................................7 Key diagram, control control current or rerigeration rerigeration plant, g. 20 .................................................................................. ..................................................... ......8 Motor starters.....................................................................................................................................................................................................................................9 Central rerigeration rerigeration plant or cold store temperatures temperatures above reezing point .................................................................................. ................................20 Evaporating pressure pressure regulator regulator ................................................ ..................................................... ..................................................... .........................................2 Check valve .........................................................................................................................................................................................................................................2 Key diagram, control control current or rerigeration rerigeration plant g. 25 ................................................................................... ..................................................... ......22 Rerigeration Rerigeratio n plant or reezer display counter counter ............................................................................... .................................................... ..........................................23 Dierential pressure control .........................................................................................................................................................................................................24 Crankcase pressure pressure regulator.................................................... ..................................................... ..................................................... .........................................25 Condensing pressure pressure regulator regulator ................................................ ..................................................... ..................................................... .........................................25 Dierential pressure valve .............................................................................................................................................................................................................26 Evaporator thermostat ...................................................................................................................................................................................................................26 Key diagram, rerigeration rerigeration plant or reezer display counter, counter, g. 29 ................................................. .................................................... ........................27 Main wiring diagram or contactors ..........................................................................................................................................................................................28 Rerigeration plant or ventilation air................................................................................................................................................................................................29
© Danoss A/S (RC-CMS / MWA), MWA), 03 - 2004
RG00A502
Manual
Hand‑regulated rerigerationplant
Automation o Commercial Rerigeration Plant
Fig.
A hand-regulated rerigeration rerigeration plant is usually built up o these components: Compressor
()
Condenser
(2)
Evaporator
(3)
In order to maintain the cold store temperature t r at the desired level, it is necessary to equip the plant with adjustable valves (4) and (5) in that changes in the loads on the evaporator and condenser under varying rerigera rerigeration tion demands can be reckoned on. For example, example, the plant will be unable to maintain the same temperature summer and winter with permanently set regulating valves and a continuously operating compressor. This can easily be shown graphically, as illustrated in g. .
temperature t o. The E-curves represent evaporator capacity, which rises with the increasing temperature dierence t r - to between room temperature (t r) and evaporating temperature (to). Where the C-curve (winter operation) and E-curve (summer operation) intersect each other, compressor, condenser and evaporator capacities are in equilibrium. As can be seen rom g. , the room temperature will all rom tr to tr' when reriger rerigeration ation demand alls rom Qo in summer to Q o' in winter. To meet this condition the capacities o the compressor, condenser and evaporator must be adjusted, or example by regulating the compressor operation, operation, and by throttling the water ow to the condenser and rerigerant liquid ow to the evaporator.
The ull lines represen representt summer operation and the dotted lines winter operation, (e.g. condensing temp. winter +25°C, summer +35°C). The C-curves represen representt compressor capacity, which rises with increasing evaporating
© Danoss A/S (RC-CMS / MWA), 03 - 2004
RG00A502
2
Manual
Rerigerationplantwith thermostaticexpansion valveandair‑cooled condenser
Automation o Commercial Rerigeration Plant
Fig. 2
Thermostatic expansion valve Automatic expansion valve
In this plant an air-cooled unit has replaced the water-cooled condenser. Air-cooled condensers are normally used where no cooling water is available or where the use o cooling water is orbidden. Replacing the manual valve ahead o the evaporator with a thermostatic expansion valve (pos. ) ensures that the evaporator is continuously supplied with the amount o rerigerantt necessary to keep a constant rerigeran superheat in proportion to the load.
Superheat in an evaporator is dened as t – ps = °C superheat, where t is the temperature measured at the point on the evaporator where the expansion valve sensor is placed, and p s is the pressure measured measured at the same point. ( The relevant pressure is converted to °C). For urther details on superheat, see page 7.
This o course presupposes that the selected expansion valve suits the evaporator concerned. A actor here is that in conditions o maximum load the expansion valve supplies precisely the amount o rerigerant the evaporator is able to evaporate.. In addition the superheat setting o evaporate the valve must match the evaporator. Superheat is generally understood as being the number o °C the evaporator has minus the boiling point o the medium at the existing pressure and with all liquid evaporated.
© Danoss A/S (RC-CMS / MWA), MWA), 03 - 2004
RG00A502
3
Manual
RerigerationwithFinned evaporator
Automation o Commercial Rerigeration Plant
Fig. 3
Thermostat type KP 6 () cuts the ans (2) in and out depending on the room temperature. Thermostatic expansion valve type TE (3) with Thermostatic external pressure equalization regulates liquid injection in the evaporator, dependent on the superheat but independent o the pressure drop across the evaporator.
Sight glass type, SGN (6) indicates too high moisture content in the rerigerant and too little ow to the thermostatic expansion valve. The indicator changes colour when the moisture content is too great. Vapour bubbles in the sight glass can mean insufcient charge, insufcient sub cooling or partial clogging o the strainer strainer..
Liquid distributor type 69G (4) distribute rerigerant liquid equally to the individual evaporator sections. The compressor is cut in and out on the lowpressure side o the combined high and low pressure control control type KP 5 (5) depending on the suction pressure. In addition, the high-pressur high-pressure e side o this control gives protection against too high a condensing pressure by cutting out the compressor i it becomes necessary (e.g. when the ventilator is deected or the airow is blocked (dirt)).
© Danoss A/S (RC-CMS / MWA), 03 - 2004
RG00A502
4
Manual
Thermostaticexpansion valve
Automation o Commercial Rerigeration Plant
Fig. 4
T 2
Thermostatic expansion valve type T 2, the bulb o which is placed immediately ater the evaporator, opens on rising superheat. Pressure on the diaphragm () increases as bulb temperature increases and pressure under the diaphragm increases as the evaporating temperature increases. The pressure dierential, which corresponds to the rerigerant superheat, maniests itsel as a orce, which tries to open the valve against the
Thermostaticexpansion valvewithdistributor
opposite orce o the spring (2). I the dierenti dierential, al, i.e. superheat, exceeds the spring orce the valve will open. The orice assembly, with orice (3) and valve cone (4) can be changed. To suit capacity requirements, there are eight dierent sizes to choose rom.
Fig. 5
TE 5 + 69G
Distributor type 69G ensures an equal distribution o rerigerant to the parallel sections o the evaporator. The distributor can be installed either direct on the thermostatic expansion valve as shown or in the line immediately ater it. A distributor ought always to be tted so that the liquid ow through the nozzle in the distributor pipes is vertical. This ensures that the eect o gravity on liquid distribution is as little as possible. All distribution pipes must be exactly the same length.
© Danoss A/S (RC-CMS / MWA), MWA), 03 - 2004
RG00A502
For evaporators with a large pressure drop, thermostatic expansion valves with external pressure equalization must always be used. Evaporatorss with liquid distributors will always Evaporator have a large pressure drop; thereore always use external pressure equalization.
5
Manual
Expansionvalves
Automation o Commercial Rerigeration Plant
Fig. 6
Upperdiagram: The diagram shows an evaporator, which is ed by a thermostatic expansion valve with internal pressure equalization. The degree o opening o the valve is regulated by: Pressure pb in the bulb and capillary tube acting on the upper side o the diaphragm and determined by the bulb temperature. Pressure po in the valve discharge connection acting under the diaphragm and determined by the evaporating temperature. Spring pressure ps acting under the diaphragm and manually adjustable. In the example shown, the pressure drop in the evaporator ∆p is measured in °C rerigerant pressure –5 – (–20) = 5°C. Provided that the valve spring has been manually adjusted to a pressure p s corresponding to 4°C, it ollows - in order to achieve equilibrium between the orces acting over and under the diaphragm - that pb = po + ps ~ –5 + 4 = –°C. That is, the rerigerant has to be superheated by – – (–20) = 9°C beore the valve begins to open.
Lowerdiagram: The same evaporator coil, but this time ed by a thermostatic expansion valve with external Pressure equalization connected to the suction line ater the bulb. The degree o opening o the valve is now regulated by: Pressure pb in the bulb and capillary tube acting on the upper side o the diaphragm and determined by the bulb temperature. Pressure po - ∆p in the evaporator outlet acting under the diaphragm and determined by the evaporating temperature and the pressure drop in the e vaporator vaporator.. Spring pressure ps acting under the diaphragm and manually adjustable. Provided that, as stated above, pressure drop ∆p in the evaporator corresponds to 5°C and spring pressure ps in the valve to 4°C rerigerant pressure, it ollows that pb = po – ∆p + ps ~ –5 – 5 + 4 = –6°C. That is, the rerigerant now has to be superheated by –6 – (–20) = 4°C beore the valve begins to open. The amount o charge in the evaporator and hence its capacity become higher since a smaller portion o the evaporator surace is used or superheating.
Conclusion: Thermostatic expansion valves with external pressure equalizing must always be used or evaporators with a large pressure drop. Evaporators with a liquid distributor will always have a large pressure drop; thereore always use external pressure equalization. © Danoss A/S (RC-CMS / MWA), 03 - 2004
RG00A502
6
Manual
Thermostaticexpansion valve,methodooperation
Automation o Commercial Rerigeration Plant
Fig. 7
The thermostatic expansion valve is controlled by the dierence between bulb temperature t b and evaporating temperature t o. The valve opens when the temperature dierential rises, t b – to = rerigerant ant superheat rises the valve ∆t, i.e. when reriger will have a larger opening rate. See g. 6. Solid curve po and dotted curve p b gives vapour pressure or the rerigerant and charge respectively.. Chain-dotted curve p o + ps respectively represents represen ts the rerigeran rerigerantt vapour pressure curve po oset in parallel with a constant spring pressure ps, the actory setting or example. At a given evaporating temperature, t o, a pressure po + ps acts under the valve diaphragm and tries to close the valve. Pressure p b acts over the diaphragm and tries to open the valve. The gure shows equilibrium between p o + ps and pb at evaporating temperature t o and bulb temperature t b respectively respectively.. Practically speaking, dierentiall tb – to, the static superheat, is the dierentia same within the entire working range o the valve rom to' to t o".
© Danoss A/S (RC-CMS / MWA), MWA), 03 - 2004
RG00A502
That is to say, irrespective o the evaporating temperature operated with inside the working range, the thermostatic expansion valve will regulate liquid injection so that rerigerant superheat ater the evaporator is held to the value determined by spring pressure p s. I the dierential between bulb temperature t b and evaporating temperature t o is less than the static superheat ∆t, the valve is closed (t b – to < ∆t; pb < po + ps) I the dierential between bulb temperature t b and evaporating temperature t o is greater than the static superheat ∆t, the valve is open (t b – to > ∆t; pb > po + ps). I the dierential between bulb temperature t b and evaporating temperature t o is equal to the static superheat ∆t, the valve is just about to open or just about to close (t b – to = ∆t; pb = po + ps).
7
Manual
Thermostaticexpansion valvewithMOPcharge
Automation o Commercial Rerigeration Plant
Fig. 8
It can sometimes be desirable to use a thermostatic expansion valve with a limited working range - or example, in rerigeration plant with only one evaporator where cooling rom a completely or partially temperature equalized condition occurs only as an exception (ater repair or derosting). For such plants it may be cheaper to use a smaller compressor motor dimensioned in accordance with the load ater cooling down. However, during cooling down such a motor will become overloaded overloade d and cut-out on the thermal overload protection.
© Danoss A/S (RC-CMS / MWA), 03 - 2004
RG00A502
To eliminate this risk, a thermostatic expansion valve with a MOP (Maximum Operating Pressure) Pressure) charge can be used. This pressure-limite pressure-limited d valve will only begin to open at a low evaporating temperature, tMOP, since the charge is adapted to produce a bend in the vapour pressure curve P b. This means that static superheat ∆t is very high at evaporating temperatures higher than t MOP, i.e. in practice the valve will remain closed until the compressor has reduced the suction pressure sufciently to ensure that the electric motor is not overloaded.
8
Manual
Combinedhighandlow pressurecontrol
Automation o Commercial Rerigeration Plant
Fig. 9
Combined high and low pressure control type KP 5 has a single-pole changeover switch (2). KP 5
Low‑pressureside(LP): The LP connector (0) is connected to the suction side o the compressor. When pressure alls on the low-pressure side the circuit between terminals 2 and 3 is broken. Turning Turning the LP spindle () clockwise adjusts the unit to cut out (break the circuit between terminals 2 and 3) at a higher pressure. Turning the dierential spindle (2) clockwise adjusts the unit to cut in again (make the circuit between terminals 2 and 3) at a smaller dierentia dierential.l. Start pressure = stop pressure + dierential. LP signal unction between terminals A and B. Low‑pressureandHigh‑ pressurecontrol
Fig. 0
Low‑pressurecontroltypeKP1 Contains a single pole changeover switch (SPDT), which breaks the circuit between terminals 2 and 3 when pressure in the bellows element (9) ails (on ailing suction pressure) pressure),, i.e. the connector (0) must be connected to the suction side o the compressor. Turning the range spindle () clockwise adjusts the unit to cut in - to make the circuit between terminals 2 and 3 at a higher pressure. Turning the dierential spindle (2) clockwise adjusts the unit to cut out again - to break the circuit between terminals and 2 at a smaller dierential. Start pressure = stop pressure + dierential.
© Danoss A/S (RC-CMS / MWA), MWA), 03 - 2004
High‑pressureside(HP): The HP connector () is connected to the discharge side o the compressor. When pressure rises, on the high-pressure side the circuit between terminals 2 and 3 is broken. Turning the HP spindle (5) clockwise adjusts the unit to cut out (break the circuit between terminals 2 and 3) at a higher pressure. The dierential is xed. Stop pressure = start pressure + dierential.
RG00A502
High‑pressurecontroltypeKP5 Is built up in the same way. Bellows, spring and scale are o course suitable or the higher working pressure. pressure. In this case, the switch breaks the circuit between terminals and 2 when pressure rises in the bellows element (9), i.e. when condensing pressure rises (the connector must be connected to the discharge side o the compressorr ahead o the shut-o valve). compresso Turning the range spindle clockwise adjusts the unit to cut out - to break the circuit between terminals and 2 at a higher pressure. Turning Turning the dierential spindle (2) clockwise adjusts the unit to cut in again - to make the circuit between terminals and 2 at a smaller dierential. Stop pressure = start pressure + dierential.
9
Manual
High‑pressurecontrol, methodooperation
Automation o Commercial Rerigeration Plant
Fig.
High-pressure control type KP 5 is connected to High-pressure the high-pressure side o the rerigeration plant and stops the compresso compressorr when the condensing pressure becomes too high. The control contains a pressure-controlled single- pole changeover switch (SPDT) where the contact position depends on the pressure in the bellows (9). See g. , drawings A and B. Via the adjusting spindle () the main spring (7) can be set to exert a suitable counter- pressure to the bellows pressure. The down-ward resultant o these two orces is transerred by a lever (2) to the main arm (3), one end o which is tted with a tumbler (6). The tumbler is held in position on the main arm by a compressive orce, which can be adjusted by using the spindle (2) to change the pull rom the dierential dieren tial spring (8). The orces rom the bellows pressure, main spring and dierential spring are thus transerred to the tumbler (6), which will tilt when the orces come out o equilibrium because o changes in the bellows pressure, i.e. the condensing pressure.
Conversely, the main arm moves instantaneously Conversely, rom the g. , drawing B position to the g. , drawing A position when the bellows pressure has risen to the stop pressure = start pressure + dierential dierent ial pressure. See also text or gs. 9 and 0 regarding adjustment o type KP. The contact system is specially designed so that the make contact travels at the initial speed o the snap action until it reaches the xed contact, while the break contact separates rom the xed contact at the maximum speed o the snap action. The system has been made possible by the use o a small striker (9) and accurately matched contact springs. The contacts (20) make with a smaller orce than they break, which means that in practice bounce during make is eliminated eliminated.. The holding orce during make is exceptionally high. At the same time the system gives an instantaneous break unction so that the holding orce is maintained 00% right up to break. For these reasons the system is able to operate with high currents and its unction is not impaired by shocks. Compared Compared with traditional designs, the system has given exceptionally good results in practice.
The main arm (3) can only take up two positions. In one position a orce is exerted on each end o the arm and creates opposite torques around its pivot (23). See drawing A. I the bellows pressure decreases, decrease s, the main spring exerts an increasing orce on the main arm. Finally, when the counter torque rom the dierential spring is overcome, the main arm tilts and the tumbler (6) instantaneously change position so that the compressive orce o the dierential spring lies on a line near the arm pivot point (23). The counter-torque rom the dierential spring thus becomes almost zero. See g. , drawing B. The bellows pressure must now rise to overcome the orce rom the main spring because the spring orce torque around the pivot point (23) must also all to zero beore the snap system can return to its initial position. On alling bellows pressure (see g. , drawing A), the main arm moves instantaneously to the position shown in g., drawing B when the bellows pressure is reduced to the stop pressure minus the set dierential pressure. pressure. © Danoss A/S (RC-CMS / MWA), 03 - 2004
RG00A502
0
Manual
Thermostat
Automation o Commercial Rerigeration Plant
Fig. 2
KP 6
Thermostat type KP 6, which has a single pole changeover switch (2), makes the circuit between terminals 2 and 3 when bulb temperature rises, i.e. when room temperature rises. Filterdrier
Turning the range spindle () clockwise, increases the cut-in and cut-out temperature o the unit. Turning the dierential dierential spindle (2) clockwise decreases the dierential between cut-in and cut-out temperatures.
Fig. 3
DML / DCL
Filter drier type DML / DCL has a sintered charge, a so-called solid core (3). This is pressed by the spring (2) against the polyester mad (4) and corrugated corrugate d perorated per orated plate (5). Sightglass
The charge or core in the lter drier consists o material which eectively removes moisture, harmull acids, oreign particles, sediment and the products o oil breakdown.
Fig. 4
SGI
Sight glass type SGI / SGN has a colour indicator () that changes rom green to yellow when the moisture content o the rerigerant exceeds the critical value. The colour indication is reversible reversible,, i.e. the colour changes back rom yellow to green when the plant has been dried, e.g. by replacing the lter drier.
© Danoss A/S (RC-CMS / MWA), MWA), 03 - 2004
RG00A502
Sight glass type SGI is or CFC, sight glass type SGN is or HFC and HCFC (R 22).
Manual
Automaticwatervalve
Automation o Commercial Rerigeration Plant
Fig. 5
WVFX
Automatic water water valve type WVFX opens on rising pressure in the bellows element (), i.e. when condensing pressure increases (the connector on the bellows housing must be connected to the rerigerant side o the condenser).
© Danoss A/S (RC-CMS / MWA), 03 - 2004
RG00A502
Turning the hand wheel (2) counter clock-wise tightens the spring, which means that the valve will open at a higher condensing pressure. pressure. I the hand wheel is turned clock-wise the valve will open at a lower condensing pressure.
2
Manual
Finnedevaporator
Automation o Commercial Rerigeration Plant
Fig. 6
The nned evaporator is designed or orced air circulation over the parallel evaporator coils. The air circulation should always be on the counter ow principle so that the evaporator coils are uniormly loaded. Thereore the relation between airow and rerigerant ow ought always to be as shown in the upper gure. In this way the largest temperature dierence (see right hand gure) is ensured between the air t l and the evaporator surace t at the rerigerant outlet o the evaporator. That is to say, rerigerant superheat ∆t will be rapidly aected by a change in the temperature o the incoming air (the load) and will thereby rapidly give a signal to the thermostatic expansion valve to change the liquid injection.
The thermostatic expansion valve bulb must not be inuenced by alse eects; such as air ow through the evaporator and the bulb must thereore thereor e be placed on the suction line outside this airow. I this is not possible, the bulb has to be isolated. Notethat a thermostatic expansion Notethat valve with external pressure equalization is used.
It is important that the evaporator coils are uniormly loaded. For example, with a downward vertical airow through the evaporator evaporator,, the incoming air will load the rst evaporator coils more than subsequent coils. The rear coils will be the least loaded and will thereore determine to what degree the thermostatic expansion valve opens. I a small amount o rerigerant liquid rom the rear evaporator coils passes the point where the bulb is located, the valve will close despite the act that the rst coils require a supply o rerigerantt liquid because o a larger load, i.e. rerigeran brisker evaporation.
© Danoss A/S (RC-CMS / MWA), MWA), 03 - 2004
RG00A502
3
Manual
Rerigerationplantwith oilseparatorandheat exchanger
Automation o Commercial Rerigeration Plant
Fig. 7
In principle, in rerigeration plant the oil should remain in the compressor. Out in the system it will do more harm than good because it will impair the capacity o the evaporator and condenser.. Also, i the oil level in the crankcase condenser becomes too low, there will be a risk o insufcient compressor lubrication. The best protection against these disadvantages is the installation o an efcient oil separator, separator, type OUB ().
Furthermore, a heat exchanger type HE (2) oers the ollowing advantages: Superheating the suction gas provides greaterr protection against liquid k nock in greate the compressor and counteracts ormation o condensate or rost on the surace o uninsulated suction lines. Sub cooling the reriger rerigerant ant liquid counter-acts the ormation o vapour, which will reduce the capacity o the thermostatic expansion valve. Operating economy will oten be improved because sources o loss such as unevaporated evaporate d liquid drops in the suction gas and insufcient sub cooling o the rerigerant liquid are completely or partially eliminated.
© Danoss A/S (RC-CMS / MWA), 03 - 2004
RG00A502
4
Manual
Oilseparator
Automation o Commercial Rerigeration Plant
Fig. 8
OUB
Hot high-pressure gas is supplied to the oil separator type OUB through the connector (). The gas then ows around the oil tank (2) and through the lter (3) where the oil is separated. The vapour, now poor in oil, leaves the oil separator through the upper connector (4).
Heatexchanger
Separated oil is collected in the bottom o the oil tank (2), which is kept heated by the incoming vapour. In this way the separated oil is stored in a warm condition, i.e. with the lowest possible rerigerant content. A oat valve (5) regulates oil return to the compressor.
Fig. 9
HE
Heat exchanger type HE has been designed with a view to achieving maximum heat transmission at minimum pressure drop. The outer spiralormed chamber (4) leads hot reriger rerigerant ant liquid in a ow counter to the ow o cold rerigerant liquid in the inner chamber (3). Built in to the inner chamber are oset n sections. Heat exchanger type HE is manuactured in brass and copper and has very small dimensions in relation to its heat transmission capacity. The
© Danoss A/S (RC-CMS / MWA), MWA), 03 - 2004
RG00A502
spiral ormed outer chamber (4) orces the hot rerigerant liquid over the entire heat transmission surace and prevents the ormation o condensate on the outer jacket. The built-in oset n sections in the inner chamber (3) produce turbulent ow in the rerigerant vapour. Heat transmission rom liquid to vapour is thus very eective. At the same time, pressure drop is kept down to a reasonable level.
5
Manual
Rerigerationplantora largercoldstore
Automation o Commercial Rerigeration Plant
Fig. 20
Complete rerigeration plant or a larger cold store with temperature above reezing point
To ensure eective eective shut-o o the liquid line during compressor standstill periods, solenoid valve EVR () has been installed since bulb temperature may be expected to rise more rapidly than evaporating temperature and cause the thermostatic expansion valve to open. Protection against overcharging the evaporator during compressor standstill periods is provided by making the solenoid valve close at the same time as the compressor is stopped.
© Danoss A/S (RC-CMS / MWA), 03 - 2004
RG00A502
The liquid line is equipped with type GBC (2) or BML manual shut-o valves to make replacement o the lter drier easy. Pressure on the high and low-pressure sides o the compressor can be read on the pressure gauges shown. The pressure gauges can be shut o with the three-way valves type BMT (3).
6
Manual
Solenoidvalve
Automation o Commercial Rerigeration Plant
Fig. 2
EVR
Solenoid valve type EVR is a servo-controlled electromagnetic electromag netic shut-o valve. Through equalizing holes (2) the upper side o the diaphragm () is pressure-equalized with the valve inlet pressure on the underside. When When current energizes energizes the coil (3) the pilot orice (4) is opened. This orice has a larger through-ow through-ow area than the total area o the equalizing holes. Shut‑ovalve
Pressure over the diaphragm is reduced by the ow through the pilot orice to the valve outlet side and the larger inlet pressure on the underside lits the diaphragm. When the coil is de-energized,, the pilot orice closes and the de-energized diaphragm is drawn onto the valve seat as the pressure over it increase through the equalizing holes.
Fig. 22
BM
Shut-o valves types BM have a triple diaphragm seal () o stainless steel. A thrust shoe (2) prevents direct contact with the spindle (3). The spring (4) together with the pre-stressed diaphragm is able to hold the valve open at operating pressures down to Pe = – bar.
© Danoss A/S (RC-CMS / MWA), MWA), 03 - 2004
RG00A502
The counter seat in the cover (5) prevents the ingress o moisture. The valves are available in straight, and /4" T versions. Flow through the side port o the T version can be shut o leaving the end ports permanently open.
7
Manual
Keydiagram,controlcurrent orrerigerationplant,fg.20
Automation o Commercial Rerigeration Plant
Fig. 23
The diagram must be read rom top to bottom and rom let to right. The individual circuits are drawn so that no leads cross. Power-consuming components are shown at the bottom o the diagram. These These include relay coils in the motor starters, solenoids coils, regulation motors, motors, etc. Motor starter thermal relays F are shown adjacent to the contacts between terminals 95 and 96. Manual reset S is also shown. Relay auxiliary contacts K between terminals 3 and 4 are shown at the top o the diagram. Designations Designations 3, 4, 95, 96, etc. correspond to those contained in Danoss inormation on contactors and motor starters. Relay coils K serve the auxiliary contacts between terminals terminals 3 and 4. The auxiliary contacts are drawn in their de-energized coil position. Under the neutral wire and each relay coil there is an indication o in, which circuit the associated auxiliary contacts, can be ound.
© Danoss A/S (RC-CMS / MWA), 03 - 2004
RG00A502
Terminal designation 3-4 is, by denition, Terminal always a make contact (NO), while terminal designation -2 is always a break contact (NC). The key diagram should be read as ollows: When, on rising cold store temperature, thermostat type KP 6 cuts in (when switches S and S2 are made) between terminals terminals 2 and 3, relays K and K2 in motor starters type CIT pull in and start the evaporator ans. At the same time the associated auxiliary contacts in circuits 3 and 4 are made. Relay K3 in compressor motor starter type CIT pulls in i the combined high and low pressure control type KP 5 is made between terminals terminals 2 and 3, and i switch S3 is made. The compressor compressor starts and at the same time the auxiliary contact in circuit 5 connects current to coil E in the EVR solenoid valve in the liquid line. The solenoid valve opens and rerigerant liquid is injected into the evaporator, regulated by thermostatic expansion valve type TE.
8
Manual
Motorstarters
Automation o Commercial Rerigeration Plant
Fig. 24
The Danoss motor starter range up to 420 A is made up o modules. It consists o a basic module (contactor type Cl) onto which up to our auxiliary contact blocks (type CB) can be clipped as necessary. There There is also a range o thermal relays (type TI). The let-hand diagram shows a motor starter with start- stop / reset unction. The start contact (type CB-S) carries the terminal designation 3-4. The right-hand diagram shows a motor starter with stop/reset unction, controlled via a thermostat, pressure control, or similar.
The motor starters are available in several versions. The examples shown are tted with a manually lockable stop and reset or the thermal relay, i.e. the starters must be manually reset ater thermal cut-out. The modules are based on thermoplastic (CI) and Bakelite/thermoplastic Bakelite/ther moplastic (TI), and all main and auxiliary contacts are made o a special silver alloy. All steel parts are eectively corrosion protected. Sot starter type MCII and circuit breaker type CTI are also available rom Danoss.
The motor starters are equipped with a thermal relay having three indirectly heated bimetals. Through a cut-out mechanism the bimetals break the bounce-ree switch between terminals 95 and 96 in the event o overloading overloading.. Large current asymmetry between the three motor phases activates a built-in dierent dierential ial cut-out, which ensures an accelerated accelerated trip - as distinct rom what occurs under a normal symmetrical overload. The cut-out is partly temperature-compensated; temperature-compensated; up to a temperature o 35°C it compensates or any rise in the ambient temperature temperature not arising rom overloading. © Danoss A/S (RC-CMS / MWA), MWA), 03 - 2004
RG00A502
9
Manual
Centralrerigerationplant orcoldstoretemperatures abovereezingpoint
Automation o Commercial Rerigeration Plant
Fig. 25
Temperature and relative humidity play a signicant role in the keeping o oodstus and the various categories o ware must be stored in the most avourable conditions. There is use thereore or cold stores having dierent temperatures and humidities; not only the room temperature but also the evaporating temperature must be under control. In the example shown, the ollowing temperatures might be considered: Room Ro om te temp mp..
Evap Ev apor ora ati ting ng temp mp..
Vegetable store
+8°C
+3°C
Sliced meat and salad store
+5°C
–5°C
Meat store
0°C
–0°C
The room temperature in all 3 cold stores are controlled with KP-62 thermostats opening and closing the EVR solenoid valves.
© Danoss A/S (RC-CMS / MWA), 03 - 2004
RG00A502
Two evaporating temperature regulators type KVP () throttle the suction line ater the evaporator in the +8°C and +5°C stores so that the evaporating temperatures are maintained at +3°C and –5°C respectively. Combined high and low pressure control type KP 5 (2) cuts the compressor in and out at a suitably low suction pressure to maintain evaporating temperature in the 0°C store at –0°C. During compressor standstill, check valve type NRV (3) prevents rerigerant rom the evaporators in the +8°C and +5°C stores condensing in the coldest evaporator, i.e. the one in the 0°C store. Check valve type NRV (4) aords protection against rerigerant condensing in the oil separator and compressor top cover i these components become colder than the evaporator during plant standstill periods.
20
Manual
Evaporatingpressure regulator
Automation o Commercial Rerigeration Plant
Fig. 26
KVP
Evaporating pressure regulator regulator type KVP opens when pressure rises on its inlet side, i.e. when pressure in the evaporator rises (increasing load). Turning the regulating screw () clockwise compressess the spring (5) and increases the compresse opening pressure, i.e. evaporating temperature rises. The regulator regulator has a bellows (0) o the same diameter as the valve plate (2). This means that pressure variations on the outlet side o the regulator have no eect on the automatic regulation o the degree o opening since Checkvalve
pressure on the top o the valve plate is balanced by pressure on the bellows. The regulator also incorporatess a damping device () so that incorporate pressure pulsations in the plant do not aect the unction o the regulator. To make adjustment o the valve easier, it is tted with a special pressure gauge connection (9), which makes it possible to t or remove a pressure gauge without rst having to empty the suction line and evaporator. evaporator.
Fig. 27
NRV
Check valve type NRV is available in straight or angle versions with are as well as solder connections. Solely the pressure drop controls the unction o the valve across it. NRV straightway version: The valve plate is tted to a brake piston (), which is held against the valve seat by a weak
© Danoss A/S (RC-CMS / MWA), MWA), 03 - 2004
RG00A502
spring (2). When the valve opens, the volume behind the brake piston becomes smaller. smaller. An equalizing hole (slot) allows the reriger rerigerant ant to slowly escape to the outlet side o the valve. In this way the movement o the piston is broken; an arrangement that makes the check valve well suited or lines where pressure pulsations can occur.
2
Manual
Keydiagram,controlcurrent orrerigerationplantfg.25
Automation o Commercial Rerigeration Plant
Fig. 28
Thermostat type KP 62 in the +8°C room controls solenoid valve E type EVR in the liquid line while the two other thermostats type KP 62 in the +5°C and 0°C rooms respectively control motor starters K and K3 type CIT or the evaporator ans, and solenoid valves K2 and K3 type EVR in the liquid lines. Combined high and low pressure control type KP 5 controls motor starter K4 type CIT or the compressor motor. A condition or this unction is that manual switches S, S2, S3 and S4 must be made.
However, since it is unlikely that all the room thermostats will cut out at the same time, this orm o control will result in some ater-evaporation, which can be advantageous as regards liquid hammer in the compressor but disadvantageouss as regards the end o a disadvantageou rerigeration period. When a room thermostat cuts out, slight evaporation will still continue and the charge in the evaporator concerned concerned will become smaller. When the room thermostat cuts in again, the eect o the smaller charge will be to make it more difcult or un-evaporated rerigerant reriger ant to enter the suction line during the sudden priming at the beginning o the evaporator-operating evaporator -operating period.
The compressor motor is thus only indirectly controlled by the room thermostats and is able; or example, to run or some time ater all the thermostats have cut out.
© Danoss A/S (RC-CMS / MWA), 03 - 2004
RG00A502
22
Manual
Rerigerationplantor reezerdisplaycounter
Automation o Commercial Rerigeration Plant
Fig. 29
As this plant operates most o the time at low evaporating temperatures, interrupted only by automatic derosting once or twice every 24 hours, it is advantageous to have an electric compressor motor o a size corresponding to normal operating conditions, i.e. relatively small load at low suction pressure. However, ater a derosting this small motor would be overloaded and there would be a risk o motor burn-out. As a saeguard against this risk a crankcase pressure regulator regulator type KVL () is installed which rst opens when suction pressure in ront o the compressor has been reduced sufciently to avoid overloading the motor. Regulating system KVR (2) + NRD (3) is used to maintain a constant and sufciently high condensing pressure in the receiver on air-cooled condensers at low ambient temperatures. During winter operation the ambient temperature ails and with it the condensing pressure pressure o the air-cooled condenser. The KVR regulates dependent on the inlet pressure and begins to throttle when the pressure drops below the set value. As a consequence consequence,, the condenser becomes becomes partly charged with liquid and its eective area is reduced. In this way the required condensing pressure is re-established. Since the actual regulating task during winter operation is to maintain the receiver pressure at a suitably high level, the KVR is combined with a type NRD dierential pressure valve installed in the bypass line shown. The NRD begins to open at a dierential pressure o .4 bars. When the
© Danoss A/S (RC-CMS / MWA), MWA), 03 - 2004
RG00A502
condensing pressure pressure ails, the KVR begins to throttle. This increases the total pressure drop across the condenser + KVR. When this pressure drop reaches .4 bars, the NRD begins to open and thus ensures that the receiver pressure is maintained. As a rule-o-thumb, it can be assumed that the pressure in the receiver is equal to the pressure set on the KVR minus bar. During summer operation, operation, when the KVR is ully open, the total pressure drop across the condenser and KVR is less than .4 bars. Thereore the NRD remains closed. The charge can collect in the receiver during summer operation. Thereore the plant must be equipped with a sufciently large receiver. The KVR can also be used as a relie valve between between the high-pressure side and low pressure side to protect the high pressure side against too high a pressure (saety unction). The pressure-lubricated compressor compressor with oil pump is protected against oil ailure by dierential dierent ial pressure control type MP 55 (4). The control stops the compressor i the dieren dierential tial between the oil pressure and suction pressure in the crankcase becomes too low. A type 077B thermostat is installed in the counter, counter, with its sensor located in the cold room. I the temperature rises above the set value, a signal lamp lights up.
23
Manual
Dierentialpressurecontrol
Automation o Commercial Rerigeration Plant
Fig. 30
MP 55
Dierential pressure control type MP 55 is used as a saety pressure control on pressure-lubricated rerigeration compressors. Ater a xed time delay the control stops the compressor in the event o oil ailure. The oil pressure element “OIL” () is connected to the oil pump outlet and the low-pressur l ow-pressure e element “LP” (2) is connected to the compressor crankcase. I the dierential between oil pressure and pressure in the crankcase becomes less than the value set on the control, current to the time relay is cut in (contact T - T2 made, see wiring diagram). I contact T - T2 remains made or a lengthy period because o a all in pressure in relation to the pressure in the crankcase (suction pressure) pressure),, the time relay cuts out the control current to the compressor motor starter (time relay contact changes over rom A to B, i.e. control current is broken between L and M).
© Danoss A/S (RC-CMS / MWA), 03 - 2004
RG00A502
The minimum permissible dierential pressure, i.e. the minimum oil pressure at which under normal operation the dierential pressure control sustains current to the time relay cut o (contact T - T2 broken), can be set on the pressure adjustment disc (3). Clockwise rotation increases the dierential, i.e. increases the minimum oil pressure at which the compressor can still run. The contact dierential is xed at 0.2 bars. Thereore, current to the time relay will be rst cut o during start, when the oil pressure is 0.2 bars higher than the minimum allowable dierential pressure. This means that at compressor start the oil pump must be capable o increasing the oil pressure to 0.2 bars more than the set minimum permissible oil pressure beore the end o the time delay. Contact T - T2 must break so quickly ater start that the time relay never reaches it’s A to B changeover point (break between L and M). See also key diagram, g. 35.
24
Manual
Crankcasepressure regulator
Automation o Commercial Rerigeration Plant
Fig. 3
KVL
Crankcase pressure regulator regulator type KVL opens on spindle () clockwise tightens the spring (5) and alling pressure on the outlet side, i.e. on alling Condensingpressure regulator
the regulator then begins to regulate at a higher pressure ahead o the compressor. Turning the pressure on the outlet side.
Fig. 32
KVR
Condensing pressure regulator regulator type KVR opens when pressure on its inlet side rises, i.e. when condensing pressure rises. Turning the spindle () clockwise tightens the spring (5) and increases
the opening pressure so that the condensing pressure rises.
Like the previously mentioned evaporating pressure regulator type KVP, all regulators are tted with a pressure-equalizing bellows (0) to eliminate pressure pressure variations on the inlet side o type KVL and the outlet side o type KVL All regulatorss are also tted with a damping device regulator () so that pressure pulsations in the plant do not aect regulator unction.
© Danoss A/S (RC-CMS / MWA), MWA), 03 - 2004
RG00A502
25
Manual
Dierentialpressurevalve
Automation o Commercial Rerigeration Plant
Fig. 33
NRD
Dierential pressure valve type NRD begins to Dierential open at a pressure drop o .4 bars and is ully open at 3 bars. When the valve is installed as a bypass, it ensures that the receiver pressure is maintained.
Evaporatorthermostat
Fig. 34
077B
The contact system in evaporator thermostat thermostat type 077B makes on rising temperatures. temperatures. Turning the range spindle clockwise increase the cutin temperature o the thermostat, i.e. the temperature at which the signal lamp lights up.
© Danoss A/S (RC-CMS / MWA), 03 - 2004
RG00A502
26
Manual
Automation o Commercial Rerigeration Plant
Keydiagram,rerigerationplantorreez Keydiagram,reri gerationplantorreezerdisplaycount erdisplaycounter,fg er,fg.29 .29 Fig. 35
Time switch P controls changeover contact t, circuit 2, which makes or breaks control current to contactors K and K2 type Cl or the respective electric heating elements under the evaporators, and or the evaporator ans. When K2 is cut in, K is cut out, i.e. the evaporator ans are stopped during derosting. At the same time, motor starter K3 type CIT or the condenser an is cut out via the auxiliary contact (brake contact between 2 and 22) in circuit 4. A signal lamp H is switched on via the auxiliary contact (make contact between 3 and 4) in circuit 6. When motor starter K3 cuts out, the auxiliary contact (make contact between 3 and 4) in circuit 5 breaks and motor starter K4 type CIT or the compressor is cut out. Thus, the compressor also remains at a standstill.
evaporators while derosting was taking place, evaporators beore the evaporator ans are started. Low-pressure control type KP (II) is connected to control the rerigeration plant during normal operation. High-pressure High-pressure control type KP 5 stops the compressor but not the condenser an when condensing pressure becomes excessive. A thermostat type 077B switches on signal lamp H3 i the temperature in the display counter exceeds –8°C. The signal lamps are connected to a 2 V battery system so that lamp H3 is able to unction even i a mains supply ailure occurs.
Pressure control control type KP () is connected so that it cuts out on rising pressure. This This cuts out derosting when the suction pressure has increased to such an extent that there is no more rost on the evaporator evaporator.. When contactor K2 is cut out, motor starter K3, and with it motor start K4 are cut in via the auxiliary contacts (make contact between 2 and 22) in circuit 4 and in circuit 5 (make contact between 3 and 4). Assuming switches S and S2 are made. This starts the condenser an and the compressor. compressor. At the same time, signal lamp H is switched o via the make contact between 3 and 4 in circuit 6 and signal lamp H2 is switched on via the auxiliary contact (make contact between 3 and 4) in circuit 7. The evaporator ans are started ater a period by time switch P cutting in contactor K. During this delay the compressor is able to remove the heat accumulated in the
© Danoss A/S (RC-CMS / MWA), MWA), 03 - 2004
RG00A502
27
Manual
Mainwiringdiagramor contactors
Automation o Commercial Rerigeration Plant
Fig. 36
Wiring diagram or contactors contactors K and K2 type Cl or the display counter rerigeration plant, g. 29. For key diagram see g. 35.
© Danoss A/S (RC-CMS / MWA), 03 - 2004
RG00A502
The changeover switch or time switch P controls the contactors so that one is cut in while the other is cut out. The main contacts -2 and 3-4 in contactor K2 are each connected to an electric heating element. Contactor K has our main contacts, each o which is connected to a single-phase an (-2, 3-4, 5-6,3-4).
28
Manual
Rerigerationplantor ventilationair
Automation o Commercial Rerigeration Plant
Fig. 37
An electronicallycontrolledsuctionpressure regulatortype regulator type KVS () is installed in the suction line. The electronic regulato regulatorr receives signals rom a central control unit, e.g. a PLC, which in turn receives signals rom a temperature sensor located in the return air ow rom the room in which the ventilation air is to be cooled. The KVS valve opens i the temperature temperature o the return air rises. I the temperature registered by the sensor rises, the valve opens a little more, and suction pressure rom the evaporator is increased. At the same time, the pressure drop across the valve is reduced as a result o reduced evaporation temperature temperatu re and increased suction pressure. This increases the capacity o the evaporator and compressor. I the temperature registered by the sensor alls, the valve closes a little more, and suction pressure rom the evaporator is reduced. At the same time, the pressure drop across the valve is increased as a result o increased evaporation temperature temperatu re and reduced suction pressure. This reduces the capacity o the evaporator and compressor. As plant such as this must be capable o running irrespective o load, compressor capacity must be adjustable.
that the compressor is either shut o by the lowpressure cut-out or is subjected to suction pressure below the acceptable minimum. This is achieved by the KVC valve being set to start opening in order to prevent the abovementioned limits rom being crossed. This hotgas bypass transers some high-pressure gas rom the pressure side o the plant to the suction side, thus reducing rerigera rerigeration tion capacity. This type o capacity regulation results in a certain degree o suction gas superheating. As a result, the temperature o the high-pressure gas increases, thus increasing the risk that oil in the compressor pressure valves will become coked. In order to prevent this, a thermostatic expansion valve type T (3) is installed in a bypass between the liquid line and the suction line. The valve sensor is installed in the suction line immediately ahead o the compressor. In case o excessive superheating superheating in this region, the valve opens and some liquid is injected into the suction line. When this liquid evaporates, superheating is reduced and thus also the highpressure gas temperature. A solenoid valve type EVR (4) is installed immediately immediate ly ahead o the thermostatic expansion valve (3) in order to prevent liquid rerigerant reriger ant rom entering the suction line when the rerigeration plant is shut down.
A capacityregulator type KVC (2) is suitable or this purpose as this regulator is able to prevent suction pressure rom dropping to such an extent Continued overleaf... © Danoss A/S (RC-CMS / MWA), MWA), 03 - 2004
RG00A502
29
Manual
Automation o Commercial Rerigeration Plant
Fig. 38
KVS
Electronicallycontrolledsuctionpressure regulator KVS () is a suction pressure regulator, regulator, activated by a stepper motor. It alters the degree o opening in response to signals rom the EKC 368 regulatorr which transmits pulses that cause the regulato valve motor to rotate in one direction or the other depending on whether the valve is to be opened more or closed more.
© Danoss A/S (RC-CMS / MWA), 03 - 2004
RG00A502
Fig. 39
KVC
Capacityregulator The capacity regulator type KVC opens in response to alling pressure on the discharge side, i.e. alling suction pressure ahead o the compressor.
30
Manual
Automation o Commercial Rerigeration Plant
© Danoss A/S (RC-CMS / MWA), MWA), 03 - 2004
RG00A502
3
Manual
Automation o Commercial Rerigeration Plant
© Danoss A/S (RC-CMS / MWA), 03 - 2004
RG00A502
32
Manual
Automation o Commercial Rerigeration Plant
© Danoss A/S (RC-CMS / MWA), MWA), 03 - 2004
RG00A502
33
TheDanossproductrangeorthe rerigerationandairconditioningindustry Compressorsorrerigerationandairconditioning These products include hermetic reciprocating compressors, scroll compressors and an-cooled condensing units. Typical applications are air conditioning units, water chillers and commercial rerigeration systems. CompressorsandCondensingUnits This part o the range includes hermetic compressors and an-cooled condensing units or household rerigerators and reezers, and or commercial units such as bottle coolers and drinks dispensers . We also oer compressors or heat pumps, and 2 and 24 V compressors or rerigerators and reezers in commercial vehicles and boats. Appliancecontrols For the regulation o rerigeration appliances and reezers Danoss supplies a product range o electromechanical thermostats produced according to customer specications; electronic temperature controls comprising models with and without displays; service thermostats – or servicing on all rerigerating and reezing appliances. Rerigerationandairconditioningcontrols Our ull product range covers all control, saety, system protection and monitoring requirements in mechanically and electronically controlled rerigeration and air conditioning systems. The products are used in countless applications within the commercial and industrial rerigeration and air conditioning sectors.
RG00A502
Produced by Danoss RC-CMS. 03.2004 .MWA