CT Sizing Calculation for HT/LV Transformer FeederFull description
CT Sizing Calculation for HT/LV Transformer FeederFull description
Full description
Full description
Siemens 7SD5 CT sizingFull description
InstrumentationFull description
CT SizingFull description
CT sizingFull description
CT SizingFull description
CT sizing
CT sizingFull description
ctFull description
CT sizing Technical dataFull description
mFull description
vsdgfsdf
CT wire sizingFull description
xfgSFFull description
Transformer Neutral CT SizingFull description
Full description
CT wire sizingFull description
CT Sizing XLS fileFull description
vsdgfsdfFull description
Neutral grounding resistorFull description
Guide Line to Size a Current Transformer from Siemens. This is good presentation of the CT applications and CT sizing guideline.Full description
CLIENT CONSULTANT CONTRACTOR PROJECT: PACKAGE-II : DOC. NAME : DESIGN CALCULATION SHEET 51NS CORE FOR NEUTRAL CT OF Converter duty TRANSFORMER OF SS2 DOCUMENT NO. 1.1
1.2
1.3
1.4
REV.-00
Dated : 03 /07/2014
System basic Input Data Transformer rating
=
630 KVA
C T ratios
=
600/1A
Design
=
3 PH 4 WIRE
Voltage
=
690
V AC
Frequency
=
50
Hz
Ratio
=
300
/
Accuracy class for Core‐II ( 51NS)
=
5P
15
Accuracy class for Core‐I
=
PS
Selected Burden ( VA ) for core‐I (PS)
=
10
VA
Primary Voltage (v)
=
11
kV
Secondary Voltage ( V )
=
690
V
Transformer rating
=
0.630
Impedence of transformer
=
4
% impedance variation on negative side
=
0
Basic Input Data of Current Transformer: 1
A
Basic Input Data of Distribution Transformer:
MVA % ( no negative tolerance‐ for calculation purpose)
Distribution System Fault Current: Full load current,IFL
=
(MVA X 106) (√ 3 X Sec. Voltage) 6
Min Transformer Impedance, ZM
=
(0.63x 10) (1.7322x690)
=
527.17
= = =
Maximum through fault current on LV side of transfromer = , MVA, IF = IF Max.through Fault current at CT Secondary Side Ifs
= = =
1 of 4
A
(% impedance x (100‐% tolerance))/100 4 x ( 100‐0))/100 4 % (IF x 100)/ ZM (527.17 x 100) /4) 13179.3 Amp IF / CTR 43.94 Amp
CT (CoreI) sizing calculation for 51NS Protection For 0.63 MVA Converter Trafo SS2 Core I: 2.0
CT sizing calculation for IDMT Earth Fault protection Relay(51NS) = Number of Identical C T S Location of C TS
2.1
2.2
2.3
=
1 NOS
Core _1 of NCT on Trafo or seperate CT
IDMT Earth Fault protection Relay(51NS) Input data Relay Module
=
E/F Setting
=
10
%
Current I/P burden, VA
=
0.1
VA
Relaty operating Current, IR
=
0.1
Amp
CoreI CT Input data Ratio
=
300
/ 1 A
Selected Burden ( VA )
=
10
VA
Accuracy Class
=
5P
15
Calculated of CT Burdens : =
50
m
Lead resistance at 70ºC for 2.5mm copper ( Ω/km )
=
8.87
Ω/km
Lead Resistance ( RL) (Ω)
=
0.89
(Ω)
Lead Burden ( VA )
=
0.89
VA
Total Meter Burden ( VA )
=
0.1
VA
=
0.99
VA
Cable Length l ( m ) 2
Total Burden on CT ( VA ) 0
CT Secondary resistance at 75 C (Rct) (Due to Design limitation of CT manufacturer,Rct) Selected burden is more than required. 2.4
= ≤
Ω
HENCE SAFE.
When CT,CoreI is used with ratio 600/1A,In case of phase to phase fault maximum primary current to be measured by the relay for operation 20%If = Fault current at Secondary
If
=
Voltage developed by CT Vct
CT Vct 2.5
4
13.2
kA
=
If X (Rct + Rl) Pri.CT Ratio
=
13.2 X 1000 X (4+0.887)/300)
=
215.03
V
Accordingly minimum VA burden of considered CT Rating with ALF 15 ALF
=
15
=
((Vct/ALF)xCT sec current) ‐ (Rct x CT sec Current)
=
((215.03/ 15 )X 1)‐(4 X1)
=
14.34
=
10.34
‐
4
Hence 10VA CT having 5P15 accuracy is adequate Hence NCT core 1 or seperate CT on 0.63 MVA Converter trafo CT 300/1A,5P15,10VA, RCT =< 4ohm